This performance work statement outlines requirements for relocating and installing a prefabricated communications shelter at a Bureau of Land Management site in California. The contractor will be responsible for picking up the Pepro 2 Bay Micro site and 20-foot mast from the BLM Redding Field Office, transporting it to the Gun Site Peak location, installing it to meet Motorola R56 standards for grounding and other requirements, and conducting tests to demonstrate proper operation. The contractor must have experience installing shelters at remote sites and following all applicable codes and regulations. The work is required to be completed by February 2025 and the contractor will be responsible for scheduling, permits, safety, documentation, and addressing any issues that arise. Acceptance criteria and processes are outlined as well as roles and responsibilities of the government and contractor.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sources_Sought_Cover_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Introduction
The Bureau of Land Management (BLM) communication network is vital to its operational mission to ensure employee safety, public safety, and resource protection. The BLM has identified a need to bring its communications sites to meet or exceed Motorola R56 standards. The Radio Infrastructure Compliance, Assessment, Safety, Health, and Environment (RI CASHE) audit program uses the Motorola Standards and Guidelines for Communication Sites as the minimum requirements for radio facility maintenance and design of the ground ring. RI-CASHE assessments have been performed for some BLM facilities to assist with correcting the deficiencies.
Objective
BLM CA needs to ensure that its operational mission is meet by installing a prefabricated communication site at Gun Site Peak in California per bureau directives. BLM CA requires a contractor with technical expertise in telecom infrastructure to relocation and installation of a government furnished Pepro 2 Bay Micro site. Contractor must have experience with relocating and installing shelters / vaults at remote communication sites to meet or exceed Motorola R56 standards.
General Scope of Work
All work performed under this project shall conform with, or exceed, all applicable requirements and guidelines including, but not limited to, the latest version of the following codes and standards:
A. Motorola R56 Standard B. International Building Code (IBC) C. American National Standards Institute (ANSI) D. American Standard Testing Material (ASTM) E. Federal Acquisition Regulations (FAR) F. National Electric Code (NEC) G. National Electrical Manufacturers Association (NEMA) H. Federal Communications Commission (FCC) I. National Telecommunications and Information Administration (NTIA) J. Any other applicable laws, rules, mandates, directives, and regulations of federal and state and local governmental agencies. Federal requirements shall take precedence in the event of a conflict with state or local regulations.
Note: The site is known as Mahogany Point, but BLM California refers to it as Gun Site Peak
Tasks
1. The Bureau of Land Management (BLM) can be known as Government requires the relocation and installation of a new communications facility (prefabricated shelter / prefabricated vault) at the site named Mahogany Point / Gun Site peak located in California (Siskiyou County).
2. Once the shelter / vault is completely installed on the ground/foundation/etc. it must meet or exceed Motorola R56 standards.
3. Pricing should include anything relevant to the project.
4. The Project consists of furnishing labor, equipment, supplies, and materials to relocate and install an existing prefabricated Pepro 2 Bay Micro Cabinet (shelter / vault) currently located at the BLM Redding Field Office (Address below) and relocate and install the shelter on top of Mahogany Point / Gun Site peak.
· Pickup Site: BLM Redding Field Office 6640 Lockheed Dr, Redding, CA 96002
· Drop off Site Information: Mahogany Point / Gun Site County: (Siskiyou County, CA)
GPS: 41°44’2.63” N 122°44’56.11”W
Elevation: 5987’ City: Yreka, CA
5. The prefabricated government Furnished Equipment (GFE) is a Pepro 2 bay micro site (shelter / vault) and the site accessories.
6. The Pepro 2 bay micro site includes a 20-foot-tall articulating mast that will also need to be installed after relocation.
7. All shelter / vault contractor installed components and accessories installation must meet or exceed Motorola R56 standards after installation. (mast/pole, ballast plates, vault hardware, grounding pads etc.)
8. The shelter / vault (Pepro 2 bay micro site) is currently located at the BLM Redding Field office in the secure parking area.
9. The shelter / vault is currently sitting directly on the ground (asphalt)
10. A forklift may be needed to load the micro site and site accessories (mast, ballast plates, vault hardware, grounding pads etc.)
11. The contractor must comply with manufacturer’s instructions and recommendations for lifting points of products in the applications indicated.
12. Any damage done to the shelter / vault in transport or site erection will be the contractor’s sole responsibility to fix prior to final acceptance by the government.
13. Most site accessories are currently in wooden crates near or around (less than 20ft away(approximate)) of the vault.
14. Two solar panels are being stored inside the Redding Field office. BLM Radio staff will provide the contractor with the solar panels when the contractor picks up the vault.
15. Solar panels can be transported inside the shelter / vault to Mahogany Point / Gun Site peak.
16. The contractor shall provide and install external system and grounding components:
· Common external grounding system
· External grounding pads, leveling jacks and ballast plates.
· Communications shelter grounding
· Grounding of the existing mast ground bus bar (TGB)
· Antenna system grounding (mast / pole)
· Solar Panel Grounding
17. A minimally acceptable final ground resistance of 25 Ohms or less is required in accordance with NEC 250.56 – Resistance of Rod, Pipe, and Plate Electrodes.
18. The contractor must be aware of the surrounding wildlife such as coyotes, rattle snakes, lizards, etc. at any of the BLM locations.
