Attachement A_ELECTRICAL ONE-LINE DRAWINGS.pdf
PDF 4 MB Posted
- Attached to
- H261--SWITCHGEAR ELECTRICAL TESTING, INSPECTION, & MAINTENANCE Federal contract opportunity
- Solicitation number
- 36C26024Q0513
About this file
This document appears to be a set of electrical one-line drawings related to a federal contract opportunity for switchgear electrical inspection, testing, and maintenance services at the Puget Sound VA Medical Center - American Lake Campus.
The key details are:
- This is a total SDVOSB set-aside solicitation (Solicitation Number: 36C26024Q0513) for switchgear electrical inspection, testing, and maintenance services.
- The solicitation includes the one-line drawings in Attachment A, a master drawing index in Attachment B, and wage determinations for Pierce County, WA in Attachment C.
- The scope of work likely includes inspection, testing, and maintenance of the electrical switchgear systems detailed in the one-line drawings.
- This contract opportunity is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26024Q0513 0003.docx | DOCX document | |
| 36C26024Q0513 0002.docx | DOCX document | |
| 36C26024Q0513_AMENDED.docx | DOCX document | |
| ATTACHMENT D- AMLK-SINGLE LINE DIAGRAM ELECTRICAL.pdf | ||
| Attachment E - MAIN SWITCH YARD PHOTOS.pdf | ||
| Attachment F - Transformer Name Plate.pdf | ||
| 36C26024Q0513 0001.docx | DOCX document | |
| Attachment C - WAGE DETERMINATIONS PIERCE COUNTY WA.pdf | ||
| 36C26024Q0513.docx | DOCX document | |
| Attachment B- Master Drawing Index.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MID
os*
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.E. SUITE #102
BOTHELL, WASHINGTON 98012 USA
PHONE: (425)-485-1778, FAX: (425)-485-0658
http: //www.controlledpowerinc.com ofr CONTROLLED POWER, INC. OLD JOB No. 6820
VA PUGET SOUND HEALTH CARE
TACOMA, WASHINGTON
GENERATOR PARALLELING SWITCHGEAR
GENERATOR 1 ADDITION, 2013
CONTROLLED POWER INC. JOB No. 7705 DRAWING No.
7705-2101—D 7705-3101—D 7705-4101—D 7705-5210—D 7705-5220—D 7705-5230—D 7705-5240—D 7705-5241—D 7705-5310—D 7705-5311—D 7705-5320—D 7705-5321—D 7705-5330—D 7705-5331—D 7705-5340-0 7705-5341-0 7705-5342-0 / 7705-5343-0/ 7705-5351-0 7705-5352-0 7705-5410-0 7705-5420-0 7705-5430-0 7705-5501-0 7705-6101-0 7705-6101A—D 7705-6201-0 7705-6201A—D 7705-6202—D 7705-6202A—D 7705-6203—D
DRAWING TITLE
COVER SHEET
SCHEMATIC LEGEND AND NOTES
GENERATOR SWITCHGEAR ELEVATION VIEW, OUTLINE DIAGRAM
GENERATOR 1 AC THREE LINE, SCHEMATIC DIAGRAM
GENERATOR 2 AC THREE LINE, SCHEMATIC DIAGRAM
GENERATOR 3 AC THREE LINE, SCHEMATIC DIAGRAM
MASTER SYNCHRONIZING & LOAD CONTROL AC THREE LINE, SCHEMATIC DIAGRAM
MAIN BUS & UTILITY THREE LINE, SCHEMATIC DIAGRAM
GENERATOR 1 DC CONTROL, SCHEMATIC DIAGRAM
GENERATOR 1 DC CONTROL, SCHEMATIC DIAGRAM
GENERATOR 2 DC CONTROL, SCHEMATIC DIAGRAM
GENERATOR 2 DC CONTROL, SCHEMATIC DIAGRAM
GENERATOR 3 DC CONTROL, SCHEMATIC DIAGRAM
GENERATOR 3 DC CONTROL, SCHEMATIC DIAGRAM
MASTER DC CONTROL, SCHEMATIC DIAGRAM
MASTER DC CONTROL, SCHEMATIC DIAGRAM
MASTER DC CONTROL, SCHEMATIC DIAGRAM
MASTER ANNUNCIATOR DC CONTROL, SCHEMATIC DIAGRAM
REMOTE ANNUNCIATOR DC CONTROL, SCHEMATIC DIAGRAM
REMOTE ANNUNCIATOR DC CONTROL, SCHEMATIC DIAGRAM
GENERATOR 1 CIRCUIT BREAKER DC CONTROL, SCHEMATIC DIAGRAM
GENERATOR 2 CIRCUIT BREAKER DC CONTROL, SCHEMATIC DIAGRAM
GENERATOR 3 CIRCUIT BREAKER DC CONTROL, SCHEMATIC DIAGRAM
PLC RACK CONFIGURATION, SCHMATIC DIAGRAM
CONTROL SWITCH TARGET DIAGRAM
GENERATOR 1 CONTROL SWITCH TARGET DIAGRAM
NAMEPLATE ENGRAVING SCHEDULE, FABRICATION DIAGRAM
GENERATOR 1 NAMEPLATE ENGRAVING SCHEDULE, FABRICATION DIAGRAM
NAMEPLATE ENGRAVING SCHEDULE, FABRICATION DIAGRAM
NAMEPLATE ENGRAVING SCHEDULE, FABRICATION DIAGRAM
ANNUNCIATOR WINDOWS, FABRICATION DIAGRAM
5,7 0 0
CIRCUIT BREAKER AUXIUARY CONTACT
CLOSED WHEN BREAKER IS CLOSED.
