Attachment_A_-_Schematics.pdf
PDF 18 MB Posted
- Attached to
- Charging Management Services for EVSE
- Solicitation number
- ITB0000014
- Issued by
- Miami-Dade County, Florida
About this file
This is a schematic drawing document for an electric bus charging infrastructure installation project at the Miami-Dade County Central Facility located at 3300 NW 32nd Avenue, Miami, Florida 33142. The project involves the installation of 24 Proterra 120kW power units, 24 Proterra charging dispensers, 2 utility transformers, 2 2500-ampere switchboards, 1 indoor Proterra 120kW power unit, and 1 indoor Proterra 120kW charging dispenser. The facility is located in flood zone AE with a base flood elevation of 8 feet. The project includes comprehensive electrical, civil, and structural work with detailed specifications for conduit routing, grounding systems, concrete pads, utility connections, and equipment anchorage. The drawings are marked as "AS BUILT" and dated 02/01/23, indicating completion of the construction phase. The project incorporates two separate electrical systems (Switchboard A and Switchboard B), each serviced by a 1500kVA utility transformer operating at 480/277 volts, three-phase, four-wire configuration with 65kA interrupting capacity.
The specifications require all work to comply with the 2020 Florida Building Code, 2017 National Electrical Code, Buy America Act requirements, and OSHA standards. The electrical contractor must obtain all necessary permits and inspections prior to work commencement and provide a one-year warranty on all materials and work from the date of acceptance. The project is located at an active 24/7 working facility where ongoing bus operations cannot be disrupted, requiring any power outages to be approved at least two weeks in advance and close coordination with facility management. The contractor is responsible for utility locating services, site security, erosion control measures, and restoration of damaged pavement to 4000 PSI concrete specifications. Grounding systems include concrete-encased electrodes with #4 AWG bare copper grounding electrode conductors and 5/8-inch by 8-foot copper-clad ground rods installed per NEC standards. The design demonstrates available fault current ranging from approximately 19.5kA to 23.7kA depending on conductor run lengths, with voltage drop calculations provided for each charging station circuit.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment A – Schematics
REV DESCRIPTIONDATE
CHECKED BY:
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
A
S
B
U
I
L
T
TITLE SHEET &
PROJECT DATA
T-1
FL-P001
3300 NW 32ND AVE
MIAMI, FL 33142
2TITLE SHEET & PROJECT DATA
OVERALL SITE PLANC-1
E-2
EQUIPMENT DETAILSD-1
T-1
THIS SITE IS LOCATED IN FLOOD ZONE "AE".
AREA DETERMINED TO BE INSIDE THE 100-YEAR FLOOD
PLAIN WITH A BASE FLOOD ELEVATION OF 8 FT.
PERMITTING JURISDICTION:
OCCUPANCY:
OCCUPANT LOAD:
MIAMI-DADE COUNTY
GROUP U
2 (SEE SHEET C-4)
SITE
SITE
FPL
POWER COMPANY:
COUNTY:
MIAMI-DADE
MIAMI-DADE COUNTY
PROPERTY OWNER:
LEAD CIVIL ENGINEER:
CHRIS ZERR
(913) 458-2792
ZERRC@BV.COM
LOCATION MAPAREA MAP PROJECT DESCRIPTIONSITE INFORMATION
CONTRACTOR NOTE
CONTRACTOR SHALL COMPLETE INSTALLED PER THE SIGNED
AND THE SEALED SET OF DRAWINGS. ANY NECESSARY
DEVIATIONS FROM THE DRAWINGS MUST BE SUBMITTED
THROUGH AN RFI REQUEST PROCESS WITH ENGINEERING FOR
AN APPROVAL PRIOR TO CONTRACTOR PROCEEDING WITH A
DEVIATION OF THE SIGNED AND SEALED SET OF DRAWINGS.
CALL BEFORE YOU DIG ENGINEER OF RECORDDO NOT SCALE DRAWINGS
CONTRACTOR SHALL VERIFY ALL PLANS, EXISTING DIMENSIONS &
CONDITIONS ON THE JOB SITE & SHALL IMMEDIATELY NOTIFY THE
ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING
WITH THE WORK.
ZONING INFORMATION
FLOOD HAZARD AREA NOTE
APPLICABLE CODES
FOR REFERENCE ONLY DRAWINGS
SHEET NO:
DRAWING INDEX
SHEET TITLE
REV
NO:
EQUIPMENT DETAILSD-2
CENTRAL FACILITY
INSTALLATION OF ELECTRIC BUS CHARGING EQUIPMENT
ELECTRICAL PLAN
E-4 ELECTRICAL DETAILS
ENLARGED SITE PLAN
C-2
ELECTRICAL DETAILS
GROUNDING DETAILSG-1
TAYLOR MURPHY
PE # 82722
BLACK & VEATCH CORPORATION
CIVIL
E-2.1
SINGLE LINE DIAGRAM
3300 NW 32ND AVE
MIAMI, FL 33142
SITE ADDRESS:
SITE ELEVATIONS
C-3
· INSTALLED (24) PROTERRA 120KW POWER UNITS
· INSTALLED (24) PROTERRA CHARGING DISPENSERS
· INSTALLED (2) UTILITY TRANSFORMERS
· INSTALLED (2) 2500 AMP SWITCHBOARDS
· INSTALLED (1) INDOOR PROTERRA 120KW POWER UNIT
· INSTALLED (1) INDOOR PROTERRA 120KW CHARGING
DISPENSER
C-5
DEMOLITION SITE PLAN
PROPERTY SURVEY
UTILITY PLAN
LEAD ELECTRICAL ENGINEER:
GREG KRUG
(913) 458-2881
KRUGGD@BV.COM
GENERAL NOTES 1GN-1
GENERAL NOTES 2GN-2
GENERAL NOTES 3GN-3
RYAN R. BINKLEY
PE # 89014
BLACK & VEATCH CORPORATION
ELECTRICAL
ALL WORK SHALL COMPLY WITH THE FOLLOWING
APPLICABLE CODES:
2020 FLORIDA BUILDING CODE
2020 FLORIDA STRUCTURAL CODE
2020 FLORIDA PLUMBING CODE
2020 FLORIDA MECHANICAL CODE
2017 NATIONAL ELECTRICAL CODE
FLORIDA FIRE PREVENTION CODE
ADAAG (FLORIDA STATE ACCESSIBILITY CODE)
IN THE EVENT OF CONFLICT, THE MOST RESTRICTIVE CODE
SHALL PREVAIL
UNDERGROUND SERVICE ALERT
UTILITY NOTIFICATION CENTER OF FLORIDA
811 OR 1-800-432-4770
3 WORKING DAYS UTILITY NOTIFICATION PRIOR TO CONSTRUCTION
CONTRACTOR MUST ALSO COORDINATE WITH DTPW ROW BEFORE EXCAVATING THE AREA
E-3
SINGLE LINE DIAGRAM
FOLIO NUMBER:
LATITUDE (NAD83):
25° 48' 18.6" N
25.805158°
LONGITUDE (NAD83):
80° 14' 57.8" W
-80.249398°
30-2128-031-0010
C-4 ENLARGED EQUIPMENT PLAN
E-1
BUS ROUTE PLANC-6
GRADING PLANC-7
POWER UNIT & DC CHARGING POST LENGTHE-1.1
OVERALL SITE PLANC-1.1
EQUIPMENT DETAILSD-3
E-2.2 ELECTRICAL PLAN & ONE LINE DIAGRAM
EQUIPMENT COMMUNICATION PLANC-4.1 2
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
GENERAL NOTES 1
GN-1
GENERAL CONSTRUCTION NOTES GENERAL CONSTRUCTION NOTES CONT.
ELECTRICAL NOTES
ELECTRICAL NOTES CONT.
1. FOR THE PURPOSE OF CONSTRUCTION DRAWINGS, THE FOLLOWING DEFINITIONS SHALL APPLY
GENERAL CONTRACTOR: OVERLAND CONTRACTING INC. (BLACK & VEATCH)
CONTRACTOR: (CONSTRUCTION) (TBD) (MUST BE LICENSED IN THE STATE OF FLORIDA)
OWNER: PROTERRA
2. ALL SITE WORK SHALL BE COMPLETED AS INDICATED ON THE DRAWINGS.
3. THE GENERAL CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE THEMSELVES WITH
ALL CONDITIONS AFFECTING THE PROPOSED WORK AND SHALL MAKE PROVISIONS. GENERAL
CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING THEMSELVES WITH ALL CONTRACT
DOCUMENTS, FIELD CONDITIONS, DIMENSIONS, AND CONFIRMING THAT THE WORK MAY BE
ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING WITH CONSTRUCTION. ANY DISCREPANCIES
SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO COMMENCEMENT OF
WORK.
4. ALL MATERIALS FURNISHED AND INSTALLEDED MUST COMPLY TO THE BUY AMERICA ACT .
SELECTED CONTRACTOR TO PROVIDE BUY AMERICA CERTIFICATION LETTER AND SHALL BE IN
STRICT ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS, AND ORDINANCES.