19. The contractor must be aware of changing weather conditions such as but not limited to high winds, rain, snow, tornadoes, hurricanes, tsunamis, etc.
20. It is the contractor’s sole responsibility to always protect their equipment or any equipment in their possession (i.e. rented, or GFE). This includes but not limited to weather (snow, rain, wind, rodents, and people).
21. The contractor is responsible for ensuring that sites are minimally disturbed/impacted during project.
22. The contractor is responsible for remove all refuse/debris must be transported and properly (legally) disposed of offsite at the contractors expense.
23. The contractor may have to demolish rock and move earth to install the vault located at Gun Site Peak. There are leveling jacks on the vault to help, but area under leveling jacks must be clear, clean, and flat.
24. The contractor will be responsible to ensure the shelter / vault is level up on installation at Gun Site Peak.
25. The contractor will be responsible to bring in material (grounding backfill (GEM- Ground Enhancement Material), etc.) to level the ground if needed.
26. It will be the contractor’s sole responsibility to transport the shelter / vault, shelter / vault components / accessories to the appropriate location identified by BLM radio staff.
27. The contractor will be responsible for all required permits to move vault from BLM Redding Field Office (Address is located in the “Administrative Matters” Section) to Mahogany Point / Gun Site Peak (GPS Coordinates are located in the “Administrative Matters” Section).
28. All approx. weights can be found in the shelter / vault Administrative Matters – GFE Shelter/ Vault - Weights section.
29. The contractor may have to drive off road to access the sites BLM Redding Field Office and Mahogany Point / Gun Site Peak.
30. A 4WD (4X4) vehicle may be required to access the sites BLM Redding Field Office and Mahogany Point / Gun Site Peak.
31. The contractor will be responsible to lock the gate(s) every time they enter or exit the main communication site gate located at Redding Field Office and the Mahogany Point / Gun Site Peak communication site.
32. The contractor will have to be always escorted in and around the BLM Redding field office by authorized BLM personnel.
33. The contractor may have to pass on private property to access Mahogany Point / Gun Site Peak.
34. The contractor will schedule a pre-installation meeting:
1. Arrange and schedule pre-installation conference prior to beginning any work on the communications facility.
2. Agenda: Clarify questions in writing related to work to be performed, scheduling, coordination, etc. with the Telecommunications staff or Contracting officer.
3. All individuals, who will be in an on-site supervisory capacity, shall be required to attend the pre-installation conference. This includes project managers, site supervisor, and lead installers.
35. All work must be done to not conflict with BLM personnel (Telecommunication Staff) and events such as but not limited to fires, Glamis, Dumont Dunes, King if the Hammers, and SABER / border operations.
36. The contractor will install the shelter / vault in the agreed orientation and location with the BLM local radio staff.
37. The BLM will supply the contractor with access to the site during normal business hours.
38. Contractor is solely responsible for transporting any required personnel, equipment, and materials to and from the job sites.
39. Transportation to and from sites will be the contractor’s sole responsibility.
40. The BLM Telecommunications Lead (Stan Strizhevsky) will provide access and oversight for any questions or concerns that may come up.
41. The contractor and BLM Telecommunication staff and the local technician will work corroboratively.
42. All Contractor’s work must be neat (tie wrapped, etc.)
43. Clean site and work areas daily including common areas.
44. Burying or burning waste materials at either site will not be permitted.
45. Washing waste materials down sewers or into waterways will not be permitted.
46. Dispose of all materials lawfully.
47. The contractor will be responsible to have certified mast climbers if needed.
48. It is the contractor’s responsibility to fix any damaged caused by the contractor in or above the ground while trenching at no additional cost to the BLM.
49. If welding is required at either site, the contractor will ensure that appropriate measures are in place to prevent a fire or any hazards.
50. Upon on contract award the contractor will provide at least 20 working days (Monday – Friday) prior to project start date sent via email to BLM Telecommunications Staff
51. The contractor will be required to take photographs of all grounding work before, during, and after, and shelter / vault installation work and email photographs to BLM Telecommunications staff via email upon 20 days of completion of project. Please see photograph requirements section.
52. All accessories/parts needed to install the vault will be purchased by the contractor, unless otherwise specified in this contract and with written approval of the Government - Contracting Officer.
53. All non-GFE equipment, material, and associated articles to be used to complete this project shall be new.
54. The contractor must comply with manufacturer’s instructions and recommendations for installation of products in the applications indicated.
55. Existing Conditions: The existence and location of facility improvements, utilities, and other work indicated as existing are not guaranteed. Before beginning work, investigate and verify the existence and location of mechanical and electrical systems affecting the work.
56. Existing Utilities: The existence and location of underground and other utilities indicated as existing are not guaranteed. Before beginning facility work, investigate and verify the existence and location of underground utilities affecting the Work.
57. Acceptance of Conditions: Examine substrates, areas, and conditions, with Installer or Applicator present where indicated, for compliance with requirements for installation tolerances and other conditions affecting performance. Record observations.
58. Existing Utility Information: Furnish information to Contracting Officer that is necessary to adjust, move, or relocate existing utility structures, utility poles, lines, services, or other utility appurtenances located in or affected by vault installation. Coordinate with authorities having jurisdiction.
59. Review of Contract Documents and Field Conditions: Immediately on discovery of the need for clarification of the Contract Documents, submit a request for information to Contracting Officer. Include a detailed description of problem encountered, together with recommendations for changing the Contract Documents.
