Attachment 2 FY 22 Lubbock B22 B24 Fire Alarm Replacement Final Drawings 2022-02-25.pdf

PDF 1 MB Posted

Attached to
Replace Fire Alarm Bldg 22 and 24 Federal contract opportunity
Solicitation number
12805B22R0005
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area

About this file

This solicitation is for a fire alarm replacement project at two buildings located at the USDA Agricultural Research Service Cropping Systems Research Lab in Lubbock, Texas. The scope of work involves replacing all fire alarm devices, components, and associated wiring throughout Building 24, as well as replacing or extending wiring to a new fire alarm control panel located in Building 24 from devices in Building 22. An alternate scope would replace all existing devices and wiring in Building 22. A mandatory pre-bid site visit will be held on March 9, 2022. Interested parties must register for the site visit by March 7. Bids for this solicitation issued by the USDA Agricultural Research Service Plains Area must be submitted in response to Solicitation Number 12805B22R0005.

View the file

Other files for this federal contract opportunity

Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.

3040 WILLIAMS DRIVE, SUITE 600

FAIRFAX, VIRGINIA 22031

P: 703-691-2115 www. .com

TM

PROJECT NUMBER: SIGQ212911.08

TRUE

NORTH

PLAN

NORTH

Plotted By: JOSE ESCOBAR Plot Date: 2022-02-18 Saved By: JOSE.ESCOBAR File: \\hq.setty.com\public\sai_gov\2021\SIGQ212911.08\28-SIGQ212911.08_FA\SIGQ212911.08_G001.dwg Save Date: 02/16/2022 03:50 PM

USDA AGRICULTURAL RESEARCH SERVICE

USDA/ARS CONTRACT #12805B21F0053

100 % CD SET

USDA PSWCL FACILITY FIRE ALARM SYSTEM DESIGN

(BUILDINGS 22 AND 24)

FIRE ALARM DRAWING LIST

SHEET DRAWING TITLE

1 G001 GENERAL COVER SHEET

www. .com

TM

3040 WILLIAMS DRIVE, SUITE 600

FAIRFAX, VIRGINIA 22031

P: 703-691-2115

FA101

GENERAL NOTES, SYMBOLS & ABBREVIATIONS

FA102

BUILDING #22 FIRE ALARM FLOOR PLAN

FA103

BUILDING #24 FIRE ALARM FLOOR PLAN (PART A)

6 FA501 FIRE ALARM RISER DIAGRAM

FA001

LUBBOCK, TEXAS

BUILDING #24 FIRE ALARM FLOOR PLAN (PART B)

G001

COVER SHEET

4TH ST.

T E

X A

S

T

E C

H

P

K W

Y

BUILDING #22

BUILDING #24

SITE LOCATION

No. PE 900024

D

I

S

T

R

I

C

T

O

F C

O

L

U

M

B

I

A

C O

N

R

A

D

O

D D

E

L

A

R

U

Z

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

E

N

G

I

N

E

E

R

02/25/2022

AutoCAD SHX Text

SAFETY & HEALTH

AutoCAD SHX Text

REAL PROPERTY

AutoCAD SHX Text

DESIGNER

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

PROJECT MANAGER

AutoCAD SHX Text

PPM

AutoCAD SHX Text

EPM

AutoCAD SHX Text

SETTY

AutoCAD SHX Text

DATE

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text

USDA

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text

NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

BY

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text Service

AutoCAD SHX Text Research

AutoCAD SHX Text Agricultural

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DWG. NO

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

SOLICITATION NO.

AutoCAD SHX Text

PSWCL FIRE ALARM SYSTEM DESIGN

AutoCAD SHX Text

AutoCAD SHX Text 01/18/2022

AutoCAD SHX Text

95%%% CD SET

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

DR

AutoCAD SHX Text

EM

AutoCAD SHX Text

CDC

AutoCAD SHX Text

JE

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

100%%% CD SET

AutoCAD SHX Text

GENERAL NOTES SYMBOLS ABBREVIATIONS

CEILING MOUNTED FIRE ALARM HEAT DETECTOR

WALL MOUNTED FIRE ALARM SYSTEM MANUAL PULL STATION AT 48"

AFF

CEILING/WALL MOUNTED FIRE ALARM SMOKE DETECTOR, DEVICES

MAY HAVE THE FOLLOWING SUBSCRIPTS:

CEILING/WALL MOUNTED FIRE ALARM COMBINATION AUDIO

(SPEAKER)/VISUAL DEVICE, ADA COMPLIANT NUMBER DENOTES

CANDELA INTENSITY RATING, MINIMUM 15cd, MOUNTING HEIGHT FROM 80" UP TO A MAXIMUM OF 96" AFF

CEILING/WALL MOUNTED FIRE ALARM VISUAL DEVICE (STROBE),

ADA COMPLIANT NUMBER DENOTES CANDELA INTENSITY RATING,

MINIMUM 15cd, MOUNTING HEIGHT FROM 80" UP TO A MAXIMUM OF

96" AFF

CEILING/WALL MOUNTED FIRE ALARM AUDIO (SPEAKER) DEVICE,

MOUNTING HEIGHT NOT LESS THAN 90" AFF AND 6" BELOW

FINISHED CEILING

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM TERMINAL CABINET

KEYED DRAWING NOTE

/ AA

H

F

SSS

15cd

AV

15cd

AV

15cd V 15cdV

FACP

FAAP

FIRE ALARM SYMBOL LIST

A AMPERE

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

C CONDUIT

CB CIRCUIT BREAKER

CU COPPER

D EXISTING TO BE DEMOLISHED

DISC. SW. DISCONNECT SWITCH

DWG DRAWING

E, EX EXISTING TO REMAIN

EM DEVICE ON EMERGENCY CIRCUIT

EMT ELECTRICAL METALLIC TUBING

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FATC FIRE ALARM TERMINAL CABINET

