2022-04-14_Fire Alarm FINAL.PDF
PDF 397 KB Posted
- Attached to
- Replace Fire Alarm Bldg 22 and 24 Federal contract opportunity
- Solicitation number
- 12805B22R0005
About this file
This document package includes a fire alarm system design drawing and related federal contract opportunity notice. The design drawing provides the fire alarm riser diagram and notes for buildings 22 and 24 at the USDA Crop Systems Research Lab in Lubbock, Texas. The scope of work involves replacing the existing fire alarm systems in both buildings.
The related federal contract opportunity is solicitation number 12805B22R0005 to replace the fire alarm systems in buildings 22 and 24. Interested contractors were required to register by March 7, 2022 to attend an optional site visit on March 9, 2022 at 9:00am Central Time. The contracting agency is the USDA Agricultural Research Service Plains Area. The solicitation and award types were not specified.
View the file
Other files for this federal contract opportunity
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FACP
BATTERY
DACT
3/4" EMPTY CONDUIT TO MAIN
TELEPHONE BOARD
(2-LINE DIALERS)
AT 120/208V NEAREST
EMERGENCY PANEL
F
FAAP
F F F F F F F F F F F F F F F
15cd V
15cd V
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
30cd V
30cd V
30cd V
30cd
AV
30cd
AV
30cd
AV
30cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
75cd
AV
A A A A
F
F F F F
WP
75cd
AV WP
75cd
AV WP
75cd
AV
A
F
75cd
AV
75cd
AV
H H H H H H H H H H H H H H H H H H H H
H H H H H H H H H H H H H H H H H H H H
COMMUNICATION
#173
LOBBY#055
BUILDING-22
MECHANICAL RM. #104
FATC
S S S SS S S SS S SS S SSS
S S SS S S SS S SS S SSS
S
S
S S S S S
H H
S S S SS S S S
S
S S S SS S S SS S SS S SSSSS
S S S SS S S SS S SS S SSSSS
S S S SS S S SS S SS S SSSSS
F
S
30cd V
15cd V
15cd V
15cd V
15cd V
15cd V
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
30cd
AV
30cd
AV
WP
30cd
AVWP
110cd
AV
A
S S S S S SS
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
15cd
AV
30cd
AV
30cd
AV
30cd
AV
30cd
AV
30cd
AV
30cd
AV
30cd
AV
30cd
AV
75cd
AV
75cd
AV
75cd
AV
110cd
AV
110cd
AV
15cd V
15cd V
15cd V
15cd V
15cd V
15cd V
15cd V
15cd V
15cd V
15cd V
15cd V
15cd V
30cd V
A A A A A
S S S SS S S SS S SS S SSSS
H H H H H H H H H H H H H H H H H H H H
15cd
AV
D D D D
30cd
AV
30cd
AV
30cd
AV
30cd
AV
30cd
AV
75cd
AV
75cd
AV
S
S
S S
S
S
75cd
AV
75cd
AV
75cd
AV
75cd
AV
KEY PLAN
GRAPHICAL
FAAP
YOU ARE
HERE
ELECTRICAL
MECHANICAL
COMMUNICATION
MECHANICAL
FATC
ELECTRICAL
FACP
EMERGENCY
GENERATOR
MECHANICAL
ELECTRICAL
R
ZONE #5
R
ZONE #2
R
ZONE #3
R
ZONE #4
R
ZONE #1
USDA PSWCL FACILITY BUILDINGS 22 AND 24
3810 4TH STREET LUBBOCK, TEXAS 79415
GROUND FLOOR
PENTHOUSE B
PENTHOUSE A-1
PENTHOUSE A-2
R
ZONE #4
R
ZONE #3
R
ZONE #2
G
POWER
ON
TROUBLE
ALARM
TROUBLE
SILENCE
