Attachment 5 - Original Construction Redlined Drawing 00.PP.406 Plumbing Details.pdf
PDF 623 KB Posted
- Attached to
- Z2DA--Replace DHW North Check Valves Federal contract opportunity
- Solicitation number
- 36C25922Q0432
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S06 - 36C25922Q0432_1 0003.docx | DOCX document | |
| 36C25922Q0432_1 0002.docx | DOCX document | |
| SOW (Replace DHW Check Valves) 07.13.22.pdf | ||
| Instructions to Offerors p.g. 16 updated.pdf | ||
| S05 - QNA (Replace DHW North Check Valves).pdf | ||
| 36C25922Q0432_1 0001.docx | DOCX document | |
| Attachment 4 - Drawing ENC_Plumbing_As-Builts.pdf | ||
| 36C25922Q0432_1.docx | DOCX document | |
| Attachment 3 - Drawing CON_Plumbing_As-Builts.pdf | ||
| Attachment 6 - Project 554-22-147 Pictures.docx | DOCX document | |
| Attachment 2 - Specifications (554-22-147).pdf | ||
| Attachment 1 - Project Drawing 1 (554-22-147).pdf | ||
| Attachment 7 - Past Performance Questionnaire.docx | DOCX document |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
OXYGEN
MEDICAL GAS MANIFOLD
P U S H T O
T E ST
SUP PLY
LEF T BA NK RIGHT B AN K
I N US E
R E AD Y
E MPT Y
I N US E
R E AD Y
E MPT Y
4'-7"
0'-9"0'-11"0'-11"0'-11"0'-11"0'-11"0'-11"0'-11"
8"
VAC
D
CWR
CWS
M P
S
MPS
MPC
SCALE: NONE
FLOOR
TANKS (TYP.)
CHECK VALVE
PIGTAIL CONNECTION WITH
CHAIN RESTRAINTS (TYP.)
SCALE: NONE
FILTER MUFFLER
AT 30" ABOVE ROOF
MAINTAIN MIN. 25'-0" FROM
ANY WINDOW OR INTAKE.
VACUUM PUMPS
(PROVIDE EMERGENCY POWER.)
LOCATE REFRIGERATED AIR DRYER
AND DEWPOINT MONITOR PER
MANUFACTURERS INSTALLATION
RECOMMENDATIONS.
WALL SWITCH W/
PILOT LIGHT, TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
06-DHX-0306-DHX-0206-DHX-01
06-DET-01
WALL SWITCH W/
PILOT LIGHT, TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
01-DHX-2/
02-DHX-2
01-DHX-1/
02-DHX-1
06-DET-01
F PS
FPS
V
VS
MA
POWER CONNECTION.
SINGLE POINT
FLOOR
AIR INTAKE
ALARM TO BAS
(PACKAGED)
DESSICANT DRYERS
(PACKAGED)
RECEIVER
RIGID BASE
4"HIGH CONC. PAD.
CONTROL PANEL (PACKAGED)
PROVIDE MIN. 36" CLEAR SPACE
IN FRONT OF PANEL.
DEW POINT
MONITOR(PACKAGED)
(TYP.)
AIR INTAKE (TYP.)
ALARM TO BAS
CHECK VALVE
(TYP.)
FLOOR
POWER CONNECTION.
SINGLE POINT
FLOOR
AIR INTAKE
ALARM TO BAS
(PACKAGED)
RECEIVER
RIGID BASE
4"HIGH CONC. PAD.
CONTROL PANEL (PACKAGED)
PROVIDE MIN. 36" CLEAR SPACE
IN FRONT OF PANEL.
(TYP.)
CHECK VALVE
(TYP.)
UNION
GAS MAIN LINE
1/2"HIGH PRESSURE VENT
FRONT VIEW
PLAN VIEW
G A S
C Y
LI
N D E R
G A S
C Y
LI
N D E R
G A S
C Y
LI
N D E R
G A S
C Y
LI
N D E R
36"LONG PIGTAIL (TYP.)