FASP FIRE ALARM SMOKE PURGE PANEL

FLA FULL LOAD AMPS

G GROUND

GFI GROUND FAULT INTERRUPTER

GRS GALVANIZED RESISTIVE CONDUIT

HP HORSE POWER

IG ISOLATED GROUND

KVA KILOVOLT-AMPS

KW KILOWATT

LM LUMEN

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUGS ONLY

MDP MAIN DISTRIBUTION PANEL

N NEW

NEC NATIONAL ELECTRICAL CODE

NFSS NON FUSED SAFETY SWITCH

NL NIGHT LIGHT FIXTURE

NTS NOT TO SCALE

P POLE

PH, Ø PHASE

PNL PANEL

R RELOCATED AT NEW LOCATION

RR REMOVE AND RELOCATE

S/N SOLID NEUTRAL

SPD SURGE PROTECTIVE DEVICE

SWBD SWITCHBOARD

XFMR TRANSFORMER

TYP. TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLTS

W WATTS

WP WEATHERPROOF

1. INSTALLATION OF ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING REGULATIONS, CODES, ETC.:

A. LOCAL CODES AND ORDINANCES.

B. PRACTICES AND PROCEDURES FOLLOWING OSHA STANDARDS.

C. THE EDITION OF THE NATIONAL ELECTRICAL CODE NFPA 70 (NEC) IN EFFECT.

D. THE EDITION OF THE INTERNATIONAL BUILDING CODE IN EFFECT.

2. BEFORE SUBMITTING BIDS, THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE ALL ADJOINING EXISTING BUILDINGS, EQUIPMENT, AND SPACE CONDITIONS ON WHICH HIS WORK IS IN ANY WAY

DEPENDENT FOR THE BEST WORKMANSHIP AND OPERATION ACCORDING TO THE INTENT OF THE

SPECIFICATIONS AND DRAWINGS. CONTRACTOR SHALL REPORT TO THE ENGINEER ANY CONDITION WHICH MIGHT PREVENT HIM FROM INSTALLING HIS EQUIPMENT IN THE MANNER SPECIFIED OR AS

SHOWN IN CONTRACT DOCUMENTS TEN BUSINESS DAYS PRIOR TO SUBMISSION OF BIDS. NO

CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO VISIT THE SITE, NOR FOR ANY ALLEGED MISUNDERSTANDING OF MATERIALS TO BE FURNISHED OR WORK TO BE PERFORMED. THE CONTRACTOR SHALL INCLUDE IN HIS BID PRICE ALL LABOR AND MATERIAL THAT MAY AFFECT HIS

WORK.

3. CONTRACTOR TO PROVIDE SUFFICIENT NOTICE TO THE OWNER'S REPRESENTATIVE PRIOR TO ANY WORK TO ALLOW ADEQUATE TIME FOR COORDINATION OF EXISTING SITE ACTIVITIES WITH THE

CONSTRUCTION WORK.

4. THE CONTRACTOR TO INCLUDE IN THEIR SCOPE ALL LABOR, MATERIALS, SERVICES, APPARATUS AND SHOP DRAWINGS IN ADDITION TO THE CONTRACT DOCUMENTS AS REQUIRED TO COMPLY WITH ALL APPLICABLE GOVERNING LAWS, CODES AND JURISDICTION REQUIREMENTS. PROVIDE FIRE ALARM

EQUIPMENT WITH ALL ASSOCIATED ACCESSORIES, BRANCH CIRCUIT WIRING AND CONDUIT

INFRASTRUCTURE AS REQUIRED TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM.

5. ALL MATERIALS AND WORK SHALL BE ACCORDING TO PROJECT SPECIFICATIONS.

6. IF DEVICES ARE INSTALLED BEFORE IT IS APPROVED, THE CONTRACTOR SHALL BE LIABLE FOR ITS REMOVAL AND REPLACEMENT AT NO ADDITIONAL CHARGE IF IN THE OPINION OF THE ENGINEER, THE MATERIAL OR EQUIPMENT DOES NOT MEET THE INTENT OF THE DRAWINGS AND/OR SPECIFICATIONS.

7. PROVIDE FIRESTOPPING MATERIALS TO MAINTAIN INTEGRITY OF THE FIRE RATED CONSTRUCTION

WHERE CONDUITS PASS THROUGH WALLS AND FLOORS.

8. PROVIDE FIRE ALARM INTERFACE HARDWARE, MODULES AND WIRING AS REQUIRED TO ALL

ELECTRICALLY SECURED DOORS. COORDINATE WITH BUILDING SECURITY SYSTEM.

A

A

1A

1B

1. WALL ASSEMBLY - THE FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE

CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE

THE FOLLOWING CONSTRUCTION FEATURES:

A.STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN 3-5/8 IN. WIDE

AND SPACED MAX 24 IN. OC.

B.GYPSUM BOARD* - THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS AS REQUIRED IN THE INDIVIDUAL WALL AND PARTITION DESIGN. MAX DIAM OF OPENING IN WOOD STUD WALLS IS 8 IN. MAX DIAM OF OPENING IN STEEL STUD WALLS IS 14 IN. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS

EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED.

2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. THE SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE A MIN 0 IN. (POINT CONTACT) TO A MAX 2 IN. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC

PIPES, CONDUITS OR TUBING MAY BE USED:

A.STEEL PIPE - NOM 12 IN. DIAM (OR SMALLER) SCHEDULE 5 (OR HEAVIER STEEL PIPE.

B.IRON PIPE - NOM 12 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C.CONDUIT - NOM 4 IN. DIAM (OR SMALLER) ELECTRICAL METALLIC TUBING, NOM 6 IN. DIAM (OR

SMALLER) STEEL CONDUIT OR NOM 1 IN. DIAM (OR SMALLER) FLEXIBLE STEEL CONDUIT.

D.COPPER TUBING - NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

E.COPPER PIPE - NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

3. FILL, VOID OR CAVITY MATERIAL* - CAULK - MIN 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 3/8 IN. DIAM BEAD OF FILL MATERIAL APPLIED AT POINT CONTACT LOCATION AT THE PENETRANT/GYPSUM BOARD INTERFACE ON BOTH

SIDES OF WALL.

PENETRATIONS THROUGH STRUCTURE SHALL MAINTAIN FIRE RESISTANCE AND COMPLY WITH

SECTION 713.4 OF THE IBC 2015. ALL ANNULAR SPACES BETWEEN RATED STRUCTURE/ENCLOSURE

SHALL BE FILLED WITH APPROVED MATERIAL COMPLYING WITH REQUIREMENTS OF UL 1479.

