This guide is supplemental in nature and not all inclusive.

PREMISE WIRING GUIDANCE

Revision C, October 2021

81st COMMUNICATIONS SQUADRON PREMISE WIRING GUIDANCE

Revision C, October 2021 Page 2 of 13

GENERAL

1. The purpose of this document is to supplement Telecommunications Industry Association/Electronic Industry Alliance (TIA/EIA) commercial standards for premise wiring (Local Area Network cabling) on Keesler AFB.

2. New construction or renovations programming premise wiring work requires coordination with the 81 CS/SCXP Plans and Programs Office, contact # 377- 7500 prior to implementation.

3. All premise wiring installed on Keesler AFB will conform to TIA/EIA wiring standards listed at the end of this document and the supplemental guidance contained in the attachments within this document.

4. Any deviations from the attached standards and this supplement should be coordinated and approved by the 81 CS/SCXP.

5. Contractual responsibilities:

5.1 Contractors selected to complete premise wiring work must have at least one experienced\technically certified Building Industry Consulting Service International (BICSI) technician on site.

5.2 Provide as-built drawings for the premise wiring work accomplished identifying installation/relocation work.

5.3 Provide test results for new\relocated premise wiring work accomplished.

5.4 Contractors shall be responsible for restoring work areas to original condition.

5.5 81 CS quality assurance office 81 CS/SCQ will be the approving authority for premise wiring work accomplished in new construction or renovations.

Revision C, October 2021 Page 3 of 13

RACKS/CABINETS (If installed)

Cabinets/Racks will be labeled on the front and rear at the top and bottom on a permanent part of the cabinet/rack. Text on labels shall be machine printed without serifs, uppercase and large enough to be read while standing near the cabinet/rack. The label color will contrast with surface upon which it is affixed (white on a dark surface, black on a light surface)(ANSI/TIA/EIA-606-A-1 section 11).

RACK 1 RACK 1

RACK 1 RACK 1

Revision C, October 2021 Page 4 of 13

CABLING

All copper cables, connectors, ports, jacks, outlets, and patch panels shall be TIA/EIA Category 6 rated.

Cat 5e UTP

Cat 6 UTP

Cat 6 FTP

Cat 6A UTP

CABLE COLOR CODING

All installations and renovations will use the following cable color code:

Alarms/Cameras – yellow Public Address (PA) Systems – gray Secure Comm (encrypted) – red Data/Voice - blue

Revision C, October 2021 Page 5 of 13

TERMINATIONS

All premise cabling supporting a Local Area Network will be terminated using 568B standards.

Pairs will not be untwisted more than .5 inch. Cable jacket will not be stripped back more than 1 inch. No nicks on the inner conductors.

Revision C, October 2021 Page 6 of 13

CABLE MANAGEMENT

The Contractor shall ensure a neat and orderly installation utilizing proper cable management IAW current applicable standards. Data drops shall be routed in a manner to ensure the cables are protected and aesthetically pleasing along the cable path. Metal raceways (cable ladder or wire basket) shall be installed and/or utilized in all communication rooms.

Cable trays shall be installed and/or utilized in all communication rooms.

Cables will be independently supported off the ceiling with supports no more than 60 inches apart.

Cable route should avoid fluorescent light ballasts, electrical cables and motors.

Revision C, October 2021 Page 7 of 13

CABLE MANAGEMENT (continued)

Cable jackets must not be distorted. Velcro or nylon are acceptable – Velcro is better at protecting cable geometry. Staples will not be used.

Any building penetrations (to include wall, ceiling, or floor), shall be in compliance with National Fire Protection Agency (NFPA) regulations and coordinated with CSC’s structural office and fire department.

Revision C, October 2021 Page 8 of 13

LABELING

All labeling shall be machine generated, without serifs, uppercase and large enough to be easily read (ANSI/TIA/EIA-606-A-1 section 11).

The naming scheme shall also be coordinated with the 81st Communications Squadron (81 CS/SCXP).

Outlet(s)

Patch Panel(s)

Example of a single quad data outlet located in room 32 and terminating in TR 110, Rack 1, Panel 1 and starting in port #1 of the patch panel

Example of a second quad data outlet located in room 32 and terminating in TR 110, Rack 1, Panel 1 and starting in port #5 of the patch panel

32-1

A B C D

32-2

A B C D

Example of RACK 1 PANEL 1 located in TR 110 and connecting to Room 32 Outlets 1 and 2.

Revision C, October 2021 Page 9 of 13

LABELING (continued)

Cables - All cables will be labeled on both ends with encoded identifiers per (ANSI/TIA/EIA-606-A-1 section 11).

(located within 12 inches of faceplate) (located within 12 inches of patch panel)

110-1-1-1

110-1-1-2

110-1-1-3

110-1-1-4

32-1-A

32-1-B

32-1-C

32-1-D

RACK 1

Example of a single quad data outlet located in room 32 and terminated in TR 110, Rack 1, Panel 1 and starting in port #1 of the patch panel

Revision C, October 2021 Page 10 of 13

GROUNDING (TIA-607-B) (If installed)

All grounds will be labeled (ANSI/TIA-607-B para 7.8) (if installed).

All ground connections will have a clear margin of bare metal-to-metal contact (ANSI/TIA-607-B para 7.6).

Cabinets, racks and other enclosures shall not be bonded serially, each shall have their own dedicated bonding conductor (ANSI/TIA-607-B para 7.1.4).