2x2 MANIFOLD SHOWN.
EXPAND TO ADDITIONAL
CYLINDERS AS SHOWN
DASHED.
HEADER SUPPORT BOLTED
TO WALL
PROVIDE CHAIN SUPPORT
FOR EACH CYLINDER
ATTACHED TO WALL.
MANIFOLD HEADER.
CYLINDER SHUTOFF VALVE
AND CHECK VALVE
ROOF
1/2"LOW PRESSURE VENT
TERMINATE 1" VENT THROUGH
ROOF OR SIDEWALL WITH GOOSENECK AT
MIN. 24" ABOVE ROOF.
(GAS MAIN)
MAIN LINE SHUTOFF VALVE
PRESSURE GAUGE
PRESSURE SWITCH
LINE PRESSURE RELIEF VALVE
TO SYSTEM
18 GAUGE SIGNAL WIRES
TO MAP. SEE PLANS FOR
MORE INFO
0'-9"0'-11"0'-11"0'-11"0'-11"0'-11"0'-11"0'-11"
TYPICAL CYLINDER
MANIFOLD
0'-11"
WALL
2x2 MANIFOLD SHOWN.
EXPAND TO ADDITIONAL
CYLINDERS AS SHOWN
DASHED.
MANIFOLD
FLOOR
DETAIL TYPICAL OF NITROGEN, NITROUS OXIDE, CARBON DIOXIDE, AND OXYGEN (RESEARCH VIVARIUM) MANIFOLDS.
NOTE:
PROVIDE 110V RECEPTICAL TO
N20 MANIFOLDS FOR BOTTLE
WARMER.
ELECTRICAL NOTE:
FLASHING
SLEEVED PENETRATION
RECESS MOUNTED
EMERGENCY OXYGEN
SUPPLY PANEL
EMERGENCY OXYGEN
CONNECTION POINT
PRESS. RELIEF
VALVE
CHECK VALVE
OUTSIDE WALL
(2 1/2" FEMALE NPT)
RE: SPEC AND NFPA 99
OUTSIDE
TO SYSTEM
SUPPLY PIPING
EMERGENCY 02
VENT TO
4"HIGH CONC. PAD.
FLOOR
ROOF
TYPICAL
FLEX. CONNECTION
18 GAUGE WIRES TO MAP.
SEE PLANS FOR MORE INFO
FLOOR SINK
3/4'' DRIP LEG/DRAIN.
VACUUM GAUGE
VACUUM SWITCH
6" VACUUM PIPING TO
SYSTEM
6"COPPER EXHAUST
SEE PLANS.
SKID MOUNTED
CONTROL PANEL WALL OR
200 GALLON RECEIVER
PROVIDE MIN. 36" CLEAR SPACE
IN FRONT OF PANEL.
SLEEVED PENETRATION
4" X 10" LONG DRIP LEG.
IN FRONT OF PANEL.
PROVIDE MIN. 36" CLEAR SPACE
CONTROL PANEL (PACKAGED)
4"HIGH CONC. PAD.
INERTIA BASE INERTIA BASE
RECEIVER
(PACKAGED)
DESSICANT FILTERS
(PACKAGED)
SKID MOUNTED PACKAGED MEDICAL
AIR COMPRESSOR AND FILTERATION
SYSTEM. SEE SPECS.
DEW POINT MONITOR(PACKAGED)
CO2 MONITOR (PACKAGED)
18 GAUGE WIRES TO
MAP. SEE PLANS.
FLEX CONN. TYP.
FLOOR
4"
4"
PRESSURE SWITCH
PRESSURE GAUGE
TYPICAL
FLEX. CONNECTION
4"COPPER AIR INTAKE
SEE PLANS.