F RATINGS - 1 AND 2 HR

T RATING - 0 HR

L RATING AT AMBIENT -

LESS THAN 1 CFM/SQ FT

L RATING AT 400 F -

LESS THAN 1 CFM/SQ FT

GYPSUM WALLBOARD

SECTION A-A

A

A

1. WHERE CONDUITS PASS THROUGH MASONRY OR CONCRETE WALLS OR FLOORS, PROVIDE AND SET

INDIVIDUAL GRC SLEEVES FOR EACH CONDUIT AND ALL OTHER WORK UNDER HIS CHARGE, AS

NECESSARY FOR PASSAGE OF ALL RACEWAYS. SLEEVES SHALL BE OF SUFFICIENT SIZE TO PROVIDE 1/2" ANNULAR SPACE AROUND THE CONDUIT PASSING THROUGH THE FLOOR OR WALLS. ALL OPENINGS

SHALL BE SEALED, MADE SMOKE RESISTANT, AND TIGHT BY JHH. THE CONTRACTOR SHALL BE

RESPONSIBLE FOR THE EXACT LOCATION OF SLEEVES PROVIDED UNDER THIS CONTRACT AND SHALL

COORDINATE ALL REQUIREMENTS FOR RACEWAY SLEEVES.

2. WALL ASSEMBLY - MIN 6 IN. (152 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 25 IN. (635 MM). SEE CONCRETE BLOCKS (CAZT)

CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR THE NAMES OF MANUFACTURERS.

3. THROUGH PENETRANT - ONE METALLIC PIPE, TUBING OR CONDUIT TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPES, TUBING OR CONDUITS AND PERIPHERY OF OPENING IS DEPENDENT UPON THE TYPE AND MAX DIAM OF THE THROUGH PENETRANT AS TABULATED BELOW. PIPE, TUBING OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, TUBING OR CONDUITS MAY BE USED:

A.STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B.IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C.COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

D.COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

E.CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING, NOM 6 IN.

(152 MM) DIAM GALV STEEL CONDUIT OR NOM 1 IN. DIAM FLEXIBLE STEEL CONDUIT.

4. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 5/8 IN. (16 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. AT THE POINT CONTACT LOCATION BETWEEN THROUGH PENETRANT AND CONCRETE, A MIN 3/8 IN. (10 MM) DIAM BEAD OF FILL MATERIAL SHALL BE

APPLIED AT THE CONCRETE/THROUGH PENETRANT INTERFACE ON BOTH SURFACES OF WALL.

PENETRATIONS THROUGH STRUCTURE SHALL MAINTAIN FIRE RESISTANCE AND COMPLY WITH SECTION

713.4 OF THE IBC 2015. ALL ANNULAR SPACES BETWEEN RATED STRUCTURE/ENCLOSURE SHALL BE

FILLED WITH APPROVED MATERIAL COMPLYING WITH REQUIREMENTS OF UL 1479.

F RATING - 2 HR.

T RATING - 0 HR.

REINFORCED CONCRETE

SECTION A-A

TYPE OF THROUGH PENETRANT

MAX DIAM OF THROUGH

PENETRANT, IN. (MM)

MIN & MAX ANNULAR

SPACE, IN. (MM)

STEEL OR IRON PIPE 4 (102) 0, 1-1/2 (38)

STEEL TUBING OR CONDUIT 4 (102) 0, 1-1/2 (38)

STEEL CONDUIT 6 (152) 1/8 (3), 1/2 (13)

STEEL OR IRON PIPE 24 (610) 1/8 (3), 1/2 (13)

COPPER TUBING OR PIPE 6 (152) 1/8 (3), 1/2 (13)

A

SECTION A-A

A

SCALE:

THROUGH-PENETRATION FIRE STOP DETAILS

NTS

FA001 SCALE:

TYPICAL DEVICE MOUNTING HEIGHT

NTS

FA001

FIRE

FIRE ALARM

FIRE FIRE

AUDIBLE/VISUAL

AND VISUAL

ONLY

APPLIANCES

CEILING MOUNTED

SMOKE/HEAT

DETECTOR

A/C SUPPLY

OR RETURN

DIFFUSER

MANUAL

PULL

STATION

FINISHED FLOOR

80" (ADA)

80" MINIMUM (NFPA)

FOR CEILING HEIGHTS LESS THAN 86",

THE VISUAL LENS MOUNTING HEIGHT

SHALL BE WITHIN 6" OF THE CEILING

FINISHED WALL

WALL

MOUNTED

SMOKE/HEAT

DETECTOR

FINISHED WALL

CEILING

36" (MINIMUM)

12" (MAXIMUM)

42"

TO EXIT DOOR

5' MAXIMUM

NOTES:

1. DEVICES SHALL BE INSTALLED ON A COMMON VERTICAL LINE WHEREVER POSSIBLE.

2. REFER TO THE PROPER DEVICE INSTALLATION INSTRUCTIONS FOR BACKBOX MOUNTING HEIGHTS.

80"

SYNCHRONIZE MORE

THAN TWO APPLIANCES

IN ANY FIELD OR VIEW

96" MAXIMUM (NFPA)

AUDIBLE

ONLY

APPLIANCES

6" MINIMUM BELOW

FINISHED CEILING (NFPA 72)

90" MINIMUM

OTHER MOUNTING HEIGHTS

SHALL BE PERMITTED BY THE AHJ

PROVIDED IT MEETS THE SOUND

LEVEL OUTPUT REQUIRED

FATC

SCOPE OF WORK NARRATIVE

1. FOR BASE SCOPE, NEW FIRE ALARM SYSTEM SHALL BE PROVIDED INCLUDING BUT NOT LIMITED TO THE REPLACEMENT OF ALL FIRE ALARM DEVICES, COMPONENTS AND ASSOCIATED WIRING THROUGHOUT BUILDING 24. DEVICES IN BUILDING 22 SHALL REMAIN AND ALL ASSOCIATED BRANCH WIRING SHALL BE

EXTENDED TO THE NEW FIRE ALARM CONTROL PANEL LOCATED IN BUILDING 24.

