9/25/2019 10:00 AM 901901 G-001.DWG

901901

25 OCT 2019

COMM. NUMBER

ISSUE DATE

DESIGNED BY

DRAWN BY

1"0" SCALE

601 College Road Fairbanks AK 99701 907.452.1241

Architects SurveyorsEngineers

AECC511 designalaska.com

CCSC BACKUP

GENERATOR

DLH

DLH

GENERAL

INFORMATION

CIRCLE

PRUDHOE

FAIRBANKS

ANCHORAGE

HOMER

KODIAK

SEWARD

KOTZEBUE

NOME

NENANA

TANANA

BAY

WHITEHORSE YT.

HAINES JCT.

CORDOVA

VALDEZ

SITKA

JUNEAU

EAGLE

TOK

GLENNALLEN

POLE

NORTH DAWSON Y.T.

OCEAN

BARROW

HAINES

1/8"=1'-0"

ROOM

NAME

A

(E) FENCED

DUMPSTER AREA

GENERATOR

DUAL FUEL AND

NATURAL GAS

(E) WATER WELL

(E)TRANSFORMER

(E) NATURAL

GAS METER

C700

E002

(E)BOLLARDS

(E) LIGHTPOLE

C700

BOLLARD, TYP OF 6

POWER AND GAS CONTROL TRENCH

(E) RETAINING WALL

CAMPBELL CREEK SCIENCE CENTER

10/24/2019 3:07 PM 901901-C100.DWG

901901

25 OCT 2019

COMM. NUMBER

ISSUE DATE

DESIGNED BY

DRAWN BY

1"0" SCALE

601 College Road Fairbanks AK 99701 907.452.1241

Architects SurveyorsEngineers

AECC511 designalaska.com

CCSC BACKUP

GENERATOR

C100

IAL

MJS

DEMOLITION AND

SITE PLAN

DEMOLITION AND SITE PLAN 1

C100 1" = 10'

LEGEND

EXISTING CONTOURS

NEW CONTOURS

DEMOLITION

STRUCTURE

EDGE OF ASPHALT PAVEMENT

GRAVEL

SIGN

BOLLARD

HYDRANT

UTILITY POLE

JUNCTION BOX

LIGHTPOLE

TREE LINE

GENERAL AND DEMOLITION NOTES

1. THE DEMOLITION WILL CONSIST OF SAW CUTTING THE EXISTING ASPHALT PAVEMENT

DRIVING SURFACE FOR TRENCHING NATURAL GAS LINE AND ELECTRICAL LINES.

2. NO SURVEY WAS PERFORMED FOR THIS PROJECT, LINE WORK IS FROM PREVIOUS

PROJECT. FIELD VERIFY DIMENSIONS AND ALL EXISTING UTILITIES

3. PLACE 4" TOPSOIL AND SEED OVER ALL DISTURBED AREAS UNLESS OTHERWISE

DIRECTED

4. ALL DISTURBED AREAS SHALL BE RETURNED TO A "LIKE NEW" CONDITION

D E S I G N

A L

A S

K A

Michael John Schmetzer

No. CE3598 24-Oct-2019

10/24/2019 3:07 PM 901901-C700.DWG

901901

25 OCT 2019

COMM. NUMBER

ISSUE DATE

DESIGNED BY

DRAWN BY

1"0" SCALE

601 College Road Fairbanks AK 99701 907.452.1241

Architects SurveyorsEngineers

AECC511 designalaska.com

CCSC BACKUP

GENERATOR

C700

IAL

MJS

DETAILS

CAP TOP SECTION

6"

1'-2"

4" ALL AROUND

3' -0

3"

4' -0

PLAN AT EQUIPMENT

EQUIPMENT

5' 5' TYP

5' O.C. TYP

AS REQ'D. TO

PROTECT

EQUIPMENT

BOLLARD, TYP (REQUIRED AT

ALL MECHANICAL AND/OR

ELECTRICAL EQUIPMENT)

CONCRETE BASE

STRUCTURAL FILL

FG

PIPE CAP, WELD TO

PIPE, GRIND SMOOTH,

AND PAINT YELLOW.

