Attachment 13 Boiler 3 Replacement.pdf

PDF 11 MB Posted

Attached to
C1DA--518-21-110 Steam Replacement and Distribution Federal contract opportunity
Solicitation number
36C24122Q0614
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This document is a sources sought notice for architectural and engineering design services for a steam replacement and distribution project at the Bedford VA Medical Center in Bedford, Massachusetts. Interested SDVOSB firms must provide SF-330 qualification statements and evidence of experience with similar medical facility projects by July 8, 2022 to be considered. The design effort is to cost between $2-5 million and be completed within 250 calendar days of notice to proceed. A two-stage evaluation process will first assess qualifications, then request pricing from the most qualified firm. The scope involves reviewing the existing energy distribution system and developing alternative upgrade scenarios and construction documents.

View the file

Other files for this federal contract opportunity

Other files attached to C1DA--518-21-110 Steam Replacement and Distribution, newest first.
File Type Posted
36C24122Q0614 0002.docx DOCX document
36C24122Q0614 0001.docx DOCX document
Attachment 22 Steam Energy Distribution Specification section 33 63 00.docx DOCX document
Attachment 14 Replace Blrs 1 2.pdf PDF
Attachment 16 Steam Heating Hot Water Outside Distribution Sys Design Manual.pdf PDF
Attachment 12b Electrical Panel Drawings 480 120 volt.pdf PDF
Attachment 7 Upgrade Steam Distribution System Phase III.pdf PDF
Attachment 3 Facility Master Plan.pdf PDF
Attachment 2 Geographic Site Overview.pdf PDF
36C24122Q0614.docx DOCX document
Attachment 23 HVAC Design Manual.pdf PDF
Attachment 18 Outside Steam Heating Hot Water Distribution Systems Design Manual.pdf PDF
Attachment 17 Boiler Plant Piping System Specification section 23 2 111.docx DOCX document
Attachment 9 Repair Stacks Steam Lines.pdf PDF
Attachment 8 Alterations to Buildings 2 4 22 and Steam Distribution System.pdf PDF
Attachment 5 Upgrade Steam Distribution System Phase I.pdf PDF
Attachment 4 Steam Distribution Drawings.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.docx DOCX document
Attachment 24 Cleaver Brookes Package Boiler Model CBLE 125 800 hp.pdf PDF
Attachment 21 Boiler Plant Mechanical Equipment Specification section 23 50 11.docx DOCX document
Attachment 20 Steam Condensate Pumps for HVAC Specification section 23 22 23.docx DOCX document
Attachment 19 Steam and Condensate Heating Piping Spec section 23 22 13.docx DOCX document
Attachment 15 Boiler Plant Safety Improvement Bldg 22.pdf PDF
Attachment 12a Updated High Voltage Electrical One-Line Schematics.pdf PDF
Attachment 11 Steam Condensate Return System.pdf PDF
Attachment 10 Standard Plumbing Sheets.pdf PDF
Attachment 6 Upgrade Steam Distribution System Phase II.pdf PDF
Show all 27

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

Architects Engineers Planners

Foxborough, Massachussetts 02035 33 Commercial Street, Suite #1

Maguire Group Inc.

AutoCAD SHX Text

GROUNDING MODIFICATIONS

22-E1

MFW

HDA

9/26/08

SKE-2

DEPT. OF VETERANS AFFAIRS

DRAWN BY:

CHK'D BY:

DATE:

REF:

DWG. NO.

SHEET OF

PROJ. NO.

E.N.R. MEM. VET. HOSPITAL REPLACE BOILER-BLDG. 22

17664

225A

125A

800A

300A

100A

175A

800A/3P MAIN

SPARE

EXISTING SWITCHBOARD; 800A, 277/480V, 3 , 4W,RATED 22,000 A.I.C.

%%UNORMAL

%%USTAND-BY

EXISTING GROUND BUS

NEW 1"C-#3/0 CU GROUND CABLE

PROVIDE A NEW GROUND CABLE AND CLAMP ON EXISTING WATER SERVICE ENTRANCE

400A

PROVIDE #3/0 CU JUMPER ACROSS FLANGE

T

2 SETS-3"C-4 #350KC MIL, 1 #2GND

NEW 600A/3P 600V "MAIN SERVICE ENTRANCE DISCONNECT SWITCH"

2 SETS-4"C-4 #350KC MIL,

NEW PADMOUNTED 500KVA TRANSFORMER 13.8KV-277/480V (601A OUTPUT)

SEE NOTE "E"

SEE NOTE "A"

NEW GROUND BUS

3/4" x 10'-0" LONG COPPERCLAD GROUND ROD. TOP OF ROD DRIVEN TO MINIMUM 6" BELOW GRADE

3/4"C-#6 COPPER GROUND CABLE

Sheets and Views

17664FE-SKE-2-SKE-2

GENERAL NOTES: DEMOLITION NOTES:

ABBREVIATIONS:

LEGEND: NOTES:

one-quarter inch=one foot one-eigth inch=one foot

0 8 16

VA FORM 08-6231A, JAN 1990

Revisions

Date

F three-eigths inch=one foot one-half inch=one foot

E one and one-half inches=one foot one inch=one foot three-quarters inch=one foot

D

C

B three inches=one foot

A

Approved: Chief, Eng. Svc

Drawing Title

Approved: Safety Manager

Approved: Project Engineer

Building Number

Project Title

Location

Checked

Dwg.

Of

518-04-106

Drawn

DRAWING NO.

06/18/07

Project No.

Architects/Engineers/Planners

Foxborough, MA 02035

33 Commercial Street, Suite 1

REVIEWED BY:

CIVIL: INITIAL&DATE INITIAL&DATEINITIAL&DATE

ARCH: INITIAL&DATE INITIAL&DATEINITIAL&DATE

STRU: INITIAL&DATE INITIAL&DATEINITIAL&DATE

PLUM: INITIAL&DATE INITIAL&DATEINITIAL&DATE

FIRE: INITIAL&DATE INITIAL&DATEINITIAL&DATE

MECH: INITIAL&DATE INITIAL&DATEINITIAL&DATE

ELEC: INITIAL&DATE INITIAL&DATEINITIAL&DATE

DEPARTMENT OF VETERANS AFFAIRS EDITH NOURSE ROGERS MEMORIAL VETERANS HOSPITAL REPLACE BOILER - BUILDING 22

BEDFORD, MASSACHUSETTS

22-E1

DLL

DRD

NOTES, ABBREVIATIONS, LEGEND, AND SINGLE-LINE DIAGRAM AND SCHEDULE

GFI

c wp

AFG

AFF

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

CIRCUIT BREAKER

C/B

FBO

GROUND

GND

GFI

FURNISHED BY OTHERS

GROUND-FAULT INTERRUPTER

RIGID GALVANIZED CONDUIT

REMOVE AND DISPOSE OF

RGC

UH

UNIT HEATER

NIC

R & D

PNL

NEC

NOT IN CONTRACT

PANEL

NATIONAL ELECTRIC CODE

MOUNTED

MAIN LUGS ONLY

MLO

MTD

NON-FUSED

NF

AMP

AMPERES

CONDUIT

MCB

MAIN CIRCUIT BREAKER

HOT WATER PUMP

HWP

S

M

ELECTRICAL CONTRACTOR

EC

SINGLE-POLE TOGGLE SWITCH, MOUNTED ON CENTERLINE 48" A.F.F.; TYPICAL FOR ALL TOGGLE SWITCHES.

J

MOTOR, NUMERAL DENOTES HORSEPOWER. WHERE MOTORS SHOW NO NUMERAL, HORSEPOWER IS OF 1/8 OR SMALLER; INSTALLED BY OTHERS, AND WIRED BY ELECTRICAL CONTRACTOR UNDER DIV. 16.

COMBINATION MAGNETIC STARTER WITH H-O-A SWITCH AND PILOT LIGHT FURNISHED UNDER DIV. 15, INSTALLED AND WIRED UNDER DIV. 16.

SPECIAL PURPOSE OUTLET, SIZE AND TYPE AS NOTED, VERIFY SIZE WITH EQUIPMENT.