2. IN ADD ALTERNATE #1 SCOPE, ALL EXISTING FIRE ALARM DEVICES, COMPONENTS AND ASSOCIATED WIRING SHALL BE REMOVED IN BUILDING 22. NEW FIRE ALARM DEVICES, COMPONENTS AND ASSOCIATED WIRING

SHALL BE PROVIDED AS SHOWN ON BUILDING #22 FIRE ALARM FLOOR PLAN, SHEET FA101

Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.

3040 WILLIAMS DRIVE, SUITE 600

FAIRFAX, VIRGINIA 22031

P: 703-691-2115 www. .com

TM

PROJECT NUMBER: SIGQ212911.08

Plotted By: JOSE ESCOBAR Plot Date: 2022-02-18 Saved By: JOSE.ESCOBAR File: \\hq.setty.com\public\SAi_Gov\2021\SIGQ212911.08\28-SIGQ212911.08_FA\SIGQ212911.08_FA001.dwg Save Date: 02/18/2022 09:11 AM

FA001

GENERAL NOTES, SYMBOLS

& ABBREVIATIONS

No. PE 900024

D

I

S

T

R

I

C

O

L

U

M

B

I

A

C O

N

R

A

D

O

D D

E

U

Z

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

G

I

N

E

E

R

02/25/2022

AutoCAD SHX Text

SAFETY & HEALTH

AutoCAD SHX Text

REAL PROPERTY

AutoCAD SHX Text

DESIGNER

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

PROJECT MANAGER

AutoCAD SHX Text

PPM

AutoCAD SHX Text

EPM

AutoCAD SHX Text

SETTY

AutoCAD SHX Text

DATE

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text

USDA

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text

NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

BY

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text Service

AutoCAD SHX Text Research

AutoCAD SHX Text Agricultural

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DWG. NO

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

SOLICITATION NO.

AutoCAD SHX Text

PSWCL FIRE ALARM SYSTEM DESIGN

AutoCAD SHX Text

AutoCAD SHX Text 01/18/2022

AutoCAD SHX Text

95%%% CD SET

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

DR

AutoCAD SHX Text

EM

AutoCAD SHX Text

CDC

AutoCAD SHX Text

JE

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

100%%% CD SET

EXIST

GREENHOUSE

EXIST

GREENHOUSE

GREENHOUSE

GROWTH

CHAMBER

WORKSPACE

MECHANICAL

WELLNESS CENTER

FOYER

TECHNICIAN

OFFICE

MECHANICAL

TRANSGENIC

SEED

MEN

SHOWER

HALL

WOMEN

SHOWER

CORR

CORR

WOMEN

TOILET

MEN

TOILET

S

S

FF

WP

75cd AV

WP

75cd AV

WP

75cd AV

15cd

AV

15cd

AV

WP

30cd

AV

WP

110cd

AV

15cd

AV

15cd V15cdV

15cd

AV

A

30cd

AV

15cd

AV

15cd V

15cd V

30cd

AV

A

15cd V

F

FF

FATC

S

S

S

S S

S

S

S S S

S

WP

S

WP

S

WP

S S S S

S S S S

H

H

1 1 1

F

15cd

AV

15cd

AV

15cd

AV

S

15cd

AV

15cd

AV

S 15cd

AV

KEY PLAN

BUILDING #22

SCALE:

BUILDING #22 FIRE ALARM FLOOR PLAN

1/8" = 1'-0"

FA101

Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.

3040 WILLIAMS DRIVE, SUITE 600

FAIRFAX, VIRGINIA 22031

P: 703-691-2115 www. .com

TM

PROJECT NUMBER: SIGQ212911.08

TRUE

NORTH

PLAN

NORTH

GENERAL NOTES

# SHEET KEY NOTES

Plotted By: ERWIN MATE Plot Date: 2022-02-18 Saved By: ERWIN.MATE File: \\hq.setty.com\public\SAi_Gov\2021\SIGQ212911.08\28-SIGQ212911.08_FA\SIGQ212911.08_FA101.dwg Save Date: 02/18/2022 06:52 PM

FA101

BUILDING #22

FIRE ALARM FLOOR PLAN

ADD ALTERNATE #1

KEY PLAN

1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL

NOTES, LEGEND AND ABBREVIATIONS. REFER TO DETAIL DRAWINGS

FOR THE PROPOSED MOUNTING REQUIREMENTS OF TYPICAL FIRE

ALARM DEVICES.

2. ALL FIRE ALARM DEVICES SHALL BE INSTALLED AS FLUSH MOUNTED

WITH CONCEALED CONDUITS. ANY SURFACE MOUNTED DEVICES

AND CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED

BY THE OWNER PRIOR TO INSTALLATION.

3. WHERE MORE THAN TWO VISUAL (STROBE) NOTIFICATION

APPLIANCES ARE IN THE FIELD OF VIEW, THEY SHALL FLASH IN

SYNCHRONIZATION. PROVIDE EXTERNAL SYNC MODULE OR SYNC

PROTOCOL BUILT IN TO THE FIRE ALARM CONTROL PANEL.

1. DEVICES IN THIS ARE SHALL BE SUITABLE TO OPERATE IN

TEMPERATURE BETWEEN 35F AND 120F.

NOTE: SEE SCOPE OF WORK NARRATIVE ON SHEET FA001 FOR FIRE ALARM SCOPE IN THIS BUILDING.

No. PE 900024

D

I

S

T

R

I

C

O

L

U

M

B

I

A

C O

N

R

A

D

O

D D

E

U

Z

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

G

I

N

E

E

R

02/25/2022

AutoCAD SHX Text

SAFETY & HEALTH

AutoCAD SHX Text

REAL PROPERTY

AutoCAD SHX Text

DESIGNER

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

PROJECT MANAGER

AutoCAD SHX Text

PPM

AutoCAD SHX Text

EPM

AutoCAD SHX Text

SETTY

AutoCAD SHX Text

DATE

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text

USDA

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text

NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

BY

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text Service

AutoCAD SHX Text Research

AutoCAD SHX Text Agricultural

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DWG. NO

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

SOLICITATION NO.