60. Verification: Before proceeding to lay out the Work, verify layout information shown on Drawings, in relation to the property survey and existing benchmarks. If discrepancies are discovered, notify Contracting Officer promptly.
61. Facility Improvements: Locate and lay out facility improvements, including grading, fill and surface course, and utility slopes.
62. Where work on masts or other communications structures are required, the contractor shall comply with the following:
· ANSI/ASSP A10.48 – Criteria for Safety Practices with the Construction, Demolition, Modification and Maintenance of Communications Structures.
· TIA-322 – Standard for Installation, Alteration & Maintenance of Antenna Supporting Structures and Antennas.
· ANSI/ASSE Z359 – Fall Protection Code
· OSHA 29 CFR 1926, Subpart M – Fall Protection, §1926.500
63. Contractor will be responsible to erecting the government supplied articulating mast that is manufactured and designed by Pepro.
64. When attached to the shelter / vault the mast is approximately 257 1/2” tall or approximately 20’
65. The approximately 20-foot-tall articulating mast will need to be attached to the cabinet and support frame.
66. Contractor will be required to follow all COVID-19 CDC guidelines.
67. Any work performed beyond the scope of the contract or done without the written authorization of the Government shall be deemed unauthorized. If required by the Government, unauthorized work shall be remedied, removed, or replaced by the installation Contractor at the installation Contractor’s sole expense.
68. A final facility inspection by BLM Telecommunication Staff will be required before final acceptance.
69. Following final installation of all components, performance and operational tests shall be performed by the installation contractor to verify proper operation of all subsystems and equipment features. The Government will witness operational performance testing prior to final acceptance, and successful passage of the performance tests shall be a condition of final acceptance and final payment.
70. Performance tests shall be completed on the following equipment and systems at a minimum:
· Installed Surge protection devices.
· Common grounding system
Tentative Schedule
The job is required to have the installation completed by Feb 2025.
Administrative Matters
Site Information: Mahogany Point / Gun Site County: (Siskiyou County, CA)
GPS: 41°44'2.63"N 122°44'56.11"W
Elevation: 5987’ City: Yreka, CA
Pickup Site Location:
BLM Redding Field Office 6640 Lockheed Dr Redding, CA 96002
SAFETY AND HEALTH
All work shall comply with applicable Federal, state, and municipal safety and health codes and requirements. Where there is a conflict between applicable regulations, the Federal requirements shall supersede the others. Contractor shall assume full responsibility and liability for compliance with all applicable regulations pertaining to the health and safety of personnel during the execution of work and shall hold the Government harmless for any action on its part or that of its employees or subcontractors, which results in illness or death. The contractor shall provide all necessary safety equipment, training, and PPE, and ensure that such equipment and all relevant safety procedures are adequate for the job being performed and are utilized properly.
Applicable Specifications, Codes, and Standards
A. The work shall be performed in compliance with applicable codes, and generally accepted standards as described in specification Sections included with this Solicitation as amended and adopted by BLM.
| 1. | In the occurrence of conflicting codes and or standards, the most stringent shall apply, unless otherwise specifically required by the Government’s engineer. |
| 2. | BLM has not adopted the Motorola R-56 Guidelines in their entirety. DOI DD 2009-008 has specific instructions addressing how to implement certain requirements that deviate from the R-56 Guidelines. |
| B. | The work shall be performed in compliance with applicable City, County, and State Codes, including but not limited to building and environmental where required. |
| 1. | In the occurrence of conflicting codes and or standards, the most stringent shall apply, unless otherwise specifically required by the Government’s engineer, Telecommunications Lead, and the Contracting Officer. |
| C. | The work shall be performed in compliance with Occupational Safety and Health Administration – Occupation (OSHA) Safety laws. |
| D. | The work shall be performed in compliance with Prevailing Labor Laws and Wage Rates. |
Document Review Contractor shall review the Motorola R56 Standard document as needed and any Government provided documents. The Government shall review and approve Contractor’s proposed schedule and Contractor’s submitted documents.
Kick-off Meeting & Site Visit Coordination Contractor shall participate in an initial virtual kick-off meeting with the Government within 30 days after award to discuss scope, schedule, logistics, access and any other relevant information for the overall project. Prior to conducting any site visits, contractor shall communicate with the Government to coordinate visits.
Project Closeout Project is complete once the vault has been installed and approved by the Government.
General BLM Responsibilities
· The BLM will provide a primary technical contact BLM Telecommunications Staff to operate as liaison with contractor.
· Attached are Google Earth images of the sites BLM Redding Field Office (Attachment 4D) and Mahogany Point / Gun Site Peak (Attachment 3C)
· BLM Telecommunications staff provide unlimited access to communications vault for project work during normal business hours.
· Provide Pepro 2 Bay Micro Site drawing.
· Provide Pepro 2 Bay Micro Site with 20-foot-tall articulating mast.
· Coordinate with contractor for a proposed project start date upon award of project.
· BLM Telecommunications staff will be available to address issues and or problems that come up before, during or after the project via phone or email.
· BLM Telecommunications staff will respond to issues or problems within one business day.
General Contractor Responsibilities
A. The contractor shall be responsible for the erection of a prefabricated radio communications facility in accordance with details provided in this Summary of Work, relevant specification Sections referenced and incorporated in this Solicitation, and applicable City, County, State, and Federal Codes and Regulations.