TURNED DOWN GOOSENECK W/BIRD SCREEN
SLEEVED PENETRATION
CDALP
CDAHP
EXHAUST
VAC
F&T F&T F&TF&T F&T
AUTOCLAVE/STERILIZER PIPING DETAIL
FOR MANUAL SWITCHOVER
TYPICAL LAB GAS MANIFOLD DETAIL
LABORATORY AIR COMPRESSOR DETAIL
SHOP AIR COMPRESSOR PIPING DETAILLABORATORY VACUUM PUMP DETAIL
MANIFOLD DETAIL
TYPICAL MEDICAL GAS
EMERGENCY OXYGEN SUPPLY DETAILPROTECTION SOLENOID VALVE
TRIPLEX DOMESTIC HOT WATER DETAIL
MEDICAL VACUUM PUMP DETAIL MEDICAL AIR COMPRESSOR DETAIL
REDUCED PRESSURE BFP W/ FLOOD
DUPLEX DOMESTIC HOT WATER DETAIL
SCALE: NONE
SCALE: NONE
FLOOR SINK
CONTINUATION
SEE PLANS FOR
PANEL
CONTROL
90° ELL (TYPICAL)
DRAIN, TERMINATE WITH
ROUTE PIPING TO FLOOR
WITH MANUAL BY-PASS.
AUTOMATIC DRAIN VALVE
COALESCING FILTER
AIR FILTER
0.5 MICRON COALESCING FILTER
5 MICRON FILTER
CONTINUATION
SEE PLANS FOR
FLOOR SINK
AUTOMATIC DRAIN VALVE
WITH MANUAL BY-PASS.
ROUTE PIPING TO FLOOR
DRAIN AND TERMINATE
WITH 90° ELL.
SCALE: NONE
FLOOR SINK
90° ELL (TYPICAL)
DRAIN, TERMINATE WITH
ROUTE PIPING TO FLOOR
WITH MANUAL BY-PASS.
AUTOMATIC DRAIN VALVE
CONTINUATION
SEE PLANS FOR
PROVIDE 36" CLEARANCE
IN FRONT OF PANEL
CONTINUATION
SEE PLANS FOR
SCALE NONE
STRUT SUPPORT TOP,
4 LEGS, CROSS
BRACED
SCALE: NONE
NOTE: PROVIDE STRUT FRAME CROSS BRACED AND
PROVIDED WITH A MINIMUM OF 6 LEG SUPPORTS
ANCHORRED TO FLOOR AND PIPE CLAMPS TO
FRAME FOR WATER, PIPE AND BACKFLOW
PREVENTER. FRAME TO BE RIGID AND SWAY
BRACED.
WATER SUPPLY TO SYSTEM
SCALE: NONE
WATER SUPPLY FROM
METER AND BUILDING
SHUT-OFF VALVE
ELECTRIC SOLENOID TIMER
CONTROLLER W/ ALARM AND
LIGHTS.
SOLENOID OPERATED HYDRAULIC
SHUT-OFF VALVE (120V) N.O.
DISCONNECT
120V POWER BY DIV. 16
1/8" FLOOR PLATE
DISCHARGE TO FLOOR SINK
WITH 1" AIR GAP.
24V TO BUILDING
AUTOMATION
SYSTEM ALARM
REDUCED PRESSURE BACKFLOW
PREVENTION ASSEMBLY
PIPE SADDLE
TO VALVE
6"-12"6"-12"
SCALE NONE
6"-12"
THERMAL EXPANSION TANK
DOUBLE WALL DOMESTIC HOT WATER HEAT EXCHANGERS
CONTROL PANEL
SOLENOID SAFETY VALVE (OVER TEMPERATURE) EXTEND
RELIEF TO FD W/AIR GAP.
T&P RELIEF VALVE, EXTEND RELIEF TO FD W/AIR GAP.
9"COLUMN THERMOMETER 0-300∅F (TYPICAL)
STEAM VALVE CONTROLLER (TYPICAL).
FULL SIZE FULL PORT BALL VALVE (TYPICAL).
UNION (TYPICAL)
ORIFICED UNION (TYPICAL) SIZE PER W.H. MFG.
STEAM VALVE OS&Y (TYPICAL).
"Y" STRAINER W/BLOW DOWN (TYPICAL).
45° CHECK VALVE (TYPICAL).