CIRCUIT BREAKER AUXIUARY CONTACT
OPEN WHEN BREAKER IS CLOSED.
52bo
DRAWOUT CONTACT
CIRCUIT BREAKER BELL ALARM CONTACT.
CLOSED ON MERCURRENT TRIP.
REQUIRES MANUAL RESET.
UGHT NAME
LENS COLOR
TERMINAL NUMBERS
AMPERE RATING
To3(5) M — TIME DELAY ON BREAK COIL
RELAY NAME
CONTROL RELAY 3
— RELAY COIL VOLTAGE
— TIME DELAY ON MAKE COIL
( + ) LADDER POLARITY
COIL OF RELAY CR3
NORMALLY CLOSED CONTACT ON RELAY CR2
NUMBER OF POLES ON RELAY
COIL Of RELAY CR1 LOCATED ON SHEET No. (5) COORDINATE E7
NORMALLY OPEN CONTACT ON RELAY CR1 — \
CR1(5) E7
POLARITY MARKING
CR2 (5) Al
' N—TERMINAL
NUMBER
OF RELAY
NORMALLY OPEN TIME DELAY ON MAKE CONTACT
FI
c
F.ILDELAY 2
TIME SETTING
NORMALLY CLOSED TIME DELAY ON BRE CONTACT ME SETTING
_ TIME DELAY 4
(24 WC)
(200001 LAMP VOLTAGE
IFS RI OT I IGHT
SHIELDED CABLE
WASTED PAIR WITH
e 100% FOIL COVERAGE
CHASSIS GROUND
TIME DELAY NAME
TERMINAL NUMBER
TIME DELAY SETING
WI—I INE TIME DEJ AT
TERMINAL NUMBER
FLASH R MOOUi F
TERMINAL NUMBER
NOTES:
1. CONSTRUCTION SHALL BE OF CODE GAUGE SHEET STEEL
NEMA TYPE 1 INDOOR ENCLOSURE.
A. SWITCHGEAR SHALL MEET REQUIREMENTS I MEND
PER NEMA, ANSI, IEEE AND UL STANDARDS
B. SVATCHGEAR SHALL BE FRONT AND REAR
Snag& DESCRIPTION.
* INDICATES TERMINALS IN MASTER CONTROL SECTION. ACCESSIBLE FOR INSTALLATION AND MAINTENANCE.
2. FINISH: ANSI 01 UGHT GRAY El INDICATES TERMINALS IN ENGINE/GENERATOR.
NOTES: INTERVAL TIMER 3. BUSSING: 1200 A. COPPER
4. SER VICE: 4160 V. 30, 3W, 60 HZ 0 INDICATES TERMINALS IN ENGINE JUNCTION BOX (IJB).
I. ALL CONTROL WIRING TO BE No. 14 AWG, 600 VOLT, TYPE SIS.
5. MAXIMUM PROJECTION OF DOOR MOUNTED c.) INDICATES TERMINALS IN GENERATOR CONTROL SECTION. EXCEPT AS NOTED. CURRENT TRANSFORMER WRING TO BE No. 12 AWG.
