B08 140L6320Q0016 - Attachment 03 - Drawings 22x34.pdf
PDF 3 MB Posted
- Attached to
- CCSC BACK-UP GENERATOR PROJECT Federal contract opportunity
- Solicitation number
- 140L6320Q0016
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140L6320Q0016.pdf | ||
| B08 140L6320Q0016 - Attachment 01 - Specifications.pdf | ||
| B08 140L6320Q0016 - Attachment 02 - Drawings 11x17.pdf | ||
| B08 140L6320Q0016 - Attachment 04 - Wage Determination.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
9/25/2019 10:00 AM 901901 G-001.DWG
901901
25 OCT 2019
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
CCSC BACKUP
GENERATOR
DLH
DLH
GENERAL
INFORMATION
CIRCLE
PRUDHOE
FAIRBANKS
ANCHORAGE
HOMER
KODIAK
SEWARD
KOTZEBUE
NOME
NENANA
TANANA
BAY
WHITEHORSE YT.
HAINES JCT.
CORDOVA
VALDEZ
SITKA
JUNEAU
EAGLE
TOK
GLENNALLEN
POLE
NORTH DAWSON Y.T.
OCEAN
BARROW
HAINES
1/8"=1'-0"
ROOM
NAME
A
(E) FENCED
DUMPSTER AREA
GENERATOR
DUAL FUEL AND
NATURAL GAS
(E) WATER WELL
(E)TRANSFORMER
(E) NATURAL
GAS METER
C700
E002
(E)BOLLARDS
(E) LIGHTPOLE
C700
BOLLARD, TYP OF 6
POWER AND GAS CONTROL TRENCH
(E) RETAINING WALL
CAMPBELL CREEK SCIENCE CENTER
10/24/2019 3:07 PM 901901-C100.DWG
901901
25 OCT 2019
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
CCSC BACKUP
GENERATOR
C100
IAL
MJS
DEMOLITION AND
SITE PLAN
DEMOLITION AND SITE PLAN 1
C100 1" = 10'
LEGEND
EXISTING CONTOURS
NEW CONTOURS
DEMOLITION
STRUCTURE
EDGE OF ASPHALT PAVEMENT
GRAVEL
SIGN
BOLLARD
HYDRANT
UTILITY POLE
JUNCTION BOX
LIGHTPOLE
TREE LINE
GENERAL AND DEMOLITION NOTES
1. THE DEMOLITION WILL CONSIST OF SAW CUTTING THE EXISTING ASPHALT PAVEMENT
DRIVING SURFACE FOR TRENCHING NATURAL GAS LINE AND ELECTRICAL LINES.
2. NO SURVEY WAS PERFORMED FOR THIS PROJECT, LINE WORK IS FROM PREVIOUS
PROJECT. FIELD VERIFY DIMENSIONS AND ALL EXISTING UTILITIES
3. PLACE 4" TOPSOIL AND SEED OVER ALL DISTURBED AREAS UNLESS OTHERWISE
DIRECTED
4. ALL DISTURBED AREAS SHALL BE RETURNED TO A "LIKE NEW" CONDITION
D E S I G N
A L
A S
K A
Michael John Schmetzer
No. CE3598 24-Oct-2019
10/24/2019 3:07 PM 901901-C700.DWG
901901
25 OCT 2019
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
CCSC BACKUP
GENERATOR
C700
IAL
MJS
DETAILS
CAP TOP SECTION
6"
1'-2"
4" ALL AROUND
3' -0
3"
4' -0
PLAN AT EQUIPMENT
EQUIPMENT
5' 5' TYP
5' O.C. TYP
AS REQ'D. TO
PROTECT
EQUIPMENT
BOLLARD, TYP (REQUIRED AT
ALL MECHANICAL AND/OR
ELECTRICAL EQUIPMENT)
CONCRETE BASE
STRUCTURAL FILL
FG
PIPE CAP, WELD TO
PIPE, GRIND SMOOTH,
AND PAINT YELLOW.