GENERAL CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS,
ORDINANCES, RULES, REGULATIONS, AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY
REGARDING THE PERFORMANCE OF WORK.
5. ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY
COMPANY SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES, AND
APPLICABLE REGULATIONS. FLORIDA BUILDING CODE - LATEST EDITION.
6. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT, APPURTENANCES, AND LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED
ON THE DRAWINGS.
7. PLANS ARE NOT TO BE SCALED. THESE PLANS ARE INTENDED TO BE A DIAGRAMMATIC OUTLINE
ONLY UNLESS OTHERWISE NOTED. DIMENSIONS SHOWN ARE TO FINISH SURFACES UNLESS
OTHERWISE NOTED. SPACING BETWEEN EQUIPMENT IS THE MINIMUM REQUIRED CLEARANCE.
THEREFORE, IT IS CRITICAL TO FIELD VERIFY DIMENSIONS, SHOULD THERE BE ANY QUESTIONS
REGARDING THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
OBTAINING A CLARIFICATION FROM THE ENGINEER PRIOR TO PROCEEDING WITH THE WORK.
DETAILS ARE INTENDED TO SHOW DESIGN INTENT. MODIFICATIONS MAY BE REQUIRED TO SUIT
JOB DIMENSIONS OR CONDITIONS AND SUCH MODIFICATIONS SHALL BE INCLUDED AS PART OF
WORK AND PREPARED BY THE ENGINEER PRIOR TO PROCEEDING WITH WORK.
8. THE CONTRACTOR SHALL INSTALLED ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE.
9. IF THE SPECIFIED EQUIPMENT CANNOT BE INSTALLEDED AS SHOWN ON THESE DRAWINGS, THE
CONTRACTOR SHALL PROPOSE AN ALTERNATIVE INSTALLEDATION SPACE FOR APPROVAL BY
DTPW AND THE ENGINEER PRIOR TO PROCEEDING.
10. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF WORK AREA,
ADJACENT AREAS, AND BUILDING OCCUPANTS THAT ARE LIKELY TO BE AFFECTED BY THE
WORK UNDER THIS CONTRACT. WORK SHALL CONFORM TO ALL OSHA REQUIREMENTS AND THE
LOCAL JURISDICTION. THIS IS A WORKING FACILITY (24-7) AND ON GOING BUS OPERATIONS
CANNOT BE IMPACTED. CLOSE COORDINATION IS REQUIRED. ANY POWER OUTRAGES MUST BE
APPROVED AT LEAST 2 WEEKS IN ADVANCED.
11. THE GENERAL CONTRACTOR SHALL COORDINATE WORK AND SCHEDULE WORK ACTIVITIES WITH
OTHER DISCIPLINES.
12. CONSTRUCTION SHALL BE DONE IN A WORKMANLIKE MANNER BY COMPETENT EXPERIENCED
WORKMAN IN ACCORDANCE WITH APPLICABLE CODES AND THE BEST ACCEPTED PRACTICES.
13. WORK PREVIOUSLY COMPLETED IS REPRESENTED BY LIGHT SHADED LINES AND NOTES. THE
SCOPE OF WORK FOR THIS PROJECT IS REPRESENTED BY DARK SHADED LINES AND NOTES.
CONTRACTOR SHALL NOTIFY THE GENERAL CONTRACTOR OF ANY EXISTING CONDITIONS THAT
DEVIATE FROM THE DRAWINGS PRIOR TO BEGINNING CONSTRUCTION.
14. THE CONTRACTOR SHALL PROVIDE WRITTEN NOTICE TO THE CONSTRUCTION MANAGER 48
HOURS PRIOR TO COMMENCEMENT OF WORK.
15. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS,
LANDSCAPING, AND STRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S
EXPENSE TO THE SATISFACTION OF THE OWNER.
16. THE CONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF
CONSTRUCTION.
17. THE GENERAL CONTRACTOR SHALL COORDINATE AND MAINTAIN ACCESS FOR ALL TRADES AND
CONTRACTORS TO THE SITE AND/OR BUILDING.
18. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR SECURITY OF THE SITE FOR THE
DURATION OF CONSTRUCTION UNTIL JOB COMPLETION.
19. THE GENERAL CONTRACTOR SHALL MAINTAIN IN GOOD CONDITION ONE COMPLETE SET OF
PLANS WITH ALL REVISIONS, ADDENDA, AND CHANGE ORDERS ON THE PREMISES AT ALL TIMES.
20. THE CONTRACTOR SHALL PROVIDE PORTABLE FIRE EXTINGUISHERS WITH A RATING OF NOT
LESS THAN A:10-B:C AND SHALL BE WITHIN 25 FEET OF TRAVEL DISTANCE TO ALL PORTIONS OF
WHERE THE WORK IS BEING COMPLETED DURING CONSTRUCTION.
21. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES SHALL BE
PROTECTED AT ALL TIMES, AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE WORK,
SHALL BE RELOCATED AS DIRECTED BY THE ENGINEER. EXTREME CAUTION SHOULD BE USED BY
THE CONTRACTOR WHEN EXCAVATING OR DRILLING PIERS AROUND OR NEAR UTILITIES. THE
CONTRACTOR SHALL PROVIDE SAFETY TRAINING FOR THE WORKING CREW. THIS SHALL
INCLUDE BUT NOT BE LIMITED TO A) FALL PROTECTION, B) CONFINED SPACE, C) ELECTRICAL
SAFETY, AND D) TRENCHING & EXCAVATION.
22. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES, WHICH
INTERFERE WITH THE EXECUTION OF THE WORK, SHALL BE REMOVED, CAPPED, PLUGGED OR
OTHERWISE DISCONNECTED AT POINTS WHICH WILL NOT INTERFERE WITH THE EXECUTION OF
THE WORK, AS DIRECTED BY THE ENGINEER, AND SUBJECT TO THE APPROVAL OF THE OWNER
AND/OR LOCAL UTILITIES.
23. THE AREAS OF THE OWNER'S PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE
EQUIPMENT OR DRIVEWAY, SHALL BE GRADED TO A UNIFORM SLOPE, AND STABILIZED TO
PREVENT EROSION.
24. CONTRACTOR SHALL MINIMIZE DISTURBANCE TO THE EXISTING SITE DURING CONSTRUCTION.
EROSION CONTROL MEASURES, IF REQUIRED DURING CONSTRUCTION, SHALL BE IN
CONFORMANCE WITH THE FEDERAL AND LOCAL JURISDICTION FOR EROSION AND SEDIMENT
CONTROL.
25. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN
MATERIALS, SNOW, OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT.
26. THE SUBGRADE SHALL BE BROUGHT TO A SMOOTH UNIFORM GRADE AND COMPACTED TO 95
PERCENT STANDARD PROCTOR DENSITY UNDER PAVEMENT AND STRUCTURES AND 80 PERCENT
STANDARD PROCTOR DENSITY IN OPEN SPACE. ALL TRENCHES IN PUBLIC RIGHT OF WAY SHALL
BE BACKFILLED WITH FLOWABLE FILL OR OTHER MATERIAL PRE-APPROVED BY THE LOCAL
JURISDICTION.
27. ALL NECESSARY RUBBISH, STUMPS, DEBRIS, STICKS, STONES, AND OTHER REFUSE SHALL BE
REMOVED FROM THE SITE AND DISPOSED OF IN A LAWFUL MANNER.
28. ALL BROCHURES, OPERATING AND MAINTENANCE MANUALS, CATALOGS, SHOP DRAWINGS, AND
OTHER DOCUMENTS SHALL BE TURNED OVER TO THE GENERAL CONTRACTOR AT COMPLETION
OF CONSTRUCTION AND PRIOR TO PAYMENT.
29. THE CONTRACTOR SHALL SUBMIT A COMPLETE SET OF AS-BUILT REDLINES TO THE GENERAL
CONTRACTOR UPON COMPLETION OF PROJECT AND PRIOR TO FINAL PAYMENT.
30. THE CONTRACTOR SHALL LEAVE THE PREMISES IN A CLEAN CONDITION.
31. THE PROPOSED FACILITY WILL BE UNMANNED AND DOES NOT REQUIRE POTABLE WATER OR
SEWER SERVICE, AND IS NOT FOR HUMAN HABITATION (NO HANDICAP ACCESS REQUIRED).
32. NO OUTDOOR STORAGE OR SOLID WASTE CONTAINERS ARE PROPOSED.
33. CONTRACTORS SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS AND INSPECTIONS
REQUIRED FOR CONSTRUCTION. IF CONTRACTOR CANNOT OBTAIN A PERMIT, THEY MUST NOTIFY
THE GENERAL CONTRACTOR IMMEDIATELY.
34. THE CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE SITE ON A DAILY BASIS.
35. INFORMATION SHOWN ON THESE DRAWINGS WAS OBTAINED FROM SITE VISITS AND/OR
DRAWINGS PROVIDED BY THE SITE OWNER. CONTRACTORS SHALL NOTIFY THE ENGINEER OF
ANY DISCREPANCIES PRIOR TO ORDERING MATERIAL OR PROCEEDING WITH CONSTRUCTION.