COMPONENTS: 3 INCHES,
6- INTERNAL WRING CONNECTIONS TO BE #12 & 14 ABS MINIMUM, TYPE
f21 INDICATES TERMINALS IN FEEDER BREAKER SECTION.
2. SHIELDED WIRE TO BE No. 18 AWG, 300 VOLT TWISTED LINE WITH
SIS RATED 605 VOLTS. 90 DEGREE EXCEPT AS NOTED. ALL 0 INDICATES TERMINALS IN UTIUTY SECTION. 100% FOIL COVERAGE.
WRING TO BE NUMBERED AT BOTH ENDS. 0 INDICATES TERMINALS IN BREAKER CELL. 3. ALL DIODES ARE 1N4007, UNLESS OTHERWISE NOTED.
7. NAMEPLATES TO BE BLACK WITH WHITE LETTERING 0 INDICATES TERMINALS IN GENERATOR SWITCHGEAR. 4. GENERATOR 1-2 SIMILAR.
SECURED TO SVATCHGEAR RID-1 CORROSION RESISTANT HARDWARE
IC I INDICATES NETWORK ADDRESS. 5. WIRE NUMBERS ARE 1—XXX FOR GEN 1, 2—GIG FOR GEN 2, ETC.
B. I= REFERENCE NAMEPLATE SCHEDULE.
— — INDICATES FIELD WIRING BY OTHERS.
R. REFER TO THE GENERATOR SVATCHGEAR SECTIONS B. 9 & 10
PARTS UST FOR PARTS SHOW ON THIS DRAWING.
REV. DESCRIPTION
PURCHASE ORDER No. 1136CONPOW-03 CONTROLLED POWER JOB N
TITLE SCHEMAT C LEGEND & NOTES
A
12-19-13
10-16-13
DATE
AS INSTALLED
SUBMITTAL
SCALE: NONE DATE: 10-16-13 DWN. BY: TR1
DWG. No: 7705-3101-D SHEET: 1 OF 1 CKD. BY: DLE
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
NOTICE
THE DRAWN.. INPORBIARON AND 0.2.001 MATTER HEREOF
ARE DIE CONFIC0,11, EXCLUSTE PROPERTY
0, COHIRCBLED PONES INC.. AND ARE HOT TO BE COPED.
REPRODUCED OR USED TO #01 0040440 PUN MY PURPOSE
RHATSOCATR HAMM RATTER CONSORT CO DRECDON. 1/11 411e.
loTa, Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.E. SUITE #102
BOTHELL, WASHINGTON 98012 USA
PHONE, (425)-485-1778, FAX, (425)-485-065E
http: //www.contronedpowerinc.com
Plot dotr 2013/12/
TOP HER
REMOTE ANNUNCIATOR ENCi OSHRE — FRONT viryi VISE ,AEw
12-19-13
A 10-16-13
AS INSTALLED
SUBMITTAL
REV. DATE DESCRIPTION
PURCHASE ORDER No. 1136CONPOW-03 CONTROLLED POWER 100 IY
TITLE GENERATOR SWITCHGEAR ELEVATION VIEW, OUTLINE DIAGRM
SCALE: NOTED DATE: 10-16-13 OWN. BY: TRI
DWG. No: 7705-4101-D SHEET: 1 OF 1 CKD. BY: DLE
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
ENGINE/GENERATOR #3 MASTER ENGINE/GENERATOR #2 ENGINE/GENERATOR #1
C
LI
N O
N U
E L 1
O N
C
U
TL
ER
H A
M M
E R
D W
G o.
E
F
• E/G #3 MASTER •
N
N U F
D
IF
T T
E R
H A
M M
F R
D W
G N o
E R
G
E N
H
O
• E/G f2 I E/G #1
2 3 5 7 8
32345676
42345676
32345674
9 10 II 12 13 34 15 IS
9 10 1 12 13 14 15 16
9 10 11 12 13 14 15 16
930 11 12 13 14 15 16
17 113 1020 23 22 23 24
17 18 19 20 21 . 2324
17 18 19 20 21 22 23 24 r4 Ver . ®
ORM
A
S
&MI
.(7) +.-.1.4 V
I 24143/
S
S 0 Laltii
P F O WM MM A
S
1 2_ I
V
GOES
20208552
G 0
HUB
F
IETD 8559
0 0
ARM LTB
CMOs
MN 0
M
,. Y
I /4. 44.4 I r
F I ......./ 1 G Y
R C .„...