1. CONTRACTOR SHALL VISIT SITE AND EXAMINE CONDITIONS UNDER WHICH WORK MUST BE CONTRACTOR SHALL VISIT SITE AND EXAMINE CONDITIONS UNDER WHICH WORK MUST BE PERFORMED. COMMENCEMENT OF WORK SHALL BE CONSTRUED AS COMPLETE ACCEPTANCE OF EXISTING CONDITIONS INCLUDING PREPARATORY WORK DONE BY OTHERS. 2. PROVIDE MATERIALS, LABOR AND EQUIPMENT TO MAKE INSTALLATION COMPLETE IN EVERY PROVIDE MATERIALS, LABOR AND EQUIPMENT TO MAKE INSTALLATION COMPLETE IN EVERY DETAIL UNDER THIS CONTRACT WHETHER OR NOT SPECIFICALLY SHOWN ON DRAWINGS. 3. ALL ELECTRICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST EDITION ALL ELECTRICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND THE COMMONWEALTH OF MASSACHUSETTS BUILDING CODE, AND THE COMMONWEALTH OF MASSACHUSETTS ELECTRICAL CODE. MATERIAL AND EQUIPMENT SHALL BE UL LISTED FOR THE INTENDED SERVICE. 4. ADDITIONAL JUNCTION BOXES SHALL BE FURNISHED AND INSTALLED WHERE REQUIRED. ADDITIONAL JUNCTION BOXES SHALL BE FURNISHED AND INSTALLED WHERE REQUIRED. 5. ALL CONDUITS SHALL CONTAIN AN INSULATED GREEN SAFETY GROUND WIRE. BOND ALL ALL CONDUITS SHALL CONTAIN AN INSULATED GREEN SAFETY GROUND WIRE. BOND ALL PANELS, CABINETS, ENCLOSURES, CONDUITS, ETC., AS REQUIRED PER CODE. 6. PROVIDE CONDUIT SLEEVES FILLED WITH AN APPROVED FIRE RESISTANT MATERIAL WHERE PROVIDE CONDUIT SLEEVES FILLED WITH AN APPROVED FIRE RESISTANT MATERIAL WHERE FIRE RATED WALLS OR CEILINGS ARE PENETRATED. APPROVED WATERTIGHT CONDUIT SLEEVES SHALL BE PROVIDED WHERE WALLS ARE PENETRATED EITHER ENTERING OR LEAVING THE BUILDING. 7. WHERE CONDUITS ARE NOT IDENTIFIED, THEY SHALL BE 3/4" WITH 2 #12, 1 #12 EQUIPMENT WHERE CONDUITS ARE NOT IDENTIFIED, THEY SHALL BE 3/4" WITH 2 #12, 1 #12 EQUIPMENT GROUND. GROUND CONDUCTOR IS NOT SHOWN ON DRAWINGS FOR CLARITY. 8. POWER ITEMS BRANCH CIRCUIT WIRING MAY NOT BE SHOWN BUT SHALL BE PROVIDED AS POWER ITEMS BRANCH CIRCUIT WIRING MAY NOT BE SHOWN BUT SHALL BE PROVIDED AS REQUIRED. MINIMUM WIRING SHALL BE 3/4"C-2 #12, 1 #12 GROUND. NO MORE THAN THREE PHASES MAY BE COMBINED IN A SINGLE HOMERUN AND EACH PHASE SHALL BE PROVIDED WITH AN INDIVIDUAL NEUTRAL. 9. FOR EXACT LOCATIONS OF MECHANICAL EQUIPMENT, REFER TO MECHANICAL DRAWINGS AND FOR EXACT LOCATIONS OF MECHANICAL EQUIPMENT, REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS. 10. ALL CONDUIT AND CABLES SHALL BE RUN EXPOSED. ALL CONDUIT AND CABLES SHALL BE RUN EXPOSED. 11. ALL CUTTING, PATCHING AND FIRE STOPPING RELATED TO ELECTRICAL WORK SHALL BE ALL CUTTING, PATCHING AND FIRE STOPPING RELATED TO ELECTRICAL WORK SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. 12. CIRCUIT WIRING AND HOMERUNS WITH LENGTHS LONGER THAN 90 FEET SHALL USE #10 CIRCUIT WIRING AND HOMERUNS WITH LENGTHS LONGER THAN 90 FEET SHALL USE #10 AWG, THOSE LONGER THAN 140 FEET SHALL USE #8 CONDUCTORS. 13. ELECTRICAL CONTRACTOR SHALL PROVIDE A TEMPORARY GENERATOR TO SUPPLY POWER TO ELECTRICAL CONTRACTOR SHALL PROVIDE A TEMPORARY GENERATOR TO SUPPLY POWER TO THE BOILER PLANT WHILE THE NORMAL ELECTRICAL POWER FEEDER TO THE POWER PLANT IS UPGRADED. CONTRACTOR MAY NEGOTIATE THE USE OF THE SITE GENERATOR WITH THE OWNER. 14. ALL WORK MUST BE INSTALLED IN ACCORDANCE WITH "OSHA" AND "ADA" REQUIREMENTS ALL WORK MUST BE INSTALLED IN ACCORDANCE WITH "OSHA" AND "ADA" REQUIREMENTS 15. ALL CONDUITS, AND EQUIPMENT ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION AND METHOD ALL CONDUITS, AND EQUIPMENT ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION AND METHOD OF SUPPORT SHALL BE DETERMINED IN THE FIELD, EXCEPT WHERE SPECIFIC DIMENSIONS AND DETAILS ARE SHOWN. 16. AS DIRECTED BY THE ENGINEER, THE CONTRACTOR SHALL , WITHOUT EXTRA CHARGE, MAKE AS DIRECTED BY THE ENGINEER, THE CONTRACTOR SHALL , WITHOUT EXTRA CHARGE, MAKE REASONABLE MODIFICATIONS IN THE LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF OTHER TRADES OR OF PROPER EXECUTION OF THE WORK. 17. ALL WIRING SHALL BE SINGLE CONDUCTOR COPPER, HEAT AND MOISTURE RESISTANT 600 VOLT ALL WIRING SHALL BE SINGLE CONDUCTOR COPPER, HEAT AND MOISTURE RESISTANT 600 VOLT INSULATION, TYPE THWN-THHN. MIN. SIZE OF CONDUCTOR SHALL BE 12 AWG, UNLESS OTHERWISE NOTED. 18. THE ELECTRICAL CONTRACTOR SHALL CONSULT AND COOPERATE WITH CONTRACTORS OF OTHER THE ELECTRICAL CONTRACTOR SHALL CONSULT AND COOPERATE WITH CONTRACTORS OF OTHER TRADES TO AVOID ANY INTERFERENCE IN THE INSTALLATION OF THEIR RESPECTIVE EQUIPMENT. 19. WHERE REQUIRED, ADDITIONAL SUPPORT STEEL OR STRUT FOR THE ELECTRICAL INSTALLATION WHERE REQUIRED, ADDITIONAL SUPPORT STEEL OR STRUT FOR THE ELECTRICAL INSTALLATION SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. 20. CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUIT, WIRE, JUNCTION BOXES, ETC. CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUIT, WIRE, JUNCTION BOXES, ETC. NECESSARY TO COMPLETE THIS INSTALLATION. 21. THE LOCATION OF ALL ITEMS SHOWN ON THESE DRAWINGS THAT ARE NOT DEFINITELY FIXED BY THE LOCATION OF ALL ITEMS SHOWN ON THESE DRAWINGS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS OR ELEVATIONS ARE APPROXIMATE ONLY. THE EXACT LOCATION NECESSARY TO SECURE THE BEST CONDITIONS AND RESULTS MUST BE DETERMINED IN THE FIELD AND SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. 22. ALL CONDUITS RUN ABOVE 4ft SHALL BE ELECTRIC METALLIC TUBING (EMT). NO CONDUIT ALL CONDUITS RUN ABOVE 4ft SHALL BE ELECTRIC METALLIC TUBING (EMT). NO CONDUIT SMALLER THAN 3/4" ELECTRICAL TRADE SIZE SHALL BE USED, UNLESS SPECIFICALLY CALLED FOR ON THE DRAWINGS, CONDUITS RUN BELOW 4ft AFF SHALL BE RIGID GALVANIZED THICK-WALLED STEEL CONDUIT. 23. MOUNTING HEIGHTS OF ELECTRICAL EQUIPMENT SHALL BE AS FOLLOWS, UNLESS OTHERWISE MOUNTING HEIGHTS OF ELECTRICAL EQUIPMENT SHALL BE AS FOLLOWS, UNLESS OTHERWISE NOTED: a. MOTOR STARTER - 6'-6" FROM FLOOR TO TOP OF ENCLOSURE b. ALL POWER RECEPTACLES PUSH BUTTON STATIONS, SAFETY SWITCHES, ETC. SHALL BE MOUNTED 4'-0" TO BOTTOM UNIT ABOVE FINISHED FLOOR OR PLATFORM ELEVATION, UNLESS OTHERWISE NOTED. 24. CONNECTIONS TO MOTORS SHALL BE MADE WITH LIQUID-TIGHT FLEXIBLE METAL CONDUIT WITH CONNECTIONS TO MOTORS SHALL BE MADE WITH LIQUID-TIGHT FLEXIBLE METAL CONDUIT WITH GROUND CONDUCTORS. WHERE FLEXIBLE CONDUIT IS UTILIZED FOR CONNECTING RIGID CONDUIT TO A MOTOR TERMINAL BOX, IT SHALL BE THE SAME SIZE AS THE RIGID CONDUIT CONTAINING THE MOTOR LEADS. A JUMPER WIRE SHALL BE INSTALLED BETWEEN THE RIGID CONDUIT AND THE MOTOR FRAME TO INSURE A POSITIVE GROUND CONNECTION. THIS GROUND WIRE SHALL BE #4 AWG. UNLESS OTHERWISE NOTED. 25. PROVIDE BLACK LAMINATED MICARTA MANEPLATES WITH 1/4" HIGH RECESSED WHITE LETTERS PROVIDE BLACK LAMINATED MICARTA MANEPLATES WITH 1/4" HIGH RECESSED WHITE LETTERS FOR DISCONNECT SWITCHES, AND OTHER ELECTRICAL EQUIPMENT. SECURE WITH PLATED MACHINE SCREWS OR POP RIVETS. 26. A SET OF RECORD DRAWING CONSISTING OF NEW INSTALLATION CIRCUITING AND CHANGES A SET OF RECORD DRAWING CONSISTING OF NEW INSTALLATION CIRCUITING AND CHANGES FROM INITIAL DRAWINGS WILL BE DEVELOPED BY THE CONTRACTOR AND DELIVERED TO THE COTR UPON COMPLETION OF WORK. 27. GUARANTEE WORK IN WRITING FOR ONE YEAR FROM DATE OF FINAL ACCEPTANCE. REPAIR OR GUARANTEE WORK IN WRITING FOR ONE YEAR FROM DATE OF FINAL ACCEPTANCE. REPAIR OR REPLACE DEFECTIVE MATERIALS AT NO COST TO OWNER. CORRECT DAMAGE CAUSED IN MAKING NECESSARY REPAIRS AND REPLACEMENTS UNDER GUARANTEE AT NO COST TO OWNER. 28. ELECTRICAL CONTRACTOR SHALL USE EXTREME CARE IN MAINTAINING THE EXISTING TELEPHONE ELECTRICAL CONTRACTOR SHALL USE EXTREME CARE IN MAINTAINING THE EXISTING TELEPHONE SYSTEM, FIRE ALARM SYSTEM, AND PA SYSTEM DURING BOILER ROOM RENOVATIONS. ALL SYSTEMS SHALL REMAIN FUNCTIONAL AT ALL TIMES. ANY DISRUPTIONS IN SERVICE SHALL BE IMMEDIATELY REPAIRED. ANY REPAIRS OR WORK REQUIRED ON THE TELEPHONE SYSTEM SHALL BE PERFORMED BY FUJITSU AND ANY REPAIRS OR WORK ON THE FIRE ALARM SYSTEM SHALL BE PERFORMED BY TARA ELECTRIC. THE COSTS FOR ANY REPAIRS OR WORK ON THESE SYSTEMS SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR & IN INCLUDED IN HIS SCOPE OF WORK.