6" OD SCHEDULE 40

STEEL PIPE. FILL

WITH CONCRETE

AND PAINT YELLOW.

CONCRETE SLAB

WHERE SHOWN

'-0

4'-6"

GENERATOR ENCLOSURE

CONCRETE SLAB

PROFILE VIEW OF CONCRETE SLAB

PLAN VIEW OF CONCRETE SLAB

BOLLARDS1

C700 N.T.S.

GENERATOR CONCRETE SLAB3

C700 N.T.S.

TYPICAL ROAD REPAVE SECTION2

C700 N.T.S.

12"

EXISTING

EXISTING

FILL

EXISTING

ASPHALT

TACK

COAT

EDGES

NEW ASPHALT PAVEMENT

4" CRUSHED AGGREGATE

SEE PLANS FOR LOCATION OF

SAWCUT. SAWCUT TO BE

PERPENDICULAR TO EXISTING

PAVEMENT SURFACE.

2" ASPHALT

PAVEMENT MATCH

EXISTING

STRUCTURAL

FILL

NOTES:

1. PROVIDE VAPOR RETARDER BENEATH SLAB PER SPECIFICATIONS.

2. COORDINATE ACTUAL SLAB DIMENSIONS FROM GENERATOR PROVIDER

FOR OVERALL DIMENSIONS, CLEARANCES AND STUB-UP LOCATIONS AND

DIMENSIONS.

6" #4 @ 12" O.C.

EACH WAY

EXISTING

FILL

EXISTING

FILL

D E S I G N

A L

A S

K A

Michael John Schmetzer

No. CE3598 24-Oct-2019

STANDBY GENERATOR

PER ELECTRICAL

EXISTING GAS METER

BURIED 2" NG. CONNECT

DOWNSTREAM OF EXISTING

GAS METER

COORDINATE GAS PIPE ROUTING

WITH CIVIL EXCAVATION LIMITS.

LOCATE EXISTING GAS SERVICE

PIPING PRIOR TO EXCAVATION.

C100

M100

PIPING UP TO GENERATOR,

COORDINATE LOCATION WITH

GENERATOR MANUFACTURER

COORDINATE GAS PIPING

INSTALLATION WITH ADJACENT

ELECTRICAL SERVICE.

C101

EXISTING ELECTRICAL

TRANSFORMER

GENSET

2" (7" W.C.) BURIED

NATURAL GAS FROM

BUILDING

LOCATION PER CIVIL

FLEXIBLE PIPE CONNECTION,

TYP.

2" NG

SEAL WATER TIGHT PIPING

PENETRATION INTO GENERATOR

ENCLOSURE, GAS TRAIN PROVIDED

BY GENERATOR MANUFACTURER

18" MIN.

EXISTING 10 PSI UTILITY

GAS PRESSURE

REGULATOR

EXISTING 7" W.C. GAS

PRESSURE REGULATOR

EXISTING GAS METER

2" NG

EXISTING NG TO BUILDING

MODIFY EXISTING NG PIPING TO

CONNECT NEW LINE INTO

EXISTING GAS RISER

EXISTING GAS FROM UTILITY

PROVIDE VALVE TAG TO

READ, "GENERATOR

SUPPLY VALVE"

10/23/2019 1:48 PM 901901 M100.DWG

901901

25 OCT 2019

COMM. NUMBER

ISSUE DATE

DESIGNED BY

DRAWN BY

1"0" SCALE

601 College Road Fairbanks AK 99701

907.452.1241

Architects SurveyorsEngineers

AECC511 designalaska.com

CCSC BACKUP

GENERATOR

M100

MPC

MPC

MECHANICAL SITE

PLAN

GAS PIPING SITE PLAN1

M100 1" = 10'