WI
OF
1.4
R C ...,..._
11/84
M s s i
P R C e
0 2 222
D 2 222 killtri dw tr
FrrierssraFi 3 i. 1 P1/CT 1031 SAl
PI/CT TEST SW 1
Mil OMB NBC
0 0 0
HSB ARB ITS
WEED IMO Q ,,,, E MC MD
0 f.) MC Ct. 0
ES!? GMS S LCS GUB
MU ER= WM
0 0 0
HSB ARB LIB
OMB MID 00111E OEM MC
ESB GMS S LCS GUB
OBEO3 OMB 01/Bil
0 0 0
FMB ARB LTB
CEMO 1:EM3 0200E OMB azza 0 .0 CP CI C Ct 0
ESB GMS S LCS GUS
BOL LTL BCL
0 R&R
0 0 0 IMMO UEcEl IMMO
C/ :4 S L11 11 1 : G
I—
SEE CUTLER
D1VG#
SHEET
I__
E9310E No. 1
HORN
HAMMER
—I
OF 2
_J
BOL LTL BC1
0 R&R
0 0 0 DIEM CREDO OMEI s
C) ti c ri 1 : G
BOL LTL BCt. 0 R&R 0 0 0
031107B IffZI MOO
C/ 44
. 8
11 16 • G
OANCEt ' fiiiit
14114614, r [ IDAtcji -DER
MGM VOLTAGE
KEEP OUT
HIGH VOLTAGE
II4 VOLTAGE
HIGH VOLTA
4 0 . . 0 . . 0 . . 0 .
15h1 60
36.00' 36.00" 36.00 MOO"
85711100 09 CC 0110N 10 SECTION IQ
SWITCHGEAR ELEVATION
FITNI)
S654R01 DE60,163106
AS AMMETER SWITCH
AM AMMETER
ARB ALARM RESET BUTTON
BCL BREAKER CLOSE LIGHT — RED
BCE BREAKER CONTROL SWITCH
BUS BREAKER MODE SWITCH, MANUAL—AUTO
ROL BREAKER OPEN LIGHT. GREEN
ECS ENGINE CONTROL SNITCH. OFF—AUTO—RUN
EPIA ELECTRONIC POWER METER
ESB EMERGENCY STOP BUTTON
FM FREQUENCY METER
GOSS GENERATOR DEMAND SELECTOR SWITCH, GEN 1-04T—GEN 2 3
GAR GENERATOR PROTECTION RELAY
OAFS GOVERNOR MODE SVATCH, LOADSHARE—BASELOAD
COB GENERATOR UNLOAD BUTTON
HORN ALARM HORN
HER HORN SILENCE BUTTON
LCS LOAD CONTROL SWITCH. LOWER—RAISE
LTB LAMP TEST BUTTON
LTL LOCKOUT TRIPPED LIGHT — RED
PP POWER FACTOR METER
TEAR 86 LOCKOUT RELAY. RESET & READY LIGHT
SIAS SYSTEM MODE SWITCH. AUTO—MAN
SS SYNCHROSCOPE SWITCH. OFF—ON
SYNC SYNCHROSCOPE, SLOW—FAST
Ts ONLINE TEST SWITCH. BUS 2—N—BUS 1 & 2
UTIAS UTILITY TRANSFER MODE SWITCH. OPEN—CLOSE
VIA VOLTMETER. 0-5250 V
VS VOLTMETER SNITCH
WM WATTUETER
86G LOCKOUT RELAY
NOTE.
1, FOR GENERAL WRING & CONSTRUCTION NOTES. SEE DRAYANG No. 7705-3101-1
2. ANNUNCIATOR LEGEND. SEE DRAWNG No. 7705-6203-0.
NOTICE
THE DRAWN., W.:PATON AND SEO,ECT HATTER HEREOF
ARE THE COHEIDENTIAL. SOLE AM EXCLUSAC PROPERTY
OF CONTR.. POHER. Inc. AND ARE NOT TO RE COPED, REPROCoCED ;IMO IN ANT PAHNER FOR ANY PuRPosE PHATSCEvER FAINCHT ViPTIEN OCCISEXT CR omEcnoK
MEI
4114. u. woe*
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.E. SUITE #102
BOTHELL. WASHINGTON 98012 USA
PHONE, (425)-485-1778, FAX: (425)-485-065E
http://www.controlledpowerinc.corn
Plot dote: 2014/1/
NOTICE
THE DRAWN., INFCRMANCR AND SUBJECT MATTER HEREOF
ARE I+ CONFIDENTIAL 504E ANO E881601E PROPERTY
OF CONTROUEL. PONER. INC.. AND ME NOT TO BE COPIED.