THREE-CIRCUIT HOMERUN TO PANELBOARD, HATCHMARKS DENOTE NUMBER OF #12AWG CONDUCTORS WHERE MORE THAN 2, EXCLUDING GROUND. (THREE PHASE CONDUCTORS AND THREE NEUTRALS ARE SHOWN.

MAGNETIC MOTOR STARTER WITH H-O-A SWITCH AND PILOT LIGHT IN COVER, FURNISHED UNDER DIV. 15, INSTALLED AND WIRED UNDER DIV. 16.

EMERGENCY BOILER DISCONNECT SWITCH MOUNTED CENTER-LINE 54" A.F.F., PROVIDE WITH RED NAMEPLATE. WIRE IN SERIES WITH FIRE-O-MATIC SWITCH INTO BOILER CONTROL CIRCUIT.

Sem

FIRE-O-MATIC SWITCH MOUNTED OVER BOILER, PROVIDED, INSTALLED, AND WIRED UNDER DIV. 16.

FM

COMPACT FLUORESCENT OR H.I.D. LIGHT FIXTURE WITH OUTLET. LETTER DENOTES FIXTURE TYPE, SEE FIXTURE SCHEDULE. SUBSCRIPT DENOTES CIRCUIT NUMBER AND SWITCH CONTROL.

MANUAL MOTOR STARTER WITH THERMAL OVERLOAD PROTECTION. "wp" DENOTES WEATHERPROOF.

DUPLEX RECEPTACLE, 125V, 20 AMP, MOUNTED 18" AFF. "GFI" DENOTES GROUND FAULT INTERRUPTING TYPE; "c" DENOTES MOUNTED 6" ABOVE COUNTER OR 42" A.F.F. TO BOTTOM.

DUPLEX RECEPTACLE, 125V, 20 AMP, MOUNTED 42" AFF OR 0'-6" ABOVE COUNTER TO BOTTOM.

ELECTRICAL CONDUIT AND WIRING RUN EXPOSED. (3/4"C-2 #12, 1 #12 GND), UNLESS OTHERWISE NOTED.

ELECTRICAL CONDUIT AND WIRING RUN 24" BELOW GRADE MINIMUM, SIZED AS INDICATED.

J

JUNCTION BOX - SIZE, TYPE AND MOUNTING AS REQUIRED.

PANELBOARD MOUNTED TOP OF PANEL 6'-6" A.F.F., SURFACE MOUNTED.

NON-FUSED DISCONNECT SWITCH, SIZE AS REQUIRED. "wp" DENOTES WEATHERPROOF, NEMA 3R.

MOMENTARY CONTACT SWITCH.

FIRE ALARM SYSTEM MANUAL PULL STATION, MOUNTED 48" A.F.F..

%%UC

B-1

%%UB

B-9

WALL-MOUNTED COMPACT FLUORESCENT OR H.I.D. LIGHT FIXTURE. LETTER DENOTES FIXTURE TYPE, SEE FIXTURE SCHEDULE. SUBSCRIPT DENOTES CIRCUIT NUMBER AND SWITCH CONTROL.

SELF-CONTAINED SINGLE-FACE ILLUMINATED EXIT SIGN. LETTER DENOTES FIXTURE TYPE, SEE LIGHTING FIXTURE SCHEDULE. CONNECT WITH 3/4"C-2 #10, 1 #10 GND. TO UNSWITCHED LOCAL AREA LIGHTING CIRCUIT.

wp

HORIZONTAL UNIT HEATER

HUH

EXISTING PANEL "L3"

T-4

EXISTING PANEL "L2"

T-3

EXISTING PANEL "L1"

T-2

EXISTING PANEL "P2"

EXISTING PANEL "P1"

800A

100A

175A

T-1

800A/3P MAIN

EXISTING PANEL "N1"

G

EXISTING SWITCHBOARD; 800A, 277/480V, 3 , 4W,RATED 22,000 A.I.C.

%%UNORMAL

%%USTAND-BY

EXISTING 112.5KVA TRANSFORMER; 480/120/208V, 3

EXISTING 2"C-3 #2/0, 1 #6 GND.

EXISTING PANEL; 120/208V, 3 ,4W, 400A

EXISTING 4"C-4 #500KC MIL, 1 #2 GND.

EXISTING FEEDER CABLE TO TRAILER

EXISTING 3"C-3 #500KC MIL, 1 #3 GND.

EXISTING JUNCTION BOX

EXISTING 3"C-3 #500KC MIL, 1 #3 GND.

EXISTING 400A AUTOMATIC TRANSFER SWITCH 277/480V

EXISTING STAND-BY 180KW GENERATOR; 277/480V, 3 , 4WSEE NOTE "B"

EXISTING TRANSFORMER; 480/208/120V, 75KVA

EXISTING 1 1/2"C-3 #1, 1 #6 GND.

EXISTING 2 1/2"C-4 #4/0, 1 #4 GND.

EXISTING PANEL; 225A, 480V, 3 , 4W

EXISTING PANEL; 400A, 480V, 3 , 4W

EXISTING PANEL; 225A, 102/208V, 3 , 4W

EXISTING PADMOUNTED 225KVA TRANSFORMER; 13.8KV-277/480V (270A OUTPUT)

EXISTING 4"C-4 #600KC MIL, 1 #2 GND.

EXISTING JUNCTION BOX

EXISTING PRIMARY TO EXISTING ELECTRICAL MANHOLE "EMH1"

EXISTING GROUND BUS

NEW 1"C-#3/0 CU GROUND CABLE

PROVIDE A NEW GROUND CABLE AND CLAMP ON EXISTING WATER SERVICE ENTRANCE

EXISTING AND NEW POWER SINGLE-LINE DIAGRAM NO SCALE

A. DISCONNECT EXISTING 500KC MIL CABLES FROM EXISTING 300A CB. RECONNECT EXISTING DISCONNECT EXISTING 500KC MIL CABLES FROM EXISTING 300A CB. RECONNECT EXISTING 500KC MIL CABLES TO NEW 400A CB INSTALLED IN EXISTING SPACE. 300 CB SHALL BE LABELED "SPARE". NEW CB LABELED "GENERATOR NORMAL". B. NEW 400A NORMAL FEED CIRCUIT BREAKER FEEDING EXISTING 400A TRANSFER SWITCH AND NEW 400A NORMAL FEED CIRCUIT BREAKER FEEDING EXISTING 400A TRANSFER SWITCH AND CONNECTION OF NEW BOILER #3 TO STANDBY SECTION OF EXISTING SWITCHBOARD IS BASED ON THE FUTURE REPLACEMENT OF THE EXISTING STANDBY 180KW GENERATOR WITH A NEW STANDBY GENERATOR AND FEEDER TO THE EXISTING TRANSFER SWITCH WITH A MIN. CAPACITY OF 400A. C. IN EXISTING PANEL "P2" CONNECT NEW BOILER #3 FEEDER TO EXISTING SPARE 125A/3P IN EXISTING PANEL "P2" CONNECT NEW BOILER #3 FEEDER TO EXISTING SPARE 125A/3P CIRCUIT BREAKER. LABEL CB "BOILER #3". D. DISCONNECT AND REMOVE EXISTING 4#4/0, 1#4GND FROM EXISTING 225A CB AND PANEL DISCONNECT AND REMOVE EXISTING 4#4/0, 1#4GND FROM EXISTING 225A CB AND PANEL "P2". INSTALL AND CONNECT NEW 350KC MIL FEEDER IN EXISTING CONDUIT TO NEW 300A CB AND PANEL "P2". LABEL NEW CB PANEL "P2" AND LABEL ORIGINAL 225A CB "SPARE". E. NEW 3-1/C#4/0 15KV SHEILDED, JACKETED CABLE 133% INSULATION RATING AND 1#3/0 NEW 3-1/C#4/0 15KV SHEILDED, JACKETED CABLE 133% INSULATION RATING AND 1#3/0 COPPER GROUND CABLE IN NEW ACTIVE 4" CONCRETE ENCASED DUCT TO EXISTING "EMH1" SHOWN ON DWG. 22 - E3

EXISTING 2 1/2" W/NEW 4#350KC MIL, 1 #3GND

SEE NOTE "C"

NEW BOILER CONTROL PANEL FUNISHED AND INSTALLED BY DIV. 15.