GAS PIPING DIAGRAM2

M100 NO SCALE

ENGLISH UNITS

# POUNDS/PSI

BTUH BRITISH THERMAL UNITS PER HOUR

F DEGREES FAHRENHEIT

FPM FEET PER MINUTE

FT FEET

FT WG FEET OF WATER GAUGE

GAL GALLONS

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

IN INCH

IN WG INCHES OF WATER GAUGE

KW KILOWATT

LB POUNDS

LF LINEAR FOOT

MBH ONE THOUSAND BTU PER HOUR

PSI POUNDS PER SQUARE INCH

WG WATER GAUGE

STANDARD ABBREVIATIONS

& AND

@ AT

# NUMBER

AFF ABOVE FINISHED FLOOR

APPR APPROVED

APPROX APPROXIMATE

ARCH ARCHITECTURAL

AUTO AUTOMATIC

BAL BALANCING

BFF BELOW FINISHED FLOOR

C COMMON

CAPAC CAPACITY

CFH CUBIC FEET PER HOUR

Cv VALVE COEFFICIENT

CW COLD WATER

DB DRYBULB

DIA DIAMETER

DN DOWN

EA EACH

ELEC ELECTRICAL

EXIST EXISTING

F DEGREES FAHRENHEIT

FLA FULL LOAD AMPERAGE

FLEX FLEXIBLE

GA GAUGE

GI GALVANIZED IRON

H20 WATER

HB HOSE BIBB

HR HOUR

HTG HEATING

HW HOT WATER

ID INSIDE DIAMETER

IE INVERT ELEVATION

INSUL INSULATION

IPS IRON PIPE SIZE

M MINUTES

MAX MAXIMUM

MECH MECHANICAL

MIN MINIMUM

MTR MOTOR

NC NORMALLY CLOSED OR NOISE CRITERIA

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OFOI OWNER FURNISHED OWNER INSTALLED

P&TRV PRESSURE AND TEMPERATURE RELIEF VALVE

PD PRESSURE DROP

PH PHASE

PRDV PRESSURE REDUCING VALVE

PRV PRESSURE RELIEF VALVE

S SECONDS

SIM SIMILAR

SP STATIC PRESSURE

SS STAINLESS STEEL

TYP TYPICAL

V VOLTS OR VENT

VERT VERTICAL

VOL VOLUME

W/ WITH

W/O WITHOUT

ABBREVIATIONS

MECHANICAL SYMBOLS

PIPE CONNECTION

ELBOW TURNED DOWN

ELBOW TURNED UP

TEE DOWN

ISOLATION VALVE

CONNECTION TO EXISTING

PIPING SYMBOLS

SYMBOL ABBREV SYSTEM

NATURAL GAS

EXISTING PIPING/DUCTWORK/

EQUIPMENT

NG

SHEET NOTES

1. REFER TO DIVISION 20 AND DIVISION 23 SPECIFICATIONS FOR ADDITIONAL

MECHANICAL REQUIREMENTS.

2. INDICATED PIPE SIZING IS BASED ON SCHEDULE 40 BLACK STEEL PIPING WITH A TOTAL

EQUIVALENT PIPING LENGTH OF 150 FEET, GENERATOR FUEL CAPACITY OF 806 CFH,

AND PRESSURE DROP LESS THAN 0.5 IN. W.C. PER NFPA 54 TABLE 6.2(B). OTHER PIPE

MATERIALS ARE ALLOWED. ALTERNATIVE PIPE MATERIAL IS ALLOWED AS INDICATED IN

PROJECT SPECIFICATIONS PROVIDED PIPE MATERIAL SIZING IS IN ACCORDANCE WITH

NFPA 54 AND PROVIDES REQUIRED GAS CAPACITY AND INLET PRESSURE TO

GENERATOR. CONTRACTOR SHALL SUBMIT WITH PIPING AND EQUIPMENT SUBMITTALS

CALCULATIONS CONFIRMING SIZING OF ALTERNATIVE PIPING MATERIAL IF USED.

3. FIELD LOCATE EXISTING GAS UTILITY PIPING AND OTHER BURIED UTILITIES THAT MAY

BE PRESENT ALONG THE INDICATED PIPING PATH. COORDINATE LOCATION OF PIPING

INSTALLED AS PART OF THIS WORK WITH EXISTING CONDITIONS AND UTILITIES.