36. ALL WORK MUST COMPLY WITH FBC 2017 - LATEST EDITION (6TH)
1. THE ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALLED ANY/ALL ELECTRICAL WORK
INDICATED. ANY/ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH DRAWINGS AND ANY/ALL
APPLICABLE SPECIFICATIONS. IF ANY PROBLEMS ARE ENCOUNTERED BY COMPLYING WITH
THESE REQUIREMENTS, CONTRACTOR SHALL NOTIFY CONSTRUCTION MANAGER AS SOON AS
POSSIBLE, AFTER THE DISCOVERY OF THE PROBLEMS, AND SHALL NOT PROCEED WITH THAT
PORTION OF WORK, UNTIL THE CONSTRUCTION MANAGER HAS DIRECTED THE CORRECTIVE
ACTIONS TO BE TAKEN.
2. THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND FAMILIARIZE THEMSELVES WITH
ANY/ALL CONDITIONS AFFECTING ELECTRICAL AND COMMUNICATION INSTALLEDATION AND
MAKE PROVISIONS AS TO THE COST THEREOF. THE CONDITION OF EXISTING ELECTRICAL EQUIP., LIGHT FIXTURES, ETC., THAT ARE PART OF THE FINAL SYSTEM, SHALL BE VERIFIED BY THE
CONTRACTOR, PRIOR TO THE SUBMITTAL OF HIS BID. FAILURE TO COMPLY WITH THIS
PARAGRAPH WILL IN NO WAY RELIEVE CONTRACTOR OF PERFORMING ALL WORK NECESSARY
FOR A COMPLETE AND WORKING SYSTEM. PLEASE COORDINATE AND SCHEDULE SITE VISITS IN
ADVANCE. APPROVAL IS REQUIRED BY THE OFFICE OF SAFETY AND SECURITY.
3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC AND
ALL CODES AND LOCAL ORDINANCES OF THE LOCAL POWER COMPANIES HAVING JURISDICTION
AND SHALL INCLUDE BUT NOT BE LIMITED TO:
A. UL - UNDERWRITERS LABORATORIES
B. NEC - NATIONAL ELECTRICAL CODE
C. NEMA - NATIONAL ELECTRICAL MANUFACTURERS ASSOC.
D. OSHA - OCCUPATIONAL SAFETY AND HEALTH ACT
E. SBC - STANDARD BUILDING CODE
F. NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
4. DO NOT SCALE ELECTRICAL DRAWINGS, REFER TO SITE PLANS AND ELEVATIONS FOR EXACT
LOCATIONS OF ALL EQUIPMENT, BUT CONFIRM WITH 'CONSTRUCTION MANAGER' ANY SIZES AND
LOCATIONS WHEN NEEDED.
5. EXISTING SERVICES: THE CONTRACTOR SHALL NOT INTERRUPT EXISTING SERVICES WITHOUT
WRITTEN PERMISSION OF THE OWNER. THIS IS A WORKING FACILITY (24-7) AND ON GOING BUS
OPERATIONS CANNOT BE IMPACTED. CLOSE COORDINATION IS REQUIRED. ANY POWER
OUTRAGES MUST BE APPROVED AT LEAST 2 WEEKS IN ADVANCED.
6. THE CONTRACTOR SHALL PAY FOR ANY/ALL PERMITS, FEES, INSPECTIONS AND TESTING. THE
CONTRACTOR IS TO OBTAIN PERMITS AND APPROVED SUBMITTALS PRIOR TO THE WORK
BEGINNING OR ORDERING THE EQUIPMENT.
7. THE TERM "PROVIDE" USED IN CONSTRUCTION DOCUMENTS AND SPECIFICATIONS, INDICATES
THAT THE CONTRACTOR SHALL FURNISH AND INSTALLED.
8. THE CONTRACTOR SHALL CONFIRM WITH LOCAL UTILITY COMPANY ANY/ALL REQUIREMENTS
SUCH AS THE: LUG SIZE RESTRICTIONS, CONDUIT ENTRY, SIZE OF TRANSFORMERS, SCHEDULED
DOWNTIME FOR THE OWNERS' CONFIRMATION, ETC. ANY/ALL CONFLICTS SHALL BE BROUGHT TO
THE ATTENTION OF THE CONSTRUCTION MANAGER, PRIOR TO BEGINNING ANY WORK.
9. CONDUCTORS: CONTRACTOR SHALL USE 98% CONDUCTIVITY COPPER OR ALUMINUM WITH TYPE
(THWN-2) INSULATION, 600 VOLT, COLOR CODED UNLESS SPECIFIED DIFFERENTLY ON DRAWINGS.
10. ALL (THWN-2) WIRING INSTALLEDATIONS TO FOLLOW MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIONS.
11. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF THE CONSTRUCTION.
CONTRACTOR IS EXPECTED TO FURNISH AND INSTALLED ALL ITEMS FOR A COMPLETE
ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS FOR THE EQUIPMENT TO BE PLACED IN
PROPER WORKING ORDER. CONTRACTOR IS TO PROVIDE ALL ELECTRICAL EQUIPMENT UNLESS
OTHERWISE DIRECTED.
12. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS, WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIONAL AND
SUBJECT TO REGULATORY INSPECTION AND APPROVAL BY CONSTRUCTION MANAGER.
13. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE
PROGRESS OF CONSTRUCTION.
14. CONTRACTOR SHALL GUARANTEE ANY/ALL MATERIALS AND WORK FREE FROM DEFECTS FOR A
PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE.
15. THE CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ANY ADDITIONAL CHARGE
AND SHALL INCLUDE THE REPLACEMENT OR THE REPAIR OF ANY OTHER PHASE OF THE
INSTALLEDATION, WHICH MAY HAVE BEEN DAMAGED THEREIN.
16. ADEQUATE AND REQUIRED LIABILITY INSURANCE SHALL BE PROVIDED FOR PROTECTION
AGAINST PUBLIC LOSS AND ANY/ALL PROPERTY DAMAGE FOR THE DURATION OF WORK.
17. PROVIDE AND INSTALLED CONDUIT, CONDUCTORS, PULL WIRES, BOXES, COVER PLATES AND
DEVICES FOR ALL OUTLETS AS INDICATED.
18. TRENCHING AND BACKFILL: THE CONTRACTOR SHALL PROVIDE FOR ALL UNDERGROUND
INSTALLEDED CONDUIT AND/OR CABLES INCLUDING EXCAVATION AND BACKFILLING AND
COMPACTION. REFER TO GENERAL SITE WORK NOTES.
19. MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE
NEW AND SHALL APPEAR ON THE LIST OF U.L. APPROVED ITEMS AND SHALL MEET OR EXCEED
THE REQUIREMENTS OF THE NEC, NEMA AND IEEE.
20. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OR MANUFACTURES CATALOG INFORMATION OF
ANY/ALL LIGHTING FIXTURES, SWITCHES AND ALL OTHER ELECTRICAL ITEMS FOR APPROVAL BY
THE CONSTRUCTION MANAGER PRIOR TO INSTALLEDATION.
21. ANY CUTTING OR PATCHING DEEMED NECESSARY FOR ELECTRICAL WORK IS THE ELECTRICAL
CONTRACTORS RESPONSIBILITY AND SHALL BE INCLUDED IN THE COST FOR WORK AND
PERFORMED TO THE SATISFACTION OF THE 'CONSTRUCTION MANAGER' UPON FINAL
ACCEPTANCE.
22. THE ELECTRICAL CONTRACTOR SHALL LABEL ALL PANELS WITH ONLY TYPEWRITTEN
DIRECTORIES.
23. DISCONNECT SWITCHES SHALL BE H.P. RATED HEAVY-DUTY, QUICK-MAKE AND QUICK-BREAK
ENCLOSURES, AS REQUIRED BY EXPOSURE TYPE.
24. ALL CONNECTIONS EXCEPT THE EV CHARGE CABLE TERMINATION IN THE CHARGE POST SHALL
BE MADE WITH A PROTECTIVE COATING OF AN ANTI-OXIDE COMPOUND SUCH AS "NOALOX" BY
IDEAL INDUSTIAL INC., COAT ALL WIRE SURFACES BEFORE CONNECTING. EXPOSED ALUMINUM &
COPPER SURFACES, INCLUDING GROUND BARS, SHALL BE TREATED - NO SUBSTITUTIONS.
25. ALL EXTERIOR AND INTERIOR ABOVE GROUND CONDUIT SHALL BE RIGID UNLESS SPECIFIED
OTHERWISE. ALL BURIED CONDUITS SHALL BE SCH 40 PVC UNLESS SPECIFIED OTHERWISE.
26. RACEWAYS: CONDUIT SHALL BE SCHEDULE 40 PVC, MEETING OR EXCEEDING NEMA TC2 - 1990.
THE CONTRACTOR SHALL PLUG AND CAP EACH END OF SPARE AND EMPTY CONDUITS AND
PROVIDE TWO SEPARATE PULL STRINGS - 200 LBS TEST POLYETHYLENE CORD. ALL CONDUIT
BENDS SHALL BE A MINIMUM OF 3 FT. RADIUS. RGS CONDUITS WHEN SPECIFIED, SHALL MEET
UL-6 FOR GALVANIZED STEEL. ALL FITTINGS SHALL BE SUITABLE FOR USE WITH THREADED
RIGID CONDUIT. COAT ALL THREADS WITH 'BRITE ZINC' OR 'GOLD GALV'.