REPROOOCED CR USED P. ANY MANNER FOR ANY PURPOSE
IOIATSOEVER IMMO. MRITIEN CONSENT OR [MECUM.
2 SYNCHRONIZING AND LOAD CONTROL GENERATOR PROTECTIVE RELAY 3 TO MAIN BUS 2 CTSB DILL,2 7705-5241-0 GPR1 4
( 0A ,-, 165 OB VOLT BIAS TO CDVR 5
158 150
SPEED BIAS TO ENGINE GOVERNOR 8 012 AWG IN
5201 1200A, 5KV VACUUM CIRCUIT BREAKER, 25014VA
BUS PT 4A-14
OVARENT
TRANSFORMER
NIORTINO INOCZ CISB-2 POWER FACTOR METER 4A1 WATT METER GENERATOR 1 GENERATOR 1 VOLTAGE FREQUENCY
261 SENSING SENSING
-25006 RELAY RELAY
4BI 1
AMMETER
AM TEST SWITCH 1 GEM 13 0-400A SC. 5A RA. 151 0.5-1-0.5
I ocEE filagI 116 116 4C1 106
116 116 16 116 116 116 14
'SET SI.ECCC'reN.7 I I (6126 161541 I
CT3 1C2 1
9I IC-HI IC-LOJ
O 0
118-H1 IB-LOI
O 0
157 1A-H1 1A-LO I
oGNO VREF 0
LVA0±
13917130 9 0-\.,-0
135 138 I 2 5 cc
137 137 1 4 I 147 147
7 9 08 119 129 9 149 129 o
5 1 158 06 05
04 03 >a "8
148 118 128 12 116 4A2
>0 "7 117 127 127 7
[LI L2 L3 N IL
Lc 3 6 11 8 29 31 33 35 ii
1 2 113 195 III 195 1 1 112 113 195 111 1 2 113 195 18182 1031828
111 -1-1- I
0 Ti 01'2 0T3
11 195 195
VOLTMETER
V1,1
0-5250 Sc 150V RA
VO
POIENTIM.
TRANSFORMER PI
X2
PT2 P2
F13 F10 P" 101 10 P11 111 101 111 , 42 52
42 41
82 82
VB
VC
M c 3f
102 112 112 102 112 103 113 103 113
0,. END
FM 112 111 SOAR FREQUENCY METER 55-65 HZ 120V
P12-4 160 P12-5 162
112 16 VOLTAGE REGULATOR ALARM RELAY TO CDVR VOLTAGE REGULATOR SENSING LOCATED ON GENERATOR 111 VOLTAGE REGULATOR FAULT RELAY SYNC CHECK RELAY 23 5 6 14
0 0
395 P12-5 161 I. .81 161
P9-6 2 FROM BUS 2 pr 7705-5241-0 184 184 0 TO COVR VOLTAGE REGULATOR LOCATED ON GENERATOR CCCT G1EDR 69 .184 31 P5-7 169 EXCITA11001 DISABLE
27 P9-8 —C1)- 0
P12-6 1,, 184 184 FAULT RESET 2
Ti 13 GENERATOR 1 2000 KW, 0.8 PF, 4160 7, 30 60 HZ T4 347 F.L.A. .r9
. VOLT BIAS TO DSLC-2 I I _
- -) -1— —1
P12-3 1,9
TO BREAKER CONTROL SCHEMATIC 7705-5410-0
NOTE 1. FOR GENERAL HARING & CONSTRUCTION NOTES. SEE DRAWING No. 7705-3101-
122 AS INSTALLED REUSE V14 & AM TERMINAL NUMBERS CORRECT GENERATOR AND CT SIZING SUBMITTAL
0 12-19-13 11-05-13 CT -8 10-29-13 10-16-13 A 121
DESCRIPTION REV. DATE CT-9 GENERATOR PROTECTIVE RELAY
PURCHASE ORDER No. 1136CONPOW-03 CONTROLLED POWER JOB N.