6" OD SCHEDULE 40
STEEL PIPE. FILL
WITH CONCRETE
AND PAINT YELLOW.
CONCRETE SLAB
WHERE SHOWN
'-0
4'-6"
GENERATOR ENCLOSURE
CONCRETE SLAB
PROFILE VIEW OF CONCRETE SLAB
PLAN VIEW OF CONCRETE SLAB
BOLLARDS1
C700 N.T.S.
GENERATOR CONCRETE SLAB3
C700 N.T.S.
TYPICAL ROAD REPAVE SECTION2
C700 N.T.S.
12"
EXISTING
EXISTING
FILL
EXISTING
ASPHALT
TACK
COAT
EDGES
NEW ASPHALT PAVEMENT
4" CRUSHED AGGREGATE
SEE PLANS FOR LOCATION OF
SAWCUT. SAWCUT TO BE
PERPENDICULAR TO EXISTING
PAVEMENT SURFACE.
2" ASPHALT
PAVEMENT MATCH
EXISTING
STRUCTURAL
FILL
NOTES:
1. PROVIDE VAPOR RETARDER BENEATH SLAB PER SPECIFICATIONS.
2. COORDINATE ACTUAL SLAB DIMENSIONS FROM GENERATOR PROVIDER
FOR OVERALL DIMENSIONS, CLEARANCES AND STUB-UP LOCATIONS AND
DIMENSIONS.
6" #4 @ 12" O.C.
EACH WAY
EXISTING
FILL
EXISTING
FILL
D E S I G N
A L
A S
K A
Michael John Schmetzer
No. CE3598 24-Oct-2019
STANDBY GENERATOR
PER ELECTRICAL
EXISTING GAS METER
BURIED 2" NG. CONNECT
DOWNSTREAM OF EXISTING
GAS METER
COORDINATE GAS PIPE ROUTING
WITH CIVIL EXCAVATION LIMITS.
LOCATE EXISTING GAS SERVICE
PIPING PRIOR TO EXCAVATION.
C100
M100
PIPING UP TO GENERATOR,
COORDINATE LOCATION WITH
GENERATOR MANUFACTURER
COORDINATE GAS PIPING
INSTALLATION WITH ADJACENT
ELECTRICAL SERVICE.
C101
EXISTING ELECTRICAL
TRANSFORMER
GENSET
2" (7" W.C.) BURIED
NATURAL GAS FROM
BUILDING
LOCATION PER CIVIL
FLEXIBLE PIPE CONNECTION,
TYP.
2" NG
SEAL WATER TIGHT PIPING
PENETRATION INTO GENERATOR
ENCLOSURE, GAS TRAIN PROVIDED
BY GENERATOR MANUFACTURER
18" MIN.