27. SUPPORT OF ALL ELECTRICAL WORK SHALL BE AS REQUIRED BY NEC.
28. CONNECTORS FOR POWER CONDUCTORS: CONTRACTOR SHALL USE PRESSURE TYPE
INSULATED TWIST-ON CONNECTORS FOR NO. 10 AWG AND SMALLER. USE SOLDERLESS
MECHANICAL TERMINAL LUGS FOR NO. 8 AWG AND LARGER.
29. THE CONTRACTOR SHALL PLACE TWO LENGTHS OF WARNING TAPE AT A DEPTH OF 12" BELOW
GROUND AND DIRECTLY ABOVE ELECTRICAL SERVICE CONDUITS. CAUTION TAPE TO READ
"CAUTION BURIED ELECTRIC".
30. WHEN DIRECTIONAL BORING IS REQUIRED, CONTRACTOR SHALL INSTALLED A LOOSE TONING
WIRE WITHIN INSTALLEDED CONDUIT TO ALLOW FOR IDENTIFICATION OF UNDERGROUND
CONDUITS.
31. ALL BOLTS SHALL BE STAINLESS STEEL.
32. ALL MATERIALS AND EQUIPMENT SUPPLIED AND INSTALLEDED BY THE CONTRACTOR SHOULD
BE NEW AND UNUSED.
33. ALL CONDUITS, FITTINGS, ETC. MUST BE RATED FOR WET LOCATIONS.
34. ANY WALL PENETRATIONS MUST BE SEALED PER CODE WITH FIRE RATED CAULKING.
35. ALL SHUTDOWNS MUST BE APPROVED IN ADVANCED WITH DTPW.
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
GENERAL NOTES 2
GN-2
GENERAL SITE WORK NOTES
GENERAL SITE WORK NOTES CONT.REINFORCED CONCRETE NOTES
1. CONCRETE SHALL ATTAIN A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI IN 28 DAYS UNLESS
OTHERWISE NOTED; CONTINUOUS INSPECTION IS NOT REQUIRED.
SLUMP: 4" MIN./6" MAX.
AIR ENTRAINMENT: 4 1/2% - 7% BY VOLUME
2. REINFORCEMENT SHALL BE A NEW BILLET STEEL DEFORMED BARS CONFORMING TO ASTM
SPECIFICATION A615 GRADE 60. MAXIMUM COARSE AGGREGATE SIZE SHALL BE 3/4".
3. REINFORCEMENT SHALL COMPLY WITH THE LATEST EDITION OF ACI-318 FOR MINIMUM
CLEARANCES.
4. ALL EMBEDDED ITEMS SHALL BE SECURELY HELD IN POSITION PRIOR TO PLACEMENT OF
CONCRETE. ALL CONCRETE SHALL BE READY-MIXED IN ACCORDANCE WITH ASTM C94.
5. MAINTAIN TEMPERATURE OF CAST IN PLACE CONCRETE BETWEEN 50 DEGREES AND 90 DEGREES
FAHRENHEIT.
6. DO NOT USE RETEMPERED CONCRETE OR ADD WATER TO READY-MIX CONCRETE AT THE JOB SITE.
7. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185.
8. EXCEPT AS DETAILED OR AUTHORIZED, MAKE BARS CONTINUOUS AROUND CORNERS. WHERE
PERMITTED, SPLICES MADE BY CONTACT LAPS SHALL BE CLASS "B" TENSION LAPS UNLESS
NOTED OTHERWISE.
9. DETAIL BARS IN ACCORDANCE WITH "ACI DETAILING MANUAL - 2004, PUBLICATION SP-66" AND
"BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE", ACI 318-14.
10. PROVIDE ACCESSORIES NECESSARY TO PROPERLY SUPPORT REINFORCING.
PART 1 - GENERAL
CLEARING, GRUBBING, STRIPPING, EROSION CONTROL, SURVEY, LAYOUT, SUBGRADE PREPARATION, AND FINISH GRADING AS REQUIRED TO COMPLETE THE PROPOSED WORK SHOWN IN THESE PLANS.
1.1 REFERENCES:
A. DOT (STATE DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR HIGHWAY
CONSTRUCTION-CURRENT EDITION).
B. ASTM (AMERICAN SOCIETY FOR TESTING AND MATERIALS).
C. OSHA (OCCUPATION SAFETY AND HEALTH ADMINISTRATION).
1.2 INSPECTION AND TESTING:
A. GENERAL CONTRACTOR SHALL PERFORM ALL WORK IN CONFORMANCE WITH THE PLANS AND
SPECIFICATIONS. PERFORM INSPECTIONS BEFORE CONCEALING WORK WITH FOLLOW-ON ACTIVITIES
(BACKFILL, CONCRETE POUR, ETC).
1.3 SITE MAINTENANCE AND PROTECTION:
A. PROVIDE ALL NECESSARY JOB SITE MAINTENANCE FROM COMMENCEMENT OF WORK UNTIL
COMPLETION OF THE CONTRACT.
B. AVOID DAMAGE TO THE SITE AND TO EXISTING FACILITIES, STRUCTURES, TREES, AND SHRUBS
DESIGNATED TO REMAIN. TAKE PROTECTIVE MEASURES TO PREVENT EXISTING FACILITIES THAT
ARE NOT DESIGNATED FOR REMOVAL FROM BEING DAMAGED BY THE WORK.
C. KEEP SITE FREE OF ALL PONDING WATER.
D. PROVIDE EROSION CONTROL MEASURES IN ACCORDANCE WITH STATE DOT, LOCAL PERMITTING
AGENCY, AND EPA REQUIREMENTS.
E. PROVIDE AND MAINTAIN ALL TEMPORARY FENCING, BARRICADES, WARNING SIGNALS, AND
SIMILAR DEVICES NECESSARY TO PROTECT AGAINST THEFT FROM PROPERTY DURING THE ENTIRE
PERIOD OF CONSTRUCTION. REMOVE ALL SUCH DEVICES UPON COMPLETION OF THE WORK.
F. EXISTING UTILITIES: DO NOT INTERRUPT EXISTING UTILITIES SERVING FACILITIES OCCUPIED BY THE
OWNER OR OTHERS, EXCEPT WHEN PERMITTED IN WRITING BY THE CONSTRUCTION MANAGER AND
THEN ONLY AFTER ACCEPTABLE TEMPORARY UTILITY SERVICES HAVE BEEN PROVIDED.
G. PROVIDE A MINIMUM 48-HOUR NOTICE TO THE CONSTRUCTION MANAGER AND RECEIVE WRITTEN
NOTICE TO PROCEED BEFORE INTERRUPTING ANY UTILITY SERVICE.
H. SOD PLANTED IN THE FALL MUST ESTABLISH ITS ROOTS BEFORE THE FIRST WINTER FROST.
DETERMINE WHEN THE FIRST FROST USUALLY OCCURS, AND PLANT THE SOD NO LATER THAN ONE
MONTH BEFORE THE FIRST FROST. IF THE CONSTRUCTION IS FINISHED LATER THAN ONE MONTH
BEFORE THE FIRST FROST, USE STRAW UNTIL SOD CAN BE INSTALLEDED.
PART 2 - PRODUCTS
2.1 GRANULAR BACKFILL: SHALL MEET THE FOLLOWING GRADATION:
2.2 GRANULAR BEDDING AND TRENCH BACKFILL: WELL-GRADED SAND MEETING THE GRADATION
REQUIREMENTS OF ASTM D2487 (SE OR SW-SM).
2.3 COARSE AGGREGATE FOR ACCESS ROAD SUBBASE COURSE SHALL CONFORM TO ASTM D2940.
2.4 UNSUITABLE MATERIAL: HIGH AND MODERATELY PLASTIC SILTS AND CLAYS (LL>45). MATERIAL
CONTAINING REFUSE, FROZEN LUMPS, DEMOLISHED BITUMINOUS MATERIAL, VEGETATIVE
MATTER, WOOD, STONES IN EXCESS OF 3 INCHES IN ANY DIMENSION, AND DEBRIS AS
DETERMINED BY THE CONSTRUCTION MANAGER. TYPICAL THESE WILL BE SOILS CLASSIFIED BY
ASTM AS PT, MH, CH, OH, ML, AND OL.
PART 3 - EXECUTION
3.1 GENERAL:
A. BEFORE STARTING GENERAL SITE PREPARATION ACTIVITIES, INSTALLED EROSION AND SEDIMENT
CONTROL MEASURES. THE WORK AREA SHALL BE CONSTRUCTED AND MAINTAINED IN SUCH
CONDITION THAT IN THE EVENT OF RAIN THE SITE WILL BE DRAINED AT ALL TIMES.