Marcus P. Curley

No. ME14660

REG IS T ER ED P R O F E S S IO NA L ENGINEER

D E S I G N A

L A

S K

A23-Oct-2019

(D) SERVICE DISCONNECT

(R) UTILITY METER

(D) METER BASE

(E) JUNCTION/PULL BOX (E) JUNCTION/PULL BOX

(R) UTILITY METER

(NEW METER BASE)

CT ENCLOSURE

400A SERVICE DISCONNECT

400A ATS

CONSTRUCTION STRUT FRAME

FOR MOUNTING NEW EQUIPMENT

(E) CONCRETE

RETAINING

WALL

(E) EDGE OF BUILDING (E) EDGE OF BUILDING

EXISTING CONFIGURATION REVISED CONFIGURATION

CONDUIT TO

GENERATOR

(E) CONDUITS AND

CONDUCTORS TO MDP

(E) CONDUITS AND CONDUCTORS

FROM SERVICE TRANSFORMER

(E) CONDUITS AND

CONDUCTORS TO MDP

(E) CONDUITS AND CONDUCTORS

FROM SERVICE TRANSFORMER

CONDUIT / CONDUCTORS

FEEDER TO MDP

SEAL

HOLES IN

J- BOX

(E) CONCRETE

RETAINING

WALL

(D) GUTTER AND RAIN CHAIN

10/24/2019 3:49 PM 901901 E001 LEGENDS, SCHEDULES.DWG

901901

25 OCT 2019

COMM. NUMBER

ISSUE DATE

DESIGNED BY

DRAWN BY

1"0" SCALE

601 College Road Fairbanks AK 99701 907.452.1241

Architects SurveyorsEngineers

AECC511 designalaska.com

CCSC BACKUP

GENERATOR

E001

DLH

DLH

ELECTRICAL

LEGENDS,

SCHEDULES AND

DETAILS

(E) PAD MOUNTED UTILITY

150 kVA TRANSFORMER

208Y/120 V. WYE-SEC

(E) PRIMARY

CONDUCTORS

(E) 'MDP'

800A MLO

208/120 V

3 PH, 4 W

(D) 600/3

NEMA 3R SERVICE

DISCONNECT / CTS

100/3

(E) PANEL 'B'

100A 208/120V

3 PH, 4 W

150/3

100/3

30/3

100/3

200/3

100/3

100/3

SPARE

SPARE

(E) PANEL 'K'

200A 208/120V

3 PH, 4 W

(E) PANEL 'A'

100A 208/120V

3 PH, 4 W

WELL

SEWAGE

LIFT

STATION

EXISTING/DEMOLITION POWER ONE LINE RISER1

E001 NO SCALE

(E) PULL

BOX

(E) PAD MOUNTED UTILITY

150 kVA TRANSFORMER

208Y/120 V. WYE-SEC

REVISED POWER ONE LINE RISER2

E001 NO SCALE

(E) PULL

BOX

(E) UTILITY METER

(RELOCATE METER)

(E) (2) 4 350 kcmil, 3" C

GEN

50 kW

GENERATOR ENCLOSURE

400A ATS

(3-POLE)

400A NEMA 3R

SERVICE DISCONNECT

(WITH NEUTRAL KIT)

(E) UTILITY METER

(RELOCATED)

NEW METER BASE

FEEDER SCHEDULE

FEEDER # FEEDER DETAIL

4 #4/0, 2" C (RIGID)

8 #4/0, 3" C

6 #10, 1 #10 GND, 1" C.