EXISTING 10 PSI UTILITY
GAS PRESSURE
REGULATOR
EXISTING 7" W.C. GAS
PRESSURE REGULATOR
EXISTING GAS METER
2" NG
EXISTING NG TO BUILDING
MODIFY EXISTING NG PIPING TO
CONNECT NEW LINE INTO
EXISTING GAS RISER
EXISTING GAS FROM UTILITY
PROVIDE VALVE TAG TO
READ, "GENERATOR
SUPPLY VALVE"
10/23/2019 1:48 PM 901901 M100.DWG
901901
25 OCT 2019
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701
907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
CCSC BACKUP
GENERATOR
M100
MPC
MPC
MECHANICAL SITE
PLAN
GAS PIPING SITE PLAN1
M100 1" = 10'
GAS PIPING DIAGRAM2
M100 NO SCALE
ENGLISH UNITS
# POUNDS/PSI
BTUH BRITISH THERMAL UNITS PER HOUR
F DEGREES FAHRENHEIT
FPM FEET PER MINUTE
FT FEET
FT WG FEET OF WATER GAUGE
GAL GALLONS
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
IN INCH
IN WG INCHES OF WATER GAUGE
KW KILOWATT
LB POUNDS
LF LINEAR FOOT
MBH ONE THOUSAND BTU PER HOUR
PSI POUNDS PER SQUARE INCH
WG WATER GAUGE
STANDARD ABBREVIATIONS
& AND
@ AT
# NUMBER
AFF ABOVE FINISHED FLOOR
APPR APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AUTO AUTOMATIC
BAL BALANCING
BFF BELOW FINISHED FLOOR
C COMMON
CAPAC CAPACITY
CFH CUBIC FEET PER HOUR
Cv VALVE COEFFICIENT
CW COLD WATER
DB DRYBULB
DIA DIAMETER
DN DOWN
EA EACH
ELEC ELECTRICAL
EXIST EXISTING
F DEGREES FAHRENHEIT
FLA FULL LOAD AMPERAGE
FLEX FLEXIBLE
GA GAUGE
GI GALVANIZED IRON
H20 WATER
HB HOSE BIBB
HR HOUR
HTG HEATING
HW HOT WATER
ID INSIDE DIAMETER
IE INVERT ELEVATION
INSUL INSULATION
IPS IRON PIPE SIZE
M MINUTES
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MTR MOTOR
NC NORMALLY CLOSED OR NOISE CRITERIA
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
P&TRV PRESSURE AND TEMPERATURE RELIEF VALVE
PD PRESSURE DROP
PH PHASE
PRDV PRESSURE REDUCING VALVE
PRV PRESSURE RELIEF VALVE
S SECONDS
SIM SIMILAR
SP STATIC PRESSURE
SS STAINLESS STEEL
TYP TYPICAL
V VOLTS OR VENT
VERT VERTICAL
VOL VOLUME
W/ WITH
W/O WITHOUT
ABBREVIATIONS
MECHANICAL SYMBOLS
PIPE CONNECTION
ELBOW TURNED DOWN
ELBOW TURNED UP
TEE DOWN
ISOLATION VALVE
CONNECTION TO EXISTING
PIPING SYMBOLS
SYMBOL ABBREV SYSTEM
NATURAL GAS
EXISTING PIPING/DUCTWORK/
EQUIPMENT
NG
SHEET NOTES
1. REFER TO DIVISION 20 AND DIVISION 23 SPECIFICATIONS FOR ADDITIONAL
MECHANICAL REQUIREMENTS.
2. INDICATED PIPE SIZING IS BASED ON SCHEDULE 40 BLACK STEEL PIPING WITH A TOTAL
EQUIVALENT PIPING LENGTH OF 150 FEET, GENERATOR FUEL CAPACITY OF 806 CFH,
AND PRESSURE DROP LESS THAN 0.5 IN. W.C. PER NFPA 54 TABLE 6.2(B). OTHER PIPE
MATERIALS ARE ALLOWED. ALTERNATIVE PIPE MATERIAL IS ALLOWED AS INDICATED IN
PROJECT SPECIFICATIONS PROVIDED PIPE MATERIAL SIZING IS IN ACCORDANCE WITH
NFPA 54 AND PROVIDES REQUIRED GAS CAPACITY AND INLET PRESSURE TO
GENERATOR. CONTRACTOR SHALL SUBMIT WITH PIPING AND EQUIPMENT SUBMITTALS
CALCULATIONS CONFIRMING SIZING OF ALTERNATIVE PIPING MATERIAL IF USED.
3. FIELD LOCATE EXISTING GAS UTILITY PIPING AND OTHER BURIED UTILITIES THAT MAY
BE PRESENT ALONG THE INDICATED PIPING PATH. COORDINATE LOCATION OF PIPING
INSTALLED AS PART OF THIS WORK WITH EXISTING CONDITIONS AND UTILITIES.