B. BEFORE ALL SURVEY, LAYOUT, STAKING, AND MARKING, ESTABLISH AND MAINTAIN ALL LINES, GRADES, ELEVATIONS AND BENCHMARKS NEEDED FOR EXECUTION OF THE WORK.
C. CLEAR AND GRUB THE AREA WITHIN THE LIMITS OF THE SITE. REMOVE TREES, BRUSH, STUMPS, RUBBISH AND OTHER DEBRIS AND VEGETATION RESTING ON OR PROTRUDING THROUGH THE
SURFACE OF THE SITE AREA TO BE CLEARED.
D. REMOVE THE FOLLOWING MATERIALS TO A DEPTH OF NO LESS THAN 12 INCHES BELOW THE
ORIGINAL GROUND SURFACE: ROOTS, STUMPS, OTHER DEBRIS, BRUSH, AND REFUSE EMBEDDED IN
OR PROTRUDING THROUGH THE GROUND SURFACE, RAKE, DISK, OR PLOW THE AREA TO A DEPTH
OF NO LESS THAN 6 INCHES, AND REMOVE TO A DEPTH OF 12 INCHES ALL ROOTS AND OTHER
DEBRIS THEREBY EXPOSED.
E. REMOVE TOPSOIL MATERIAL COMPLETELY FROM THE SURFACE UNTIL THE SOIL NO LONGER
MEETS THE DEFINITION OF TOPSOIL. AVOID MIXING TOPSOIL WITH SUBSOIL OR OTHER
UNDESIRABLE MATERIALS.
F. EXCEPT WHERE EXCAVATION TO GREATER DEPTH IS INDICATED, FILL DEPRESSIONS RESULTING
FROM CLEARING, GRUBBING AND DEMOLITION WORK COMPLETELY WITH SUITABLE FILL.
G. REMOVE FROM THE SITE AND DISPOSE IN AN AUTHORIZED LANDFILL ALL DEBRIS RESULTING FROM
CLEARING AND GRUBBING OPERATIONS. BURNING WILL NOT BE PERMITTED.
H. PRIOR TO EXCAVATING, THOROUGHLY EXAMINE THE AREA TO BE EXCAVATED AND/OR TRENCHED
TO VERIFY THE LOCATIONS OF FEATURES INDICATED ON THE DRAWINGS AND TO ASCERTAIN THE
EXISTENCE AND LOCATION OF ANY STRUCTURE, UNDERGROUND STRUCTURE, OR OTHER ITEM NOT
SHOWN THAT MIGHT INTERFERE WITH THE PROPOSED CONSTRUCTION. NOTIFY THE
CONSTRUCTION MANAGER OF ANY OBSTRUCTIONS THAT WILL PREVENT ACCOMPLISHMENT OF
THE WORK AS INDICATED ON THE DRAWINGS.
I. SEPARATE AND STOCK PILE ALL EXCAVATED MATERIALS SUITABLE FOR BACKFILL. ALL EXCESS
EXCAVATED AND UNSUITABLE MATERIALS SHALL BE DISPOSED OF OFF-SITE IN A LEGAL MANNER.
J. DURING EXCAVATION, THE CONTRACTOR SHALL PROVIDE SHORING, SHEETING, AND BRACING AS
REQUIRED TO PREVENT CAVING OR SLOUGHING OF EXCAVATION.
3.2 BACKFILL:
A. AS SOON AS PRACTICAL, AFTER COMPLETING CONSTRUCTION OF THE RELATED STRUCTURE,
INCLUDING EXPIRATION OF THE SPECIFIED MINIMUM CURING PERIOD FOR CAST-IN-PLACE
CONCRETE, BACKFILL THE EXCAVATION WITH APPROVED MATERIAL TO RESTORE THE REQUIRED
FINISHED GRADE.
B. PRIOR TO PLACING BACKFILL AROUND STRUCTURES, ALL FORMS SHALL BE REMOVED AND THE
EXCAVATION CLEANED OF ALL TRASH, DEBRIS, AND UNSUITABLE MATERIALS.
C. DO NOT PLACE FROZEN MATERIAL AS BACKFILL.
D. BACKFILL BY PLACING AND COMPACTING SUITABLE BACKFILL MATERIAL OR SELECT GRANULAR
BACKFILL MATERIAL WHEN REQUIRED IN UNIFORM HORIZONTAL LAYERS OF NO GREATER THAN
8-INCHES LOOSE THICKNESS AND COMPACTED. WHERE HAND OPERATED COMPACTORS ARE USED,
THE FILL MATERIAL SHALL BE PLACED IN LIFTS NOT TO EXCEED 4 INCHES IN LOOSE DEPTH AND
COMPACTED.
E. WHENEVER THE DENSITY TESTING INDICATES THAT THE CONTRACTOR HAS NOT OBTAINED THE
SPECIFIED DENSITY, THE SUCCEEDING LAYER SHALL NOT BE PLACED UNTIL THE SPECIFICATION
REQUIREMENTS ARE MET UNLESS OTHERWISE AUTHORIZED BY THE CONSTRUCTION MANAGER.
THE CONTRACTOR SHALL TAKE WHATEVER APPROPRIATE ACTION IS NECESSARY, SUCH AS
DISKING AND DRYING, ADDING WATER, OR INCREASING THE COMPACTIVE EFFORT TO MEET THE
MINIMUM COMPACTION REQUIREMENTS.
F. THOROUGHLY COMPACT EACH LAYER OF BACKFILL TO A MINIMUM OF 95 PERCENT OF THE
MAXIMUM DRY DENSITY AS PROVIDED BY THE STANDARD PROCTOR TEST, ASTM D 698.
3.3 TRENCH EXCAVATION:
A. UTILITY TRENCHES SHALL BE EXCAVATED TO THE LINES AND GRADES SHOWN ON THE DRAWINGS
OR AS DIRECTED BY THE GENERAL CONTRACTOR. PROVIDE SHORING, SHEETING, AND BRACING AS
REQUIRED TO PREVENT CAVING OR SLOUGHING OF THE TRENCH WALLS.
B. EXTEND THE TRENCH WIDTH A MINIMUM OF 6 INCHES BEYOND THE OUTSIDE EDGE OF THE
OUTERMOST CONDUIT.
C. WHEN SOFT YIELDING, OR OTHERWISE UNSTABLE SOIL CONDITIONS ARE ENCOUNTERED,
EXCAVATE THE REQUIRED TRENCH TO A DEPTH OF NO LESS THAN 12 INCHES BELOW THE
REQUIRED ELEVATION, THEN BACKFILL WITH 12" OF GRANULAR BEDDING MATERIAL.
3.4 TRENCH BACKFILL:
A. PROVIDE GRANULAR BEDDING MATERIAL IN ACCORDANCE WITH THE DRAWINGS AND THE UTILITY
REQUIREMENTS.
B. NOTIFY THE GENERAL CONTRACTOR 24 HOURS IN ADVANCE OF BACKFILLING.
C. CONDUCT UTILITY CHECK TESTS BEFORE BACKFILLING. BACKFILL AND COMPACT TRENCH BEFORE
ACCEPTANCE TESTING.
D. PLACE GRANULAR TRENCH BACKFILL UNIFORMLY ON BOTH SIDES OF THE CONDUITS IN 6-INCH
UNCOMPACTED LIFTS UNTIL 12 INCHES OVER THE CONDUITS. SOLIDLY RAM AND TAMP BACKFILL
INTO SPACE AROUND CONDUITS.
E. PROTECT CONDUIT FROM LATERAL MOVEMENT, IMPACT DAMAGE, OR UNBALANCED LOADING.
F. ABOVE THE CONDUIT EMBEDMENT ZONE, PLACE AND COMPACT SATISFACTORY BACKFILL
MATERIAL IN 8-INCH MAXIMUM LOOSE THICKNESS LIFTS TO RESTORE THE REQUIRED FINISHED
SURFACE GRADE.
G. COMPACT FINAL TRENCH BACKFILL TO A DENSITY EQUAL TO OR GREATER THAN THAT OF THE
EXISTING UNDISTURBED MATERIAL IMMEDIATELY ADJACENT TO THE TRENCH BUT NO LESS THAN A
MINIMUM OF 95 PERCENT OF THE MAXIMUM DRY DENSITY AS PROVIDED BY THE STANDARD
PROCTOR TEST, ASTM D 698.
3.5 FINISH GRADING:
A. PERFORM ALL GRADING TO PROVIDE POSITIVE DRAINAGE AWAY FROM STRUCTURES AND
SMOOTH, EVEN SURFACE DRAINAGE OF THE ENTIRE AREA WITHIN THE LIMITS OF CONSTRUCTION.
GRADING SHALL BE COMPATIBLE WITH ALL SURROUNDING TOPOGRAPHY AND STRUCTURES.
B. UTILIZE SATISFACTORY FILL MATERIAL RESULTING FROM THE EXCAVATION WORK IN THE
CONSTRUCTION OF FILLS, EMBANKMENTS, AND FOR REPLACEMENT OF REMOVED UNSUITABLE
MATERIALS.
C. REPAIR ALL ACCESS ROADS AND SURROUNDING AREAS USED DURING THE COURSE OF THIS
WORK TO THEIR ORIGINAL CONDITION.
