Attachment 4 Example Panel Boards and Circuit Breaker.pdf
PDF 11 MB Posted
- Attached to
- Electrical Panel Upgrade Building 5 Federal contract opportunity
- Solicitation number
- 12805B20Q0201
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 2 SOW Electrical Service Upgrade Bldg 5.pdf | ||
| Solicitation 12805B20Q0201.pdf | ||
| Attachment 7 ARS-371.pdf | ||
| Attachment 6 Panel Schedule Schedules.xls | XLS spreadsheet | |
| Attachment 3 Arc Flash.pdf | ||
| Attachment 8 ARS-372.pdf | ||
| Attachment 5 Diagrams.pdf | ||
| Attachment 1 Bid Schedule MS Excel Interactive Document.xlsx | XLSX spreadsheet | |
| Attachment 9 Wage Determination TX20200234.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Installation Consult instructions NEMA PB-1.1 located in the circuit directory on the front door before installing this panelboard. If necessary, order replacement manual from supplier.
Wiring Guidelines (Cu or Al)
• Use 60°C or 75°C ampacity sized wire on line and neutral and equipment ground terminals.
• Standard wire sizes listed in this publication may be changed by using alternate terminal kits.
• Refer to circuit breakers for allowable wire temperature rating, wire size and tightening torque.
• Neutral rated for 200% panelboard phase current option.
• Use copper wire only at neutral main lugs
- 125A (1) neutral cables 250 mcm maximum
- 225A (2) neutral cables 250 mcm maximum
- 400A (2) neutral cables 600 mcm maximum
- 600A (4) neutral cables 350 mcm maximum
Suitable for nonlinear loads, 200% rated neutral, additional “Y” lugs provided for 200% neutral.
Short Circuit Current Rating The panelboard’s maximum short circuit interrupting rating in rms symmetrical amperes, is equal to the lowest interrupting rating of any device installed, except as noted in the series rating listed in DEH-40007, with integral or remote main circuit breaker or fusible switch installed upstream of the panelboard.
Devices to be installed or replacement units shall be from the same manufacturer, of the same type, and have equal or greater interrupting capacity.
Maximum continuous loads on main or branch circuits shall not exceed 80% of the ratings of the listed circuit breakers. Branch breaker straps suitable for 180A maximum.
Tripped Breaker If the breaker trips, handle will be in intermediate position.
Instructions To Restore Power
1. Move handle to OFF position.
2. Then move handle to ON position.
Typical AQ/AL Panelboard
Seismic Rating Meets or Exceeds the Requirements According to
• IEEE-693-2005
High Level with 1.8 Amplication Factor
• IBC-2006
Sds = 1.3g, Ss = 200%, Ip = 1.5, for z/h > 0 Sds = 2.0g, Ss = 300%, Ip = 1.5, for z/h = 0 In accordance with ICC-ES-AC156
Polybag Contents A polybag of goods supplied with every panelboard interior contains:
• Arc flash label
• DEH-40007 Series Ratings, Wiring Diagrams & Circuit Directory
• Series rating sticker
• Front installation instructions
• ANSI PB1 documentation
• Circuit numbering stickers (1-84)
• Front and shield mounting screws
Torque
Rating Pressure Lug Kit Crimp Lug Kit Pressure Lug Kit
Cat. No. Wire Range Al/Cu Cat. No. Wire Range Al/Cu Cat. No. Wire Range Cu Only
125A MLA1 6-350 MLT1 4-300 MLR1 4-350
225A MLA2 1/0-250 MLT2 2/0 - 500 MLR2 1/0-600
400A Standard - MLA41 4-600 MLT41 500-750 (Cu Only) MLR41 1/0-600
Oversize – MLA62 3/0 - 800 (Main) & 4-600 (Neutral) - - - -
600A Standard -MLA61 4-500 - - MLR61 1/0-600
Wire Crimp Tool
All Al & Up to 500 MCM Cu Hubbell Anderson VC6
500-750 MCM Cu Hubbell Anderson VC7
Up to #6-1000 MCM Cu & #5-750 kcmil Al Burndy Tool Y644HS
Holes Wire Size – Cu / Al
Large 2 / 0 - 14
Small No. 4 – 14
Slotted Screw
AWG
Wire
Lbs-Ins
Min Max
14-10 32 35
8 36 40
6-4 41 45
3-2/0 45 50
Screw Size Torque (In-Lbs)
#4 Steel 16
#10 Plastic 16
#8 Cu/Al/Steel 24
#10-32 Cu/Al/Steel 32
1/4-20 Al/<.150 Thick Cu 44
1/4-20 .150 Thick Cu 60
5/16-18 Cu/Al/Steel 110
3/8-16 Cu/Al/Steel 220
1/2-13 Cu/Al/Steel 220
Internal Hex
Hex Size
Lbs-Ins
Min Max
3/16 108 120
1/4 180 200
5/16 240 275
3/8 330 375
1/2 450 500
Lug Kits
Tightening Torque Applies to line, neutral and equipment ground terminal
Torque Values for Hardware
Lug Kits for A-Series II Panelboards
Crimp Tools
Neutral Lug Z
Arc fault label included with all interiors to be applied by electrical contractor.
Interrupting Ratings - Molded Case Circuit Breakers
Circuit Breaker Terminals (Cu-Al) Frame
Poles No. per Pole Cat. No.
Wire Cu-Al (Unless otherwise specified)
Standard Current Limiting / High Interrupting Per Lug Range
THQB, TXQB, THHQB,
THQL, THHQL, TXQL - 1,2,3 1 Fixed to Breaker Terminal 1 (15-30A) #14-4 Cu or #12-4 Al, (35-100A) #14-10 Cu or #12-1/0 Al
- SEH, SEL, SEP 2,3 1 TCAL18 1 #12-3/0 Al; #12-3/0 Cu
SFHA SFLA, SFPA 2,3 1 TCAL129 1 #8-350kcmil
SGHA SGL, SGP
2 1 TCLK265 - 2 (2/0-400kcmil, Cu) or 2 (2/0-500kcmil, Al) or #6-600kcmil
3 1 TCLK365 - 2 (2/0-400kcmil, Cu) or 2 (2/0-500kcmil, Al) or #6-600kcmil
- FGN4, FGH4 2,3 1 FCALK318H - Top Hole #8-400kcmil Cu or #6-500kcmil Al.