AutoCAD SHX Text

PSWCL FIRE ALARM SYSTEM DESIGN

AutoCAD SHX Text

AutoCAD SHX Text 01/18/2022

AutoCAD SHX Text

95%%% CD SET

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

DR

AutoCAD SHX Text

EM

AutoCAD SHX Text

CDC

AutoCAD SHX Text

JE

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

100%%% CD SET

ELECTRICAL

MECHANICAL

COMMUNICATION

174A

ELECTRICAL

I.T.

ROOM

TORNADO

SHELTER

ROOM

CORRIDOR

RADIO-ACTIVE

CHEM. WASTE

STOR.

427C

CORRIDOR

SHARED

SUPPORT

LABORATORY

LABORATORY

JANITOR

STORAGE

181B

RECEIVING

181A

CHEMICAL

WASTE

STORAGE

JANITOR

CLOSET

CORRIDOR

LABORATORY

LABORATORY

TEMPERATURE

CONTROL

ROOM

CORRIDOR

TEMPERATURE

CONTROL ROOM

535A

CLOSET

LABORATORY

LABORATORY

LABORATORY

LABORATORY

SHARED

SUPPORT

MECHANICAL

CONFERENCE

ROOM

P.I.

OFFICE

P.I.

OFFICE

P.I.

OFFICE

P.I.

OFFICE

P.I.

OFFICE

P.I.

OFFICE

P.I.

OFFICE

P.I.

OFFICE

P.I.

OFFICE

P.I.

OFFICE

GLASS

WASH

433A

CLOSET

LABORATORY

LABORATORY

LABORATORY

LABORATORY

LABORATORY

TOILET

510A

VESTIBULE

TOILET

610A

VESTIBULE

LABORATORY

LABORATORY

LABORATORY

LABORATORY

LABORATORY

CLOSET

COLD

STORAGE

CORRIDOR

TECH

OFFICE

TECH

OFFICE

TECH

OFFICE

TECH

OFFICE

TECH

OFFICE

CORRIDOR

ELECTRICAL

CHILLERS

ENERGY BLD 24

BOILERS

EMERGENCY

GENERATOR

UTILITY

CORRIDOR

CORRRIDOR

C 3

C 2

C 2

C 3

C 3

C 2

C 2

C 3

C 3

C 2

C 2

C 3

C 3

C 2

C 2

C 3

C 3

C 2

C 2

C 3

C 3

C 2

C 2

C 3

C 3

C 2

C 2

C 3

C

3C

2C

2C

C

3C

2C

2C

C

2C

C

3C

2C

2C

C

3C

2C

2C

C

3C

2C

2C

C

3C

2C

2C d 3 d 2 d 2 d 3 d 3 d 2 d 2 d 3 d 3 d 2 d 2 d 3 d 3 d 2 d 2 d 3 d 3 d 2 d 3 d 2 d 2 d 3 d 3 d 2 d 2 d 3 d 3 d 2 d 2 d 3 d 3 d 2 d 2 d 3 d

3d

2d

2d d

3d

2d

2d d

3d

2d

2d d

3d

2d

2d d

3d

2d

2d d

3d

2d

2d d

3d

2d

2d d

3d

2d

2d d

3d

2d

2d

603A

CHEMICAL

STORAGE

AREA

CORRIDOR

UTILITY

CORRIDOR

CORRIDOR

SHARED

SUPPORT

F

F

F

SS

S30cd

AV

110cd

AV

S

F

S

F 15cd

V

F F15cd V

F

A

A

30cd

AV

A

15cdV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

30cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd AV 15cd

AV 15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

30cd V

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

30cd

AV

30cd

AV

15cd V

SA

75cd

AV

F F

A

15cd

V 15cd

V 15cd

AV

F

15cd V

15cd

AV

15cd

AV

S

A

FACP

H

H H

H H

H

H

H

H

H

H

H

H

H

H

H H H

H

H

H

H H

H H

H

H

H H

H H

H

H

H

H

H H

H H

H

H

H

F

S

S

S

S

S

S S

S

S

S

S

S

S

S

S

S

S

S

SS

S

S

S

S

S

S

SS

SSS

SSS

S

S

S

S

S

S

S

S

S

S

S

S S

S

PART B

PART A

S A

A

A

A

A

SA

SA

H

KEY PLAN

BUILDING #24

PART A

SCALE:

BUILDING #24 FIRE ALARM FLOOR PLAN (PART A)

1/8" = 1'-0"

FA102

Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.

3040 WILLIAMS DRIVE, SUITE 600

FAIRFAX, VIRGINIA 22031

P: 703-691-2115 www. .com

TM

PROJECT NUMBER: SIGQ212911.08

TRUE

NORTH

PLAN

NORTH

GENERAL NOTES

Plotted By: JOSE ESCOBAR Plot Date: 2022-02-18 Saved By: JOSE.ESCOBAR File: \\hq.setty.com\public\SAi_Gov\2021\SIGQ212911.08\28-SIGQ212911.08_FA\SIGQ212911.08_FA102.dwg Save Date: 02/18/2022 04:51 PM

FA102

BUILDING #24

FIRE ALARM FLOOR PLAN

(PART A)

KEY PLAN

1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL

NOTES, LEGEND AND ABBREVIATIONS. REFER TO DETAIL DRAWINGS

FOR THE PROPOSED MOUNTING REQUIREMENTS OF TYPICAL FIRE

ALARM DEVICES.

2. ALL FIRE ALARM DEVICES SHALL BE INSTALLED AS FLUSH MOUNTED

WITH CONCEALED CONDUITS. ANY SURFACE MOUNTED DEVICES

AND CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED

BY THE OWNER PRIOR TO INSTALLATION.

3. WHERE MORE THAN TWO VISUAL (STROBE) NOTIFICATION

APPLIANCES ARE IN THE FIELD OF VIEW, THEY SHALL FLASH IN

SYNCHRONIZATION. PROVIDE EXTERNAL SYNC MODULE OR SYNC

PROTOCOL BUILT IN TO THE FIRE ALARM CONTROL PANEL.

NOTE: SEE SCOPE OF WORK NARRATIVE ON SHEET FA001 FOR FIRE ALARM SCOPE IN THIS AND ADJACENT BUILDING.