B. Utility Location Service: The site erection contractor shall identify location of existing belowground utilities to include but not limited to Telephone Company copper and fiber optic lines, gas lines and electrical transmission lines.
1. Identification and markings of belowground utilities must be performed by a local professional Utility Locator service prior to final design and prior to excavation at the facility.
C. The site erection contractor shall transport and install a new communications equipment cabinet GFE as described in the additional information section.
D. Coordinate with the BLM Telecommunications Staff for a proposed project start date.
E. Ground the prefabricated shelter / vault to meet or exceed Motorola R56 Standards F. Place all ground rings and ground rods to meet or exceed Motorola R56 standards.
G. Communicate all issues and or problems that come up before, during or after the project to BLM point of contact.
H. Ensure all work is done safely.
I. Take all safety measures possible to prevent a Wildfire while working.
J. Keep BLM Radio staff informed of all problems / issues via phone and email during the process.
K. Contractor shall submit a single electronic file containing final installation pictures and reports for Mahogany Point / Gun Site peak.
L. Reports shall be delivered electronically in PDF format to the BLM Radio Staff at the CA State Office.
M. Contractor shall provide the reports and any other documents via email or a filesharing service if the file sizes are too large for email.
N. Pictures included in the reports must be of adequate quality and size to clearly identify the observed facility or deficiency.
O. The Government shall have 30 calendar days after receipt of report(s) to review and comment, and Contractor shall respond to and address any Government comments within 10 calendar days after receipt of comments.
P. Contractor shall include this review period allowance in their submitted schedule(s).
Grounding Electrode System Resistance Test reports
A. Ground resistance testing shall comply with methods approved and described in IEEE 81 – Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System (Current Revision IEEE 81-2012 dated 12/28/2012).
| B. | The following forms are to be used for recording test results of the grounding electrode system. |
| 1. | Attachment 2B – Fall-of-Potential Ground Resistance Field Report |
| 2. | Attachment 1A – Clamp-On Ground Resistance Field Report |
Grounding Electrode System Resistance Testing
A. Fall-of-Potential Testing – Small Grounding systems – 62% Rule (1 to 6 Grounding Electrodes)
1. The fall-of-potential method is often referred to as the "three-point method". Utilizing a ground resistance meter (digital is preferred), two auxiliary electrodes are driven into the soil at predetermined distances (up to 10 times the cross-sectional dimension of the grounding system), per the testing specifications, in a straight line from the ground being tested.
2. During a normal test of ground rod(s) the meter supplies a constant current between the ground rod(s) under test and the most remote auxiliary electrode. A series of measurements of the voltage drops between the ground rod(s) under test and the remote electrode are made by moving the intermediate electrode in steps away from the ground rod under test. The goal is to reach the actual rod’s resistance, and this is most often reached at the 62% distance point.
| B. | Fall-of-Potential Testing – Large Grounding systems (6 or More Grounding Electrodes) The usual method of measurement that works very well has one disadvantage; namely, that it is generally necessary to place the auxiliary current probe at a considerable distance from the earth-electrode system. In some cases, this distance can be as much as 3000 ft., and this is not always convenient or possible. |
| 1. | Intersecting Curves: An alternative method, in which such long leads are not necessary, has been devised called Intersecting Curves. The basic principle is to obtain earth resistance curves for several current electrode spacing and, by assuming several successive positions for the electrical center of the system, to produce intersection curves which will give the earth resistance and the position of the electrical center. |
| a. | Some rather difficult problems are encountered when the resistance of an earth-electrode system, consisting of a few grounding electrodes, ground rods, plates, etc., all connected in parallel and spread over a large area, is to be measured. |
| 2. | Slope Method is a variation of the Intersecting Curves method. This method does not require long lengths of test leads. The section labeled Slope Method provides a detailed explanation of the Slope Method, including relevant tables. |
Fall-of-Potential Method
| A. | The fall-of-potential method is often referred to as the "three-point method". Utilizing a ground resistance meter (digital is preferred), two auxiliary electrodes are driven into the soil at predetermined distances, per the testing specifications, in a straight line from the ground being tested. |