3.6 ASPHALT PAVING ROAD:
A. CONTRACTOR RESPONSIBLE FOR RE-STRIPING AND APPLYING SEALCOATING, UNLESS OTHERWISE
SPECIFIED.
B. ALL ELECTRIC VEHICLE CHARGING STALLS WITH AN ASPHALT SURFACE SHALL BE SEALCOATED.
SIEVE SIZE TOTAL PERCENT PASSING
1 1/2 INCH (37.5 MM)
1 INCH (25.0 MM)
75 TO 100
3/4 INCH (19.0 MM)
80 TO 100
3/8 INCH (9.5 MM)
35 TO 75
NO. 4 (4.75 MM)
30 TO 60
NO. 30 (0.600 MM)
7 TO 30
NO 200 (0.075 MM)
3 TO 15
GENERAL SITE WORK NOTES CONT.
FLORIDA STANDARD SPECIFICATIONS
SECTION 300-340 - FDOT PAVEMENT
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
GENERAL NOTES 3
GN-3
GROUNDING NOTES
1. ALL HARDWARE SHALL BE STAINLESS STEEL 3/8" DIAMETER OR LARGER. ALL HARDWARE 18-8
STAINLESS STEEL INCLUDING LOCK WASHERS, COAT ALL SURFACES WITH AN ANTI-OXIDANT
COMPOUND BEFORE MATING.
2. FOR GROUND BOND TO STEEL ONLY: INSERT A CADMIUM FLAT WASHER BETWEEN LUG AND STEEL, COAT ALL SURFACES WITH AN ANTI-OXIDANT COMPOUND BEFORE MATING.
3. ENSURE THE WIRE INSULATION TERMINATION IS WITHIN 1/8" OF THE BARREL (NO SHINERS).
4. ALL BELOW GRADE BONDS TO BE EXOTHERMIC WELDS OR IRREVERSIBLE COMPRESSION TYPE
CONNECTIONS LISTED FOR USE IN THE APPLICATION WHICH THEY ARE INSTALLED.
ELECTRICAL NOTES ELECTRICAL NOTES CONT.
1. THE ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL ANY/ALL ELECTRICAL WORK
INDICATED. ANY/ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH DRAWINGS AND ANY/ALL
APPLICABLE SPECIFICATIONS. IF ANY PROBLEMS ARE ENCOUNTERED BY COMPLYING WITH
THESE REQUIREMENTS, CONTRACTOR SHALL NOTIFY 'CONSTRUCTION MANAGER' AS SOON AS
POSSIBLE, AFTER THE DISCOVERY OF THE PROBLEMS, AND SHALL NOT PROCEED WITH THAT
PORTION OF WORK, UNTIL THE 'CONSTRUCTION MANAGER' HAS DIRECTED THE CORRECTIVE
ACTIONS TO BE TAKEN.
2. THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND FAMILIARIZE THEMSELVES WITH
ANY/ALL CONDITIONS AFFECTING ELECTRICAL AND COMMUNICATION INSTALLATION AND MAKE
PROVISIONS AS TO THE COST THEREOF. THE CONDITION OF EXISTING ELECTRICAL EQUIP.,
LIGHT FIXTURES, ETC., THAT ARE PART OF THE FINAL SYSTEM, SHALL BE VERIFIED BY THE
CONTRACTOR, PRIOR TO THE SUBMITTAL OF HIS BID. FAILURE TO COMPLY WITH THIS
PARAGRAPH WILL IN NO WAY RELIEVE CONTRACTOR OF PERFORMING ALL WORK NECESSARY
FOR A COMPLETE AND WORKING SYSTEM.
3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC AND
ALL CODES AND LOCAL ORDINANCES OF THE LOCAL POWER COMPANIES HAVING JURISDICTION
AND SHALL INCLUDE BUT NOT BE LIMITED TO:
A. UL - UNDERWRITERS LABORATORIES
B. NEC - NATIONAL ELECTRICAL CODE
C. NEMA - NATIONAL ELECTRICAL MANUFACTURERS ASSOC.
D. OSHA - OCCUPATIONAL SAFETY AND HEALTH ACT
E. SBC - STANDARD BUILDING CODE
F. NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
4. DO NOT SCALE ELECTRICAL DRAWINGS, REFER TO SITE PLANS AND ELEVATIONS FOR EXACT
LOCATIONS OF ALL EQUIPMENT, BUT CONFIRM WITH 'CONSTRUCTION MANAGER' ANY SIZES AND
LOCATIONS WHEN NEEDED.
5. EXISTING SERVICES: THE CONTRACTOR SHALL NOT INTERRUPT EXISTING SERVICES WITHOUT
WRITTEN PERMISSION OF THE OWNER.
6. THE CONTRACTOR SHALL PAY FOR ANY/ALL PERMITS, FEES, INSPECTIONS AND TESTING. THE
CONTRACTOR IS TO OBTAIN PERMITS AND APPROVED SUBMITTALS PRIOR TO THE WORK
BEGINNING OR ORDERING THE EQUIPMENT.
7. THE TERM "PROVIDE" USED IN CONSTRUCTION DOCUMENTS AND SPECIFICATIONS, INDICATES
THAT THE CONTRACTOR SHALL FURNISH AND INSTALLED.
8. THE CONTRACTOR SHALL CONFIRM WITH LOCAL UTILITY COMPANY ANY/ALL REQUIREMENTS
SUCH AS THE: LUG SIZE RESTRICTIONS, CONDUIT ENTRY, SIZE OF TRANSFORMERS, SCHEDULED
DOWNTIME FOR THE OWNERS' CONFIRMATION, ETC. ANY/ALL CONFLICTS SHALL BE BROUGHT
TO THE ATTENTION OF THE CONSTRUCTION MANAGER, PRIOR TO BEGINNING ANY WORK.
9. CONDUCTORS: CONTRACTOR SHALL USE 98% CONDUCTIVITY COPPER OR ALUMINUM WITH TYPE
(THWN-2) INSULATION, 600 VOLT, COLOR CODED UNLESS SPECIFIED DIFFERENTLY ON
DRAWINGS.
10. ALL WIRING INSTALLATIONS SHALL BE COMPLIANT WITH NEC ARTICLE 310.10 AND TO FOLLOW
MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS.
11. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED
HUBS IN WET/DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS.
12. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF THE CONSTRUCTION.
CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL
SYSTEM AND PROVIDE ALL REQUIREMENTS FOR THE EQUIPMENT TO BE PLACED IN PROPER
WORKING ORDER. CONTRACTOR IS TO PROVIDE ALL ELECTRICAL EQUIPMENT UNLESS
OTHERWISE DIRECTED.
13. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS, WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIONAL AND
SUBJECT TO REGULATORY INSPECTION AND APPROVAL BY CONSTRUCTION MANAGER.
14. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE
PROGRESS OF CONSTRUCTION.
15. CONTRACTOR SHALL GUARANTEE ANY/ALL MATERIALS AND WORK FREE FROM DEFECTS FOR A
PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE.
16. THE CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ANY ADDITIONAL CHARGE
AND SHALL INCLUDE THE REPLACEMENT OR THE REPAIR OF ANY OTHER PHASE OF THE
INSTALLATION, WHICH MAY HAVE BEEN DAMAGED THEREIN.
17. ADEQUATE AND REQUIRED LIABILITY INSURANCE SHALL BE PROVIDED FOR PROTECTION
AGAINST PUBLIC LOSS AND ANY/ALL PROPERTY DAMAGE FOR THE DURATION OF WORK.
18. PROVIDE AND INSTALLED CONDUIT, CONDUCTORS, PULL WIRES, BOXES, COVER PLATES AND
DEVICES FOR ALL OUTLETS AS INDICATED.
19. TRENCHING AND BACKFILL: THE CONTRACTOR SHALL PROVIDE FOR ALL UNDERGROUND
INSTALLED CONDUIT AND/OR CABLES INCLUDING EXCAVATION AND BACKFILLING AND
COMPACTION. REFER TO GENERAL SITE WORK NOTES.
20. MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE
NEW AND SHALL APPEAR ON THE LIST OF U.L. APPROVED ITEMS AND SHALL MEET OR EXCEED
THE REQUIREMENTS OF THE NEC, NEMA AND IEEE.
21. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OR MANUFACTURES CATALOG INFORMATION OF
ANY/ALL LIGHTING FIXTURES, SWITCHES AND ALL OTHER ELECTRICAL ITEMS FOR APPROVAL BY
THE CONSTRUCTION MANAGER PRIOR TO INSTALLATION.
22. ANY CUTTING OR PATCHING DEEMED NECESSARY FOR ELECTRICAL WORK IS THE ELECTRICAL
CONTRACTORS RESPONSIBILITY AND SHALL BE INCLUDED IN THE COST FOR WORK AND
PERFORMED TO THE SATISFACTION OF THE 'CONSTRUCTION MANAGER' UPON FINAL
ACCEPTANCE.
23. THE ELECTRICAL CONTRACTOR SHALL LABEL ALL PANELS WITH ONLY TYPEWRITTEN
DIRECTORIES.