# SHEET KEY NOTES

1. NEW FIRE ALARM CONTROL PANEL TO REPLACE EXISTING FIRE

ALARM CONTROL IN PLACE. FIELD COORDINATE EXACT LOCATION.

2. REPLACE EXISTING PNEUMATIC DAMPER WITH NEW ELECTRONIC

DAMPER AND TIE THE NEW DEVICE INTO THE BAS AND FIRE ALARM

SYSTEM THROUGH THE ACTIVATION OF DUCT SMOKE DETECTOR.

No. PE 900024

D

I

S

T

R

I

C

O

L

U

M

B

I

A

C O

N

R

A

D

O

D D

E

U

Z

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

G

I

N

E

E

R

02/25/2022

AutoCAD SHX Text

SAFETY & HEALTH

AutoCAD SHX Text

REAL PROPERTY

AutoCAD SHX Text

DESIGNER

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

PROJECT MANAGER

AutoCAD SHX Text

PPM

AutoCAD SHX Text

EPM

AutoCAD SHX Text

SETTY

AutoCAD SHX Text

DATE

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text

USDA

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text

NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

BY

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text Service

AutoCAD SHX Text Research

AutoCAD SHX Text Agricultural

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DWG. NO

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

SOLICITATION NO.

AutoCAD SHX Text

PSWCL FIRE ALARM SYSTEM DESIGN

AutoCAD SHX Text

AutoCAD SHX Text 01/18/2022

AutoCAD SHX Text

95%%% CD SET

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

DR

AutoCAD SHX Text

EM

AutoCAD SHX Text

CDC

AutoCAD SHX Text

JE

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

100%%% CD SET

a a a a

2 3 a a a a

2 3 a a a a

2 3 a a

2 3 a a b

2 3

2 3 b b b b b b b a a a a

2 3 a a a a

2 3 a a a a

2 3 a a

2 3 a a a a a a

2 3 a a a a

2 3 a a a a

2 3 a a

2 3 a a a a a a

2 3 a a a a

2 3 a a a a

2 3 a a

2 3 a a a a a a

2 3 a a a a

2 3 b b b b

2 3 b b b b

2 3 b

2 3

2 3 b b b b b b b b b b b

2 3 b b b b

2 3 b

2 3

2 3 b b b b b b b b b b b

2 3 b b b b

2 3 b

2 3 b b b b b b b

2 3166

MECHANICAL

210A

VESTIBULE

TOILET

236A

CLOSET

TEMPERATURE

CONTROL

ROOM

TEMPERATURE

CONTROL

ROOM

103A

VESTIBULE

TOILET

210A

VESTIBULE

LABORATORY

LABORATORY

LABORATORY

LABORATORY

LABORATORY

LABORATORY

LABORATORY

LABORATORY

LABORATORY

225A

CLOSET

020A

CLOSET

020G

CLOSET

020B

CLOSET

CORRIDOR

CORRIDOR

066A

FILES

066B

SERVER

DIRECTORS

OFFICE

ADMIN.

OFFICE

ADMINISTRATION

LABORATORY

LABORATORY

LABORATORY

LABORATORY

SHARED

SUPPORT

SHARED

SUPPORT

LABORATORY

LABORATORY

LABORATORY

LABORATORY

CORRIDOR

232 UTILITY CORRIDOR

CORRIDOR

RECEPTION

055A

VESTIBULE

LOBBY

BREAK

ROOM

030B

BREAK

030A

STORAGE

140A

121 122

CORRIDOR

C O

R R

ID

O

R

CONF.

ROOM

STOR.

TOILET

TOILET

165A

CLOSET

OPEN

COURTYARD

COLONNADE

TECH.

OFFICE

TECH.

OFFICE

TECH.

OFFICE

TECH.

OFFICE

TECH.

OFFICE

CORRIDOR

130A

010122A

CLOSET

UTILITY CORRIDOR

CORRIDOR

CORRRIDOR

COAT ROOM

COPY / MAIL

CORRRIDOR

CORRIDOR

GERMPLASM

STORAGE

LABORATORY

OFFICE

75cd

AV

F

S

F

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

V

F

15cd V

F

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

30cd V

15cd

AV

15cd

AV

15cd

AV

30cd

AV

15cd

AV

15cd

AV

15cd

AV

75cd

AV

F

15cd

V

30cd

AV

30cd

AV

75cd

AV

110cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

30cd

AV

75cd

AV

75cd

AV

30cd

AV

15cd

V

75cd

AV

75cd

AV

75cd

AV

30cd

AV

30cd

AV

30cd

V

15cd AV 15cd

AV

15cd

AV

15cd

AV

15cd

V

15cd

AV

15cd V

15cd V

FAAP

HH

HH

H H H H H

H H H H H H

H

H

H

30cd V

S

H

S

S

S

S

SSS S S S S S

S S S S S S S S

S

S

S

SS S S S S

S

S

S

S

S

S

S

S

S

S S

S

S

S S

S

S

S S S S S S

S

S

S

S

S

PART B

PART A

M A

TC

H

LI

N

E

B U

IL

D

IN

G

A

A

A

15cd

AV

15cd

AV

1 1 1 1

F

F

KEY PLAN

BUILDING #24

PART B

SCALE:

BUILDING #24 FIRE ALARM FLOOR PLAN (PART B)

1/8" = 1'-0"

FA103

Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.

3040 WILLIAMS DRIVE, SUITE 600

FAIRFAX, VIRGINIA 22031

P: 703-691-2115 www. .com

TM

PROJECT NUMBER: SIGQ212911.08

TRUE

NORTH

PLAN

NORTH

GENERAL NOTES

Plotted By: ERWIN MATE Plot Date: 2022-02-18 Saved By: ERWIN.MATE File: \\hq.setty.com\public\SAi_Gov\2021\SIGQ212911.08\28-SIGQ212911.08_FA\SIGQ212911.08_FA103.dwg Save Date: 02/18/2022 06:46 PM

FA103

BUILDING #24

FIRE ALARM FLOOR PLAN

(PART B)

KEY PLAN

1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL

NOTES, LEGEND AND ABBREVIATIONS. REFER TO DETAIL DRAWINGS

FOR THE PROPOSED MOUNTING REQUIREMENTS OF TYPICAL FIRE

ALARM DEVICES.