(TWO CIRCUITS)

2 2

(E) GROUNDING ELECTRODE SYSTEM(E) (2) 4 350 kcmil, 3" C

(E) (2) 4 350 kcmil, 3" C

(E) (2) 4 350 kcmil, 3" C

(E) 'MDP'

800A MLO

208/120 V

3 PH, 4 W

100/3

(E) PANEL 'B'

100A 208/120V

3 PH, 4 W

150/3

100/3

30/3

100/3

200/3

100/3

100/3

SPARE

SPARE

(E) PANEL 'K'

200A 208/120V

3 PH, 4 W

WELL

SEWAGE

LIFT

STATION

ELECTRICAL SYMBOL LEGEND

NOTE KEY - INDICATES NOTES APPLICABLE ON EACH SHEET

DUPLEX RECEPTACLE UP 18" AFF OR +4" ABOVE COUNTERTOP OR

BACKSPLASH, UON

GFCI RECEPTACLE UP 18" AFF, UON

PANELBOARD: FLUSH MOUNTED, SURFACE MOUNTED

JUNCTION BOX

EQUIPMENT CONNECTION

WP WEATHERPROOF

UON UNLESS OTHERWISE NOTED

(E) (D) (R) (E) EXISTING, (D) DEMOLISH, (R) RE-USE OR RELOCATE

EXPOSED CONDUIT (NOTE A BELOW)

BELOW GRADE CONDUIT (NOTE A BELOW)

J

ALL BRANCH CIRCUITS 2#12, 1/2" C. TO 20A., 1P. CIRCUIT BREAKER UON

e.g. A-30(4 #8, 3/4" C. TO 40/3) INDICATES CIRCUIT BREAKER

30 IN PANEL 'A' FEEDS TO EQUIPMENT FROM A 40 A. 3P. CIRCUIT

BREAKER WITH 4 #8 AWG WIRES RUN IN 3/4" CONDUIT.

A. NO. OF WIRES (IF OTHER THAN 2) INDICATED BY NO. OF SLASHES

( = TWO 'HOT' WIRES AND TWO NEUTRAL WIRES )

B. HOME-RUN DESIGNATION: 'A' = PANELBOARD NOTATION, '-2,4' =

CIRCUIT NUMBERS

C. INSTALL INSULATED GROUNDING CONDUCTOR, SIZED IN

ACCORDANCE WITH NEC REQUIREMENTS IN ALL FEEDER AND

BRANCH CIRCUIT CONDUITS.

SYMBOLS SHOWN ABOVE ARE DRAWN AS THEY ARE USED ON THE

DRAWINGS TO INDICATE NEW WORK OR NEW LOCATIONS OF EXISTING

EQUIPMENT. EXISTING EQUIPMENT TO BE ABANDONED IN PLACE,

REMOVED OR RELOCATED IS SHOWN USING THE SAME SYMBOLS BUT

DRAWN WITH DASHED LINES.

(D) 200A GENERATOR RECEPTACLE

(D) 200A 4-POLE MANUAL

TRANSFER SWITCH

(E) PANEL 'A'

100A 208/120V

3 PH, 4 W

PROVIDE JUNCTION BOX(S) TO SPLICE

EXISTING FEEDER AND ROUTE

BRANCH CIRCUITS TO GENERATOR

(E) PANEL 'M1'

225A 208/120V

3 PH, 4 W

(E) PANEL 'M2'

225A 208/120V

3 PH, 4 W

(E) GROUNDING ELECTRODE SYSTEM

(E) PRIMARY

CONDUCTORS

CONTROL

CABLE

20/1

(E) PANEL 'M1'

225A 208/120V

3 PH, 4 W

(E) PANEL 'M2'

225A 208/120V

3 PH, 4 W

GROUNDING SYSTEM TO CONSIST OF:

2 GROUND RODS 1' OFFSET FROM OPPOSITE CORNERS OF PAD

#4 BARE COPPER GROUND RING ~1' OUTSIDE OF FOUNDATION

EXISTING AND REVISED SERVICE EQUIPMENT ELEVATIONS3

E001 NO SCALE

400/3

GENERAL PROJECT PHASING NOTES

1. NEW SERVICE EQUIPMENT TO BE INSTALLED IN LOCATION OUTSIDE OF EXISTING SERVICE

DISCONNECT FOOTPRINT AND ATTACHED TO STRUT FRAME SYSTEM AFFIXED TO EXISTING

RETAINING WALL. GENERATOR SYSTEM SHALL BE INSTALLED AND COMMISSIONED PRIOR TO

TRANSITIONING OF POWER FROM EXISTING SERVICE DISCONNECT TO NEW SERVICE

DISCONNECT AND AUTOMATIC TRANSFER SWITCH. THIS WORK IS PHASED TO MITIGATE POWER

OUTAGES TO THE FACILITY.