24. DISCONNECT SWITCHES SHALL BE H.P. RATED HEAVY-DUTY, QUICK-MAKE AND QUICK-BREAK
ENCLOSURES, AS REQUIRED BY EXPOSURE TYPE.
25. ALL CONNECTIONS EXCEPT THE EV CHARGE CABLE TERMINATION IN THE CHARGE POST SHALL
BE MADE WITH A PROTECTIVE COATING OF AN ANTI-OXIDE COMPOUND SUCH AS "NOALOX" BY
IDEAL INDUSTRIAL INC., COAT ALL WIRE SURFACES BEFORE CONNECTING. EXPOSED ALUMINUM
& COPPER SURFACES, INCLUDING GROUND BARS, SHALL BE TREATED - NO SUBSTITUTIONS.
26. ALL EXTERIOR AND INTERIOR ABOVE GROUND CONDUIT SHALL BE RIGID UNLESS SPECIFIED
OTHERWISE. ALL BURIED CONDUITS SHALL BE SCH 40 PVC UNLESS SPECIFIED OTHERWISE.
27. RACEWAYS: CONDUIT SHALL BE SCHEDULE 40 PVC, MEETING OR EXCEEDING NEMA TC2 - 2013.
THE CONTRACTOR SHALL PLUG AND CAP EACH END OF SPARE AND EMPTY CONDUITS AND
PROVIDE TWO SEPARATE PULL STRINGS - 200 LBS TEST POLYETHYLENE CORD. ALL CONDUIT
BENDS SHALL BE A MINIMUM OF 3 FT. RADIUS. RGS CONDUITS WHEN SPECIFIED, SHALL MEET
UL-6 FOR GALVANIZED STEEL. ALL FITTINGS SHALL BE SUITABLE FOR USE WITH THREADED
RIGID CONDUIT. COAT ALL THREADS WITH 'BRITE ZINC' OR 'GOLD GALV'.
28. SUPPORT OF ALL ELECTRICAL WORK SHALL BE AS REQUIRED BY NEC.
29. CONNECTORS FOR POWER CONDUCTORS: CONTRACTOR SHALL USE PRESSURE TYPE
INSULATED TWIST-ON CONNECTORS FOR NO. 10 AWG AND SMALLER. USE SOLDERLESS
MECHANICAL TERMINAL LUGS FOR NO. 8 AWG AND LARGER.
30. THE CONTRACTOR SHALL PLACE TWO LENGTHS OF WARNING TAPE AT A DEPTH OF 12" BELOW
GROUND AND DIRECTLY ABOVE ELECTRICAL SERVICE CONDUITS. CAUTION TAPE TO READ
"CAUTION BURIED ELECTRIC".
31. WHEN DIRECTIONAL BORING IS REQUIRED, CONTRACTOR SHALL INSTALL A LOOSE TONING
WIRE WITHIN INSTALLED CONDUIT TO ALLOW FOR IDENTIFICATION OF UNDERGROUND
CONDUITS.
32. ALL BOLTS SHALL BE STAINLESS STEEL.
33. ALL MATERIALS AND EQUIPMENT SUPPLIED AND INSTALLED BY THE CONTRACTOR SHOULD BE
NEW AND UNUSED.
FIBER OPTIC NOTES
USE CABLE WITH THE FOLLOWING MINIMUM PROPERTIES:
1. HIGH TENSILE STRENGTH >150 LB
2. TIGHT BUFFERED
3. INDOOR / OUTDOOR UV AND MOISTURE RESISTANT “RISER” CABLE
4. CONNECTOR TYPE: ST-ST
5. FIBER TYPE: MULTI-MODE 6-FIBER (3 PAIR) 62.5UM. 6 CONNECTORS ON BOTH ENDS.
6. JACKET: INDOOR/OUTDOOR RISER, BLACK
7. BREAKOUT: SIDE A: INNER END - 24 INCHES WITH 2MM FURCATION
SIDE B: OUTER END - 24 INCHES - 2MM FURCATION - STAGGERED EVERY 1"
8. WITH PULLING EYE ON SIDE B (OUTER END) AND SPOOL REEL
STRUCTURAL DESIGN CRITERIA
WIND
WIND SPEED (Vult) 175MPH
WIND EXPOSURE C
WIND IMPORTANCE FACTOR, lw 1.00
STRUCTURAL OCCUPANCY CATEGORY II
SEISMIC
MAPPED SPECTRAL RESPONSE ACCELERATIONS Ss = 0.041 g
S1 = 0.020 g
SITE CLASS D
SPECTRAL RESPONSE COEFFICIENTS SDS = 0.043 g
SD1 = 0.032 g
SEISMIC DESIGN CATEGORY A
STRUCTURAL OCCUPANCY CATEGORY II
FOUNDATION MIN. ALLOWABLE BEARING
PRESSURE OF 1,500 PSF.
F R
O N
T
F R
O N
T
REV DESCRIPTIONDATE
CHECKED BY:
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
OVERALL SITE PLAN
C-1
20' 10' 0 20' 40'
1"=20'
OVERALL SITE PLAN
EXISTING
UNDERGROUND
STORM LINE (TYP)
EXISTING
UNDERGROUND
ELECTRICAL LINE (TYP)
EXISTING
UNDERGROUND
SANITARY LINE (TYP)
EXISTING PROPERTY
LINE (TYP)
EXISTING
UNDERGROUND
WATER LINE (TYP)
EXISTING
BUILDING (TYP)
EXISTING 12'-0"
UTILITY EASEMENT
E X
I S
T I N
G
U T
I L
I T
Y
E
A S
E M
E N
T
EXISTING
MANHOLE (TYP)
EXISTING 6'-0"
HIGH CBS WALL
EXISTING
TRANSFORMER
EXISTING
BOLLARD (TYP)
EXISTING
CHAINLINK
FENCE (TYP)
EXISTING ASPHALT
PARKING LOT (TYP)
EXISTING LIGHT
POLE (TYP)
NW
3RD A
VE
SEE ENLARGED
SITE PLAN SHEET
C-3 (SEE NOTE 1)
EXISTING ROOF
EXISTING PARKING
LINE (TYP)
1. SCOPE OF WORK SHALL BE CONTAINED WITHIN ENLARGED SITE PLAN AREA.
NOTE
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
OVERALL SITE PLAN
C-1.1
40' 20' 0 40' 80'
1"=40'
OVERALL SITE PLAN
1. SCOPE OF WORK SHALL BE CONTAINED WITHIN ENLARGED SITE PLAN AREA.
2. ELECTRICAL CONDUITS SHALL BE GREATER THAN 18" BELOW THE CEILING DUE TO POSSIBLE CLASS 1 DIV 2
AREAS CREATED BY CNG BUS REPAIRERS.
NOTES
EXISTING ASPHALT
PARKING LOT
N W
N
D
A
V E
N U
E
EXISTING CONCRETE
CURB (TYP)
EXISTING
SWITCHGEAR
EXISTING
SIDEWALK
EXISTING
TREE (TYP)
EXISTING
GRASSY
AREA (TYP)
EXISTING MIAMI-DADE
TRANSIT CENTRAL BUS
FACILITY BUILDING
EXISTING
BUILDING (TYP)
SEE ELECTRICAL
PLAN SHEET E-2.2
APPROXIMATE
LOCATION OF
ELECTRICAL ROOM
NEW CONDUIT
ROUTE (NTS)
APPROXIMATELY 300'
ALONG THE CEILING
(SEE NOTE 2)
GARAGE ENTRANCE
BUS SITE ENTRANCE
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
DEMOLITION SITE PLAN
C-2
16' 12' 8' 4' 0 16' 32'
1/16"=1'-0"
DEMOLITION SITE PLAN
EXISTING 6'-0"
HIGH CBS WALL
EXISTING PROPERTY
LINE (TYP)
EXISTING
UNDERGROUND
STORM LINE (TYP)
EXISTING
UNDERGROUND
ELECTRICAL LINE (TYP)
EXISTING
UNDERGROUND
WATER LINE (TYP)
EXISTING
TREE (TYP)
EXISTING
CONCRETE
BARRIER (TYP)
EXISTING
STRIPING
REMOVE EXISTING PARKING
LINE BY GRINDING
SEE DEMO LEGEND
DEMO LEGEND
PARKING LINES
CONCRETE
EXISTING ASPHALT
PARKING LOT
EXISTING
CONCRETE
PAVEMENT
1. REPAIR CONCRETE PAVEMENT ALONG TRENCHED AREA TO MATCH EXISTING THICKNESS WITH 4000 PSI
CONCRETE MIX.
2. PLACE ALL STORM WATER INLET PROTECTION BEFORE BEGINNING DEMOLITION. DO NOT REMOVE INLET
PROTECTION UNTIL AFTER CONSTRUCTION COMPLETE.