NEW 200A/3P 600V DISCONNECT SWITCH

2"C-3 #1, 1 #6GND

400A

PROVIDE #3/0 CU JUMPER ACROSS FLANGE

2 SETS-3"C-4 #350KC MIL, 1 #2GND

NEW 600A/3P 600V "MAIN SERVICE ENTRANCE DISCONNECT SWITCH"

2 SETS-4"C-4 #350KC MIL, 1 #2GND

NEW PADMOUNTED 500KVA TRANSFORMER 13.8KV-277/480V (601A OUTPUT)

1. EXISTING ELECTRICAL EQUIPMENT INDICATED ON PLANS HAS BEEN DERIVED FROM THE EXISTING ELECTRICAL EQUIPMENT INDICATED ON PLANS HAS BEEN DERIVED FROM THE BEST AVAILABLE EXISTING DRAWINGS AND MUST BE FIELD VERIFIED PRIOR TO CONSTRUCTION AS REQUIRED. ANY EQUIPMENT THAT IS NOT IDENTIFIED AND CONFLICTS WITH CONSTRUCTION SHALL NOT BE DISCONNECTED AND SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER/ENGINEER FOR DISPOSITION. 2. EXISTING ELECTRICAL EQUIPMENT AND DEVICES TO BE REMOVED SHALL BE REMOVED EXISTING ELECTRICAL EQUIPMENT AND DEVICES TO BE REMOVED SHALL BE REMOVED COMPLETELY INCLUDING WIRING BACK TO EXISTING POWER DISTRIBUTION SOURCE. WHERE WIRING IS TO BE REMOVED, RELOCATED OR RECONNECTED, THE CONTRACTOR SHALL PROTECT WIRING FROM DAMAGE. CONTRACTOR SHALL TAKE PRECAUTIONS AND ASSUME CIRCUIT MAY BE ACTIVE. CONTRACTOR TO TEST, VERIFY AND SECURE ALL CIRCUITS BEFORE REMOVAL. UNKNOWN WIRING SHALL BE IDENTIFIED. ANY WIRING TO REMAIN SHALL BE VERIFIED BY THE CONTRACTOR AND SHALL BE TAGGED AND IDENTIFIED. 3. EXISTING ELECTRICAL EQUIPMENT TO REMAIN SHALL BE PROTECTED FROM DAMAGE AS EXISTING ELECTRICAL EQUIPMENT TO REMAIN SHALL BE PROTECTED FROM DAMAGE AS REQUIRED DURING THE CONSTRUCTION PERIOD AND LEFT IN GOOD WORKING ORDER AT COMPLETION. ANY EQUIPMENT DAMAGED SHALL BE REPLACED BY THE ELECTRICAL CONTRACTOR AT NO EXPENSE TO THE OWNER. 4. OWNER AND CODE REQUIRED SYSTEMS THAT ARE REQUIRED TO REMAIN ACTIVE DURING OWNER AND CODE REQUIRED SYSTEMS THAT ARE REQUIRED TO REMAIN ACTIVE DURING CONSTRUCTION SHALL BE TEMPORARILY WIRED TO REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD OR UNTIL NEW SYSTEMS ARE INSTALLED, TESTED AND ACCEPTED. 5. IN CONDITIONS WHERE, IN THE OPINION OF THIS CONTRACTOR, IT IS NOT CLEAR WHETHER IN CONDITIONS WHERE, IN THE OPINION OF THIS CONTRACTOR, IT IS NOT CLEAR WHETHER EXISTING ELECTRICAL EQUIPMENT IS TO BE REMOVED OR REMAIN, IT SHOULD BE BROUGHT TO THE ATTENTION OF THE ENGINEER FOR REVIEW AND FINAL DECISION. 6. ANY DISRUPTION OF ANY ELECTRICAL SERVICE NECESSITATED BY THE ELECTRICAL ANY DISRUPTION OF ANY ELECTRICAL SERVICE NECESSITATED BY THE ELECTRICAL RENOVATIONS SHALL BE COORDINATED WITH THE OWNER IN ORDER FOR PROPER NOTICE GIVEN TO THE OCCUPANTS PRIOR TO THE DISCONNECTION OF ANY SERVICE. 7. EXISTING ELECTRICAL EQUIPMENT REMOVED SHALL BE BROKEN DOWN INTO MANAGEABLE EXISTING ELECTRICAL EQUIPMENT REMOVED SHALL BE BROKEN DOWN INTO MANAGEABLE LENGTHS FOR STORAGE, HANDLING AND DISPOSAL. 8. EXISTING ELECTRICAL EQUIPMENT REMOVED OF MATERIAL VALUE SHALL BE TURNED OVER EXISTING ELECTRICAL EQUIPMENT REMOVED OF MATERIAL VALUE SHALL BE TURNED OVER TO THE OWNER FOR HIS FINAL DISPOSITION. 9. ELECTRICAL RENOVATION WORK SHALL BE ACCOMPLISHED IN CONFORMANCE WITH THE ELECTRICAL RENOVATION WORK SHALL BE ACCOMPLISHED IN CONFORMANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE. 10. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND FEEDERS PASSING THROUGH MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND FEEDERS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS. 11. EXISTING CONDUIT MAY BE REUSED WHERE FEASIBLE. ALL OTHER MATERIAL AND EXISTING CONDUIT MAY BE REUSED WHERE FEASIBLE. ALL OTHER MATERIAL AND EQUIPMENT SHALL BE REMOVED FROM THE JOB SITE UNLESS OTHERWISE DIRECTED BY THE COTR. 12. RELOCATE EXISTING TELEPHONE/PA EQUIPMENT, AND BRANCH WIRING AS NECESSARY. RELOCATE EXISTING TELEPHONE/PA EQUIPMENT, AND BRANCH WIRING AS NECESSARY. COORDINATE RELOCATION WITH VA PERSONAL. 13. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE TEMPORARY POWER DURING ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE TEMPORARY POWER DURING CONSTRUCTION TO THE BOILERS, CITY WASTE LIFT PUMPS, CONDENSATE RETURN PUMPS, TEMPORARY CONSTRUCTION POWER FOR LIGHTING AND RECEPTACLES, FOR CONSTRUCTION WELDING OUTLETS, FIRE ALARM CONTROL PANEL AND ENERGY MANAGEMENT CONTROL PANELS.

SEE NOTE "D"

SEE NOTE "E"

SEE NOTE "A"

Sheets and Views

17664FE01-Layout1

INTERIOR ELEVATION - DEMOLITION

1/4" = 1'-0"

INTERIOR ELEVATION - PROPOSED

EXISTING CLEAR STORY WINDOW

EXISTING STEEL BEAM

REMOVE AND DISPOSE OF BRICK

REMOVE AND DISPOSE OF COILING AND PEDESTRIAN PASS DOOR AND FRAME

COILING DOOR W/ PEDESTRIAN PASS DOOR

UTILITY BRICK INFILL (SIZE TO MATCH EXIST., PAINTED TO MATCH EXIST.)

22-A1

EXISTING UTILITY BRICK

NOTE: PAINT WALLS IMPACTED BY RENOVATION TO MATCH EXISTING

CHAIN HOLD BACK AT WALL

EXISTING EXTERIOR ELEVATION

EXISTING LIGHT FIXTURE

EXISTING COILING DOOR W/ INTREGAL MAN DOOR

EXISTING SIGNAGE

EXISTING BRICK SOLDIER COURSE

EXISTING INTERIOR ELEVATION

EXISTING COILING DOOR W/ PEDESTRIAN PASS DOOR

RELOCATE ALL EXISTING UTILITIES AS REQUIRED

EXISTING INTERIOR ELEVATION

EXISTING STEEL BEAM

RELOCATE ALL EXISTING UTILITIES AS REQUIRED

EXTERIOR ELEVATION - DEMOLITION

EXTERIOR ELEVATION - PROPOSED

EXISTING BRICK SOLDIER COURSE

REMOVE AND DISPOSE OF BRICK

REMOVE AND DISPOSE OF COILING AND PEDESTRIAN PASS DOOR AND FRAME

COILING DOOR W/ PEDESTRIAN PASS DOOR

UTILITY BRICK INFILL (SIZE AND COLOR TO MATCH EXISTING)

REMOVE AND RELOCATE EXISTING LIGHT FIXTURE (SEE ELECTRICAL DRAWINGS)

REMOVE AND RELOCATE EXISTING SIGNAGE

EXISTING LIGHT FIXTURE RELOCATED

EXISTING SIGNAGE RELOCATED

CORNER GUARD (TYP. AT BOTH EXTERIOR JAMBS)

REMOVE RQUIRED AMOUNT OF BRICK IN ORDER TO REMOVE STEEL BEAM WITH-IN WALL (TYP. AT BOTH JAMBS)

UTILITY BRICK INFILL (SIZE AND COLOR TO MATCH EXISTING)

WEATHER STRIPPING

MOTORIZED OVERHEAD COILING DOOR

NEW UTILITY BRICK INFILL (SIZE TO MATCH EXIST., PAINTED TO MATCH EXIST.)