1.1. CONTRACTOR TO COORDINATE WITH SERVING UTILITY TO DETERMINE IF THEY PREFER

RE-USE OF THE EXISTING CT's WITHIN THE EXISTING SERVICE DISCONNECT OR THEY WILL PROVIDE NEW RE-SIZED CT's TO BE INSTALLED WITHIN THE NEW ENCLOSURE.

2. ONCE THESE NEW SYSTEMS ARE INSTALLED, THE CONTRACTOR SHALL COORDINATE WITH BOTH

THE SERVING UTILITY AND THE BLM FOR A SPECIFIC DATE WHERE THE SERVICE MAY BE

TRANSITIONED OVER (REQUIRES A BUILDING OUTAGE) TO THIS NEW SERVICE EQUIPMENT.

3. CONTRACTOR SHALL PRE-CONFIGURE AS MUCH OF THIS EQUIPMENT AS PRACTICAL; i.e.

CONDUITS, SUPPORTS, ENCLOSURES SO THE DURATION OF THE SCHEDULED OUTAGE SHALL

NOT EXCEED AN 8-HOUR PERIOD. NOTE AS THE GENERATOR SHOULD BE AVAILABLE FOR

POWERING THE BUILDING, THE CONTRACTOR MAY UTILIZE THE NEW GENERATOR AS A POWER

SOURCE FOR THE FACILITY TO MINIMIZE THE POWER OUTAGE DURATION WHERE THEY CAN

PROVIDE TEMPORARY WIRING AS NECESSARY TO ACCOMPLISH THIS TASK.

4. DURING THIS UTILITY SERVICE OUTAGE, THE EXISTING SERVICE DISCONNECT ASSEMBLY WILL

BE REMOVED; WHERE THE EXISTING SERVICE CONDUCTORS SHALL BE PRESERVED FOR

CONNECTION TO THE NEW CT ENCLOSURE. THE NEW CT ENCLOSURE WILL BE SET AND

CONNECTED TO THE EXISTING INCOMING SERVICE CONDUCTORS.

5. ONCE THE EXISTING SERVICE DISCONNECT IS REMOVED AND THE NEW EQUIPMENT IS

INSTALLED, CONTRACTOR TO TRANSITION THE SERVICE TO UTILITY POWER AND REMOVE ALL

TEMPORARY WIRING SYSTEMS INSTALLED.

30/2

GENERATOR

FOUNDATION

Donald L. Hopkins

No. EE10582

D E S I G N A

L A

S

119"

12"12"

40"

SERVICE PANEL

SERVICE

DOORS

LEFT SIDE VIEW

FUEL CONNECTIONS

AIR FLOW

DISTANCE

REQUIRED

TO OPEN

DOORS

CENTER OF GRAVITY

OUTLET VIEW

INLET VIEW

AIR INTAKE AREA

/2

RADIATOR FILL ACCESS

AIR AND EXHAUST DISCHARGE AREA

SERVICE PANEL

SERVICE

DOORS

RIGHT SIDE VIEW

TOP VIEW

PROVIDE CUSTOM AUXILIARY HOOD OVER

EXHAUST TO PROTECT SNOW/RAIN/DEBRIS

FROM ENTERING EXHAUST DISCHARGE

AREA AND PROVIDE ACCESS FOR

MAINTAINING RADIATOR FLUID AIR INTAKE SILENCER VERTICAL HOOD

AIR FLOW

10/23/2019 2:06 PM 901901 E002 DETAILS.DWG

901901

25 OCT 2019

COMM. NUMBER

ISSUE DATE

DESIGNED BY

DRAWN BY

1"0" SCALE

601 College Road Fairbanks AK 99701 907.452.1241

Architects SurveyorsEngineers

AECC511 designalaska.com

CCSC BACKUP

GENERATOR

E002

DLH

DLH

ELECTRICAL

DETAILS

GENERATOR DETAILS1

E002 NO SCALE

PANEL 'M1'

CKT P TRIP LOAD SERVED LOAD

TYPE

LOAD

(VA) BUS

LOAD

(VA)

LOAD

TYPE LOAD SERVED TRIP P CKT

NO.NO.