Bottom hole #2/0-600kcmil Cu & Al
SKHA8 SKLA8, SKPA8 2,3 1
TCAL41 1 #4-600kcmil or 2(1/0-250kcmil)
TCAL61 2 2/0-500kcmil
TCAL81 3 3/0-500kcmil
Molded Case Circuit Breakers Federal Spec UL Listed Interrupting Ratings in kA
Construction Frame Trip Range (Amps) Pole AC DC C/B Class W-C-375B
RMS Symmetrical AC Volts
120 120/ 240 240 277 480Y/277 480 600
HQ Frame
THQB 15-70 1 120/240 12a 10 10
THQL
15-125 2 120/240 12a 10
15-100 2,3 240 12a 10
THQL-AF 15-20 1 120/240 10
THQL-DF 15-20 1 120 10
THQL-GF 15-30 1,2 120/240 10
THQL-HID 15-20 1,2 120/240 10
THQB-GF 15-30 1,2 120/240 10
THQB-HID 15-20 1,2 120/240 10
TXQB 15-30 1,2 120/240 65
HHQ Frame
THHQB 15-70 1 120/240 14a 22 22
THHQL
15-125 2 120/240 14a 22
15-100 2 240 14b 22
15-100 3 240 14b 22
THHQL-AF 15-20 1 120/240
THHQL-DF 15-20 1 120 22
THHQL-GF 15-30 1 120/240 22
THHQL-HID 15-20 1,2 120/240 22
THHQB-GF 15-30 1 120/240 22
THHQB-HID 15-20 1,2 120/240 22
Standard Frames TQD 125-225 2,3 240 12b 10
TJD 250-400 2,3 240 2501 14b 22
Hi-Break Frames THQD 125-225 2,3 N/A 22
Spectra RMS
SEH2 15-150
2 480 13b, 15b 65 25
3 600 22a 65 25 18
SEL 15-150
2 480 13b, 15b 100 65
3 600 21a, 22a, 23a 100 65 25
SEP 15-150
2 480 16a 200 100
3 600 16a, 23a 200 100 25
SFH 70-250
2 480 13b 65 35
3 600 20a, 22a 65 35 22
SFL 70-250
2 480 13b 100 65
3 600 21a, 23a 100 65 25
SFP 70-250
2 480 16a 200 65
3 600 16a, 23a 200 65 25
SGH42 125-400 2,3 600 21a, 23a 65 35 25
SGH62 250-600 2,3 600 23a 65 35 25
SGL4 125-400 2,3 600 23a 100 65 65
SGP4 125-400 2,3 600 23a 200 100 65
SGL6 250-600 2,3 600 24a 100 65 65
SGP6 250-600 2,3 600 25a 200 100 65
SKH8 300-800 2,3 600 21a, 23a 65 50 25
SKL8 300-800 2,3 600 24a 100 65 42
SKP8 300-800 2,3 600 25a 200 100 65 13 Poles are not DC rated 2Not current limiting breaker type
Wiring Space
Main rating in amps Main Lugs Only, to End Wall
Frame Type Mounting Main Circuit Breaker
Phase Lug Neutral Lug Phase Lug
Neutral Lug To Side Wall (20” Wide box) To End Wall
125A MLO, 100A Main Breaker 6 6 TEY, SE Horizontal 5 - 6 225A 12 12 TFJ, SF Vertical - 6 12 400A 15 113 SF, SG, FG Vertical - 15 113
600A 15 113 SG Vertical - 16 - 800A4 15 113 SK Vertical - 18 -
3To side wall 4Box width is 30” and 7.81” deep
Branch Circuit Devices Frame No. of Poles Minimum Wiring Spaces To Side Wall (20” Wide Box) Double Branched Bolt-on Devices THQL, THHQL, THQB, THHQB 1,2,3 6.5"
Horizontal Subfeeds Single Branch Mounted TQD, THQD 2,3 5.5"
Panel Size Box
Front Cat. No.7
Cat. No.5 Size Inches6
0-25.5 AB25B 25.5 AF25F,S
28.5-31.5 AB31B 31.5 AF31F,S
34.5-37.5 AB37B 37.5 AF37F,S
40.5-43.5 AB43B 43.5 AF43F,S
46.5-49.5 AB49B 49.5 AF49F,S
52.5-55.5 AB55B 55.5 AF55F,S
57.5-64.5 AB64B 64.5 AF64F,S
67.5-76.5 AB76B 76.5 AF76F,S
5“ B” suffix provides blank end walls. Order “K” suffix for endwalls with knockouts.
6Standard boxes are 20” wide by 5.81” deep.
7Flush fronts are 1 1/2” larger than box. Surface fronts are 1/4” larger.
Description Cat. No. Suffix11
Painted Box P 30" wide12 W NEMA 3R/12/4S/4X 3 or 4 NEMA 3RX Door-in-door 3M NEMA 4X (316 Stainless Steel) 4S
11Add to base box product number.
12Includes field installable gutter barrier.
Description Cat. No. Suffix8
Screw cover C Front hinged to box D Yale 5116 w/Rosette Lock Y Corbin 15767 Lock L GE 75 Key Lock E Corbin 60 Key Lock J Door within a door9 P Stainless steel10 S 30” wide W Nameplate N Screw on nameplate U Metal directory M
Dimensions (inches) Cat No.
H W D UL Standard CSA Labeled
25.5 20 6 AB254S AB254AS
25.5 30 8 AB254DWS AB254DWAS
31.5 20 6 AB314S AB314AS
31.5 30 8 AB314DWS AB314DWAS
37.5 20 6 AB374S AB374AS
37.5 30 8 AB374DWS AB374DWAS
43.5 20 6 AB434S AB434AS
43.5 30 8 AB434DWS AB434DWAS
49.5 20 6 AB494S AB494AS
49.5 30 8 AB494DWS AB494DWAS
55.5 20 6 AB554S AB554AS
55.5 30 8 AB554DWS AB554DWAS
64.5 20 6 AB644S AB644AS
64.5 30 8 AB644DWS AB644DWAS
76.5 20 6 AB764S AB764AS
76.5 30 8 AB764DWS AB764DWAS
Minimum Wiring Space, From End of Lug to Box Wall, in Inches
Wiring Space – Branch Circuit Breakers
Enclosures Front Options
Box Options Stainless Steel Enclosures
Description Cat. No.
1-48 APN48
43-84 APN84
85-126 APN126
Permanent Circuit Number Kits
Typical Panelboard Front view with trim removed
Typical Front w/Concealed Hinges and Trim Adjusting Screws Surface mounting – add 1/4” to inside box dimensions Flush mounting – add 1 1/2” to inside box dimensions
8 Add to base front catalog number.
9 Consists of two lockable doors—one over panel interior and one over box wiring gutters. Yale locks not available.
10 Flush only. Available with C and N options.
Typical Box
Wiring Space
Minimum Wiring Space, From End of Lug to Box Wall, in Inches
(1) To side wall (2) Box width is 30” and 7.81” deep
Wiring Space – Branch Circuit Breakers
Branch Circuit Devices Frame No. of Poles Minimum Wiring Spaces To Side Wall (20" Wide Box)
Double Branched Bolt-on Devices THQL, THHQL, THQB, THHQB 1,2,3 6.5" Horizontal Subfeeds Single Branch Mounted TQD, THQD 2,3 5.5"
Main rating in amps
Main Lugs Only, to End Wall Frame
Type Mounting
Main Circuit Breaker Phase Lug Neutral Lug
Phase Lug Neutral Lug To Side Wall (20" Wide box) To End Wall
125A MLO, 100A Main Breaker 6 6 TEY, SE Horizontal 5 - 6 225A 12 12 TFJ, SF Vertical - 6 12 400A 15 11 (1) SF, SG, FG Vertical - 15 11 (1)
600A 15 11 (1) SG Vertical - 16 - 800A (2) 15 11 (1) SK Vertical - 18 -
Typical Panelboard Front view with trim removed
Typical Front w/Concealed Hinges and Trim Adjusting Screws Surface mounting – add 1/4” to inside box dimensions Flush mounting – add 1 1/2” to inside box dimensions
For 3/8” Bolt
Box Width (Inside)
Bo x
H ei gh t (
In si de
3 3
Typical Box
Enclosures
(1) “B” suffix provides blank end walls. Order “K” suffix for endwalls with knockouts.
(2) Standard boxes are 20" wide by 5.81" deep.
(3) Flush fronts are 1 1/2" larger than box. Surface fronts are 1/4" larger.
Box Options
(1) Add to base box product number.