GALV. CONT. PL. "x11 " 38"x11 " 12" (LENGTH TO BE OPENING WIDTH - ")12")

14 2-12

GALV. W8x24 W/ 8" END BEARING EACH END

WEATHER STRIPPING

EXISTING UTILITY BRICK (PAINTED TO MATCH EXISTING)

JAMB STOP CHANNELS

1" FRAME IN

HOLLOW METAL DOOR

SECTION

3" = 1'-0"

4"x4"x1/4" STEEL ANGLES CORNER GUARDS (GALVANIZED AND PAINTED)

5/16" DIA. COUNTERSUNK EXPANSION ANCHORS @ 16"O.C. (STAGGERED) WITH A MIN 1-1/4" EMBEDMENT

STEEL BENT PLATE (PAINTED)

EXISTING CONCRETE SLAB TO REMAIN

OVERHEAD COILING DOOR AND TRACK

SECTION

3" = 1'-0"

4"x4"x1/4" STEEL ANGLES CORNER GUARDS (GALVANIZED AND PAINTED)

DEPARTMENT OF VETERANS AFFAIRS EDITH NOURSE ROGERS MEMORIAL VETERANS HOSPITAL REPLACE BOILER - BUILDING 22

NORTH

FC

JMP

BOILER PLANT - PARTIAL PLAN

PARTIAL NORTH ELEVATION

(DEMOLITION AND RENOVATION)

Sheets and Views

17664-A1-Layout1

CHEMICAL ROOM

SEWAGE EJECTOR ROOM

PARTS STORAGE AREA

TOILET ROOM

LOCKER ROOM

TOOL CRIB

ELECTRIC ROOM

GENERATOR ROOM

OPERATORS BOOTH

STORAGE AREA AND PUMP ROOM

7.5

EXISTING BOILER #1 TO REMAIN

EXISTING BOILER #2 TO REMAIN

NEW BOILER #3

EXISTING CONTROL PANEL

EXISTING CONTROL PANEL

CONNECT FEEDER TO NEW BOILER CONTROL PANEL

NEW OIL PUMP MOTOR

NEW BLOWER MOTOR

NEW COMPRESSOR MOTOR

EXISTING PANEL "P-2"

EXISTING PANEL "P-1"

EXISTING PANEL "L-3"

EXISTING PANEL "L-1"

EXISTING PANEL "N-2"

EXISTING "LB" FITTING

EXISTING PADMOUNTED 225KVA TRANSFORMER; 13.8KV, 3W, 277/480V, 3 , 4WTO BE REMOVED

EXISTING PRIMARY FEED FROM BASE UTILITIES TO BE REMOVED

EXISTING UNDERGROUND ELECTRIC SERVICE TO BUILDING- ((4) 600KC MIL, TO BE REMOVED)

EXISTING BOILER #3; DISCONNECT ; DISCONNECT AND REMOVE ALL WIRING AND APPERTENANCES ASSOCIATED WITH EXISTING BOILER #3 BACK TO SOURCE

%%UEXISTING BFP-3

%%UEXISTING BFP-2

%%UEXISTING BFP-1

EXISTING CONDENSATE TANK

EXISTING CTP-1

EXISTING CTP-2

CO

ELECTRICAL CONTRACTOR TO WIRE NEW CO DETECTORS, PER MANUFACTURERS' WIRING DIAGRAM (TYPICAL FOR 3) SEE NOTE 7

NEW BOILER CONTROL PANEL BY DIV. 15

FM

EXISTING BOILER #3 CONTROL PANEL & MASTER CONTROL PANEL TO BE REPLACED BY DIV. 15

EXISTING MASTER CP

EXISTING CP-3

NEW FIRE-O-MATIC SWITCH; MOUNT OVER BURNER

EXISTING PANEL "N-1"

T-1

T-4

T-2

T-3

EXISTING PULL BOX #3

EXISTING MAIN SWITCHBOARD

N-1 38

SEE NOTE 6

O.H. DOOR PUSH-BUTTON STATION

N-1 23

SEE NOTE 1

SEE NOTE 5

SEE NOTE 2

SEE NOTE 3

SEE NOTE 4

EXISTING JUNCTION BOX #1 TO REMAIN

EXISTING PULL BOX #2 ON CEILING TO REMAIN

EXISTING FUEL OIL DUPLEX PUMP SET

EXISTING CP-2

EXISTING CP-1

SEE NOTE 8

EXISTING BOILER CONTROL PANEL TO REMAIN

EXISTING EQUIPMENT AND WIRING TO REMAIN

1.5

1.5

P-1 32

P-1 31

EXISTING FOP-1 TO REMAIN

EXISTING FOP-2 TO REMAIN

CP-3

NEW BOILER #3 CONTROL PANEL & MASTER CONTROL PANEL FURNISHED AND INSTALLED BY DIV. 15

FORCED DRAFT FAN STARTER TO BE REMOVED

30A/3P

REMOVE EXISTING 4#4/0, 1#4GND REWIRE WITH NEW 4#350KC MIL. 1#3GND

NEW 600A/3P, 600V "MAIN SERVICE DISCONNCT SWITCH"

TO NEW PULL BOX, FOR DETAILS SEE 22-E3

2 SETS-3"C-4#350KC MIL, 1#2GND

FREE STANDING JBOX TO REMAIN

(4) 4"C (2) ACTIVE (2) SPARE-STUB AND CAP 6" AFG

NEW 200A/3P 600V DISCONNECT SWITCH

2"C-3#1, 1#6GND

EXISTING FORCED DRAFT FAN- BOILER #3

SEE NOTE 9

VSD

REPLACE COMBINATION MOTOR STARTER FOR BFP-3 W/VARIABLE SPEED MOTOR STARTER (30 HP), CONTROLS & CONTROLS WIRING BY DIV. 15

DEPARTMENT OF VETERANS AFFAIRS EDITH NOURSE ROGERS MEMORIAL VETERANS HOSPITAL REPLACE BOILER - BUILDING 22

22-E2

ELECTRICAL DEMOLITION AND NEW WORK PLAN

%%UNOTE:

1. FOR NOTES, LEGEND, ABBREVIATIONS, AND FOR NOTES, LEGEND, ABBREVIATIONS, AND SINGLE LINED DIAGRAM SEE DRAWING NO. 22-E1.

ELECTRICAL DEMOLITION AND NEW WORK PLAN SCALE: 1/4" = 1'-0"

%%UNOTES:

1. EXISTING EXIT LIGHTING FIXTURE TO BE REMOVED. REMOVE WIRING EXISTING EXIT LIGHTING FIXTURE TO BE REMOVED. REMOVE WIRING REMOVE WIRING BACK TO CLEAR NEW OVERHEAD DOOR; PROVIDE JUNCTION BOX AND EXTEND WIRING TO NEW EXIT LIGHTING FIXTURE MOUNTED ON WALL ABOVE NEW OVERHEAD DOOR AND ABOVE MANDOOR IN O.H. DOOR. 2. NEW EXIT LIGHTING FIXTURE; EMERGI-LITE #WW-SVXN-IRD-4X-D. NEW EXIT LIGHTING FIXTURE; EMERGI-LITE #WW-SVXN-IRD-4X-D. EXTEND NEW WIRING TO NEW JUNCTION BOX IN EXISTING CIRCUIT. 3. REMOVE EXISTING FIRE ALARM MANUAL PULL STATION. REMOVE REMOVE EXISTING FIRE ALARM MANUAL PULL STATION. REMOVE EXISTING WIRING BACK TO CLEAR NEW OVERHEAD DOOR; PROVIDE JUNCTION BOX AND EXTEND NEW WIRING TO NEW FIRE ALARM PULL STATION LOCATION ON LEFT OF NEW DOOR; CENTERLINE MOUNT AT 48" A.F.F. 4. REMOVE EXISTING GROUND TO WATER PIPING BACK TO SOURCE. REMOVE EXISTING GROUND TO WATER PIPING BACK TO SOURCE. PROVIDE NEW GROUND; 3/4"C-#3/0 STR. CU BACK TO GROUND BUS IN BUS IN EXISTING MAIN SWITCHBOARD. INSTALL SO AS TO CLEAR NEW NEW OVERHEAD DOOR. PROVIDE NEW BRONZE GROUND CONNECTOR AT AT WATER PIPE.

5. REMOVE EXISTING WIRING AND LIGHTING FIXTURE OVER EXISTING OVERHEAD DOOR. REMOVE EXISTING WIRING AND LIGHTING FIXTURE OVER EXISTING OVERHEAD DOOR. PROVIDE NEW FIXTURE; DAY-BRITE NITE BRITERS #WLM-175-M-PCR/PE-QEM, WITH 175 WATT METAL-HALIDE LAMP AND (1) 100 WATT QUARTZ LAMP. CENTER FIXTURE ABOVE NEW OVERHEAD DOOR. PROVIDE NEW WIRING 3/4"C-2 #12, 1 #12 GND. TO EXISTING PANEL "N-1" AND CONNECT TO CIRCUIT #23. 6. NEW OVERHEAD DOOR OPERATOR. PROVIDE NEW 30A/3P/250V DISCONNECT SWITCH NEW OVERHEAD DOOR OPERATOR. PROVIDE NEW 30A/3P/250V DISCONNECT SWITCH TO PANEL "N-1" WITH 3/4"C-3 #12, 1 #12 GND. REMOVE (3) 20A, 1-POLE CIRCUIT BREAKERS FROM PANEL "N-1" (#38, 40, 42). PROVIDE NEW 20A/3P CIRCUIT BREAKER IN THAT SPACE. DELIVER THE (3) 20A/1P CIRCUIT BREAKERS BACK TO OWNER. OVERHEAD DOOR PUSH-BUTTON STATION TO BE SUPPLIED WITH DOOR OPERATOR AND INSTALLED AND WIRED BY THE ELECTRICAL CONTRACTOR. 7. NEW "CO" MONITORS ARE TO BE FURNISHED AND INSTALLED BY THE MECHANICAL NEW "CO" MONITORS ARE TO BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR AND HARDWIRED BY THE ELECTRICAL CONTRACTOR. 8. BLOWER MOTOR FOR EXISTING BOILER #3; DISCONNECT AND REMOVE WIRING BACK TO BLOWER MOTOR FOR EXISTING BOILER #3; DISCONNECT AND REMOVE WIRING BACK TO SOURCE. 9. AFTER CUTOVER OF NEW SERVICE, REMOVE EXISTING 4"C-4#600KC MIL. AND AFTER CUTOVER OF NEW SERVICE, REMOVE EXISTING 4"C-4#600KC MIL. AND ASSOCIATED PULL BOXES (3) WITH FITTINGS FROM PULL BOX #1 THRU TO THE EXISTING MAIN SWITCHBOARD. THIS MUST BE ACCOMPLISHED TO INCREASE THE HEIGHT AT THE OVERHEAD DOOR AREA TO ALLOW DELIVERY OF THE NEW BOILER. 10. ALL BOILERS ARE SUPPLIED BY STANDBY POWER TO OPERATE AT THE SAME TIME. ALL BOILERS ARE SUPPLIED BY STANDBY POWER TO OPERATE AT THE SAME TIME.