A
LAMP
TEST
TROUBLE
BUZZER
TROUBLE
SILENCE
RESET
SWITCH
MANUAL PULL STATION
SMOKE DETECTOR
HEAT DETECTOR
FIRE SERVICE LINE
DUCT SMOKE DETECTOR
SPRINKLER FLOW SWITCH
SPARE
SPARE
R
R
R
A
R
R
R
R
ALARM DEVICES
RUNNING
OFF
EPO
NOT IN AUTOMATIC MODE
BATTERY CHARGER NOT FUNCTIONING
EMERGENCY SYSTEM GROUND FAUL
G
R
A
A
A
A
EMERGENCY GENERATOR
SYSTEM CONTROL
FLOORS
GROUND FLOOR
PENTHOUSE
R
R
N
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
3040 WILLIAMS DRIVE, SUITE 600
FAIRFAX, VIRGINIA 22031
P: 703-691-2115 www. .com
TM
PROJECT NUMBER: SIGQ212911.08
GENERAL NOTES
SCALE:
FIRE ALARM RISER DIAGRAM
NTS
FA501
Plotted By: JOSE ESCOBAR Plot Date: 2022-04-14 Saved By: JOSE.ESCOBAR File: \\hq.setty.com\public\SAi_Gov\2021\SIGQ212911.08\28-SIGQ212911.08_FA\SIGQ212911.08_FA501.dwg Save Date: 04/14/2022 02:40 PM
FA501
FIRE ALARM
RISER DIAGRAM
1. THE FIRE ALARM RISER DIAGRAM IS PROVIDED FOR REFERENCE ONLY AND IS NOT
INTENDED TO DESCRIBE THE SYSTEM ARCHITECTURE AND DOES NOT INCLUDE ALL
NECESSARY INFORMATION TO INSTALL THE SYSTEM. THE INSTALLED SYSTEM MUST
MEET ALL REQUIREMENTS OF THE NFPA AND AHJ.
2. THE FIRE ALARM SYSTEM IS DESIGNED TO UTILIZE SPEAKER MODULES FOR AUDIBLE
NOTIFICATIONS.
3. ALL FLOW AND TAMPER SWITCHES AND ASSOCIATED COMPONENTS ARE TO REMAIN.
PROVIDE INTERFACE ADDRESSABLE MODULE IF NECESSARY AND CONNECT TO NEW
FIRE ALARM SYSTEM.
4. ALL FIRE ALARM VISUAL NOTIFICATION DEVICES IN THE SCOPE OF WORK AREA MUST BE
ADA COMPLIANT.
5. THE FIRE ALARM AUDIBLE DEVICE SHALL HAVE A SOUND LEVEL AT LEAST 15 dBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 dBA ABOVE THE MAXIMUM SOUND LEVEL
HAVING A DURATION OF AT LEAST 60 SECONDS, WHICHEVER IS GREATER,
THROUGHOUT THE AREA OF WORK.
6. PROVIDE WEATHER ALERT BUTTON TO THE VOICE ALERT SYSTEM TO ALLOW
WEATHER/TORNADO MESSAGE TO SOUND THROUGH THE FACILITY WHEN ACTIVATED
THROUGH A PRERECORDED MESSAGE.
7. ALL FIRE ALARM DEVICES INSTALLED IN THE AREA OF WORK SHALL CONFORM WITH ALL
STANDARDS AND REQUIREMENTS OF ADA, UL, ANSI AND NFPA. VISUAL (STROBE)
DEVICES SHALL BE EQUIPPED WITH FIELD SELECTABLE WITH MINIMUM 15 AND
MAXIMUM 110 CANDELA RATED LIGHT OUTPUT OPTION AND SIMULTANEOUS FLASH
RATE OF 1 TO 3 Hz.
8. CONTRACTOR TO PROVIDE ADDRESSABLE MONITOR INTERFACE/RELAY MODULES AS
REQUIRED TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM FOR ALL APPLICABLE
EQUIPMENT AND DEVICES INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
· FLOW SWITCHES
· TAMPER SWITCHES
· DRY PIPE SYSTEM
· GENERATOR
· SECURITY SYSTEMS
· HVAC UNITS
8. ALL FIRE ALARM WIRING SHALL BE IN 3/4" EMT CONDUIT.
9. ALL SOUND MASKING, WHITE NOISE, PA AND SIMILAR SYSTEMS MUST BE DEACTIVATED
WHEN AN ALARM SIGNAL IS INITIATED BY THE FIRE ALARM SYSTEM. CONTRACTOR TO
PROVIDE MODULES TO INTERFACE WITH THE FIRE ALARM SYSTEM AS REQUIRED.