(2) Includes field installable gutter barrier.
Permanent Circuit Number Kits
Front Options
Stainless Steel Enclosures Dimensions (inches) Cat No.
H W D UL Standard CSA Labeled
25.5 20 6 AB254S AB254AS
25.5 30 8 AB254DWS AB254DWAS
31.5 20 6 AB314S AB314AS
31.5 30 8 AB314DWS AB314DWAS
37.5 20 6 AB374S AB374AS
37.5 30 8 AB374DWS AB374DWAS
43.5 20 6 AB434S AB434AS
43.5 30 8 AB434DWS AB434DWAS
49.5 20 6 AB494S AB494AS
49.5 30 8 AB494DWS AB494DWAS
55.5 20 6 AB554S AB554AS
55.5 30 8 AB554DWS AB554DWAS
64.5 20 6 AB644S AB644AS
64.5 30 8 AB644DWS AB644DWAS
76.5 20 6 AB764S AB764AS
76.5 30 8 AB764DWS AB764DWAS
Description Cat. No. Suffix (1)
Screw cover C Front hinged to box D Yale 5116 w/Rosette Lock Y Corbin 15767 Lock L GE 75 Key Lock E Corbin 60 Key Lock J Door within a door (2) P Stainless steel (3) S 30” wide W Nameplate N Screw on nameplate U Metal directory M
Description Cat. No.
1-48 APN48
43-84 APN84
85-126 APN126
Description Cat. No. Suffix (1)
Painted Box P 30" wide (2) W NEMA 3R/12/4S/4X 3 or 4 NEMA 4X (316 Stainless Steel) 4S
Panel Size Box Front Cat. No. (3)Cat. No. (1) Size Inches (2)
0-25.5 AB25B 25.5 AF25F,S
28.5-31.5 AB31B 31.5 AF31F,S
34.5-37.5 AB37B 37.5 AF37F,S
40.5-43.5 AB43B 43.5 AF43F,S
46.5-49.5 AB49B 49.5 AF49F,S
52.5-55.5 AB55B 55.5 AF55F,S
57.5-64.5 AB64B 64.5 AF64F,S
67.5-76.5 AB76B 76.5 AF76F,S
(1) Add to base front catalog number.
(2) Consists of two lock-able doors—one over panel interior and one over box wiring gutters. Yale locks not available.
(3) Flush only. Available with C and N options.
Wiring Space
Minimum Wiring Space, From End of Lug to Box Wall, in Inches
(1) To side wall (2) Box width is 30” and 7.81” deep
Wiring Space – Branch Circuit Breakers
Branch Circuit Devices Frame No. of Poles Minimum Wiring Spaces To Side Wall (20" Wide Box)
Double Branched Bolt-on Devices THQL, THHQL, THQB, THHQB 1,2,3 6.5" Horizontal Subfeeds Single Branch Mounted TQD, THQD 2,3 5.5"
Main rating in amps
Main Lugs Only, to End Wall Frame
Type Mounting
Main Circuit Breaker Phase Lug Neutral Lug
Phase Lug Neutral Lug To Side Wall (20" Wide box) To End Wall
125A MLO, 100A Main Breaker 6 6 TEY, SE Horizontal 5 - 6 225A 12 12 TFJ, SF Vertical - 6 12 400A 15 11 (1) SF, SG, FG Vertical - 15 11 (1)
600A 15 11 (1) SG Vertical - 16 - 800A (2) 15 11 (1) SK Vertical - 18 -
Typical Panelboard Front view with trim removed
Typical Front w/Concealed Hinges and Trim Adjusting Screws Surface mounting – add 1/4” to inside box dimensions Flush mounting – add 1 1/2” to inside box dimensions
For 3/8” Bolt
Box Width (Inside)
Bo x
H ei gh t (
In si de
3 3
Typical Box
Enclosures
(1) “B” suffix provides blank end walls. Order “K” suffix for endwalls with knockouts.
(2) Standard boxes are 20" wide by 5.81" deep.
(3) Flush fronts are 1 1/2" larger than box. Surface fronts are 1/4" larger.
Box Options
(1) Add to base box product number.
(2) Includes field installable gutter barrier.
Permanent Circuit Number Kits
Front Options
Stainless Steel Enclosures Dimensions (inches) Cat No.
H W D UL Standard CSA Labeled
25.5 20 6 AB254S AB254AS
25.5 30 8 AB254DWS AB254DWAS
31.5 20 6 AB314S AB314AS
31.5 30 8 AB314DWS AB314DWAS
37.5 20 6 AB374S AB374AS
37.5 30 8 AB374DWS AB374DWAS
43.5 20 6 AB434S AB434AS
43.5 30 8 AB434DWS AB434DWAS
49.5 20 6 AB494S AB494AS
49.5 30 8 AB494DWS AB494DWAS
55.5 20 6 AB554S AB554AS
55.5 30 8 AB554DWS AB554DWAS
64.5 20 6 AB644S AB644AS
64.5 30 8 AB644DWS AB644DWAS
76.5 20 6 AB764S AB764AS
76.5 30 8 AB764DWS AB764DWAS
Description Cat. No. Suffix (1)
Screw cover C Front hinged to box D Yale 5116 w/Rosette Lock Y Corbin 15767 Lock L GE 75 Key Lock E Corbin 60 Key Lock J Door within a door (2) P Stainless steel (3) S 30” wide W Nameplate N Screw on nameplate U Metal directory M
Description Cat. No.
1-48 APN48
43-84 APN84
85-126 APN126
Description Cat. No. Suffix (1)
Painted Box P 30" wide (2) W NEMA 3R/12/4S/4X 3 or 4 NEMA 4X (316 Stainless Steel) 4S
Panel Size Box Front Cat. No. (3)Cat. No. (1) Size Inches (2)
0-25.5 AB25B 25.5 AF25F,S
28.5-31.5 AB31B 31.5 AF31F,S
34.5-37.5 AB37B 37.5 AF37F,S
40.5-43.5 AB43B 43.5 AF43F,S
46.5-49.5 AB49B 49.5 AF49F,S
52.5-55.5 AB55B 55.5 AF55F,S
57.5-64.5 AB64B 64.5 AF64F,S
67.5-76.5 AB76B 76.5 AF76F,S
(1) Add to base front catalog number.
(2) Consists of two lock-able doors—one over panel interior and one over box wiring gutters. Yale locks not available.
(3) Flush only. Available with C and N options.
Wiring Space
Minimum Wiring Space, From End of Lug to Box Wall, in Inches
(1) To side wall (2) Box width is 30” and 7.81” deep
Wiring Space – Branch Circuit Breakers
Branch Circuit Devices Frame No. of Poles Minimum Wiring Spaces To Side Wall (20" Wide Box)
Double Branched Bolt-on Devices THQL, THHQL, THQB, THHQB 1,2,3 6.5" Horizontal Subfeeds Single Branch Mounted TQD, THQD 2,3 5.5"
Main rating in amps
Main Lugs Only, to End Wall Frame
Type Mounting
Main Circuit Breaker Phase Lug Neutral Lug
Phase Lug Neutral Lug To Side Wall (20" Wide box) To End Wall
125A MLO, 100A Main Breaker 6 6 TEY, SE Horizontal 5 - 6 225A 12 12 TFJ, SF Vertical - 6 12 400A 15 11 (1) SF, SG, FG Vertical - 15 11 (1)
600A 15 11 (1) SG Vertical - 16 - 800A (2) 15 11 (1) SK Vertical - 18 -
Typical Panelboard Front view with trim removed
Typical Front w/Concealed Hinges and Trim Adjusting Screws Surface mounting – add 1/4” to inside box dimensions Flush mounting – add 1 1/2” to inside box dimensions
For 3/8” Bolt
Box Width (Inside)
Bo x
H ei gh t (
In si de
3 3
Typical Box
Enclosures
(1) “B” suffix provides blank end walls. Order “K” suffix for endwalls with knockouts.