Sheets and Views

17664FE02-Layout1

PIPING SYMBOLS INSTRUMENT/CONTROL SYMBOLS GENERAL NOTES:

EQUIPMENT TAGS

PIPING SYSTEMS

ABBREVIATIONS

CONVECTOR

CV

PRESSURE SENSOR, SWITCH

SMOKE DETECTOR

ENTHALPY SENSOR

PRESSURE GAUGE W/ SHUTOFF (LIQUID FILLED)

DIFFERENTAL PRESSURE SENSOR/ SWITCH

TEMPERATURE INDICATION (LIQUID TYPE W/ WELL)

HAND-OFF-AUTO SWITCH

ANGLE VALVE

MANUAL AIR VENT

M

TEMPERATURE SENSOR, THERMOSTAT

HAND SWITCH

MAKE-UP AIR UNIT

HEAT EXCHANGER

MAU

P

PUMP

HX

PUMPED CONDENSATE

PC

BOILER

VENT LINE

V

LOW PRESSURE STEAM

LOW PRESSURE CONDENSATE

MEDIUM PRESSURE STEAM

MEDIUM PRESSURE CONDENSATE

MPS

MPC

LPC

LPS

GAUGE LINE

FUEL OIL VENT

HIGH PRESSURE STEAM

HIGH PRESSURE CONDENSATE

HPC

HPS

FOV

CITY WATER, COLD WATER

DRAIN LINE

FUEL OIL SUPPLY

FUEL OIL RETURN

FOS

CW

BLOWDOWN

BOILER FEED WATER

CHEMICAL FEED

CF

BD

PRE-HEAT COIL

PHC

BP

BOILER PUMP

CUT AND CAP

C/C

ABOVE FINISHED FLOOR

APPROXIMATELY

AT

AUTOMATIC AIR VENT

AUTOMATIC CONTROL VALVE

ATMOSPHERE

AUXILIARY

BRITISH THERMAL UNITS PER HOUR

CLEANOUT

CONCRETE

CUBIC FEET PER MINUTE

DECIBEL, DRY BULB

DIFFERENTIAL PRESSURE SWITCH

DIFFERENTIAL PRESSURE TRANSMITTER

DOWN

DEMOLITION

ECCENTRIC

ENTERING AIR TEMPERATURE

EFFICIENCY

EXISTING TO REMAIN

ELEVATION

EXHAUST

ENTERING WATER TEMPERATURE

DEGREES FAHRENHEIT

FEET PER MINUTE

FOOT, FEET

GALLONS PER HOUR

HEATER

HERTZ

INDUCED DRAFT OR INSIDE DIAMETER

INCH, INCHES

ISOLATION

LEAVING AIR TEMPERATURE

LEAVING WATER TEMPERATURE

KILOWATTS

IN, "

LWT

LAT

KW

ISOL

CFM

AFF

APPROX

AAV

ID

HZ

HTR

GPH

FT, '

FPM

°F

EWT

EXH

ELEV

ETR

EFF

EAT

ECC

DEMO

DN

DPT

DPS

DB

CONC

BTUH or

AUX

ATM

ACV

DIA,

THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERALLY THE LOCATION OF MATERIALS AND EQUIPMENT. THE CONTRACTOR SHALL PROVIDE ALL LABOR, EQUIPMENT, AND MATERIALS, UNLESS OTHERWISE NOTED, TO HAVE A COMPLETE AND FUNCTIONING SYSTEM. "PROVIDE" SHALL MEAN TO FURNISH AND INSTALL.

ALL SERVICES THAT ARE INTERRUPTED OR DISCONNECTED SHALL BE REROUTED AND RECONNECTED IN ORDER TO PROVIDE A COMPLETE INSTALLATION.

THE WORK SHALL BE DONE IN ACCORDANCE WITH THE LOCAL BUILDING CODES, NFPA AND ALL OTHER APPLICABLE STATE AND FEDERAL CODES.

FINAL LOCATION OF EQUIPMENT AND CONNECTION POINTS SHALL BE DETERMINED IN THE FIELD WITH THE CONTRACTOR BEING RESPONSIBLE FOR DIMENSIONS THAT SHALL BE CONFIRMED AND CORRELATED AT THE JOB SITE.

INSTALL EQUIPMENT SO AS TO BE READILY ACCESSIBLE FOR OPERATION, MAINTENANCE, AND REPAIR. MINOR DEVIATIONS FROM THE DRAWINGS MAY BE MADE TO ACCOMPLISH THIS, BUT CHANGES WHICH INVOLVE EXTRA COST SHALL NOT BE MADE WITHOUT PRIOR APPROVAL OF THE OWNER OR CONSTRUCTION MANAGER.

FOR RENOVATION WORK, A CONTRACTOR'S SUBMISSION OF A BID SHALL BE CONSTRUED AS EVIDENCE THAT A CAREFUL EXAMINATION OF THE PORTIONS OF THE EXISTING BUILDING, EQUIPMENT, ETC., WHICH AFFECT THIS WORK AND THE ACCESS TO SUCH SPACES, HAS BEEN MADE AND THAT THE CONTRACTOR IS FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT THE EXECUTION OF THE WORK. LATER CLAIMS SHALL NOT BE MADE FOR ADDITIONAL LABOR, EQUIPMENT OR MATERIALS BECAUSE OF DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN DURING SUCH AN EXAMINATION.

THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND INSPECTIONS REQUIRED FOR THE EXECUTION OF THIS WORK AND SHALL OBTAIN NECESSARY APPROVALS FROM AUTHORITIES THAT HAVE JURISDICTION.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CORING NEEDS FOR PASSAGE OF PIPING THROUGH SOLID CONCRETE WALLS, FLOORS OR FOUNDATION WALLS.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR HANDLING, STORAGE, RIGGING AND SETTING OF ALL EQUIPMENT AND MATERIALS. CRANES, LIFTS, HOIST AND SCAFFOLDING OF ALL EQUIPMENT SHALL BE EMPLOYED AS REQUIRED TO COMPLETE THE INSTALLATION.

INFORMATION SHOWN ON FLOW DIAGRAMS AND DETAIL DRAWINGS BUT NOT SHOWN ON FLOOR PLANS, AND VICE VERSA, SHALL MUTUALLY APPLY. IT IS NOT INTENDED TO SHOW EVERY OFFSET, FITTING OR COMPONENT; HOWEVER, THE CONTRACTOR SHALL PROVIDE A COMPLETE INSTALLATION AS NECESSARY.

10.

9.

8.

7.

6.

5.

4.

3.

2.

1.

DEMO OR NEW WORK-SHOWN DARK LINED (SEE NOTE 11)

EXISTING TO REMAIN WORK-SHOWN LIGHT LINED (SEE NOTE 12)

RISER UP

RISER DOWN

BRANCH-TOP CONNECTION

BRANCH-BOTTOM CONNECTION

TEE

UNION

FLANGE

CONCENTRIC REDUCER

ECCENTRIC REDUCER

PIPE ANCHOR

PIPE GUIDE

DIRECTION OF FLOW

DIRECTION OF DOWNWARD PITCH

CAP ON END OF PIPE

STRAINER

SUCTION DIFFUSER W/ STRAINER

FLEX HOSE

STEAM TRAP

AUTOMATIC AIR VENT

BALL VALVE

BUTTERFLY VALVE

BALANCING AND SHUT-OFF VALVE

CHECK VALVE (SILENT TYPE)

FLOW CONTROL VALVE (GRISWOLD DEVICE)

GATE VALVE

GLOBE VALVE

PLUG VALVE

DRAIN VALVE W/ HOSE CONNECTION

PRESSURE REDUCING VALVE (SELF CONTAINED)

SAFETY VALVE OR PRESSURE RELIEF

THREE-WAY CONTROL VALVE (ELECTRIC ACTUATOR)

TWO-WAY CONTROL VALVE (ELECTRIC ACTUATOR)

THREE-WAY CONTROL VALVE (PNEUMATIC ACTUATOR)

TWO-WAY CONTROL VALVE (PNEUMATIC ACTUATOR)

BACKFLOW PREVENTER (REDUCED PRESSURE TYPE)