F&T STEAM TRAP (TYPICAL).
PIPE CAP AND 6x6x1/8" S.S. FLOOR PLATE (TYPICAL).
DRAIN VALVE WITH BACKFLOW PREVENTER (TYPICAL).
STEAM CONTROL VALVE.
CONDENSATE PIPING TO CONDENSATE PUMP.
HOT WATER CIRCULATING PUMP, SEE SCHEDULE &
DETAIL.
GRAVITY STEAM CONDENSATE RETURN.
TOP TAKE-OFF FOR STEAM SUPPLY.
STEAM MAIN.
HOT WATER MAIN.
HOT WATER CIRCULATION MAIN.
COLD WATER MAIN.
CONTROL TUBING (RIGID).
SCALE NONE SCALE NONE
INTEGRAL RELIEF VALVE
MONITOR SWITCH
SWING CHECK VALVE
TO RELIEF VALVE MONITOR
SWITCH
20 2020
(SYSTEM LOCATED IN BOILER ROOM 06-SV1-F2-E2 AT ENERGY CENTER)
14 9
9 16
6"-12"
SCALE NONE
6"-12"
THERMAL EXPANSION TANK
DOUBLE WALL DOMESTIC HOT WATER HEAT EXCHANGERS
CONTROL PANEL
SOLENOID SAFETY VALVE (OVER TEMPERATURE) EXTEND
RELIEF TO FD W/AIR GAP.
T&P RELIEF VALVE, EXTEND RELIEF TO FD W/AIR GAP.
9"COLUMN THERMOMETER 0-300∅F (TYPICAL)
STEAM VALVE CONTROLLER (TYPICAL).
FULL SIZE FULL PORT BALL VALVE (TYPICAL).
UNION (TYPICAL)
ORIFICED UNION (TYPICAL) SIZE PER W.H. MFG.
STEAM VALVE OS&Y (TYPICAL).
"Y" STRAINER W/BLOW DOWN (TYPICAL).
45° CHECK VALVE (TYPICAL).
F&T STEAM TRAP (TYPICAL).
PIPE CAP AND 6x6x1/8" S.S. FLOOR PLATE (TYPICAL).
DRAIN VALVE WITH BACKFLOW PREVENTER (TYPICAL).
STEAM CONTROL VALVE.
CONDENSATE PIPING TO CONDENSATE PUMP.
HOT WATER CIRCULATING PUMP, SEE SCHEDULE &
DETAIL.
GRAVITY STEAM CONDENSATE RETURN.
TOP TAKE-OFF FOR STEAM SUPPLY.
STEAM MAIN.
HOT WATER MAIN.
HOT WATER CIRCULATION MAIN.
COLD WATER MAIN.
CONTROL TUBING (RIGID).
(SYSTEMS LOCATED IN CONCOURSE MECHANICAL ROOM 01-SV-C35-M4 AND
AND RESEARCH PENTHOUSE HEAT EXCHANGER ROOM 02-PH-G3-M1
EOMD
CONNECT TO HEAT
EXCHANGER,
COORDINATE
LOCATION WITH G.C.
CA
AUTOCLAVE
FLOOR
DEEP SEAL TRAP
FLOOR SINK
DRAIN
AUTOCLAVE
SA
NOTE:
DETAIL IS DIAGRAMMATIC
AND DOES NOT REFLECT
EXACT LOCATIONS FOR
CONNECTIONS. REFER TO
INSTALLATION
INSTRUCTIONS
REDUCED PRESSURE
BACKFLOW PREVENTER.
INSTALL AT ACCESSIBLE
LOCATION PER CODE.
LABEL PIPING WITH
TYPE OF GAS
PRESSURE
REGULATOR
PRESSURE GAUGE
PRESSURE RELIEF VALVE
SOURCE SHUT-OFF VALVE
TO OUTLETS
FOR LARGER BANKS,
EXTEND HEADER AND
DROPS AS NEEDED
FLEX
CONNECTION
(TYP.)