| 1. | Grounding mats and grounding systems, other than rods, often require a modified test method. During a normal test of ground rod(s) the meter supplies a constant current between the ground rod(s) under test and the most remote auxiliary electrode. |
| 2. | A series of measurements of the voltage drops between the ground rod(s) under test and the remote test electrode (Z – Probe – Current) are made by moving the Y – Probe (Potential) in steps away from the ground rod under test. |
| 3. | The goal is to reach the actual rod’s resistance, and this is most often reached at the 62% distance point. |
| 4. | The Z – Probe (current) must be placed a minimum of 5 times the distance of the length of the ground rod being tested. It is preferable the most remote electrode be placed a distance equal to 10 times the length of the rod under test. |
| a. | During the test, the neutral for the commercial electrical service must not be connected to the ground rod. The neutral-to-ground bond must be disconnected, as the current flow on the neutral will invalidate the test results and not all the test instruments provide an accurate reading. |
| 5. | When graphed, the series of measurements of the voltage drops between the ground rod under test and the remote electrode when graphed will provide a chart that will look like the one below. The band of error will be those areas outside the flat part of the graph. |
Slope Method:
| A. | The Slope Method can be used effectively because it does not require the user to find the “flat” portion of the curve or to know the electrical center as a point from which to measure. Readings are taken at 20 percent, 40 percent, and 60 percent of the current probe distance and fit into a mathematical model of the resistance characteristic. |
| B. | It is the purpose of this method to reduce that distance to the current probe, and this appears to have been achieved, but there are some additional points to be noted. From the work, which has been done on the method, there are certain limits to the distance to the current probe. |
| 1. | To comply, if the grounding system is in the form of a square, the minimum distance to the current probe should not be less than the side of the square. On the other hand, the maximum distance should not be too great. If it is, the resulting curve is very flat, and the intersection point becomes rather indefinite. |
| 2. | For a square grounding system, this maximum distance should not exceed twice the side of the square. For other shapes of earth-electrode systems, it is necessary to judge suitable minimum and maximum values for the distance to the current probe. |
| 3. | Suppose that all measurements are made from an arbitrary starting point O, the distance Z to the current probe and the variable distance Y to the potential probe being measured from this point. Then a curve such as ABC (See Figure Below), giving the measured resistance against the value of Z, can be obtained. |
| 4. | Now suppose the electrical center of the earth-electrode system is actually at D, distance X from O. Then the true distance from the center to the current probe is Z + X, and the true resistance is obtained when the potential probe is at a distance 0.618 (Z + X) from D. This means that the value of Y, measured from O, is 0.618 (Z + X) - X. |
| 5. | If X is now given a number of values, the corresponding values of P can be calculated, and the resistance read off the curve. These resistances can be plotted against the values of X in another curve. When this process is repeated for a different value of C, and another curve of resistance against X obtained, the two curves should cross at the required resistance. The process can be repeated for a third value of C as a check. These curves are called intersection curves. It has been assumed that D, O and C are in the same straight line. |
IMAGE 4.6 A
IMAGE 4.6 B
| Probe Setup |
| Enter Resistance Measurement |
| U |
Calculation Enter Value From Table based on Calculated u Value in Column D
| Place Y Probe (Yellow) at Calculated Distance |
| Enter Resistance Measurement |
| Reading |
| Distance to Y |
| Measurement Ohms |
| R3 - R2 = u |
R2 - R1 u = DP/DC from Table Distance to Z Probe (ft.)
(DZ)
True Resistance Distance (ft.) = (u x DZ) True Resistance (Ohms)
| R1 - 60% |
| 36 |
| 28 |
| 1.00 |
| 0.542 |
| 60 |
| 33 |
| 25 |
| R2-- 40% |
| 24 |
| 23 |
| R3 - 20% |
| 12 |
| 18 |
Table 4.6 A – Example of Calculations
| 6. | The other challenges faced in testing large ground systems relate to the capabilities of the test instrument. Improved technology has made it possible for instruments to be designed that address problems created by the characteristics and conditions found in and around large ground systems. |
| 7. | For the Slope Method to provide meaningful results, accurate measurement of the variations at different points is critical. Since large ground systems typically have resistance values of less than 0.5 Ω, the differences can be quite small. An instrument with 1 mΩ measurement resolution can indicate the small differences between low readings. |