2. ALL FIRE ALARM DEVICES SHALL BE INSTALLED AS FLUSH MOUNTED

WITH CONCEALED CONDUITS. ANY SURFACE MOUNTED DEVICES

AND CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED

BY THE OWNER PRIOR TO INSTALLATION.

3. WHERE MORE THAN TWO VISUAL (STROBE) NOTIFICATION

APPLIANCES ARE IN THE FIELD OF VIEW, THEY SHALL FLASH IN

SYNCHRONIZATION. PROVIDE EXTERNAL SYNC MODULE OR SYNC

PROTOCOL BUILT IN TO THE FIRE ALARM CONTROL PANEL.

NOTE: SEE SCOPE OF WORK NARRATIVE ON SHEET FA001 FOR FIRE ALARM SCOPE IN THIS AND ADJACENT BUILDING.

# SHEET KEY NOTES

1. REPLACE EXISTING PNEUMATIC DAMPER WITH NEW ELECTRONIC

DAMPER AND TIE THE NEW DEVICE INTO THE BAS AND FIRE ALARM

SYSTEM THROUGH THE ACTIVATION OF DUCT SMOKE DETECTOR.

No. PE 900024

D

I

S

T

R

I

C

O

L

U

M

B

I

A

C O

N

R

A

D

O

D D

E

U

Z

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

G

I

N

E

E

R

02/25/2022

AutoCAD SHX Text

SAFETY & HEALTH

AutoCAD SHX Text

REAL PROPERTY

AutoCAD SHX Text

DESIGNER

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

PROJECT MANAGER

AutoCAD SHX Text

PPM

AutoCAD SHX Text

EPM

AutoCAD SHX Text

SETTY

AutoCAD SHX Text

DATE

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text

USDA

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text

NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

BY

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text Service

AutoCAD SHX Text Research

AutoCAD SHX Text Agricultural

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DWG. NO

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

SOLICITATION NO.

AutoCAD SHX Text

PSWCL FIRE ALARM SYSTEM DESIGN

AutoCAD SHX Text

AutoCAD SHX Text 01/18/2022

AutoCAD SHX Text

95%%% CD SET

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

DR

AutoCAD SHX Text

EM

AutoCAD SHX Text

CDC

AutoCAD SHX Text

JE

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

100%%% CD SET

FACP

BATTERY

DACT

3/4" EMPTY CONDUIT TO MAIN

TELEPHONE BOARD

(2-LINE DIALERS)

AT 120/208V NEAREST

EMERGENCY PANEL

F

FAAP

F F F F F F F F F F F F F F F

15cd V

15cd V

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

30cd V

30cd V

30cd V

30cd

AV

30cd

AV

30cd

AV

30cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

75cd

AV

A A A A

F

F F F F

WP

75cd

AV WP

75cd

AV WP

75cd

AV

A

F

75cd

AV

75cd

AV

H H H H H H H H H H H H H H H H H H H H

H H H H H H H H H H H H H H H H H H H H

COMMUNICATION

#173

LOBBY#055

BUILDING-22

MECHANICAL RM. #104

FATC

SS S S SS S S SS S S SS S SSS

SS S S SS S S SS S S SS S SSS

S

S

S S S S S

H H

S S S SS S S S

S

S

SS S S SS S S SS S S SS S SSSSS

SS S S SS S S SS S S SS S SSSSS

S S S SS S S SS S SS S SSSSS

F

S

30cd V

15cd V

15cd V

15cd V

15cd V

15cd V

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

30cd

AV

30cd

AV

WP

30cd

AVWP

110cd

AV

A

S S S S S SS

WP

S

WP

S

WP

S

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

15cd

AV

30cd

AV

30cd

AV

30cd

AV

30cd

AV

30cd

AV

30cd

AV

30cd

AV

30cd

AV

75cd

AV

75cd

AV

75cd

AV

110cd

AV

110cd

AV

15cd V

15cd V

15cd V

15cd V

15cd V

15cd V

15cd V

15cd V

15cd V

15cd V

15cd V

15cd V

30cd V

A A A A A A A A A A A A

SS S S SS S S SS S S SS S SSSS S

H H H H H H H H H H H H H H H H H H H H

H H

15cd

AV

Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.

3040 WILLIAMS DRIVE, SUITE 600

FAIRFAX, VIRGINIA 22031

P: 703-691-2115 www. .com

TM

PROJECT NUMBER: SIGQ212911.08

GENERAL NOTES

SCALE:

FIRE ALARM RISER DIAGRAM

NTS

FA501

Plotted By: JOSE ESCOBAR Plot Date: 2022-02-18 Saved By: JOSE.ESCOBAR File: \\hq.setty.com\public\SAi_Gov\2021\SIGQ212911.08\28-SIGQ212911.08_FA\SIGQ212911.08_FA501.dwg Save Date: 02/18/2022 04:07 PM

FA501

FIRE ALARM

RISER DIAGRAM

1. THE FIRE ALARM RISER DIAGRAM IS PROVIDED FOR REFERENCE ONLY AND IS NOT

INTENDED TO DESCRIBE THE SYSTEM ARCHITECTURE AND DOES NOT INCLUDE ALL

NECESSARY INFORMATION TO INSTALL THE SYSTEM. THE INSTALLED SYSTEM MUST

MEET ALL REQUIREMENTS OF THE NFPA AND AHJ.

2. THE FIRE ALARM SYSTEM IS DESIGNED TO UTILIZE SPEAKER MODULES FOR AUDIBLE

NOTIFICATIONS.

3. ALL EXISTING DUCT SMOKE DETECTOR, FLOW AND TAMPER SWITCHES AND

ASSOCIATED COMPONENTS ARE TO REMAIN. PROVIDE INTERFACE ADDRESSABLE

MODULE IF NECESSARY AND CONNECT TO NEW FIRE ALARM SYSTEM.

4. ALL FIRE ALARM VISUAL NOTIFICATION DEVICES IN THE SCOPE OF WORK AREA MUST BE

ADA COMPLIANT.