Marcus P. Curley
No. ME14660
REG IS T ER ED P R O F E S S IO NA L ENGINEER
D E S I G N A
L A
S K
A23-Oct-2019
(D) SERVICE DISCONNECT
(R) UTILITY METER
(D) METER BASE
(E) JUNCTION/PULL BOX (E) JUNCTION/PULL BOX
(R) UTILITY METER
(NEW METER BASE)
CT ENCLOSURE
400A SERVICE DISCONNECT
400A ATS
CONSTRUCTION STRUT FRAME
FOR MOUNTING NEW EQUIPMENT
(E) CONCRETE
RETAINING
WALL
(E) EDGE OF BUILDING (E) EDGE OF BUILDING
EXISTING CONFIGURATION REVISED CONFIGURATION
CONDUIT TO
GENERATOR
(E) CONDUITS AND
CONDUCTORS TO MDP
(E) CONDUITS AND CONDUCTORS
FROM SERVICE TRANSFORMER
(E) CONDUITS AND
CONDUCTORS TO MDP
(E) CONDUITS AND CONDUCTORS
FROM SERVICE TRANSFORMER
CONDUIT / CONDUCTORS
FEEDER TO MDP
SEAL
HOLES IN
J- BOX
(E) CONCRETE
RETAINING
WALL
(D) GUTTER AND RAIN CHAIN
10/24/2019 3:49 PM 901901 E001 LEGENDS, SCHEDULES.DWG
901901
25 OCT 2019
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
CCSC BACKUP
GENERATOR
E001
DLH
DLH
ELECTRICAL
LEGENDS,
SCHEDULES AND
DETAILS
(E) PAD MOUNTED UTILITY
150 kVA TRANSFORMER
208Y/120 V. WYE-SEC
(E) PRIMARY
CONDUCTORS
(E) 'MDP'
800A MLO
208/120 V
3 PH, 4 W
(D) 600/3
NEMA 3R SERVICE
DISCONNECT / CTS
100/3
(E) PANEL 'B'
100A 208/120V
3 PH, 4 W
150/3
100/3
30/3
100/3
200/3
100/3
100/3
SPARE
SPARE
(E) PANEL 'K'
200A 208/120V
3 PH, 4 W
(E) PANEL 'A'
100A 208/120V
3 PH, 4 W
WELL
SEWAGE
LIFT
STATION
EXISTING/DEMOLITION POWER ONE LINE RISER1
E001 NO SCALE
(E) PULL
BOX
(E) PAD MOUNTED UTILITY
150 kVA TRANSFORMER
208Y/120 V. WYE-SEC
REVISED POWER ONE LINE RISER2
E001 NO SCALE
(E) PULL
BOX
(E) UTILITY METER
(RELOCATE METER)
(E) (2) 4 350 kcmil, 3" C
GEN
50 kW
GENERATOR ENCLOSURE
400A ATS
(3-POLE)
400A NEMA 3R
SERVICE DISCONNECT
(WITH NEUTRAL KIT)
(E) UTILITY METER
(RELOCATED)
NEW METER BASE
FEEDER SCHEDULE
FEEDER # FEEDER DETAIL
4 #4/0, 2" C (RIGID)
8 #4/0, 3" C
6 #10, 1 #10 GND, 1" C.