| 8. | Noise is a major problem in testing large ground systems and must be addressed to ensure accurate results. To be effective, the test instrument must be designed to overcome the effects of significant noise in the test environment. Among the technical capabilities that can help offset the noise problem are: |
| a. | A variable test frequency (rather than a single, fixed test frequency) which can help remove any stray noise that could affect the reading. |
| b. | A high peak-to-peak interference suppression level. |
| c. | A sophisticated filter system to reject more noise. |
| d. | Various current settings to improve the signal-to-noise ratio when necessary. |
| μ |
| DP/Dc |
| μ |
| DP/Dc |
| μ |
| DP/Dc |
| μ |
| DP/Dc |
| μ |
| DP/Dc |
| 0.65 |
| 0.606 |
| 0.91 |
| 0.560 |
| 1.17 |
| 0.502 |
| 1.43 |
| 0.418 |
| 0.40 |
| 0.643 |
| 0.66 |
| 0.604 |
| 0.92 |
| 0.558 |
| 1.18 |
| 0.499 |
| 1.44 |
| 0.414 |
| 0.41 |
| 0.642 |
| 0.67 |
| 0.602 |
| 0.93 |
| 0.556 |
| 1.19 |
| 0.497 |
| 1.45 |
| 0.410 |
| 0.42 |
| 0.640 |
| 0.68 |
| 0.601 |
| 0.94 |
| 0.554 |
| 1.20 |
| 0.494 |
| 1.46 |
| 0.406 |
| 0.43 |
| 0.639 |
| 0.69 |
| 0.599 |
| 0.95 |
| 0.552 |
| 1.21 |
| 0.491 |
| 1.47 |
| 0.401 |
| 0.44 |
| 0.637 |
| 0.70 |
| 0.597 |
| 0.96 |
| 0.550 |
| 1.22 |
| 0.488 |
| 1.48 |
| 0.397 |
| 0.45 |
| 0.636 |
| 0.71 |
| 0.596 |
| 0.97 |
| 0.548 |
| 1.23 |
| 0.486 |
| 1.49 |
| 0.393 |
| 0.46 |
| 0.635 |
| 0.72 |
| 0.594 |
| 0.98 |
| 0.546 |
| 1.24 |
| 0.483 |
| 1.50 |
| 0.389 |
| 0.47 |
| 0.633 |
| 0.73 |
| 0.592 |
| 0.99 |
| 0.544 |
| 1.25 |
| 0.480 |
| 1.51 |
| 0.384 |
| 0.48 |
| 0.632 |
| 0.74 |
| 0.591 |
| 1.00 |
| 0.542 |
| 1.26 |
| 0.477 |
| 1.52 |
| 0.379 |
| 0.49 |
| 0.630 |
| 0.75 |
| 0.589 |
| 1.01 |
| 0.539 |
| 1.27 |
| 0.474 |
| 1.53 |
| 0.374 |
| 0.50 |
| 0.629 |
| 0.76 |
| 0.587 |
| 1.02 |
| 0.537 |
| 1.28 |
| 0.471 |
| 1.54 |
| 0.369 |
| 0.51 |
| 0.627 |
| 0.77 |
| 0.585 |
| 1.03 |
| 0.535 |
| 1.29 |
| 0.468 |
| 1.55 |
| 0.364 |
| 0.52 |
| 0.626 |
| 0.78 |
| 0.584 |
| 1.04 |
| 0.533 |
| 1.30 |
| 0.465 |
| 1.56 |
| 0.358 |
| 0.53 |
| 0.624 |
| 0.79 |
| 0.582 |
| 1.05 |
| 0.531 |
| 1.31 |
| 0.462 |
| 1.57 |
| 0.352 |
| 0.54 |
| 0.623 |
| 0.80 |
| 0.580 |
| 1.06 |
| 0.528 |
| 1.32 |
| 0.458 |
| 1.58 |
| 0.347 |
| 0.55 |
| 0.621 |
| 0.81 |
| 0.579 |
| 1.07 |
| 0.526 |
| 1.33 |
| 0.455 |
| 1.59 |
| 0.341 |
| 0.56 |
| 0.620 |
| 0.82 |
| 0.577 |
| 1.08 |
| 0.524 |
| 1.34 |
| 0.452 |
| 1.60 |
| 0.338 |
| 0.57 |
| 0.618 |
| 0.83 |
| 0.575 |
| 1.09 |
| 0.522 |
| 1.35 |
| 0.448 |
| 1.61 |
| 0.335 |
| 0.58 |
| 0.617 |
| 0.84 |
| 0.573 |
| 1.10 |
| 0.519 |
| 1.36 |
| 0.445 |
| 1.62 |
| 0.331 |
| 0.59 |
| 0.615 |
| 0.85 |
| 0.571 |
| 1.11 |
| 0.517 |
| 1.37 |
| 0.441 |
| 1.63 |
| 0.328 |
| 0.60 |
| 0.614 |
| 0.86 |
| 0.569 |
| 1.12 |
| 0.514 |
| 1.38 |
| 0.438 |
| 1.64 |
| 0.325 |
| 0.61 |
| 0.612 |
| 0.87 |
| 0.567 |
| 1.13 |
| 0.512 |
| 1.39 |
| 0.434 |
| 1.65 |
| 0.322 |
| 0.62 |
| 0.610 |
| 0.88 |
| 0.566 |
| 1.14 |
| 0.509 |
| 1.40 |
| 0.431 |
| 1.66 |
| 0.319 |
| 0.63 |
| 0.609 |
| 0.89 |
| 0.564 |
| 1.15 |
| 0.507 |
| 1.41 |
| 0.427 |
| 1.67 |
| 0.316 |
| 0.64 |
| 0.607 |
| 0.90 |
| 0.562 |
| 1.16 |
| 0.504 |
| 1.42 |
| 0.423 |
| 1.68 |
| 0.313 |
Typical view of an aluminum 2-Bay Micro Cabinet grounding system is shown below.
Keynotes
Keynote symbols are used throughout this Performance Work Statement and on the Government provided layout drawings. The Keynotes provide easy reference between the work required and the preliminary designs. Each symbol represents a separate area of concern. The contractor shall include these Keynotes as an easy reference to this Performance Work Statement.
1. Oval – External Grounding Device
KEYNOTE Table
| DESCRIPTION |
| KEYNOTE |
Ground Rod
Concrete Encased Electrode (UFER)
Tower / Mast Ground Bus Bar
#2 AWG, bare solid tinned copper Conductor
Shelter Ground Ring
Photograph Requirements The contractor shall provide digital photographs of all below grade ground rings prior to backfill and concrete. Formatting requirements for photographs are listed below:
| 1. | Photographs shall be taken with a minimum 11-megapixel resolution. |
| 2. | Photographs shall be labeled, and time stamped with the date taken. |
| 3. | A measuring tape shall be included in photographs referencing all measurements specific to the requirements of the facility. (e.g. mast ground ring conductor at a depth of two feet and maintaining a distance of two feet from the mast foundation) |
D. The following shall be provided at a minimum:
1. Shelter Foundation Installation
a. Complete photographs of reinforcement structure including, but not limited to, diameter of reinforcement bar, spacing of reinforcement bar, total reinforcement structure, reinforcement structure with measurements depicting proximity from concrete forms (fabricated and earthen), and depth below grade for each foundation.
b. Photographs of all sides of each concrete foundation(s) with forms removed prior to backfill.
c. Tape measurements of each final foundation dimensions for width, length, and height extending above grade.