(2) Standard boxes are 20" wide by 5.81" deep.
(3) Flush fronts are 1 1/2" larger than box. Surface fronts are 1/4" larger.
Box Options
(1) Add to base box product number.
(2) Includes field installable gutter barrier.
Permanent Circuit Number Kits
Front Options
Stainless Steel Enclosures Dimensions (inches) Cat No.
H W D UL Standard CSA Labeled
25.5 20 6 AB254S AB254AS
25.5 30 8 AB254DWS AB254DWAS
31.5 20 6 AB314S AB314AS
31.5 30 8 AB314DWS AB314DWAS
37.5 20 6 AB374S AB374AS
37.5 30 8 AB374DWS AB374DWAS
43.5 20 6 AB434S AB434AS
43.5 30 8 AB434DWS AB434DWAS
49.5 20 6 AB494S AB494AS
49.5 30 8 AB494DWS AB494DWAS
55.5 20 6 AB554S AB554AS
55.5 30 8 AB554DWS AB554DWAS
64.5 20 6 AB644S AB644AS
64.5 30 8 AB644DWS AB644DWAS
76.5 20 6 AB764S AB764AS
76.5 30 8 AB764DWS AB764DWAS
Description Cat. No. Suffix (1)
Screw cover C Front hinged to box D Yale 5116 w/Rosette Lock Y Corbin 15767 Lock L GE 75 Key Lock E Corbin 60 Key Lock J Door within a door (2) P Stainless steel (3) S 30” wide W Nameplate N Screw on nameplate U Metal directory M
Description Cat. No.
1-48 APN48
43-84 APN84
85-126 APN126
Description Cat. No. Suffix (1)
Painted Box P 30" wide (2) W NEMA 3R/12/4S/4X 3 or 4 NEMA 4X (316 Stainless Steel) 4S
Panel Size Box Front Cat. No. (3)Cat. No. (1) Size Inches (2)
0-25.5 AB25B 25.5 AF25F,S
28.5-31.5 AB31B 31.5 AF31F,S
34.5-37.5 AB37B 37.5 AF37F,S
40.5-43.5 AB43B 43.5 AF43F,S
46.5-49.5 AB49B 49.5 AF49F,S
52.5-55.5 AB55B 55.5 AF55F,S
57.5-64.5 AB64B 64.5 AF64F,S
67.5-76.5 AB76B 76.5 AF76F,S
(1) Add to base front catalog number.
(2) Consists of two lock-able doors—one over panel interior and one over box wiring gutters. Yale locks not available.
(3) Flush only. Available with C and N options.
Accessories Field Installed Kits/Replacement Parts
Item Description Wire Range Cat. No.
Metal Equipment
Ground
Bonded #14-#8 Cu, #12-#8 Al (small holes);
#14-#4 Cu, #6-#4 Al (large holes) TGL2
Extruded Bonded #14-#8 Cu, #12-#8 Al (small holes);
#14-#4 Cu, #6-#4 Al (large holes) EGS12
Aluminum Equipment
Ground
Extruded Bonded (1) #6-350MCM AEBG Extruded Isolated (2) #6-250MCM AEIG
Main Lug #14-#8 Cu, #12-#8 Al (small holes);
#14-#4 Cu, #6-#4 Al (large holes) TGL2
Copper Equipment
Ground
Bonded #14-#8 Cu, #12-#8 Al (small holes);
#14-#4 Cu, #6-#4 Al (large holes) TGC2
Extruded Bonded (1) #4-350MCM AEBGC Extruded Isolated (1) #6-250MCM AEIGC Insulated Isolated 2/0 max. ASPGIBC
Box Width and Depth Box Mounting Box Extension Length (Inches) Cat. No.
20 x 5.81
Flush
9 ABX2509F
18 ABX2518F
24 ABX2524F
Surface
9 ABX2509S
18 ABX2518S
24 ABX2524S
31 ABX2531S
37 ABX2537S
43 ABX2543S
49 ABX2549S
55 ABX2555S
64 ABX2564S
76 ABX2576S
30 x 5.81 Flush
18 ABX3518F
24 ABX3524F
Surface
18 ABX3518S
24 ABX3524S
30 x 7.81 Flush
18 ABX3718F
24 ABX3724F
Surface
18 ABX3718S
24 ABX3724S
Breaker Type Cat. No.
THQB/THHQB/THQL THHQL/TEY TQLFP1
TQD/THQD/TED4/SE/FB TEDFP1
Breaker Type Cat. No.
TED/THED4/SE ASPTED3P
TQD/THQD ASPTQD3P
FB ASPFB12P
Description Cat. No.
For Split & Load End Neutral 343L886G16 For 225A Horizontal Neutrals 343L886G13 225A Horizontal Neutral To Convert 3W to 4W ASP225HNCP 125/225A Horizontal Neutral Conversion from Service Entrance to Non-Service Entrance ASPHNCPSENOT
125/225A Horizontal Neutral to Convert from Non-Service Entrance to Service Entrance ASPHNCPSE
Description Cat. No.
9" Covers Surface ASPABX09S 9" Covers Flush ASPABX09F 18" Covers Surface ASPABX18S 18" Covers Flush ASPABX18F 64" to 76" Covers Surface ASPABX20S 64" to 76" Covers Flush ASPABX20F
Description Cat. No.
Directory Card 139C5612P3 Replacement Lock with Std. Key 569B737P1 Replacement Lock with GE75 Key 569B737P2 Additional Keys for Above Lock 569B737P5 Circuit Numbering Strips 1-48 569B806G1 Circuit Numbering Strips 49-84 569B806G2 Circuit Numbering Strips 85-126 569B806G3 Adhesive Backed Lamicoid Nameplate 3/4" x 3" 315A7190P1 Metal Directory Card Holder 139C5491G1 Directory Card Holder 139C5491P4 Delta Hi-leg Conversion Kit, to Add B-Phase Plug on AL Panels APHBL Bolt on AE/AQ Panels APHBQ NEMA 3R/12 Tamper Proof Tork Screw Kit NEMATRX 2P to 3P TQD Conv. Kit ASP2PTQD3P 2P to 3P SF Conv. Kit for horizontal subfeed ASP2PTFJ3P AD 25 to 65 kAIC Barrier kit ASP25AD65KA1 Service Entrance Kit ASPSERENT 2 wire Relay Kit ASP2WRelay Yale Lock Kit ASPYALE47 Corbin Lock Kit ASPCORBNTEU1 2-3 pole TQD Mechanical Interlock TQDFM1 AQ/AL/AE Rail Bracket ASPAQLEBKT Front Flush Adjust Kit ASPFLUSHADJ AE Front Mounting Kit 139C5720G3 AQ/AL Front Mounting Kit 139C5720G6 AD Front Mounting Kit 139C5728G9 Front Hinge to Box Mounting Kit 139C5700G6 Front Extension Mounting Kit 139C5700G11
Type Cat. No.
Blank ABEW2 Knockout ABEW2
Filler Plates Endwall Kits Field installed.