10. THE FIRE ALARM SYSTEM IS TO BE CLEAR OF ALL TROUBLE AND ALARM SIGNALS AT THE
END OF EACH DAY INCLUDING ANY REPROGRAMMING REQUIRED BY THE TEMPORARY
OR PERMANENT REMOVAL OF EXISTING DEVICES.
11. ALL FIRE ALARM WORK MUST BE COORDINATED WITH THE OWNER AND BUILDING
ENGINEER AT LEAST 3 DAYS PRIOR TO INSTALLATION. THE FIRE ALARM SYSTEM MUST
REMAIN OPERATIONAL AS THE BUILD OUT OCCURS. OBTAIN WRITTEN PERMISSION
FROM THE OWNER PRIOR TO THE INTERRUPTION OF THE BUILDING FIRE ALARM
SYSTEM. THE CONTRACTOR MUST FOLLOW ALL BUILDING OWNER PROTOCOLS AND
CODE REQUIREMENTS FOR A FIRE ALARM INTERRUPTION.
12. THE BUILDING FIRE ALARM SYSTEM IS MONITORED BY "ADT COMMERCIAL", PHONE
NUMBER 817-537-5600.
13. CONTRACTOR TO PREPARE AND SUBMIT FIRE ALARM SHOP DRAWINGS TO THE
ENGINEER AND THE FIRE MARSHAL FOR REVIEW AND FINAL APPROVAL. CONTRACTOR
TO BE PRESENT DURING FINAL INSPECTION AND TESTING BY THE FIRE MARSHALL.
SHOP DRAWINGS SHALL INCLUDE:
· SYSTEM RISER DIAGRAM AND FLOOR PLAN WITH DEVICE ADDRESSES,
CONDUIT SIZES AND WIRE TYPE AND SIZES
· FIRE ALARM EXTENDER PANEL, IF REQUIRED
· COMPONENT WIRING DIAGRAMS
· PRODUCT DATA SHEETS AND EQUIPMENT DESCRIPTION
· BATTERY SIZE CALCULATIONS
· DETAIL OF MODIFIED ANNUNCIATOR PANEL
ANY REVISIONS AND ADDITIONS REQUIRED BY THE AHJ PRIOR TO OBTAINING THE
CERTIFICATE OF OCCUPANCY ARE THE RESPONSIBILITY OF THE CONTRACTOR.
NOTES:
1. REFER TO FLOOR PLANS FOR EXACT NUMBER AND TYPE OF FIRE ALARM DEVICES AND LOCATIONS.
2. SEE SCOPE OF WORK NARRATIVE ON SHEET FA001 FOR FIRE ALARM SCOPE.
NOTES:
1. EXISTING SMOKE DAMPERS SHALL BE MONITORED BY THE FIRE ALARM SYSTEM. PROVIDE NECESSARY MODULES WHERE REQUIRED. ALL FIRE ALARM
SHALL CAUSE THE SUPPLY FAN AND RETURN FAN TO SHUT DOWN, AS WELL AS THE SMOKE DAMPERS. THE AIR HANDLING UNIT SHALL NOT START
UNTIL THE ALARM CONDITION IS RESET AT THE FIRE ALARM CONTROL PANEL.
SCALE:
FIRE ALARM ANNUNCIATOR PANEL
NTS
FA501
No. PE 900024
D
I
S
T
R
I
C
T
O
F C
O
L
U
M
B
I
A
C O
N
R
A
D
O
D D
E
L
A
C
R
U
Z
R
E
G
I
S T
E
R
E
D
P
R
O
F
E
S
S
I
O
N A
L
E
N
G
I
N
E
E
R
04/14/2022
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SETTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DWG. NO
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
PSWCL FIRE ALARM SYSTEM DESIGN
AutoCAD SHX Text
AutoCAD SHX Text 04/14/2022
AutoCAD SHX Text
DR
AutoCAD SHX Text
EM
AutoCAD SHX Text
CDC
AutoCAD SHX Text
JE
AutoCAD SHX Text 02/18/2022
AutoCAD SHX Text
100%%% CD SET
AutoCAD SHX Text 03/24/2022
AutoCAD SHX Text
FIRE MARSHALL COMMENTS
AutoCAD SHX Text 04/14/2022
AutoCAD SHX Text
BID RFI REVISIONS
AutoCAD SHX Text