Attachment_3_-_GSA_FICAM_compliant_System_Overview_-_Rev_2_0-_3dec21.pdf
PDF 911 KB Posted
- Attached to
- NIFC CAMPUS PACS MODERNIZATION Federal contract opportunity
- Solicitation number
- 140L3722R0022
About this file
This document provides an overview of a physical access control system solution compliant with U.S. government standards. The solution includes AMAG Technology's Symmetry access control management software integrated with HID's pivCLASS components. The system architecture diagram shows the main software components would be installed on Windows servers, including the Symmetry application server, SQL database server, and pivCLASS certificate manager. Field hardware would consist of AMAG M2150 and M4000 controllers supporting up to 144 card readers total. The M2150 nodes can each connect up to 32 expansion nodes with 16 readers each, while the M4000 nodes can each connect up to 20 readers. Related federal contract opportunity NIFC CAMPUS PACS MODERNIZATION is a solicitation from the Department of the Interior Bureau of Land Management Idaho Region to modernize its physical access control system.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| NIFC_Campus_PACS_Modernization_Service_-_QA_8-15-2022_0001.pdf | ||
| SOW_FICAM_COMPLIANCE_UPGRADES_SPECIFICTION_-_Addendum_1_0001.pdf | ||
| Sol_140L3722R0022_Amd_0001.pdf | ||
| Sign_In_Site_Visit_0001.pdf | ||
| NIFC_Campus_PACS_Modernization_Addendum_1_Synopsis_0001.pdf | ||
| Attachment_1_-_FICAM_Drawings_25June2022.pdf | ||
| PROLOUGE_FICAM_UPGRADE__25June2022.docx | DOCX document | |
| Sol_140L3722R0022.pdf | ||
| DOL_Wage_Rate_Service_Contract.pdf | ||
| SOW_FICAM_COMPLIANCE_UPGRADE_SPECIFICATION_27June2022.pdf | ||
| Attachment_2_-_Schedule_of_Values_25June2022.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GSA Compliant Reader (FICAM Reader category)
* Passes APDUs between PAM and smart card
* Passes responses to APDUs back to PAM
* Displays LCD prompts generated by PAM
* Varies LED color, based on commands from PAM
* Supports CAK, PKI + PIN, PKI + BIO
Application Server
Firewall
Internet
Access
OCSP/SCVP
Responder
Certificate
Authority(s)
HTTPS://
- Windows Server 2016 / 2019
- Symmetry v9.3-HSE (Enterprise or Professional)
Symmetry Professional
- Limited to SQL Express
- Limited to 512 readers
- Limited to nine (9) Thick Clients
- Requires added DATA-CONNECT license
Symmetry Enterprise
- Requires licensed SQL instance
- no software limit on readers count
- no software limit on thick clients
- Includes DATA-CONNECT license
Database Server (Optional)
- Windows Server 2016 / 2019
- Microsoft SQL 2017 / 2019
- Requires Symmetry Enterprise
Certificate Manager Server
Required if compliant reader count is above ten (10)
- Windows Server 2016 / 2019
- Microsoft SQL 2017 / 2019
- HID pivCLASS Certificate Manager v 5.12 or above
Optional
Credential Enrollment Workstation(s) minimum of 1 per system
Required to authenticate and validate federal credentials during enrollment
- Windows 10 Enterprise
- Symmetry Client license
- pivCLASS Registration Engine license
Symmetry Client Workstation(s) User interface to Symmetry
- Windows 10 Enterprise
- Symmetry Client license
M2150-Node(s)
M4000-Node(s)
See M2150 Node Architecture drawing for details
See M4000 Node Architecture drawing for details
3dec21 – tph rs485
The M2150 LAN chain can support up to
32 individual nodes, each with 16 readers, on one LAN connection rs485
AMAG Technology Symmetry 9.3 with HID pivCLASS
GSA FRTC 1.3.3 compliant solution
FICAM / HSPD-12 / FRTC 1.3.3 / FIPS 201-1, FIPS 201-2, FIPS-201-3
Head End / LAN / Controller Architecture pivCLASS Certificate Manager (Validation System and PACS Infrastructure component)
* Deactivates (de-provisions) credentials in PACS based on PD-VAL results
* Activates credentials when certificate revocation status transitions from unknown to known.