1 3 30 MUA E 0 A 0 E AHU 20 3 2

3 " " E 0 B 0 E " " 4 5 " " E 0 C 0 E " " 6

7 3 20 EF4 E 0 A 0 E AHU2 40 3 8

9 " " E 0 B 0 E " " 10 11 " " E 0 C 0 E " " 12

13 1 20 UNIT HEATERS LG FAN RM E 0 A 0 E TELEPHONE OUTLET 20 1 14

15 1 20 SPARE (RED) IN UN1 E 0 B 0 E COMPUTER OUTLET 20 1 16

17 1 20 UNIT HEAT & EXH FAN3 E 0 C 0 E TV OUTLET 20 1 18

19 1 20 EXH FAN 1 & 2 E 0 A 0 E WATER CHILLER 20 1 20

21 1 20 PARKING POLE LIGHTS E 0 B 0 E LARGE FAN TM OUTLET 20 1 22

23 1 20 PARKING LIGHTS & VIDEO CAMERA E 0 C 0 E MAINTENANCE SHED 50 3 24

25 1 20 PORCH LIGHT E 0 A 0 E " " 26

27 1 20 LIGHTING CONT & CLOCK E 0 B 0 E " " 28

29 1 20 GFI - HEAT TRACE (PINK) E 0 C 0 E HEATER FAN REC 20 1 30

31 1 20 DDC PANEL LG FAN ROOM E 0 A 0 E GFCI HEAT TRACE (GRAY) 20 1 32

33 1 20 ?? E 0 B 0 S SPARE (YELLOW IN UN1) 20 1 34

35 2 30 (N) GENERATOR POWER E 1,620 C 0 S PREPARED SPACE -- -- 36

37 (PROVIDE 2-NEUTRALS) E 600 A 0 S " " -- -- 38

39 1 20 (N) GENERATOR REC S 180 B 0 S " " -- -- 40

41 -- -- PREPARED SPACE S 0 C 0 S " " -- -- 42

MAIN: 225 AMPS MLO PHASE A: 600 VA 5.0 A CONNECTED: 2,400 VA NOTES

TYPE: 208Y/120 V 3 PH, 4 W. PHASE B: 180 VA 1.5 A AMPS: 6.7 A

AIC: 10,000 RMS SYMM. AMPS PHASE C: 1,620 VA 13.5 A VOLTAGE: 208 V

N.E.C. FEEDER CALCULATIONS: (VA) (A) LOAD TYPE:

LIGHTING 0 VA 0.0 A L = LIGHTING (LOAD X 125%)

RECEPTACLES 0 VA 0.0 A R = RECEPTACLES (NEC 220.44)

EQUIPMENT (CONTINUOUS) 0 VA 0.0 A C = EQUIPMENT (CONTINUOUS) X 125%

EQUIPMENT (NON-CONTINUOUS) 2,220 VA 6.2 A E = EQUIPMENT (NON-CONTINUOUS) X 100%

MOTORS 500 VA 1.4 A M = MOTORS (LOAD + 25% OF LARGEST MOTOR)

TOTAL DEMAND LOAD 2,720 VA 7.5 A F = FEEDERS

MOUNTING SPECIAL REQUIREMENTS: S = SPARE OR SPACE LOCATION

SURFACE RM MECH

12"

12"

1. CONDUIT, TYPE SIZE AND NUMBER OF CONDUITS AS SHOWN ON DRAWINGS (TYPICAL).

2. TRENCH MAY BE EXPANDED TO INCLUDE OTHER SYSTEMS (i.e. NATURAL GAS PIPING)

WHERE THESE SYSTEMS ARE INSTALLED A MINIMUM OF 12" FROM ELECTRICAL RACEWAYS.