AIR SEPARATOR

AS

ABANDON IN PLACE

AIP

AHU

AIR HANDLING UNIT

AF

AIR FILTRATION UNIT

DFW

DEAERATING FEEDWATER HEATER

DH

DEHUMIDIFIER

DP

DOMESTIC PUMP

FT

FLASH TANK

BHP

BRAKE HORSEPOWER, BOILLER HORSEPOWER

CAP

CAPACITY

EXPANSION

FLA

FULL LOAD AMPS

LRA

LOCKED ROTOR AMPS

AD

ACCESS DOOR

ADJ

ADJUSTABLE

APD

AIR PRESSURE DROP

AMP

AMPERE

AUTO

AUTOMATIC

BDD

BACK DRAFT DAMPER

BOP

BOTTOM OF PIPE

BLDG

BUILDING

CLG

CEILING

CL

CENTERLINE

CHP

CENTRAL HEATING PLANT

COL

COLUMN

CONT

CONTINUOUS

CI

CUBIC INCHES

DIM

DIMENSION

DWG

DRAWING

EA

EACH, EXHAUST AIR

ELEC

ELECTRIC

EMER

EMERGENCY

ENT

ENTERING

EQUIP

EQUIPMENT

EXP JT

EXPANSION JOINT

F&T

FLOAT AND THERMOSTATIC

FD

FIRE DAMPER

FDR

FLOOR DRAIN

FIG

FIGURE

FIN

FINISH

FL, FLR

FLOOR

FO

FUEL OIL

GALV

GALVANIZED

GAL

GALLONS

GA

GAUGE

GND

GROUND

GPM

GALLONS PER MINUTE

HD

HEAD

H, HT

HEIGHT

HP

HORSEPOWER

INSUL

INSULATION

INT

INTERIOR

KVAR

KILOVOLT AMPERE REACTIVE

MATL

MATERIAL

WATER PRESSURE DROP

TOTAL DYNAMIC HEAD

TOTAL STATIC PRESSURE

MAXIMUM OVERCURRENT PROTECTION

MINIMUM CIRCUIT AMPACITY

SUPPLY AIR TEMPERATURE

TEMPERATURE DIFFERENCE

REVOLUTIONS PER MINUTE

PRESSURE REDUCING VALVE

RESISTANCE TEMPERATURE DETECTOR

POINT OF CONNECTION

PRESSURE DROP, PUMP DISCHARGE

THOUSAND BRITISH THERMAL UNITS PER HOUR

WATER GAUGE

WG

WPD

TDH

TSP

SUPPLY AIR

SA

STATIC PRESSURE

SP

SENSIBLE

SENS

RUNNING LOAD AMPS

RLA

QUANTITY

QTY

PSIG

PSIA

OUTSIDE AIR

OA

MOP

MCA

MOTOR

MTR

MANUFACTURER

MFGR

MR

MECHANICAL ROOM

SPECIFICATION

SPEC

SAT

NOM

POC

LBS/HR

PRESS

RTD

PRV

RH

RPM

SQ

SQ FT

ST

TEMP

TD

TYP

V

WB

MAX

MBH

MIN

NC

NIC

NO

No.

PD

PH

LBS

WITHOUT

WITH

WET BULB

VOLTS

TYPICAL

TEMPERATURE

SQUARE FOOT

SQUARE

RELATIVE HUMIDITY

PRESSURE

POUNDS PER HOUR

POUNDS

PHASE

NUMBER

NORMALLY OPEN

NOMINAL

NOT IN CONTRACT

NORMALLY CLOSED

MINIMUM

MAXIMUM

MCC

MOTOR CONTROL CENTER

MTD

MOUNTED

MOUNTING

MTG

NTS

NOT TO SCALE

OD

OUTSIDE DIAMETER

OZ

OUNCE

PRESSURE DIFFERENTIAL

SCFM

STANDARD CUBIC FEET PER MINUTE

SCHD

SCHEDULE

SS

STAINLESS STEEL

STD

STANDARD

STL

STEEL

TCP

TEMPERATURE CONTROL PANEL

THEMOSTAT

UG

UNDERGROUND

UNDERWRITERS LABORATORY

UL

VAC

VOLTS ALTERNATING CURRENT

WATER, WATTS, WIDTH

W

WT

WEIGHT

90° ELBOW

PRESSURE REDUCING VALVE

PRV

SC

STEAM COIL

ST

AIR FLOW MEASURING STATION

ARMS

WATER SOFTENER

ELECTRIC CONTROL/ SIGNAL CIRCUIT

ANALOG INPUT

ANALOG OUTPUT

FLOW SENSOR, SWITCH

AIR FLOW MEASURING STATION

VARIABLE FREQUENCY DRIVE

DISCRETE OUTPUT

DISCRETE INPUT

PREUMATIC CONTROL/ SIGNAL TUBING

DI

DO

AI

AO

VFD

FOR

WS

BTU/HR

DIAMETER

EXIST

EXISTING

POUNDS PER SQUARE INCH (ABSOLUTE)

POUNDS PER SQUARE INCH (GAGE)

HOA

PI

TI

DP

SD

DHW

DOMESTIC HOT WATER

EXP

EXT

EXTERIOR

GENERAL CONTRACTOR

GC

L

LENGTH

LF

LINEAR FEET

ARCH

ARCHITECTURAL

T ' STAT

W/

W/O

MECH

MECHANICAL

PLUMB

PLUMBING

RM

ROOM

VOL

VOLUME

VTR

VENT THRU ROOF

VAR

VARIABLE

ALUM

ALUMINUM

ON DEMOLITION DRAWINGS, ALL DARK LINED OBJECTS ARE TO BE REMOVED UNLESS NOTED OTHERWISE. ON NEW WORK DRAWINGS, ALL DARK LINED OBJECTS ARE NEW, UNLESS NOTED OTHERWISE.

11.

ON BOTH DEMOLITION DRAWINGS, AND NEW WORK DRAWINGS, OBJECTS SHOWN LIGHT LINED ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

12.

ABV

ABOVE

BF

CONTINUOUS BLOWDOWN

CBD

SH

SPRING HANGER

ALL GAUGES AND INDICATORS SHALL BE CLEARLY VISIBLE FROM PERSONNEL STANDING ON THE FLOOR OR ON PERMANENT PLATFORMS.

13.

ALL NEW PIPING SHALL BE TAGGED AND IDENTIFIED PER V.A. REQUIREMENTS.

14.

22-G1

MECHANICAL LEGEND, ABBREVIATIONS, AND SYMBOLS

JK

DD

DEPARTMENT OF VETERANS AFFAIRS EDITH NOURSE ROGERS MEMORIAL VETERANS HOSPITAL REPLACE BOILER - BUILDING 22

Sheets and Views

17664-G1-Work

EXISTING EMH-1

EXISTING SECONDARY

EXISTING PADMOUNTED TRANSFORMER 225 KVA PM8120-0050

EXISTING U/G PRIMARY DUCT BANK

EXISTING FIRE HYDRANT

EXISTING LIGHT POLE

PROVIDE NEW PADMOUNTED TRANSFORMER 500 KVA (7'x7'x1' THICK SLAB) DETAILS THIS DWG. 22-E3

EXISTING GAS PIPING FENCE ENCLOSURE

FOR CONTINUATION SEE DWG. 22-E2

NOTE: SEE DUCT BANK ELEVATION THIS DWG.

EXISTING ELBOW ENTER BUILDING

NEW PULLBOX SEE DETAIL THIS DRAWING

DEPARTMENT OF VETERANS AFFAIRS EDITH NOURSE ROGERS MEMORIAL VETERANS HOSPITAL REPLACE BOILER - BUILDING 22

22-E3

ELECTRICAL PARTIAL SITE PLAN, AND SITE DETAILS

%%URESTORATION/DUCTBANK DETAIL

ALL DIMENSIONS ARE MINIMUM

REQUIREMENTS.

3"

A-A

%%UCONCRETE ENCASED DUCT BANK DETAIL

C-C

ACTIVE PRIMARY-4"PVC WITH (3) 1/c #4/0, 15KV SHIELDED JACKETED CABLE IN CONCRETE ENVELOPE. TOP OF DUCT ENCASEMENT TO BE 24" MINIMUM BELOW GRADE

PREFORMED SPACERS 6'-0" O.C. ALONG ENTIRE LENGTH OF DUCT BANK

UNDISTURBED SOIL OR COMPACTED FILL BELOW ENTIRE LENGTH OF DUCT BANK

SPARE (PRIMARY) 4"PVC

UNDISTURBED EXISTING PAVEMENT

AC WEARING COURSE

SAW CUT

AC BINDER COURSE

6" MIN

PERMANENT PAVEMENT

TRENCH WIDTH

12"

24" MIN.

FINE SELECTED BACKFILL

4"PVC-(4) 350KC MIL (CU), (1) #2 GND. IN CONCRETE ENVELOPE. TOP OF ENVELOPE 24" MINIMUM BELOW GRADE

SPARE 4"PVC CONDUIT

1. ALL WORK SHALL BE APPROVED BY THE RESIDENT ENGINEER PRIOR TO POURING

2. DUCTS SHOULD NOT EXTEND MORE THAN 1" ABOVE THE TOP OF THE FOUNDATION.

PROVIDE GROUNDING BUSHING ON EACH DUCT, WITH 1/C #2 GROUNDING WHIP

4. GROUND AND SAND - GRAVEL SHALL BE COMPACTED AND THE SAND SHALL BE

TO GROUND GRID.

3. CONCRETE TO BE 3000#.

WETTED JUST BEFORE POURING THE CONCRETE.

PRIMARY DUCTS

10"

4"

SECONDARY DUCTS

24"

8"

%%UFRONT

%%UPLAN

84"

PRIMARY DUCTS

3/4" CHAMFER ON OUTSIDE EDGES

2" SAND

2"

25"

13"

15"

61"

84"

CONCRETE.

GROUND ROD - TYP. FOR 4 ( "x10' COPPERWELD)34"x10' COPPERWELD)

CONCRETE ENCASEMENT (TYP.)