PRESSURE
RELIEF
0-150 PSI 0-100 PSI
SET TO
65 PSI
0-150 PSI
HIGH PRESSURE LAB AIR
LOW PRESSURE LAB AIR
FLEX
CONNECTION
(TYP.)
VACUUM GAUGE
(125 PSI)
(65 PSI)
EXP.
TANK
THRU ROOF PER
NFPA 99C
RE: MECH PLANS FOR
EXACT REQUIREMENTS, TYP.
EXP.
TANK
RE: MECH PLANS FOR
EXACT REQUIREMENTS, TYP.
KEY NOTES:KEY NOTES:
T
T
T
TT
O2 DISS
FLOW METER AND
HOSE BY OTHERS
NOTE:
ONE OXYGEN CONTROL STATION PER SLEEP
STUDY PATIENT ROOM, LOCATED PER PLANS.
O2 QUICK
CONNECT O2 OUTLET
1/2" O2
MONITORING/
CONTROL ROOM
1/2" O2
SLEEP STUDY PATIENT ROOM HEADWALL
1/2" O2
FROM ZVB LOCKABLE BALL VALVE
(TYPICAL)
INTERSTITIAL LEVEL
PIPING DETAIL
NTS
SLEEP STUDY OXYGEN
11 12 08 09 13
03040506
Drawing Number
Building Number
Project NumberProject Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
Key Plan
CONSULTANTS:
DateRevisions
1 2 3 4 5 6 7 8 9 10 11 12
D
C
B
A
554-501REPLACEMENT MEDICAL CENTER
FACILITY, EASTERN COLORADO
HEALTH CARE SYSTEM
AURORA, COLORADO
N
C O
N
R E
S
D A
T
I B
S
I B
N
E N
C
C L C
C B
N
C B
C
C B
S
P S
N
P V
N
P V
S
13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
E
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT/ENGINEERS:
H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202
Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604
Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401
S. A. Miro, Inc.
4582 South Ulster Street Pkwy.
Suite 300 Denver, CO 80237
Professional Seal
/2
/2
:4 :2
A
M D
R e v it L o c a l P ro je c ts
\2 \P
L -I
F O
-S h e e ts b g e tt e l.
rv t
00.PP.406
PLUMBING DETAILS
08/31/2012CDI No.12 08/31/2012
See RFI 1088 See RFI 1088
See RFI 1088See RFI 1088 See KT RFI
2559/VA
RFI 2243
KT RFI #03823/VA #30536:
The flood protection solenoid valve shall be monitored by the building automation system as an alarm point. If the solenoid valves closed due to local detection, an alarm shall be sent to the energy command center in the ENC Bldg.
Ensure the electric solenoid timer control is being provided with a dry contact. If not, then provide an interposing relay with a contact to generate a digital input to the DDC system indicating the status of flood protection solenoid. If the packaged system has a "ready" or "fault" contact, also monitor it as an input to the DDC System.
KT RFI #04155/VA #03990:
The detail shall be reviewed to accomplish connection/interface of the DHWC/cold water piping into each DHX.
KT RFI 3229 / VA RFI 2845
Install compressed air and vacuum pump assemblies on inertia bases with housekeeping pads.
KT RFI 3229 / VA RFI 2845
Install compressed air and vacuum pump assemblies on inertia bases with housekeeping pads.
See RFI 8375 The venting of the manifold PRVs to the outside of the building is required by NFPA 99 - 5.1.3.5.6.1-(6)
Daniel.Erickson Callout RFI #9238: Use manual switch over in lieu of automatic.
Blaine.Odom Callout RFI #10189: Apollo has been instructed to pipe the pressure relief valves from room 03-02-F6-02 and 03-02-E3-03 outside the building to meet NFPA 99 medical gas code. These manifolds cannot be connected to mechanically therefore install a tee downstream of the regulator in the copper tubing and install the relief valve on the branch of the tee and vent the relief valve to the outside.
| 2012-08-27T10:08:10-0600 | |
| Dennis F. Rudko |
File details come from the government source that posted it. Updated .