Text version

11575 New Water Heater Specifications:

-750 MBH with 225 gallons of water storage

-Recovery rate of ~870 gph at 100°F temperature rise (40°F to 140°F)

-120 VAC, 1 ph, 60Hz.

-Minimum thermal efficiency of 95%

-Duplex stainless steel tank with ASME rating (no anodes to be required)

-Steel jacket panels

-Electronic operating system with integrated ignition and operating controls

-Full modulation with digital readout and adjustable temperature controls

-Electronic low water cutoff with manual reset

-CSD-1 controls

-Condensate neutralizer

-LonWorks compatible (may require additional equipment)