FINISH GRADE

STRUCTURAL FILL

BEDDING MATERIAL

POWER CONDUIT

CONTROL CONDUIT

SURFACE FINISH TO MATCH

ADJACENT FINISH

MARKER

TAPE (ELEC)

MIN. 24"

6"

6"

6"

AS REQ'D

TYPICAL ELECTRICAL TRENCH DETAIL2

E002 NO SCALE

12" MIN

NATURAL GAS LINE

(WHERE PRESENT)

MARKER

TAPE (GAS)

1. GENERATOR SIZE IS REPRESENTATIVE AND MAY DIFFER FROM FINAL UNIT PROVIDED BY CONTRACTOR.

Donald L. Hopkins

No. EE10582

D E S I G N A

L A

S

(E) WATER WELL

(E) AREA LIGHT POLE

(E) UTILITY TRANSFORMER

AND PAD

(D) 200A MTS

(E) WELL PUMP CONTROLLER

(D) SERVICE DISCONNECT

CABINET WITH INTERNAL CT'S

(SHOWN DASHED LINES)

(E) PULL BOX & METER

(E) NATURAL GAS METER

(E) MDP

(E) BOLLARDS

(E) FENCED

DUMPSTER

AREA

(E) RETAINING WALL

GENERATOR

50 kW 208Y/120V

DUAL FUEL PROPANE/NATURAL GAS

(E) UNDERGROUND PRIMARY

(UTILITY TO LOCATE)

(E) UNDERGROUND SECONDARY

(CONTRACTOR TO LOCATE)

SERVICE DISCONNECT SWITCH &

CT ENCLOSURE

400A AUTOMATIC

TRANSFER SWITCH

FEEDER FROM

GENERATOR AND

CONTROL CABLE

(E) ABANDONED

HEATING PIPES

CAMPBELL CREEK SCIENCE CENTER

REMOTE

ANNUNCIATOR

PANEL

BRANCH CIRCUITS

FOR GENERATOR

SUPPORT POWER

1 JUNCTION BOX

(E) PANEL M1

(E) PANEL M2

DIRECT EXHAUST & NOISE

AWAY FROM BUILDING

10/23/2019 2:06 PM 901901 E100 SITE PLAN.DWG

901901

25 OCT 2019

COMM. NUMBER

ISSUE DATE

DESIGNED BY

DRAWN BY

1"0" SCALE

601 College Road Fairbanks AK 99701 907.452.1241

Architects SurveyorsEngineers

AECC511 designalaska.com

CCSC BACKUP

GENERATOR

E100

DLH

DLH

ELECTRICAL SITE

PLAN

ELECTRICAL SITE PLAN1

E100 1" = 10'

SPECIFIC NOTES

REMOVE EXISTING MANUAL TRANSFER SWITCH AND REPLACE WITH 12" W X 12" LX 8" D

NEMA 3R JUNCTION BOX AND SPLICE EXISTING CONDUCTORS WITHIN NEW ENCLOSURE.

PROVIDE UTILITY LOCATES TO IDENTIFY BELOW GROUND INFRASTRUCTURE AT THE SITE.

KNOWN INFRASTRUCTURE INCLUDES BELOW GRADE UTILITY PRIMARY CONDUCTORS

(ASSUMED TO BE DIRECT BURIAL TYPE). COORDINATE FINAL LOCATION OF GENERATOR

AND PAD WITH BLM PRIOR TO EXCAVATION AND PLACEMENT. CONTRACTOR SHALL NOT

DISTURB GROUND OF TREES WITHIN A RADIUS OF 10' FROM BASE OF TREE.

(E) WELL PUMP CONTROLLER

(D) 200A MTS

(E) CONDUITS TO

MECHANICAL ROOM

REPRESENTATIVE

GENERATOR UNIT

Donald L. Hopkins

No. EE10582

D E S I G N A

L A

S

G001
C100
C700
M100
E001
E002
E100