(TWO CIRCUITS)
2 2
(E) GROUNDING ELECTRODE SYSTEM(E) (2) 4 350 kcmil, 3" C
(E) (2) 4 350 kcmil, 3" C
(E) (2) 4 350 kcmil, 3" C
(E) 'MDP'
800A MLO
208/120 V
3 PH, 4 W
100/3
(E) PANEL 'B'
100A 208/120V
3 PH, 4 W
150/3
100/3
30/3
100/3
200/3
100/3
100/3
SPARE
SPARE
(E) PANEL 'K'
200A 208/120V
3 PH, 4 W
WELL
SEWAGE
LIFT
STATION
ELECTRICAL SYMBOL LEGEND
NOTE KEY - INDICATES NOTES APPLICABLE ON EACH SHEET
DUPLEX RECEPTACLE UP 18" AFF OR +4" ABOVE COUNTERTOP OR
BACKSPLASH, UON
GFCI RECEPTACLE UP 18" AFF, UON
PANELBOARD: FLUSH MOUNTED, SURFACE MOUNTED
JUNCTION BOX
EQUIPMENT CONNECTION
WP WEATHERPROOF
UON UNLESS OTHERWISE NOTED
(E) (D) (R) (E) EXISTING, (D) DEMOLISH, (R) RE-USE OR RELOCATE
EXPOSED CONDUIT (NOTE A BELOW)
BELOW GRADE CONDUIT (NOTE A BELOW)
J
ALL BRANCH CIRCUITS 2#12, 1/2" C. TO 20A., 1P. CIRCUIT BREAKER UON
e.g. A-30(4 #8, 3/4" C. TO 40/3) INDICATES CIRCUIT BREAKER
30 IN PANEL 'A' FEEDS TO EQUIPMENT FROM A 40 A. 3P. CIRCUIT
BREAKER WITH 4 #8 AWG WIRES RUN IN 3/4" CONDUIT.
A. NO. OF WIRES (IF OTHER THAN 2) INDICATED BY NO. OF SLASHES
( = TWO 'HOT' WIRES AND TWO NEUTRAL WIRES )
B. HOME-RUN DESIGNATION: 'A' = PANELBOARD NOTATION, '-2,4' =
CIRCUIT NUMBERS
C. INSTALL INSULATED GROUNDING CONDUCTOR, SIZED IN
ACCORDANCE WITH NEC REQUIREMENTS IN ALL FEEDER AND
BRANCH CIRCUIT CONDUITS.
SYMBOLS SHOWN ABOVE ARE DRAWN AS THEY ARE USED ON THE
DRAWINGS TO INDICATE NEW WORK OR NEW LOCATIONS OF EXISTING
EQUIPMENT. EXISTING EQUIPMENT TO BE ABANDONED IN PLACE,
REMOVED OR RELOCATED IS SHOWN USING THE SAME SYMBOLS BUT
DRAWN WITH DASHED LINES.
(D) 200A GENERATOR RECEPTACLE
(D) 200A 4-POLE MANUAL
TRANSFER SWITCH
(E) PANEL 'A'
100A 208/120V
3 PH, 4 W
PROVIDE JUNCTION BOX(S) TO SPLICE
EXISTING FEEDER AND ROUTE
BRANCH CIRCUITS TO GENERATOR
(E) PANEL 'M1'
225A 208/120V
3 PH, 4 W
(E) PANEL 'M2'
225A 208/120V
3 PH, 4 W
(E) GROUNDING ELECTRODE SYSTEM
(E) PRIMARY
CONDUCTORS
CONTROL
CABLE
20/1
(E) PANEL 'M1'
225A 208/120V
3 PH, 4 W
(E) PANEL 'M2'
225A 208/120V
3 PH, 4 W
GROUNDING SYSTEM TO CONSIST OF:
2 GROUND RODS 1' OFFSET FROM OPPOSITE CORNERS OF PAD
#4 BARE COPPER GROUND RING ~1' OUTSIDE OF FOUNDATION
EXISTING AND REVISED SERVICE EQUIPMENT ELEVATIONS3
E001 NO SCALE
400/3
GENERAL PROJECT PHASING NOTES
1. NEW SERVICE EQUIPMENT TO BE INSTALLED IN LOCATION OUTSIDE OF EXISTING SERVICE
DISCONNECT FOOTPRINT AND ATTACHED TO STRUT FRAME SYSTEM AFFIXED TO EXISTING
RETAINING WALL. GENERATOR SYSTEM SHALL BE INSTALLED AND COMMISSIONED PRIOR TO
TRANSITIONING OF POWER FROM EXISTING SERVICE DISCONNECT TO NEW SERVICE
DISCONNECT AND AUTOMATIC TRANSFER SWITCH. THIS WORK IS PHASED TO MITIGATE POWER
OUTAGES TO THE FACILITY.