1 each, for standard 20”w x 5.81”d boxes.
Parts
Box Extensions Bolts to box with or without endwall in place. Extensions can be combined to obtain lengths greater than 18 and 24 inches.
Box Extension Covers Only 10 covers per kit
Breaker Mounting Hardware Kits For mounting breaker in existing space
Equipment Grounds
Bonding Kits
Installation & Maintenance Kit Order catalog number PROCARE. Kit includes:
(5) filler plate hardware kits
(9) bus stud nuts
(5) MLA1 filler plates
(2) 225A phase barriers
(2) feed-thru barriers
(1) 400/600A phase barrier
(50) directory cards/rating books
(50) circuit number strips (1-48)
(50) circuit number strips (43-84)
(5) standard locks & keys
(50) deadfront screws
(10) AQ/AE front hardware kits
(10) AD front hardware kits
(50) service disconnect labels
(50) main labels
AEBG
AEBGC AEIGC
AEIG
ASPGIBC
Specifications A-Series Panelboards and branch breakers meet or exceed the following standards and specifications:
• UL 50 Cabinets and Boxes
• UL 67 Panelboards
• UL 489 Circuit Breakers
• NEMA AB-1 Circuit Breakers
• NEMA PB-1 and PB-1.1 Panelboards
• US Federal Spec W-P.115B Panelboards
• US Federal Spec W-C375b Gen Circuit Breakers
Boxes
• Galvanized steel
• Blank end walls are standard; knockouts are available when specified
• Boxes furnished with provisions for ground bus as standard
Fronts
• Finished in ANSI-61 grey polyester powder coat paint.
• Equipped with corrosion-resistant Valox combination catch and lock door latch (doors over 48” high provided with 2 latches)
• Equipped with concealed hinges and trim adjusting screws
• Directory holder permanently mounted to door
Panels
• Dead front construction
• Interiors are factory assembled on rigid steel frames
• Metal gages in accordance with UL and NEMA standards
• Solderless, anti-turn main lugs suitable for copper or aluminium wires are front removable and branch straps are silver-plated copper fully rated at 100 amperes
• Main bus is aluminum with copper branch connections unless otherwise specified
• Main disconnect device is identified when supplied, and numbers are provided for branch circuits
• Interior base assemblies are Noryl and provide breaker mounting and busbar insulation
Publications
E-DET-465 Certification of Seismic Compliance
DE-42 Typical AL/AQ Panelboard Technical Information
DEH 40007 Lighting Panels Rating Labels, Wiring Diagrams and Circuit Directory
DEH 047 TED, THED, SED, SHE, SEL, SEP Circuit Breaker Mounting Instructions
DEH 059 SGH, SFL, SFP Circuit Breaker Mounting Instructions
DEH 060 SGH, SGL, SGP Circuit Breaker Mounting Instructions
DEH 061 SKH, SKL, SKP Circuit Breaker Mounting Instructions
DEH 065 TQD, THQD Circuit Breaker Mounting Instructions
GE
41 Woodford Avenue Plainville, CT 06062 1-800-431-7867 www.geindustrial.com
Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, express or implied, that such performance will be obtained under end-use conditions.
©2017, General Electric Company and/or its affiliates. All rights reserved.
12.17 DE-42C
Molded Case Circuit Breakers
Application and Selection
Contents
Page
The GE Family of Molded Case Circuit Breakers
Thermal Magnetic & Solid State Trip Types
MicroVersaTrip Plus Tripping Functions
Power+ 4 Tripping Functions
Current Limiting Circuit Breakers
Mag-Break® Motor Circuit Protectors
Accessories
Application Data
Current Ratings
Interrupting Ratings
Time Current Curves
Inspection and Testing
Outline Drawings
The GE Family of Molded Case Circuit Breakers From 10-1200 Amperes
Q-Line TEY E150 F225 J600 K1200
Application Flexibility In switchboards, motor control centers and lighting, power and customized control panelboards, General Electric molded case circuit breakers are used to provide reliable circuit protection. Molded case circuit breakers in individual enclosures are also used in numerous applications.
Minimum Downtime Downtime is reduced and fuse replacement is eliminated with circuit breakers. In case of overload or short circuit, the breaker trips, opening the circuit and protecting the conductors. When normal conditions are restored, the breaker can be closed (“ON”) again.
Trip-Free Mechanism The breaker’s trip-free mechanism opens the breaker contacts under overload or short circuit conditions, even with the breaker handle held in the ON position.
Eliminates Single-Phasing Circuit breakers eliminate single-phasing. When an overload or short circuit occurs on any one conductor, a common trip bar simultaneously disconnects all three conductors of a three-phase circuit.
Easy System Upgrading With General Electric circuit breakers, the circuit can be uprated, even after the breaker has been installed.
Interchangeable trips provide a wide range of ratings within the same frame size.
Accessory Functions Application flexibility of molded case circuit breakers is enhanced by a breaker accessory line. Remote closing or opening, undervoltage protection, indication of “tripped” condition at a remote location, electrical or mechanical interlocking, automatic reclosing, and primary or sequential operation are some of the functions practical with accessories.
Space Savings Space savings can be an important factor in selecting General Electric molded case circuit breakers as equipment components. Higher rated breakers in particular, offer major space economies over fused switches.
Interrupting Ability Interrupting ratings of General Electric molded case circuit breakers are based on actual short circuit tests.
Breakers are rated for RMS symmetrical ac amperes and for maximum dc amperes.
Standards and Specifications General Electric molded case circuit breakers meet standards established by Underwriters’ Laboratories, National Electric Manufacturers Association, Federal Specifications, Institute of Electronic Engineers, National Electric Code and General Electric Company’s own high quality standards.
Rugged, Dependable Construction
Circuit Breaker Frame
• Molded case is molded from high-mechanical and high-dielectric strength engineered plastic.
• Trip indication is shown by handle position midway between ON and OFF. To reset the trip mechanism, move the handle to extreme OFF, then to ON position.
• Quick-make, quick-break, trip-free mechanism minimizes arcing during breaker operation. Contacts cannot be “teased” into position. Trip-free mechanism is independent of manual handle control. The breaker trips under short circuit or overload, even though the operating handle is held in ON position.
• Verifier “Twist-to-Trip” and “Push-to-Trip” mechanically simulates over-current tripping through actuation of linkages not operated by the ON-OFF handle. Experience has shown that thermal magnetic circuit breakers in industrial applications better maintain their original protective characteristics when regularly exercised.
• Common-trip bar assures instant disconnect of all conductors when an overload or short circuit occurs on any one conductor in the circuit, or an accessory trip device operates.
• Silver alloy contacts combine the conductive properties of silver with other elements for clean, positive electrical contacting. Pitting and burning are minimized for longer contact life.
• Arc chutes of heat-absorbing, insulating material and metal grid plates quickly “extinguish” arcs.
• UL listed lugs for copper or aluminum cable, at full frame rating. Easy access and simple, straight-in wiring.
Thermal Magnetic Trip System
• Front-adjustable magnetic trip provides instantaneous trip in event of short circuit. Any current surge above the trip setting produces a magnetic field which instantly actuates the trip mechanism and opens the circuit.
• Thermal trip provides protection against sustained overloads. A bi-metallic element reacts time-wise in inverse proportion to the current. If a circuit is overloaded, heat resulting from excessive current flow causes the bi-metal to bend, actuating the trip mechanism to open the circuit.