| 2. | Concrete Encased Electrode (Ufer) Installation |
| a. | Photograph of tape measurement of each grounding electrode conductor or rebar section verifying minimum 20-foot length. |
| 1) | Where reinforcing bar (rebar) is used as the grounding electrode, a photograph of each grounding pigtail connection to the rebar shall be provided. |
| 2) | Photograph of tape measurement of each grounding pigtail length extending through the PVC conduit. |
2. Equipment Shelter Grounding
| a. | Prefabricated Shelter |
| 1) | Tape measurement showing depth of each ground rod and the conductor to grade. |
| 2) | Tape measurement showing distance of ground rods and conductors from shelter foundation. |
| 3) | All exothermic welds or high-compression crimp connections including ancillary device conductors to ground ring, ground ring conductors to each other, and ground ring conductors to ground rods. |
| 4) | Tape measurement showing distance between ground rods. |
| 5) | Tape measurement showing diameter of ground rods and grounding conductors. |
| 6) | Photographs of both grounding conductors bonding the shelter ground ring to the mast ground ring. |
| 4. | Ancillary Device Grounding |
| a. | Photograph of each ancillary device grounding conductor pigtail connection to the shelter or mast ground ring. |
| b. | Fences and Gates, if applicable |
| c. | Ice-bridges, if applicable |
| 5. | Ground Bus Bars |
a. Photograph of each bus bar grounding conductor pigtail connection to the shelter or mast ground ring. To Include:
| 1) | External Ground Bus Bar |
| 2) | Mast Ground Bus Bar |
| 3) | Master Ground Bus Bar |
| 4) | Subsystem Ground Bus Bar |
| 6. | Electrical Service-Entrance Conduits (If applicable) |
| a. | Tape measurement showing depth of trench to grade. |
| b. | Tape measurement showing depth of contractor-provided conduit between the transformer/utility pole and the shelter. |
| c. | Tape measurement showing the diameter of conduit installed. |
| 7. | Electrical Service-Entrance Grounding (If applicable) |
a. Photograph of the service-entrance grounding conductor pigtail connection to the shelter ground ring.
| 8. | Mast Grounding |
| a. | Tape measurement showing depth of each ground rod and the conductor to grade. |
| b. | Tape measurement showing distance of ground rods and conductors from mast foundation. |
| c. | All exothermic welds or high-compression crimp connections including ancillary device conductors to ground ring, ground ring conductors to each other, and ground ring conductors to ground rods. |
d. Tape measurement showing distance between ground rods.
| e. | Tape measurement showing diameter of ground rods and grounding conductors. |
| f. | Photographs of both grounding conductors bonding the mast ground ring to the shelter ground ring. |
| g. | Photograph of each mast leg ground conductor connection to the mast ground ring. |
| h. | Photograph ground conductor connection to the mast ground ring. |
GOVERNMENT FURNISHED Equipment
· Pepro 2 Bay Micro Site, 20-foot-tall articulating mast, and site accessories (Ballast Plates, Solar Panels, concrete pads, solar bracket, etc.)
GFE Shelter / Vault Information
2 Bay Micro Site is MAnufactured by Pepro
Link FOR REFERENCE ONLY to PEPRO, LLC http://www.peprollc.com/
Aluminum Enclosure
A. Uni-Body Aluminum Enclosure
| 1. | Material: |
| a. | Wall, Roof, & Floor Sheathing: 3/16" Aluminum- 5052 |
| b. | Wall & Roof Studs: 2x2x0.25 Aluminum Tube- 6061 & 3x2x0.25 Aluminum Tube- 6061 |
| c. | Floor Supports: I3x2.59 Aluminum I-Beam- 6061D. |
| B. | Finish: |
| 1. | Exterior: 3/16" Aluminum with UV resistant Primer & Paint |
| 2. | Interior: |
| a. | Walls and Ceiling: 1/16”” FRP Paneling |
| C. | Cabinet Exterior Color: The cabinet’s exterior color shall be PEPRO Clay |
| D. | Cabinet Insulation Values: |
| 1. | Wall = R-13 Foil faced Foam Board Insulation |
| 2. | Ceiling = R-13 Foil faced Foam Board Insulation |
| E. | Cabinet Loads: Cabinet will meet listed loads. |
| 1. | Wind loads |
| a. | Ultimate Wind Speed (Vult), for a Risk Category IV structure = 120 mph. |
| b. | Nominal Wind Speed (Vasd) = 93 mph. |
| c. | Wind Exposure Class for this site is Exposure C, with a Surface Roughness Category C for all directions. |
| d. | The Topographic Factor for this site (Kzt) = 1.3225. |
| e. | Wind Load Importance factor is 1.15. |
| 2. | Flat-roof snow load (Pf) = 15 PSF; Snow exposure factor (Ce) = 0.9; Snow load importance factor (I) = 1.2; Thermal Factor (Ct) = 1.0 (Refer to ASCE 7-10, Chapters 1, 7 and appendices) |
| 3. | Earthquake Design Loading: |
| a. | “Risk Category for this facility is III (essential facility). Therefore, the Importance factor to be applied to the seismic calculations is 1.5. |
| b. | Site Class (soil type) is Class D, Stiff Soil (since we do not have site-specific soil information). The following are the parameters to be used in designing the facility and supports for internal equipment: |
| 4. | Soil Bearing Capacity: |
a. Use results from the site-specific soil investigation report. If no report is available, use a maximum surface soil bearing capacity of 1,500 PSF.