1.1. CONTRACTOR TO COORDINATE WITH SERVING UTILITY TO DETERMINE IF THEY PREFER
RE-USE OF THE EXISTING CT's WITHIN THE EXISTING SERVICE DISCONNECT OR THEY WILL PROVIDE NEW RE-SIZED CT's TO BE INSTALLED WITHIN THE NEW ENCLOSURE.
2. ONCE THESE NEW SYSTEMS ARE INSTALLED, THE CONTRACTOR SHALL COORDINATE WITH BOTH
THE SERVING UTILITY AND THE BLM FOR A SPECIFIC DATE WHERE THE SERVICE MAY BE
TRANSITIONED OVER (REQUIRES A BUILDING OUTAGE) TO THIS NEW SERVICE EQUIPMENT.
3. CONTRACTOR SHALL PRE-CONFIGURE AS MUCH OF THIS EQUIPMENT AS PRACTICAL; i.e.
CONDUITS, SUPPORTS, ENCLOSURES SO THE DURATION OF THE SCHEDULED OUTAGE SHALL
NOT EXCEED AN 8-HOUR PERIOD. NOTE AS THE GENERATOR SHOULD BE AVAILABLE FOR
POWERING THE BUILDING, THE CONTRACTOR MAY UTILIZE THE NEW GENERATOR AS A POWER
SOURCE FOR THE FACILITY TO MINIMIZE THE POWER OUTAGE DURATION WHERE THEY CAN
PROVIDE TEMPORARY WIRING AS NECESSARY TO ACCOMPLISH THIS TASK.
4. DURING THIS UTILITY SERVICE OUTAGE, THE EXISTING SERVICE DISCONNECT ASSEMBLY WILL
BE REMOVED; WHERE THE EXISTING SERVICE CONDUCTORS SHALL BE PRESERVED FOR
CONNECTION TO THE NEW CT ENCLOSURE. THE NEW CT ENCLOSURE WILL BE SET AND
CONNECTED TO THE EXISTING INCOMING SERVICE CONDUCTORS.
5. ONCE THE EXISTING SERVICE DISCONNECT IS REMOVED AND THE NEW EQUIPMENT IS
INSTALLED, CONTRACTOR TO TRANSITION THE SERVICE TO UTILITY POWER AND REMOVE ALL
TEMPORARY WIRING SYSTEMS INSTALLED.
30/2
GENERATOR
FOUNDATION
Donald L. Hopkins
No. EE10582
D E S I G N A
L A
S
119"
12"12"
40"
SERVICE PANEL
SERVICE
DOORS
LEFT SIDE VIEW
FUEL CONNECTIONS
AIR FLOW
DISTANCE
REQUIRED
TO OPEN
DOORS
CENTER OF GRAVITY
OUTLET VIEW
INLET VIEW
AIR INTAKE AREA
/2
RADIATOR FILL ACCESS
AIR AND EXHAUST DISCHARGE AREA
SERVICE PANEL
SERVICE
DOORS
RIGHT SIDE VIEW
TOP VIEW
PROVIDE CUSTOM AUXILIARY HOOD OVER
EXHAUST TO PROTECT SNOW/RAIN/DEBRIS
FROM ENTERING EXHAUST DISCHARGE
AREA AND PROVIDE ACCESS FOR
MAINTAINING RADIATOR FLUID AIR INTAKE SILENCER VERTICAL HOOD
AIR FLOW
10/23/2019 2:06 PM 901901 E002 DETAILS.DWG
901901
25 OCT 2019
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
CCSC BACKUP
GENERATOR
E002
DLH
DLH
ELECTRICAL
DETAILS
GENERATOR DETAILS1
E002 NO SCALE
PANEL 'M1'
CKT P TRIP LOAD SERVED LOAD
TYPE
LOAD
(VA) BUS
LOAD
(VA)
LOAD
TYPE LOAD SERVED TRIP P CKT
NO.NO.
