11575 New Water Heater Specifications:
-750 MBH with 225 gallons of water storage
-Recovery rate of ~870 gph at 100°F temperature rise (40°F to 140°F)
-120 VAC, 1 ph, 60Hz.
-Minimum thermal efficiency of 95%
-Duplex stainless steel tank with ASME rating (no anodes to be required)
-Steel jacket panels
-Electronic operating system with integrated ignition and operating controls
-Full modulation with digital readout and adjustable temperature controls
-Electronic low water cutoff with manual reset
-CSD-1 controls
-Condensate neutralizer
-LonWorks compatible (may require additional equipment)