5. Flood Design
a. The site is not located in any known flood hazard zones and is not subject to localized flooding.
Weights
| Enclosure weight: | 900lbs | ||
| 20ft Mast Assembly weight: | 200lbs | ||
| Mast Platform weight: | 620lbs | ||
| (16) Steel Ballast Plate weight: | 1600lbs | ||
| (4) Concrete Pad weight: | 880lbs | ||
| Solar Bracket weight: | 200lbs |
Total Shelter/Vault Weight 4,400lbs (Approximate)
Work Hours
The performance period established for this contract is based upon all work being conducted by the contractor and scheduled by the contractor. Contractor will require initial site access afterwards they are free to come and go to complete the work.
Government personnel will be available for communication or access to sites during regular working hours between 8:00 am and 4:00 pm PST, Monday through Friday, excluding government holidays.
Communications
“Time” for communications received after 3:00pm, after 12:00 pm locally on Fridays, or after 12:00 pm locally prior to a holiday will not start until the next business day. All times are local Pacific Standard Time (PST).
The following Federal Holidays are observed
| Monday, January 01 | New Year’s Day | |
| Monday, January 15 | Birthday of Martin Luther King, Jr. | |
| Monday, February 19 | Washington’s Birthday | |
| Monday, May 27 | Memorial Day | |
| Wednesday, June 19 | Juneteenth National Independence Day | |
| Thursday, July 04 | Independence Day | |
| Monday, September 02 | Labor Day | |
| Monday, October 14 | Columbus Day | |
| Monday, November 11 | Veterans Day | |
| Thursday, November 28 | Thanksgiving Day | |
| Wednesday, December 25 | Christmas Day |
BLM Telecommunications (Telecom) Staff
No questions will be asked to the BLM Radio Staff until after the contract has been awarded. For all questions prior to the solicitation must go through the contracting officer / contract specialist assigned to the requirement.
Additional Information
Final Inspection and Acceptance Criteria
The Government may conduct inspections and site visits during and after the performance of maintenance work.
Contractor will demonstrate (at a minimum) the following:
· Inspection and testing of all equipment and systems have been completed in a professional manner that is consistent with industry and applicable standards.
· Any removed BLM equipment is accounted for and placed together as designated by BLM at each site in good condition.
· Work site is clean and free of contractor debris and material at the end of the assessments.
· As-builts/record drawings of ground ring, any support documentation (e.g. passwords, manuals, photographs, etc.), and other relevant materials are given to BLM designated personnel BLM Radio Staff at completion of project.
Final Acceptance
Acceptance by the Government shall only occur after the satisfactory completion of the inspection and assessments of the facilities and their systems, testing, reporting, and any other requirements within the PWS.
Warranty
The contractor shall guarantee that all inspected parts, components, and systems meet the minimum requirements and specifications set forth in this document unless explicitly noted otherwise in the contractor’s reports for 30 days.
Definitions
Backfill Material: Ground Enhancement Material (GEM) - a conductive material used in areas of poor conductivity, such as rocky ground, mountain tops and sandy soil. It has low-resistance, non-corrosive, and is a carbon-based material.
Government: refers to the Bureau of Land Management Contracting Officer (CO) or the Contracting Officer’s Representative (COR).
Government Furnished Equipment (GFE) – equipment/property owned by the government and delivered to or made available to a contractor Land Mobile Radio - a person-to-person voice communication system consisting of two-way radio transceivers which can be stationary, mobile, or portable.
Panel - A collection of modules mechanically fastened together, wired, and designed to provide a field-installable unit.
Shelter / Vault – Pepro 2 Bay Micro site
Attachment 1A
ATTACHMENT 2B
PROJECT TITLE: RI CASHE Gun Site Peak Site Install Performance Work Statement (PWS)
2 | Page RI CASHE - Gun Site Peak - Vault Install Attachment 3C
Attachment 4D
Performance Requirements Summary (PRS) (How will you determine that success has been achieved? This QASP summarizes in one table what the Government's expectations are, how deliverables or services will be monitored and evaluated, and applicable consequences and [dis]incentives that encourage the contractor to fully perform to the appropriate standards.)
| Work Tasks to be Performed |
| Acceptable Quality Level |
| Method of Surveillance |
| Consequences, Remedies, and/or Deduction(s) |
Task(s) 1-3
1. Pick up the prefabricated vault.
2. Transport the vault.
3. Install the vault to R56 Standards
| Must meet R56 Standards |
| Contractor will be required to take photos of work. |
| Vendor will be required to meet R56 standards prior to request for payment. |
image3.jpg image4.jpg image5.jpg image6.jpg image7.jpg image8.jpg image9.jpg image10.jpg image11.jpg image12.jpg image13.jpg image14.jpg image15.jpg image16.jpg image17.jpg image18.jpg image19.jpg image20.jpg image21.jpg image22.jpg image23.jpg image24.jpg image25.jpg image26.jpg image27.jpg image28.jpg image29.jpg image30.jpg image31.jpg image32.jpg image33.jpg image34.jpg image35.jpg image36.jpg image37.jpg image38.jpg image39.png image40.jpg image41.JPG image42.JPG image1.jpg image2.jpg