1 3 30 MUA E 0 A 0 E AHU 20 3 2
3 " " E 0 B 0 E " " 4 5 " " E 0 C 0 E " " 6
7 3 20 EF4 E 0 A 0 E AHU2 40 3 8
9 " " E 0 B 0 E " " 10 11 " " E 0 C 0 E " " 12
13 1 20 UNIT HEATERS LG FAN RM E 0 A 0 E TELEPHONE OUTLET 20 1 14
15 1 20 SPARE (RED) IN UN1 E 0 B 0 E COMPUTER OUTLET 20 1 16
17 1 20 UNIT HEAT & EXH FAN3 E 0 C 0 E TV OUTLET 20 1 18
19 1 20 EXH FAN 1 & 2 E 0 A 0 E WATER CHILLER 20 1 20
21 1 20 PARKING POLE LIGHTS E 0 B 0 E LARGE FAN TM OUTLET 20 1 22
23 1 20 PARKING LIGHTS & VIDEO CAMERA E 0 C 0 E MAINTENANCE SHED 50 3 24
25 1 20 PORCH LIGHT E 0 A 0 E " " 26
27 1 20 LIGHTING CONT & CLOCK E 0 B 0 E " " 28
29 1 20 GFI - HEAT TRACE (PINK) E 0 C 0 E HEATER FAN REC 20 1 30
31 1 20 DDC PANEL LG FAN ROOM E 0 A 0 E GFCI HEAT TRACE (GRAY) 20 1 32
33 1 20 ?? E 0 B 0 S SPARE (YELLOW IN UN1) 20 1 34
35 2 30 (N) GENERATOR POWER E 1,620 C 0 S PREPARED SPACE -- -- 36
37 (PROVIDE 2-NEUTRALS) E 600 A 0 S " " -- -- 38
39 1 20 (N) GENERATOR REC S 180 B 0 S " " -- -- 40
41 -- -- PREPARED SPACE S 0 C 0 S " " -- -- 42
MAIN: 225 AMPS MLO PHASE A: 600 VA 5.0 A CONNECTED: 2,400 VA NOTES
TYPE: 208Y/120 V 3 PH, 4 W. PHASE B: 180 VA 1.5 A AMPS: 6.7 A
AIC: 10,000 RMS SYMM. AMPS PHASE C: 1,620 VA 13.5 A VOLTAGE: 208 V
N.E.C. FEEDER CALCULATIONS: (VA) (A) LOAD TYPE:
LIGHTING 0 VA 0.0 A L = LIGHTING (LOAD X 125%)
RECEPTACLES 0 VA 0.0 A R = RECEPTACLES (NEC 220.44)
EQUIPMENT (CONTINUOUS) 0 VA 0.0 A C = EQUIPMENT (CONTINUOUS) X 125%
EQUIPMENT (NON-CONTINUOUS) 2,220 VA 6.2 A E = EQUIPMENT (NON-CONTINUOUS) X 100%
MOTORS 500 VA 1.4 A M = MOTORS (LOAD + 25% OF LARGEST MOTOR)
TOTAL DEMAND LOAD 2,720 VA 7.5 A F = FEEDERS
MOUNTING SPECIAL REQUIREMENTS: S = SPARE OR SPACE LOCATION
SURFACE RM MECH
12"
12"
1. CONDUIT, TYPE SIZE AND NUMBER OF CONDUITS AS SHOWN ON DRAWINGS (TYPICAL).
2. TRENCH MAY BE EXPANDED TO INCLUDE OTHER SYSTEMS (i.e. NATURAL GAS PIPING)
WHERE THESE SYSTEMS ARE INSTALLED A MINIMUM OF 12" FROM ELECTRICAL RACEWAYS.