Revision C, October 2021 Page 11 of 13

Premise Wiring References

NUMBER TITLE WEBSITE OR LOCATION

BICSI TDM Manual Building Industries Consulting Services International (BICSI) Telecommunications Distribution Methods (TDM) Manual http://www.bicsi.org/

NFPA 70 (2008) National Fire Protection Association (NFPA), National Electric Code (NEC) http://www.nfpa.org/

29 CFR 1910.268 Occupational Safety and Health Standards, Telecommunications http://www.osha.gov

ANSI American National Standards Institute (ANSI) and Internet Standards Resources http://www.ansi.org/

TIA Telecommunications Industry Association (TIA): TIA Standards See Commodity Specific Appendices and Individual Task Orders https://tiaonline.org/

TIA-526-7 (Jul 2015) Measurement of Optical Power Loss of Installed Single-Mode Fiber Cable Plant https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-568.0

(Mar 2020)

Generic Telecommunications Cabling for Customer Premises

TIA-568 SET (Mar 2020)

Commercial Building Telecommunications Cabling Standard

TIA-568.2

(Sep 2018)

Balanced Twisted-Pair Telecommunications Cabling and Components Standard http://www.tiaonline.org/

TIA-568.3 (Oct 2016) Optical Fiber Cabling and Components Standard

ASTM D4566-20 Standard Test Methods for Electrical Performance Properties of Insulations and Jackets for Telecommunications Wire and Cable http://webstore.ansi.org/

TIA-569 (May 2019) Telecommunications Pathways and Spaces http://www.bicsi.org/ http://www.nfpa.org/ http://www.osha.gov/ http://www.ansi.org/ https://tiaonline.org/ https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA http://www.tiaonline.org/ https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA http://webstore.ansi.org/ https://global.ihs.com/csf_home.cfm?&csf=TIA

Revision C, October 2021 Page 12 of 13

TIA-570 (Jul 2018) Residential Telecommunications Cabling Standard

TIA-598 (Jul 2014) Optical Fiber Cable Color Coding https://global.ihs.com/csf_hom

TIA-606 (Oct 2021) Administration Standard for Telecommunications Infrastructure

TIA-607

(Jul 2019)

Commercial Building Grounding and Bonding Requirements for Telecommunications

TIA/EIA-758 (Mar 2012)

Customer-Owned Outside Plant Telecommunications Infrastructure Standard

EIA/ECA-310 (Dec 2005)

Racks, Panels and Associated Equipment https://standards.globalspec.c om/std/195405/EIA/ECA-310

ICEA S-80-576 (2002) Category 1 & 2 Individually Unshielded Twisted Pair Indoor Cables for Use in Communications Wiring Systems https://www.techstreet.com/ice a/searches/33123596

ICEA S-83-596-2016 Fiber Optic Premises Distribution Cable https://www.techstreet.com/ice a/subgroups/54441

GR-409, Issue 2 (Nov 2008)

Generic Requirements for Indoor Fiber Optic Cable https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=21553131 5SEARCH&DOCUMENT=gr

GR-20, Issue 4 (July 2013)

Generic Requirements for Optical Fiber and Optical Fiber Cable https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=21553131 5SEARCH&DOCUMENT=gr

NEMA TC 2-2020 Electrical Polyvinyl Chloride (PVC) Conduit http://www.nema.org/stds/tc2.cfm

NEMA TC 6&8-2020 PVC Plastic Utilities Duct for Underground Installations http://www.nema.org/stds/tc6_8.c fm

NEMA TC 9-2020 Fittings for PVC Plastic Utilities Duct for Underground Installation http://www.nema.org/stds/tc9.cfm

RUS Bulletin 1751F-

Underground Plant Design https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 51F-643.pdf https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://standards.globalspec.com/std/195405/EIA/ECA-310 https://standards.globalspec.com/std/195405/EIA/ECA-310 https://www.techstreet.com/icea/searches/33123596 https://www.techstreet.com/icea/searches/33123596 https://www.techstreet.com/icea/subgroups/54441 https://www.techstreet.com/icea/subgroups/54441 https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr http://www.nema.org/stds/tc2.cfm http://www.nema.org/stds/tc6_8.cfm http://www.nema.org/stds/tc6_8.cfm http://www.nema.org/stds/tc9.cfm https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-643.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-643.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-643.pdf

Revision C, October 2021 Page 13 of 13

RUS Bulletin 1751F-

Underground Plant Construction https://www.rd.usda.gov/sites/

51F-644.pdf

RUS Bulletin 1753F-

801(PC-5A)

RUS Standard for Service Installations at Customer Access Locations https://www.rd.usda.gov/sites/

53F-801.pdf

401 (PC-2)

RUS Standards for Splicing Copper and Fiber Optic Cable https://www.rd.usda.gov/sites/

53F-401.pdf

601a

RUS Specifications for Fiber Optic Cables (PE-90a) https://www.rd.usda.gov/files/ UTP_Bulletins_1753F- 601a.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-644.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-644.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-644.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-801.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-801.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-801.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-401.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-401.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-401.pdf https://www.rd.usda.gov/files/UTP_Bulletins_1753F-601a.pdf https://www.rd.usda.gov/files/UTP_Bulletins_1753F-601a.pdf https://www.rd.usda.gov/files/UTP_Bulletins_1753F-601a.pdf