4" R.G.S. ELBOWS PVC COATED 36" RADIUS

PVC TO RIGID ADAPTOR

SECONDARY CONDUITS TO BUILDING (4)

12" GRAVEL

GROUND WIRE # (CU)10 (CU)

FINISHED GRADE

REINFORCING SHALL STOP 3" FROM SIDES AND OPENINGS

EXOTHERMICALLY WELED CONNETION (TYPICAL)

3/4" x 10' LONGCOPPERWELD GROUND ROD (TYP. FOR 4)

COILED SLACK FOR CONNECTION TO TRANSFORMER GROUND LUGS (TYPICAL)

# 7-STRAND BARE 10 7-STRAND BARE COPPER GROUND 12" MIN. BELOW GRADE (TYPICAL)

%%UCONCRETE ENCASED DUCT BANK DETAIL

B-B

4"PVC-(4) 350KC MIL (CU), (1) #2 GND. IN CONCRETE ENVELOPE. TOP OF ENVELOPE 24" MINIMUM BELOW GRADE

SPARE 4"PVC CONDUIT

FINISHED GRADE, LOAM AND SEED ALL UNPAVED AREAS DISTURBED BY CONSTRUCTION

WARNING TAPE

%%UPARTIAL ELECTRICAL SITE PLAN

SCALE: 1'-0"=20'

REINFORCING TO BE #4 GRADE 60 BARS PER ASTM A.615, LOCATE IN CENTER OF SLAB, MIN. 2" CLEARANCE FROM FACE OF CONCRETE.

SEE NOTE 2 (TYPICAL)

TRANSFORMER PAD DETAILS

NOTES:

ELEVATION

%%UPARTIAL DUCTBANK ELEVATION

5' APPROX.

6' APPROX.

13' APPROX.

CURB

PAVEMENT

FINISHED GRADE

CONCRETE TRANSFORMER PAD (7'x7'x1' THICK)

PAVEMENT

CONCRETE DUCT BANK

CONCRETE DUCT BANK

EXISTING STONE RETAINING WALL WITH CONCRETE CAP

NEW 36"x36"x24 DP NEMA 4X PULL BOX

FLOOR SLAB

NEW "MAIN SERVICE DISCONNECT SWITCH" SEE DWG. 22-E2

STANDBY GENERATOR ROOM

TO EXISTING ELECTRIC MANHOLE "EMH1"

%%UPAVEMENT SLAB RESTORATION/DUCTBANK DETAIL

FINE SELECTED

BACKFILL

6" COMPACTED

GRAVEL

TRENCH WIDTH

PERMANENT PAVEMENT

24" MINIMUM

AC WEARING COURSE

AC BINDER COURSE

D-D

ACTIVE PRIMARY-4"PVC WITH (3) 1/c #4/0, 15KV SHIELDED JACKETED CABLE IN CONCRETE ENVELOPE. TOP OF DUCT ENCASEMENT TO BE 24" MINIMUM BELOW GRADE

SPARE (PRIMARY) 4"PVC

FINISHED GRADE, LOAM AND SEED ALL UNPAVED AREAS DISTURBED BY CONSTRUCTION

MIN. 6" COMPACTED GRAVEL BEDDING

Sheets and Views

17664FE03-Layout1

CP-2

CP-1

BOILER #2

BOILER #1

BFP-1

BFP-2

CTP-1

CTP-2

EXISTING CONDENSATE TANK

2 " FOS12" FOS

FUEL OIL DUPLEX PUMP SET

BDT-1

SOFTENER 1

BRINE TANK

FILTER #1

FILTER #2

FOP-1

FOP-2

SOFTENER 2

SOFTENER 3

CONCRETE PAD

FUNNEL DRAIN WITH 3/4" UP TO SAFETY VALVE DRAINS (TYP FOR 2)

3/4" HEADER DRAIN

3/4" STRAINER BLOWDOWN FROM D.A. TANK P.R.V.

3/4" NON-RETURN VALVE DRAIN (TYP FOR 2)

FUNNEL DRAIN FOR LWCO BLOWDOWN DRAINS (TYP FOR 6)

6"

2 1/2"

2" FOS/FOR UP

1 1/2"

3/4"

NEW BOILERFEED PUMP, BFP-3.

3/4" NON-RETURN VALVE DRAIN

2" BD CONN.

2" BD CONN.

TANDEM BOTTOM BLOW-OFF VALVE (TYPICAL)

1"

NEW MASTER/CP-3 CONTROL PANEL.

NEW 2 1/2" BF UP

G2 G4

N.C.

N.O.

NEW GATE VALVE IN BY-PASS

DEPARTMENT OF VETERANS AFFAIRS EDITH NOURSE ROGERS MEMORIAL VETERANS HOSPITAL REPLACE BOILER - BUILDING 22

22-G2

JD

RD

BOILER ROOM

LOWER PIPING PLAN

%%UBOILER ROOM - LOWER PIPING PLAN

SCALE: 1/4"=1'-0"

Sheets and Views

17664-G2-Layout1

%%UNEW BOILER NO. 3

FLOOR

5'-0"

2'-0"

72'-0"

EXISTING CATWALK

GRADE

48" I.D. FLUE WITHIN 58"O.D. STACK.

10'-5"

EXIST. HPS HEADER

DRAIN

34" EXIT DIAMETER

12'-0"

CENTER LINE

40"I.D.

40"I.D.

ALL FASTENERS 4'-0" ON CENTER MINIMUM. FASTENING TO STACK SHALL BE COORDINATED WITH AND APPROVED BY STACK MANUFACTURER

COPPER 20 STRAND #14 CONDUCTOR DOWN LEAD (TWO SIDES AND RING CONNECTING TERMINALS)

3/4"x10' COPPER CLAD GROUND ROD (TYP. 2)

LIGHTNING PROTECTION AIR TERMINAL 5/8" DIAMETER SOLID COPPER LEAD COATED (TYP. 2)

2'-0" MIN. TO TOP OF ROD

3/4" RIGID STEEL CONDUIT FROM 6" AFG TO GROUND ROD (TYP. 2)

CONNECT BOTH GROUND RODS TO EXISTING GROUND LOOP

UPPER 25'. ALL COMPONENTS LEAD COVERING MIN. 1/16" THICK

COPPER 20 STRAND #14 LEAD COVERED CONDUCTOR RING LOOP AROUND STACK CONNECTED TO BOTH TERMINALS

EXOTHERMIC WELD TYPICAL UNDERGROUND

DEPARTMENT OF VETERANS AFFAIRS EDITH NOURSE ROGERS MEMORIAL VETERANS HOSPITAL REPLACE BOILER - BUILDING 22

22-G9

ELEVATION AT BOILER No. 3

1. FOR NOTES, LEGEND, ABBREVIATIONS, AND FOR NOTES, LEGEND, ABBREVIATIONS, AND SINGLE LINED DIAGRAM SEE DRAWING NO. 22-E1.

ELEVATION AT BOILER No. 3 SCALE: 1/4" = 1'-0"

Sheets and Views

17664FE04-E4

B22 Pipe & Catwalk (12465+12467).pdf

B22 New Catwalk (12466+12468).pdf

OFFICE

1" FOS/FOR

6" HPS

6" HPS

1" HPR

1 1/2" HPR

1" HPR

1 1/2" HPR TO DA TANK

2" FOS/FOR FROM BELOW

4" HPS TO LAUNDRY

%%UNEW

%%UBOILER #3

%%UEXIST.

%%UBOILER #2

%%UBOILER #1

%%UNEW

%%UECONOMIZER #3

%%UECONOMIZER #2

%%UECONOMIZER #1

NEW 6" HPS

NEW 1" HPR

NEW 1 1/2" HPR

NEW 2 1/2" BF

NEW 1" FOS/FOR. CONNECT TO BOILER

NEW 3/4" CF. CONNECT TO BOILER.

NEW 2 1/2" BF FROM BELOW

PROVIDE NEW BACKPRESSURE VALVE TO REPLACE EXIST. BACKPRESSURE VALVE

GATE VALVE IN VERTICAL

NON-RETURN VALVE

NEW STEAM METER

LOCATE NEW 2 1/2" BOILER FEEDWATER PIPE TO MAINTAIN CLEAR ACCESS AT EXIST. BOILERS #1 & #2 AND AT NEW BOILER #3.

PROVIDE ADJUSTABLE HANGER THIS LOCATION. HANGER SHALL BE PROVIDED WITH LOADING INFORMATION, DEFLECTION INDICATOR AND COMPRESSION RING KAPPA RATING.

PROVIDE VENT UP THRU ROOF

DEPARTMENT OF VETERANS AFFAIRS EDITH NOURSE ROGERS MEMORIAL VETERANS HOSPITAL REPLACE BOILER - BUILDING 22

22-G3

JD

DD

BOILER ROOM

UPPER PIPING PLAN

%%UBOILER ROOM - UPPER PIPING PLAN

SCALE: 1/4"=1'-0"

Sheets and Views

17664-G3-Layout1

OL106310 WD.pdf

OL106310 DD.pdf

OL106310 DD 1.pdf

%%UEXISTING GAS PRESSURE

%%UREDUCING STATION AND METER

EXIST. 2" PILOT GAS

EXISTING VENTS TO ATMOSPHERE

EXISTING GAS TRAIN

EXISTING GAS TRAIN

NEW GAS TRAIN

RUN THREE NEW 1" VENTS & ONE NEW 1 1/2" VENT UP THRU EXTERIOR WALL ABOVE. PROVIDE INDIVIDUAL SLEEVES FOR EACH PENETRATION. OFFSET AROUND GUTTER WITH SCREENED RETURN BEND. PAINT PIPING YELLOW. (PORTIONS OF EXISTING VENT PIPING MAY BE RE-USED BY CONTRACTOR SUBJECT TO APPROVAL OF OWNER'S REPRESENTATIVE)

REMOVE EXIST. GAS PIPING DOWNSTREAM OF CUT-POINTS AND PROVIDE NEW GAS PIPING AS INDICATED.

EXISTING PROPANE TANKS

EXIST. PROPANE

NEW PROPANE