NOTES
PROVIDE GRATE GATOR
INLET PROTECTION WITH
OVERFLOW RING OR
EQUIVALENT
EXISTING 12'-0"
UTILITY EASEMENT
O N
T F
R O
N T
NEW DISPENSERS
(TYP OF 23)
REV DESCRIPTIONDATE
CHECKED BY:
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
ENLARGED SITE PLAN
C-3
16' 12' 8' 4' 0 16' 32'
1/16"=1'-0"
ENLARGED SITE PLAN B
NEW ELECTRICAL
SERVICES AND PCS
CHARGER LOCATION
EXISTING 6'-0"
HIGH CBS WALL
EXISTING PROPERTY
LINE (TYP)
EXISTING
UNDERGROUND
STORM LINE (TYP)
EXISTING
UNDERGROUND
ELECTRICAL LINE (TYP)
EXISTING
UNDERGROUND
WATER LINE (TYP)
EXISTING 12'-0"
UTILITY EASEMENT
EXISTING
TREE (TYP)
T
Y
P
EXISTING
CONCRETE
BARRIER (TYP)
NEW
DISPENSER
T
Y
P
28'-1"
21'-0"
(TYP)
EXISTING
STRIPING
NEW UTILITY
TRANSFORMER PAD
(TYP OF 2)
(SEE NOTE 3)
A
C-5
A
C-5
A
D-1
E
D-2
SEE ENLARGED
EQUIPMENT LAYOUT
SHEET C-4
1. ALL EXISTING UTILITIES SHOWN ON THE PLANS ARE FOR REFERENCE PURPOSE. ALL PRECAUTIONS MUST BE
TAKEN TO AVOID BREAKING ANY UNDERGROUND UTILITIES.
2. PROTECT EXISTING FACILITIES FROM DAMAGE. DAMAGE TO EXISTING FACILITIES CAUSED BY THE
CONTRACTOR SHALL BE CORRECTED BY THE CONTRACTOR AT NO COST TO THE MIAMI-DADE COUNTY (MDC).
3. TO BE COMPLETED UNDER SEPARATE PERMIT ACQUIRED BY UTILITY.
NOTES
NEW PROTECTION
BOLLARD (TYP OF 26)
C
D-2
40'-0"
10'-7"
T
Y P
NEW 6" WIDE YELLOW
PARKING LINE (TYP)
1A 2A 3A 4A 5A 6A 7A 8A 9A 10A 11A 12A 1B 2B 3B 4B 5B 6B 7B 8B 9B 10B 11B 12B
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUTDC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
1% SLOPE
FOR DRAINAGE
REV DESCRIPTIONDATE
CHECKED BY:
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
ENLARGED EQUIPMENT PLAN
C-4
12" 6" 0 1' 2' 3' 4' 5'
1/2"=1'-0"
ENLARGED EQUIPMENT LAYOUT
12B
11B
10B
9B
3B
2B
1B
12A
11A
5A
4A
3A
2A
1A 8B
7B
6B
5B
4B
10A
9A
8A
7A
6A
C
D-1
NEW SWITCHBOARD
ASSEMBLY #B
NEW POWER UNIT
(TYP OF 24)
B
D-1
NEW CONCRETE
PAD
A
D-2
NEW STAIR WITH
HANDRAILS (TYP)
5'-0"
(TYP)
T
Y P
NEW 42" HIGH
GUARD RAIL
38'-8"
T
Y P
37'-2"9"
(TYP)
4"
(TYP)
T
Y P
1'-1"
(TYP)
4'-0"
(TYP)
T
Y P
1'-9"
(TYP)
NEW CONCRETE
BOLLARD (TYP OF 12)
C
D-2
T
Y P
5'-11"
(TYP)
5'-11"
(TYP)
T
Y P
1'-6"
(TYP)
T
Y P
T
Y P
1. OCCUPANT LOAD CALCULATIONS PER
1004.1.2. AREAS WITHOUT FIXED IS 1 PER
300 GROSS SQUARE FEET. 867 SF /300
(SF/OCCUPANT) = 2.9 OCCUPANTS.
2. OCCUPANT LOAD: 2
3. MAXIMUM DISTANCE FOR MEANS OF
EGRESS IS 54 FEET.
4. EQUIPMENT AREA IS ILLUMINATED FROM
EXISTING LIGHT POLES WITHIN THE BUS
FACILITY AT 1 FOOT-CANDLES.
NOTES
FG 9.38'
FG 9.38'
M
I N
FG 9.00'
FG 9.00'
MEANS OF EGRESS
(SEE NOTE 3)
T
Y P
NEW EXPANSION
JOINT (TYP)
NEW HANDRAIL
EXTENSION (TYP)
E
D-1
D
D-1
D
D-2
M
I N
INCOMING
6'-0"
1'-6"
(TYP)
INCOMING
C
D-1
NEW SWITCHBOARD
ASSEMBLY #A
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUT
DC OUTPUT
AC INPUTDC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
DC OUTPUT
AC OUTPUT
REV DESCRIPTIONDATE
CHECKED BY:
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
EQUIPMENT
COMMUNICATION PLAN
C-4.1
12" 6" 0 1' 2' 3' 4' 5'
1/2"=1'-0"
EQUIPMENT COMMUNICATION PLAN
12B
11B
10B
9B
3B
2B
1B
12A
11A
5A
4A
3A
2A
1A 8B
7B
6B
5B
4B
10A
9A
8A
7A
6A
INCOMING
INCOMING
1. CABINET 1A AND 12B CONTAIN CRADLE POINTS INSTALLEDED BY MANUFACTURER FOR THE 4G WIRELESS NETWORK MODERN.
NOTE
JUNCTION BOX DETAIL
NOTE
QUAZITE 15,000 LB. UNDERGROUND ENCLOSURE
MFR #: PC0608Z80009
NOMINAL HEIGHT: 6"
USABLE INTERIOR LENGTH: 8 1/2"
LOAD RATING (LB): 15,000
H
W
L
A
NO SCALE
NEW 1.25"
CONDUITS CAT6
NEW PULL BOX FOR ANY FUTURE
ON-SITE COMMUNICATION
A
NEW 1.25" PVC CONDUIT NEW CRADLE POINT
CABINET (SEE NOTE 5)
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
SITE ELEVATIONS
C-5
12' 8' 4' 0 10' 20'
3/32"=1'-0"
SITE ELEVATION A
NEW UTILITY
TRANSFORMER (TYP OF 2)
NEW
SWITCHBOARD
ASSEMBLY
C
D-1
EXISTING
TREE (TYP)
EXISTING
PAVEMENT
EXISTING
6'-0" WALL
NEW DISPENSERS (TYP)
NEW
DISPENSER
NEW 125KW POWER
UNIT (TYP OF 24)
NEW
CONCRETE PAD
A
D-2
B
D-1
A
D-1
1A 2A 3A 4A 5A 6A 7A 8A 9A 10A 11A 12A 1B 2B 3B 4B 5B
6B 7B
8B 9B 10B 11B
12B
NEW REMOVABLE
UTILITY BOLLARDS (TYP)
NEW STAIR WITH 42" HIGH
GUARD RAIL AND 36" TALL
HANDRAIL WITH 21" MAX
PICKET SPACING (TYP)
NEW 42" HIGH
GUARD RAIL WITH
21" MAXIMUM
PICKET SPACING
NEW CONCRETE
BOLLARD (TYP)
C
D-2
NEW PROTECTION
BOLLARD (TYP)
C
D-2
E
D-2
NEW UTILITY METER
MOUNTED ON UNISTRUT
H-FRAME (TYP OF 2)
O N
T
F R
O N
T
REV DESCRIPTIONDATE
CHECKED BY:
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913) 458-2000
TAYLOR MURPHY
CIVIL PE# 82722
R
BLACK & VEATCH
RYAN R. BINKLEY
ELEC PE# 89014
I
L
T
BUS ROUTE PLAN
C-6
20' 10' 0 20' 40'
1"=20'
BUS ROUTE PLAN
EXISTING PROPERTY
LINE (TYP)
EXISTING
BUILDING (TYP)
EXISTING
MANHOLE (TYP)
EXISTING 6'-0"
HIGH CBS WALL
EXISTING
TRANSFORMER
EXISTING
BOLLARD (TYP)
EXISTING
CHAINLINK
FENCE (TYP)
EXISTING ASPHALT
PARKING LOT (TYP)
EXISTING LIGHT
POLE (TYP)
NW
3RD A
VE
EXISTING ROOF
EXISTING PARKING
LINE (TYP)
BUS TURNING
ROUTE (TYP)
O N
T F
R O
N T
REV DESCRIPTIONDATE
CHECKED BY:
DRAWN BY:
PROJECT NO:
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS
DOCUMENT.
SHEET NUMBER
SHEET TITLE
406365
AKJ
JDN
0 02/17/21 ISSUED FOR CONSTRUCTION
1 09/20/21 RE-ISSUED FOR CONSTRUCTION
2 02/01/23 AS BUILT
FL-P001
CENTRAL FACILITY
3300 NW 32ND AVE
MIAMI, FL 33142
1 WHITLEE CT.
GREENVILLE, SC 29627
(864) 214-2693
6800 W 115th ST, SUITE 2292
OVERLAND PARK, KS 66211
(913)…
This is the start of the file's text. The full file is on GovTribe.