5. THE FIRE ALARM AUDIBLE DEVICE SHALL HAVE A SOUND LEVEL AT LEAST 15 dBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 dBA ABOVE THE MAXIMUM SOUND LEVEL

HAVING A DURATION OF AT LEAST 60 SECONDS, WHICHEVER IS GREATER,

THROUGHOUT THE AREA OF WORK.

6. ALL FIRE ALARM DEVICES INSTALLED IN THE AREA OF WORK SHALL CONFORM WITH ALL

STANDARDS AND REQUIREMENTS OF ADA, UL, ANSI AND NFPA. VISUAL (STROBE)

DEVICES SHALL BE EQUIPPED WITH FIELD SELECTABLE WITH MINIMUM 15 AND

MAXIMUM 110 CANDELA RATED LIGHT OUTPUT OPTION AND SIMULTANEOUS FLASH

RATE OF 1 TO 3 Hz.

7. CONTRACTOR TO PROVIDE ADDRESSABLE MONITOR INTERFACE/RELAY MODULES AS

REQUIRED TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM FOR ALL APPLICABLE

EQUIPMENT AND DEVICES INCLUDING BUT NOT LIMITED TO THE FOLLOWING:

· FLOW SWITCHES

· TAMPER SWITCHES

· DRY PIPE SYSTEM

· GENERATOR

· SECURITY SYSTEMS

· HVAC UNITS

8. ALL FIRE ALARM WIRING SHALL BE IN 3/4" EMT CONDUIT.

9. ALL SOUND MASKING, WHITE NOISE, PA AND SIMILAR SYSTEMS MUST BE DEACTIVATED

WHEN AN ALARM SIGNAL IS INITIATED BY THE FIRE ALARM SYSTEM. CONTRACTOR TO

PROVIDE MODULES TO INTERFACE WITH THE FIRE ALARM SYSTEM AS REQUIRED.

10. THE FIRE ALARM SYSTEM IS TO BE CLEAR OF ALL TROUBLE AND ALARM SIGNALS AT THE

END OF EACH DAY INCLUDING ANY REPROGRAMMING REQUIRED BY THE TEMPORARY

OR PERMANENT REMOVAL OF EXISTING DEVICES.

11. ALL FIRE ALARM WORK MUST BE COORDINATED WITH THE OWNER AND BUILDING

ENGINEER AT LEAST 3 DAYS PRIOR TO INSTALLATION. THE FIRE ALARM SYSTEM MUST

REMAIN OPERATIONAL AS THE BUILD OUT OCCURS. OBTAIN WRITTEN PERMISSION

FROM THE OWNER PRIOR TO THE INTERRUPTION OF THE BUILDING FIRE ALARM

SYSTEM. THE CONTRACTOR MUST FOLLOW ALL BUILDING OWNER PROTOCOLS AND

CODE REQUIREMENTS FOR A FIRE ALARM INTERRUPTION.

12. THE BUILDING FIRE ALARM SYSTEM IS MONITORED BY "ADT COMMERCIAL", PHONE

NUMBER 817-537-5600.

13. CONTRACTOR TO PREPARE AND SUBMIT FIRE ALARM SHOP DRAWINGS TO THE

ENGINEER AND THE FIRE MARSHAL FOR REVIEW AND FINAL APPROVAL. CONTRACTOR

TO BE PRESENT DURING FINAL INSPECTION AND TESTING BY THE FIRE MARSHALL.

SHOP DRAWINGS SHALL INCLUDE:

· SYSTEM RISER DIAGRAM AND FLOOR PLAN WITH DEVICE ADDRESSES,

CONDUIT SIZES AND WIRE TYPE AND SIZES

· FIRE ALARM EXTENDER PANEL, IF REQUIRED

· COMPONENT WIRING DIAGRAMS

· PRODUCT DATA SHEETS AND EQUIPMENT DESCRIPTION

· BATTERY SIZE CALCULATIONS

· DETAIL OF MODIFIED ANNUNCIATOR PANEL

ANY REVISIONS AND ADDITIONS REQUIRED BY THE AHJ PRIOR TO OBTAINING THE

CERTIFICATE OF OCCUPANCY ARE THE RESPONSIBILITY OF THE CONTRACTOR.

NOTES:

1. REFER TO FLOOR PLANS FOR EXACT NUMBER AND TYPE OF FIRE ALARM DEVICES AND LOCATIONS.

2. SEE SCOPE OF WORK NARRATIVE ON SHEET FA001 FOR FIRE ALARM SCOPE.

No. PE 900024

D

I

S

T

R

I

C

O

L

U

M

B

I

A

C O

N

R

A

D

O

D D

E

U

Z

R

E

G

I

S T

E

R

E

D

P

R

O

F

E

S

S

I

O

N

G

I

N

E

E

R

02/25/2022

AutoCAD SHX Text

SAFETY & HEALTH

AutoCAD SHX Text

REAL PROPERTY

AutoCAD SHX Text

DESIGNER

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

PROJECT MANAGER

AutoCAD SHX Text

PPM

AutoCAD SHX Text

EPM

AutoCAD SHX Text

SETTY

AutoCAD SHX Text

DATE

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text

USDA

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text

NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

BY

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text Service

AutoCAD SHX Text Research

AutoCAD SHX Text Agricultural

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DWG. NO

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

SOLICITATION NO.

AutoCAD SHX Text

PSWCL FIRE ALARM SYSTEM DESIGN

AutoCAD SHX Text

AutoCAD SHX Text 01/18/2022

AutoCAD SHX Text

95%%% CD SET

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

DR

AutoCAD SHX Text

EM

AutoCAD SHX Text

CDC

AutoCAD SHX Text

JE

AutoCAD SHX Text 02/18/2022

AutoCAD SHX Text

100%%% CD SET

Sheets and Views
G001 COVER SHEET
FA001 GENERAL NOTES, SYMBOLS & ABBREVIATIONS
FA101 BUILDING #22 FIRE ALARM FLOOR PLAN ADD ALTERNATE #1
FA102 BUILDING #24 FIRE ALARM FLOOR PLAN (PART A)
FA103 BUILDING #24 FIRE ALARM FLOOR PLAN (PART B)
FA501 FIRE ALARM RISER DIAGRAM

File details come from the government source that posted it. Updated .