• Interchangeable trip units (for frames over 150 ampere rating) simplify stocking and reduce inventory requirements.
Field interchangeability assures maximum flexibility.
Electronic Trip System
• Front adjustable programming functions (Power+ 4, MicroVersaTrip Plus) provide a high degree of flexibility and convenience in making and checking settings.
• Long-time pick up indication is illuminated whenever the breaker is experiencing an overload condition. The light is extinguished by removing the overload or tripping the breaker.
• Glass epoxy printed circuit boards with epoxy conformal coating over all assembled components provide long life with error free operation.
• Switch contacts and board interconnectors provide corrosion resistance and long product life.
• Neutral current sensor connections located between the breaker lugs allow panelboard mounting of breakers without special fillers or increased panel space.
• Fault trip indicators for overload, short circuit, and ground fault are available for local indication.
Thermal Magnetic and Solid State Trip Types
Spectra RMS™ circuit breakers with digital rms-sensing electronic trip units provide many features and benefits not offered by thermal magnetic breakers (refer to GET-7002).
Thermal magnetic trip units are available in all GE molded case circuit breakers from Q Line through K frame.
Solid state trip units may be alternatively selected for J and K frame circuit breakers. Additionally, non-automatic circuit interrupters, or molded case switches, are available. These interrupters have no automatic overload or short circuit trip elements. They are used for manual switching and isolation.
Enclosure Compensated Thermal Trip: 40°C An enclosure compensated thermal trip is constructed to permit an enclosed circuit breaker in a 25°C room ambient to carry 100% of its nameplate current intermittently and 80% of its nameplate current continuously when cabled with conductor sized per the UL 489 standard (see Figure 29.1).
The thermal trip action is accomplished by a bimetallic strip. The movement of the bimetal and thus tripping is proportional to the current — high current fast response, low current slow response. This action provides a time delay which prevents service interruptions from normal inrush currents or temporary overloads. Continuous overloads will cause the bimetal to deflect sufficiently to release the latch and open the breaker contacts. However, the bimetal is also sensitive to ambient temperatures. If the room ambient is above or below 25°C, or the enclosure is warmer than normal, the breaker rating will vary inversely to the temperature: higher ambient-lower current, lower ambient-higher current. Enclosure compensation is furnished on Q-Line, TEB, TEY, TB-1, TED 277 volt and TED 480 volt circuit breakers.
Ambient Temperature Compensated Thermal Trip: 10° TO 50°C An ambient compensating or “Ambient Compensated” thermal trip is the same as an enclosure compensated trip with one notable exception. It has a reduced sensitivity to changes in ambient temperature. In an ambient compen-sating thermal trip an additional bimetal is added to the circuit breaker. This bimetal responds to breaker ambient and modifies the characteristics of the current sensing bimetal to compensate for ambient temperature changes.
Ambient compensating thermal trips are provided as standard in all 600 volt thermal-magnetic molded case circuit breakers.
Adjustable Magnetic Trip — F225, J600, K1200 and TEC, TEML, TFC, TJC, TKC, TFL, THLC-2, THLC-4, TLB4 An electromagnet which partially surrounds the bimetal is used to provide instantaneous trip in the event of a short circuit. The high current creates a strong magnetic field attracting the armature and instantaneously releasing the trip latch in the same manner as the bimetal does on overload.
For short circuit protection, the adjustable magnetic trip provides high, low and intermediate trip settings.
Solid State Trip: -20° TO +55°C Solid state MicroVersaTrip® Plus trip units meet the same standards as thermal trip units. Complete circuit breakers equipped with MicroVersaTrip Plus trip units are rated to carry 100% of their current sensor rating intermittently and 80% continuously in a 40°C breaker ambient. Some MicroVersaTrip Plus equipped breakers are rated to carry 100% continuously and are so marked.
In addition to the protection of conductors as required by codes and standards, MicroVersaTrip Plus can be set to provide protection for equipment such as motors, generators, or transformers and provide improved distribution system selectivity.
OFF
ON
BIMETAL
OVERLOAD PROTECTION
CONTACTS
OFF
ON
BIMETAL
ELECTROMAGNET
CONTACTS
ARCING
SHORT CIRCUIT PROTECTION
Figure 4.1 Operation of Thermal-Mag Trip Units
Frame Type Sensor Rating (Amps) Current Rating (Amps)
J400 150 60, 80, 100, 125, 150
J400 400 150, 200, 225, 250, 300, 400
J600 600 300, 400, 450, 500, 600
K800 800 300, 400, 500, 600, 700, 800
K1200 1200 600, 800, 1000, 1200
Molded Case Circuit Breakers
Table 5.1 Breaker Trip Types
Table 5.2 J/K Rating Plug Selection
Breaker Type Trip Type
Q-Line All Non-Interchangeable
TEY-100 TEY Non-Interchangeable
TEB Non-Interchangeable E150 TED Non-Interchangeable
THED Hi-Break Non-Interchangeable
TFJ Non-Interchangeable F225 TFK Interchangeable
THFK Hi-Break Interchangeable
TJJ Non-Interchangeable TJK Interchangeable
J600 THJK Hi-Break Interchangeable TJ4V Non-Interchangeable TJH4V Hi-Break Non-Interchangeable TJH Hi-Break MVT Plus Interchangeable (Rating Plug ① )
TKM-800 Interchangeable TKM-1200 Interchangeable
K1200 THKM Hi-Break Interchangeable TK4V Non-Interchangeable TKH Hi-Break MVT Plus Interchangeable (Rating Plug ① )
TEL, TEML② Non-Interchangeable TFL② Non-Interchangeable TJL4V Hi-I.C. Non-Interchangeable
Hi-I.C.
TJL Hi-I.C. MVT Plus Interchangeable (Rating Plug ① ) TKL4V Hi-I.C. Non-Interchangeable TKL Hi-I.C. MVT Plus Interchangeable (Rating Plug ① ) TLB-2② Non-Interchangeable TLB-4② Non-Interchangeable
THLC-1② Non-Interchangeable Current Limiting THLC-2② Non-Interchangeable
THLC-4② Non-Interchangeable
TB-1 Non-Interchangeable Tri-Break TB-4 Non-Interchangeable (fused) TB-6 Non-Interchangeable
TB-8 Non-Interchangeable
① MicroVersaTrip® Plus incorporates trip units with field replaceable rating plugs providing ease of changing ratings within frame size and sensor rating, with minimum downtime. See Table 5.2 for rating plug selection.
② Obsolete type.