FINISH GRADE
STRUCTURAL FILL
BEDDING MATERIAL
POWER CONDUIT
CONTROL CONDUIT
SURFACE FINISH TO MATCH
ADJACENT FINISH
MARKER
TAPE (ELEC)
MIN. 24"
6"
6"
6"
AS REQ'D
TYPICAL ELECTRICAL TRENCH DETAIL2
E002 NO SCALE
12" MIN
NATURAL GAS LINE
(WHERE PRESENT)
MARKER
TAPE (GAS)
1. GENERATOR SIZE IS REPRESENTATIVE AND MAY DIFFER FROM FINAL UNIT PROVIDED BY CONTRACTOR.
Donald L. Hopkins
No. EE10582
D E S I G N A
L A
S
(E) WATER WELL
(E) AREA LIGHT POLE
(E) UTILITY TRANSFORMER
AND PAD
(D) 200A MTS
(E) WELL PUMP CONTROLLER
(D) SERVICE DISCONNECT
CABINET WITH INTERNAL CT'S
(SHOWN DASHED LINES)
(E) PULL BOX & METER
(E) NATURAL GAS METER
(E) MDP
(E) BOLLARDS
(E) FENCED
DUMPSTER
AREA
(E) RETAINING WALL
GENERATOR
50 kW 208Y/120V
DUAL FUEL PROPANE/NATURAL GAS
(E) UNDERGROUND PRIMARY
(UTILITY TO LOCATE)
(E) UNDERGROUND SECONDARY
(CONTRACTOR TO LOCATE)
SERVICE DISCONNECT SWITCH &
CT ENCLOSURE
400A AUTOMATIC
TRANSFER SWITCH
FEEDER FROM
GENERATOR AND
CONTROL CABLE
(E) ABANDONED
HEATING PIPES
CAMPBELL CREEK SCIENCE CENTER
REMOTE
ANNUNCIATOR
PANEL
BRANCH CIRCUITS
FOR GENERATOR
SUPPORT POWER
1 JUNCTION BOX
(E) PANEL M1
(E) PANEL M2
DIRECT EXHAUST & NOISE
AWAY FROM BUILDING
10/23/2019 2:06 PM 901901 E100 SITE PLAN.DWG
901901
25 OCT 2019
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
CCSC BACKUP
GENERATOR
E100
DLH
DLH
ELECTRICAL SITE
PLAN
ELECTRICAL SITE PLAN1
E100 1" = 10'
SPECIFIC NOTES
REMOVE EXISTING MANUAL TRANSFER SWITCH AND REPLACE WITH 12" W X 12" LX 8" D
NEMA 3R JUNCTION BOX AND SPLICE EXISTING CONDUCTORS WITHIN NEW ENCLOSURE.
PROVIDE UTILITY LOCATES TO IDENTIFY BELOW GROUND INFRASTRUCTURE AT THE SITE.
KNOWN INFRASTRUCTURE INCLUDES BELOW GRADE UTILITY PRIMARY CONDUCTORS
(ASSUMED TO BE DIRECT BURIAL TYPE). COORDINATE FINAL LOCATION OF GENERATOR
AND PAD WITH BLM PRIOR TO EXCAVATION AND PLACEMENT. CONTRACTOR SHALL NOT
DISTURB GROUND OF TREES WITHIN A RADIUS OF 10' FROM BASE OF TREE.
(E) WELL PUMP CONTROLLER
(D) 200A MTS
(E) CONDUITS TO
MECHANICAL ROOM
REPRESENTATIVE
GENERATOR UNIT
Donald L. Hopkins
No. EE10582
D E S I G N A
L A
S
| G001 |
| C100 |
| C700 |
| M100 |
| E001 |
| E002 |
| E100 |