Symmetry SMS (PACS Infrastructure component)
* Maps PIV/PIV-I credential data elements to PACS database fields for provisioning/de-provisioning as well as activating and deactivating PACS credential records
* communicates to M2150 / M4000 controllers
- One (1) M4000-DBB (intelligent controller)
- One (1) M4000-DEC4
M4000-DDC
3dec21 – tph
M4000-DDC
rs
Each M4000 Node requires a dedicated LAN connection
M4000 nodes cannot be configured using a LAN chain
- Four (4) reader expansion board
- up to four (5) Five can be supported form one (1) M4000-DBB
M4000-DEC4
- Adding large Input / Output expansion boards DOES NOT impact reader capacity
HID
P.A.M
HID
P.A.M
- Support two (2) Readers
- Requires LAN connection
- Requires pivCLASS certificate Manger
HID pivCLASS Authentication Module (PAM)
W ie g a n d
W ie g a n d rs485 rs485
Reader 1
Reader 2 rs485 rs485
Reader 3
Reader 4
M4000-DEC4
AMAG Technology Symmetry 9.3 with HID pivCLASS
GSA FRTC 1.3.3 compliant solution
FICAM / HSPD-12 / FRTC 1.3.3 / FIPS 201-1, FIPS 201-2, FIPS-201-3
Field Hardware - M4000 Node Architecture
Supports up to 4 readers
M4000
DBB
The Federal M4000 controller series can support up to twenty (20) readers per Node
HID
P.A.M
HID
P.A.M
W ie g a n d
W ie g a n d rs485 rs485
Reader 5
Reader 6 rs485 rs485
Reader 7
Reader 8
M4000-DEC4
NOT SHOWN
Three additional M4000-DEC4 boards six Additional HID PAM modules support for a total of twenty GSA compliant readers, per M4000 node rs485 Full Duplex rs485 Full Duplex
Reader 9
Reader 10 rs485 Full Duplex rs485 Full Duplex
Reader 11
Reader 12 rs485 Full Duplex rs485 Full Duplex Reader 14 rs485 Full Duplex rs485 Full Duplex
Reader 15
Reader 16
Reader 13 rs485 Full Duplex rs485 Full Duplex Reader 18 rs485 Full Duplex rs485 Full Duplex
Reader 19
Reader 20
Reader 17
Please reference
COMPLIANT READERS page for GSA approved readers and reader connection details
LAN
M4000-DBB
M4000-DEC4
TCP / IP
Up to Four (4) M4000-DEC4 boards can be connected to the Host board ( 20 total readers)
Up to 4 Readers per M4000-DEC4
M4000-DEC4
M4000-DEC4
M4000-DEC4
M4000-DEC4
AMAG Technology Symmetry 9.3 with HID pivCLASS
GSA FRTC 1.3.3 compliant solution
FICAM / HSPD-12 / FRTC 1.3.3 / FIPS 201-1, FIPS 201-2, FIPS-201-3
Field Hardware - M4000 - Power
Sub boards can be up to 2000' from host controllers -with proper cabling and local controller power
M4000 / HID PAM Power
The M4000-DBB draws power from its host controller, and is NOT included in power budget calculation's
All Power budget calculations are listed at full draw (inrush)
• Each M4000-DEC4 and M4000-IOC20/16 requires 2amps @ 12vdc
• HID PAM modules require 2amps @ 12vdc.
• Each M4000-IPS (Intelligent Power Supply) provides 6.25 Amps @
12vdc
M4000-IOC20/16
M4000-IOC20/16
M4000-IOC20/16
M4000-IOC20/16
In this configurations, Add-On Input Output boards (20 inputs / 16 outputs per board)
REQUIRES added power supplies
To Host Controller
HID
P.A.M
(2)
(1) M4000-IPS
HID
P.A.M
(2)
(1) M4000-IPS
HID
P.A.M
(2)
(1) M4000-IPS
HID
P.A.M
(2)
(1) M4000-IPS
HID
P.A.M
(2)
(1) M4000-IPS
One M4000-IPS can support a combination of up to three (3) local M4000
Control boards or HID PAM modules
3dec21 – tph
HID - RKBCL40
924NPRTEK00504
Insert Card, enter card PIN
Assurance Level 2
HID – RKCL40
923NPRTEK0032V
Veridt – Stealth Dual
900W2036 series
Veridt – Stealth BIO
900W2030 series
Assurance Level 3
Insert Card, enter card PIN, verify Fingerprint
AMAG Technology Symmetry 9.3 with HID pivCLASS
GSA FRTC 1.3.3 compliant solution
FICAM / HSPD-12 / FRTC 1.3.3 / FIPS 201-1, FIPS 201-2, FIPS-201-3
Compliant Reader options rs485 rs485 rs485 rs485
Symmetry Application Server
Database Server
Certificate Manager Server
Optional
Credential Enrollment Workstation(s)
Symmetry Client Workstation(s)
M2150-Node(s)
0 M4000-Node(s) pivCLASS Authentication
Module(s)
8 Up to 16 Compliant Readers
Up to 16 Compliant Readers
Up to16 Compliant Readers
One LAN drop for each PAM
One LAN drop for each PAM
One LAN drop for each PAM
Up to 16 Compliant Readers8
One LAN drop for each PAM
Up to 20 Compliant Readers10 One LAN drop for each PAM
Up to 20 Compliant Readers10 One LAN drop for each PAM
Up to 20 Compliant Readers10 One LAN drop for each PAM
Up to 20 Compliant Readers10 One LAN drop for each PAM
Communication between
M2150 Nodes
Wiegand Data
(controller to PAM) rs485 Data
(PAM to reader)
Legend
AMAG Technology Symmetry 9.3 with HID pivCLASS
GSA FRTC 1.3.3 compliant solution
FICAM / HSPD-12 / FRTC 1.3.3 / FIPS 201-1, FIPS 201-2, FIPS-201-3
Example of larger system (144 readers)
System Components
• Application Server (1)
• SQL Server (1)
• Certificate Manager Server (1)
• Credential Enrollment Station (1)
• Symmetry Client (1)
• Lan Architecture (as needed)
• M2150-EN-DBU-xxK-MK2-HSE(4)
• M2150-4DC-F-HSE (16)
• M4000-DBB (3)
• M4000-DEC4 (15)
• HID PAM Modules (62)
• Card Readers (144)
Not Listed
• LAN Components
• Symmetry Software & Licensing
• Microsoft Operating System software
• Microsoft SQL
• Full instance if using Symmetry Enterprise
• Full instance for HID Certificate Manager
• Credential Enrollment hardware
• controller and PAM:
• Power supplies
• Enclosures
• Cabling
• Misc conduit etc
File details come from the government source that posted it. Updated .