Type Reverse Feed Trip Unit Type Trip Unit Ratings (Amperes) Instantaneous Type
Q-Line Yes Non-interchangeable 10, 15, 20, 25, 30, 35, 40, 45, 50, Fixed
(THQB, L, C) 60, 70, 80, 90, 100, 110① , 125①
TEY Yes Non-interchangeable 15, 20, 30, 40, 50, 60, 70, 80, Fixed 90, 100
E150 Yes Non-interchangeable 10, 15, 20, 25, 30, 35, 40, 45, 50, Fixed 60, 70, 80, 90, 110, 125, 150
TEL② Yes Non-interchangeable 15, 20, 25, 30, 35, 40, 50, 50, 60, Fixed 70, 80, 90, 100, 125, 150
THLC-1② Yes Non-interchangeable 15, 20, 30, 40, 50, 60, 70, 80, 90, Fixed 100, 125, 150
TB-1 No Non-interchangeable 15, 20, 25, 30, 35, 40, 45, 50, 60, Fixed 70, 80, 90, 100
TQD Yes Non-interchangeable 100, 125, 150, 175, 200, 225 Fixed
F225 TFJ Yes Non-interchangeable 70, 80, 90, 100, 110, 125, 150, Adjustable TFK No Interchangeable 175, 200, 225
TFL② Yes Non-interchangeable 70, 80, 90, 100, 125, 150, 175, Adjustable 200, 225
THLC-2② Yes Non-interchangeable 125, 150, 175, 200, 225 Adjustable
TJD Yes Non-interchangeable 250, 300, 350, 400 Fixed
J400 TJJ Yes Non-interchangeable 125, 150, 175, 200, 225, 250, Adjustable TJK No Interchangeable 300, 350, 400
J600 No Interchangeable 250, 300, 350, 400, 450, 500, 600 Adjustable
TLB-4② Yes Non-interchangeable 250, 300, 350, 400 Adjustable
THLC-4② Yes Non-interchangeable 250, 300, 350, 400 Adjustable
TB-4 No Non-interchangeable 125, 150, 175, 200, 225, 250, Adjustable 300, 350, 400
TB-6 No Non-interchangeable 300, 350, 400, 500, 600 Adjustable
K800 No Interchangeable 300, 350, 400, 450, 500, 600, Adjustable 700, 800
K1200 No Interchangeable 600, 700, 800, 1000, 1200 Adjustable
TB-8 No Non-interchangeable 600, 700, 800 Adjustable
① THQL only (2 pole).
② Obsolete type.
Trip Unit Ratings Molded Case Circuit Breakers Table 6.1 Trip Unit Ratings
MicroVersaTrip Plus™ Tripping Functions
MicroVersaTrip Plus is a trip unit for J and K frame circuit breakers incorporating the newest technological advances in over-current protection for improved reliability, long-life, and flexibility. Operation is fully automatic and normally no external logic or control power inputs are required. It uses digital rms sensing to accurately measure the waveshape and has an LCD display including overload, short circuit, and ground fault indicators.
Programmable Microelectronic Processor This forms the basis of the MicroVersaTrip Plus protection programmer. This miniaturization of circuitry provides the increased flexibility required to incorporate nine adjustable time-current functions, three mechanical fault indicators (local), a long-time pickup indicator (local), and zone selective interlocking. All adjustable programmer functions are automatic and self-contained. This compilation of functions provides the basis for the most flexible and useful breaker design presently available anywhere.
Specially Treated Printed Circuit Boards Each printed circuit board has a protective conformal epoxy coating to prevent moisture absorption, fungus growth, and signal leakage. All electronics are housed within a metallic enclosure designed to protect against hi-fault interruption arcs, magnetic interference, dust, and other contaminants.
Flux-Shift Trip Device A low energy, positive action tripping device which is self-powered by and controlled by the trip unit.
Current Sensor Package Three-phase current sensors are incorporated into a single package providing greater flexibility and reliability.
Molded Case Circuit Breakers
Table 8.1 MicroVersaTrip Plus Trip Unit Functions
Table 8.2 MicroVersaTrip Plus Trip Unit Function Characteristics
LI LIG LIGZ1 LIGZ2 LSI LSIG LSIGZI LSIGZ2
Long-Time Adjustable Current Setting X X X X X X X X Adjustable Long Time Delay X X X X X X X X
Adjustable Pick-Up X X X X Short-Time Adjustable Delay X X X X
I2t Switch X X X X
Adjustable Instantaneous Pick-Up X X X X X X X X
Adjustable Pick-Up X X X X X X Ground Fault Adjustable Delay X X X X X X
I2t Switch X X X X X X
Zone Interlock GF X X
GF-ST X X
Current Long-Time➂ Short-Time Adjustable Ground Fault Setting Instantaneous
Frame Sensor Rating (Multiple Delay Pick-Up Delay Pick-Up Pick-Up Delay Type (Amps) of Rating (Seconds) (Multiple of (Seconds) (Multiple of (Multiple of (Seconds)
Plug Amp) Current Rating Plug Sensor Amp
(X) Setting) (C) Amp) (X) Rating) (S)
J400 150, 400 1.5 to 10.0 2.4, 4.9, 9.8, I2T in .40➃ without I2T in .40➄
J600 600 20 at 600% short-time in .50 to 1.00 of current 1.5 to 9.0 steps of 0.5 0.2 to 0.6
K800 800 in steps setting at in steps 1.5 to 15.0② in steps of .05 lower limit of .05 I2T out① with of 0.01 I2T out①
K1200 1200 of each band .10, .21, .35 short-time in .10, .21, .35 steps of 0.5
① Time delay shown at lower limit of each band. Pick-up tolerances ±10%. Ground fault pick-up not to exceed 1200 amps.
② J600 frame with 600-amp sensor for high IC 65kA rating (TJL) limited to 10X.
➂ Pick-up fixed at 1.05C.
➃ Time delay at 600% of current setting at lower limit of band.
➄ Time delay at 200% of pick-up setting at lower limit of band.
X = rating plug amps S = sensor amp rating C = current setting
Setup Mode Set points for all trip unit functions can be entered into the trip system via the 5-function key pad and LCD display.
When working in Setup Mode, the trip unit must be provided with control power from the internal battery, or the MicroVersaTrip Portable Power Pack or by loading the breaker to at least 20% of its sensor value. While still in Setup Mode, settings can be automatically scanned by depressing the VALUE key for 5 seconds.
Current Setting (Standard) The adjustable current setting determines the nominal long time current setting with a ±10% bandwidth. With a 1.0 setting the breaker will carry indefinitely without tripping the rating plug rating. Changing the setting changes the nominal current rating for the breaker.
Long-Time Delay (Standard) This long-time delay adjustment varies the time it will take the breaker to trip under sustained overload conditions. It provides the function of with-standing momentary overloads such as motor starting, welding, or other overcurrent conditions without interrupting the service.
LShort-Time Pickup (Optional) This short-time pickup adjustment controls the level of high current the breaker can carry for short periods of time without tripping. Permits downstream breakers to clear short circuit faults without tripping out the upstream protective device.
Short-Time Delay (Optional) The short-time delay adjustment is used in conjunction with the short-time pickup setting to provide a further refinement of coordination between circuit breakers. It establishes the time interval the breaker will wait before responding to the short-circuit current level selected on the short-time trip point adjustment.
Adjustable Instantaneous Pickup (Standard) The instantaneous trip point determines the level at which the breaker will trip without intentional time delay (0.025 seconds or less). This immediate interruption occurs only as a result of a severe overcurrent condition, thereby minimizing damage to the electrical system and equipment.
I2T IN
I2T OUT
Ground Fault Pickup and Ground Fault Delay (Optional) The ground fault pickup adjustment controls the level of ground fault current at which circuit interruption will occur. To comply with the National Electrical Code (NEC 230-95), no trip point exceeds 1200 amperes. The common square knee of the curve can be replaced with an I2t function to facilitate coordination with downstream devices such as thermal-magnetic breakers and fuses. The ground fault delay adjustment is used to add a pre-determined delay in time to the trip point once the ground fault pickup level has been reached. This provides tripping selec-tivity between main and feeder or other downstream breakers. The ground fault unit also includes as standard an inverse I2t ramp to substantially improve coordination with downstream protective devices such as fuses and thermal magnetic circuit breakers.
Memory Circuit Because of the highly intermittent and erratic nature of arcing ground faults, a memory circuit has been incorporated in all MicroVersaTrip Plus ground fault-sensing circuits as standard. The memory circuit integrates arcing fault current with time, essentially summing the intermittent ground current spikes. In the diagrams, it can be seen how the memory function works.
Diagram A shows a typical ground fault with half-cycles, whole cycles and multiple cycles missing, as normally occurs.
Diagram B shows trip response of a typical ground fault function, which does not include memory. The breaker never trips because the time delay circuits are reset with every missing cycle.
Diagram C shows response of MicroVersaTrip Plus ground fault circuits to the same ground fault; the circuit’s memory carries through the missing cycles and generates a trip signal after the preset time delay.
Status Indication The LCD display provides continuous information on the operating status of the circuit breaker. Under normal conditions the status screen simply displays the OK message. After a fault event occurs, the LCD display indicates the event type, the magnitude, and overcurrent target when appropriate.
Ground Fault
Trip Line
Trip Line t t t
Ground Fault without Memory
Ground Fault Response with Memory
A
B
C
OK
STATUS
FAULT
STATUSAMPS
I>
LT
Ø1
96 4
Display ModeFault Phase
Fault IndicationTrip Targets
Fault Magnitude
Zone Selective Interlocking The standard means of obtaining selectivity between main and feeder breakers is by incorporating programmers with time-coordinated trip characteristics. This consists of setting the farthest downstream breaker with a small time delay, and progressively increasing the time delay as you get closer to the main protective device. The disadvantage of this method is that the system must now endure the stress of a high current fault between the main and feeder until time-out occurs.
The Zone Selective Interlock module, Figure 11.1, receives a signal from a downstream MicroVersaTrip Plus programmer (Logic 0) which causes the module to transmit a low-level interlock signal to a MicroVersaTrip Plus programmer upstream. The interlock signal activates the LED portion of an LED-Transistor Opto-isolator in the upstream programmer causing the fixed delay band to shift from “MIN” to the programmer delay band setting.
Both the Short-Time and Ground Fault functions are capable of being inter-locked.
Zone Selective Interlocking is available for both the short-time function and the ground fault function, or the ground fault function only.
Test Jack The Test Jack located on the front of the rating plug accepts a test cable supplied with a portable, battery operated (or 120Vac) test kit separately available. The test kit will test the circuit breaker while the circuit breaker is carrying load, and provides either a trip or no trip test. The test kit will simulate a time-over current condition for the long-time, short-time and ground fault functions. It will also read trip unit switch settings and provide a report on the trip unit self-test feature.
Rating Plugs (Standard) Various rating plugs are available to fix the ampere rating equal to or lower than the sensor ampere rating as in Table 5.2.
SOURCE
ZONE 0 CB 1
ZONE 1 CB 2
ZONE 2 CB 3
ZONE 3
MOTOR
"OUTPUT" FROM PROGRAMMER
"INPUT" TO PROGRAMMER
DOWNSTREAM
CONNECTIONS
UPSTREAM
CONNECTIONS
WIRINGBUS
ZSIM
CB 4
ZSIM NO. 3
ZSIM NO. 2
ZSIM NO. 1
M V T
M V T
M V T
M V T
M V T
L1 L2
Figure 11.1 Multi-Zone Interlocking
Power+™ 4 Tripping Functions
Power+ 4 is the standard electronic trip device for GE J and K frame circuit breakers.
This trip unit is integral to the breaker and is not available separately. Operation is fully automatic and, normally, no external logic or control power inputs are required.
Protection Trip Unit The current sensor-powered solid-state logic unit incorporates rotary adjustment knobs for up to four functions. The functions available are Current Setting (standard), Instantaneous Pickup (standard) or Short-time Pickup with Fixed Instantaneous (optional), Ground Fault Delay (optional), and Ground Fault Pick Up (optional).
The Long-time Delay features four user selectable bands, and there are three short time constant delay bands with I2t in or I2t out.
Flux Shift Trip Device A low energy, positive action tripping device is automatically powered and controlled by the protection programmer.
Current Sensor Package Three phase current sensors are incorporated into a single package for maximum flexibility and reliability.
Protective Function Pickup Settings Nominal Midpoint Delay Settings Delay Curve
Long-Time (C) .5, .6, .7, .8, .9, .95, 1.0 3, 6, 8, 12, 25 seconds Fixed multiple of Sensor Rating (X) (Bands 1, 2, 3, 4) at 600% C
Short-Time 1.5, 2, 2.5, 3, 4, 5, 7, 9 .13, .26, .42 second I2t In, I2t Outmultiple of Long-Time Setting (C) (Min, Int, Max) I2t Out
Adjustable 1.5, 2, 3, 5, 7, 9, 10 No Delay N/A Instantaneous ① multiple of Sensor Rating (X)
Ground-Fault .2, .25, .3, .35, .4, .45, .5, .6 .13, .26, .42 second
I2t In, I2t Outmultiple of Sensor Rating (X) (Min, Int, Max) I2t Out
① When short-time protection is provided, instantaneous is fixed at 15X.
Table 12.1 Power+ 4 Protection Functions and Setting Values
Trip Unit Functions Suffix
None N G NG
Adjustable Current Setting X X X X
Long-Time Fixed Long-Time Pickup X X X X Fixed Long-Time Delay X X X X Long-Time Timing Light X X X X
Short-Time Adjustable Short-Time Pickup X X Fixed Short-Time Delay I2t Ramp X X
Instantaneous Adjustable Instantaneous Pickup X X Fixed Instantaneous Pickup② X X
Ground Fault ① Adjustable Group Fault Pickup - Zero Sequence X X Adjustable Ground Fault Delay X X
① For single-phase, 3-wire or 3-phase, 4-wire applications, select appropriate neutral current sensor.
② TJL4V with 500A and 600A sensors available with adjustable instantaneous only.
Table 12.2 Power+ 4 Trip Unit Selection
Current-Limiting Circuit Breakers
Note: OBSOLETE — for reference use only.
To meet increased demands for electrical service by residential, commercial, and industrial users, and to reduce system power losses and cost, larger low-impedance transformers are being installed by power companies. The result is sys-tems with higher available short circuit currents. Traditional branch circuit equipment cannot handle the fault cur-rents available in these systems which can reach 150,000 rms symmetrical amperes or more.
THLC current-limiting circuit breakers (CLB) react far more quickly to high-level short circuits than conventional breakers. In fact, the higher the short circuit current, the faster the THLC operates, because of its magnetic repulsion design.
Example: if a 150,000 RMS symmetrical ampere short circuit at 480 volts ac were to threaten your system, the THLC1 would interrupt it in just 3 milliseconds. At the same time, the THLC1 would limit peak let-through current to less than 42,000 amperes – only 13% of the destructive energy that would flow through without THLC1 protection, and a small enough current to be controlled by standard series-connected circuit breakers.
But a fast break isn’t enough; a CLB must control arc voltage quickly and efficiently, too.
GE THLC current limiting breakers force the arc into patented, U-shaped arc plates where sufficient voltage is developed to “dominate” the short circuit fast. During a 480 volt interruption, for example, the THLC1 quickly counters the driving voltage with a peak arc-voltage in the range of 800 volts – sufficient voltage to quench the short circuit without causing unwanted dielectric breakdown elsewhere down the line.
And for long, reliable life, the THLC is also equipped with special baffles to vent hot gases out of the breaker during the arc-quenching process.
The THLC current-limiting circuit breaker is designed to protect standard circuit breakers with ratings as low as 10,000 AIC on systems with…