OAS.,
IRANSFORMER
OKKI1N.0 KO. SR CTSB-3 TITLE GENERATOR 1 AC THREE LINE, SCHEMATIC DIAGRAM
felt1 167 I G9
OWN. BY: TRI DATE: 10-16-13 SCALE: NONE CT 168 H9
CKD. BY: DB SHEET: 1 OF 1 DWG. No: 7705-5210-0
(NEW UNIT) JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
rg .110
Controlled Power, hlc, 17909 BOTHELL EVERETT HWY. SL SUITE #102 BOTHELL, WASHINGTON 96712 USA PHONE: (425)-485-17713, FAX: (425)-485-0655 http, //www.c.trolledpowerinc.com
UNE
SYNCHRONIZING
AND
LOAD CONTROL GENERATOR
PROTECDVE
RELAY TO MAIN BUS 2 CTS8-1
7705-5241-0 1 I 120 4
166 )
Y c •
.0
I 123 VOLT BIAS
TO COW r-
To
1 50 it)
SPEED BIAS
TO ENGINE
GOVERNOR f12 ARC. BIN
1200A, 5KV
VACUUM CIRCUIT
BREAKER, 250MVA BUS PT MA-N 311
CTSB-2
4A1 1 01 POWER
FACTOR
METER
2 WAIT
METER GENERATOR 1
FREQUENCY
SENSING
RELAY
GENERATOR I
VOLTAGE
SENSING
RELAY
AMMETER
AlA TEST SWITCH 1
1 0-400A SC.
SARA.
06 116 6 16
, 59 C O
-HI IC-
L0
1158 1B-H1 ia-tol
IA-HI IA-LO
0 0
VA ONO VREF
59 15
4A2 I 0-0
71T7, 'To • 127 127 04 03 137 137 1 4 147 147 It 4 107 157
[LI L2 L3 N
1 L N 113 29 31 33 35 3 6 11 8 111 18
9 - ?-?-?
111 112 I 3 195
I 112 I 3 195
9-?-?-?
950 III 12 113 195
VOLTMETER
VM
0-5250 Sc
150V RA
VA
va
SC
T1 012 013 mnwn&
WARSPORTAM
PT1 .1 P1
- 8 X2
F112 ,.z
P2
-28 02
F13 F10 101 PT
111 101 111 G, Eli
PI 103 3 113
02 P6 1950 1950 v7f 35:1 195 195
PI PI
rm
112 111 FREQUENCY METER
55.ir v
1-12
VRAR
P2 ACM
FS
.1
E
OS-50
CCA_41
EX 015
FRES
vo l y
P2 112
VOLTAGE REGULATOR
ALARM RELAY TO COVE VOLTAGE REGULATOR SENSING
LOCATED ON GENERATOR 111
VOLTAGE REGULATOR
FAULT RELAY SYNC CHECK
RELAY 395 2E01
12 SS 141 3 6
SS
0 0 0 142 0 1 312
S 111 1 0 143
.:1
. 0 26 2
FROM BUS 2 PE!
7705-5241-0
TO COW VOLTAGE REGULATOR
LOCATED ON GENERATOR
CCCT
yo, EXCITATION DISABLE
FAULT RESET
1.A
T2
71 03
GENERATOR 1
2000 KW, 0.8 PF,
4160 1, 30
60 HZ
T4 347 L.A. 16
VOLT BIAS
TO DSLC-2
7- -1- -1 TO BREAKER CONTROL
SCHEMATIC
7705-5410-0
121 122 123 12 CTS8
123 o0
NOTE.
1. FOR GENERAL WIRING & CONSTRUCTION NOTES, SEE DRAWING No. 7705-3101-
CT-7
122 o0
CT-8
' 0
AS INSTALLED
REVISE VM & AU TERMINAL NUMBERS
CORRECT GENERATOR AND CT SIZING
SUBMITTAL
12-19-13
11-05-13
10-29-13 8
10-16-13 A 121 o •
DESCRIPTION DATE REV.
CT-9 GENERATOR
PROTECTIVE
RELAY
PURCHASE ORDER No. 1136CONPOW-03 CONTROLLED POWER JOB NI sr
MICR
.660-60 KOLL
CTSB CTS13-3
1 167
TITLE GENERATOR 1 AC THREE LINE, SCHEMATIC DIAGRAM
OWN. BY: TRT DATE: 10-16-13 SCALE: NONE CT 168
CKD. BY: DB SHEET: 1 OF 1 DWG. No: 7705-5210-D
(NEW UNIT) JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
NOTICE
THE DRAVANGS, INFORBARON AND SUBJECT MATTER HEREOP
ARE THE CON210ENTI, SO. AND EXCLUSIVE PROPERTY
OF CONTROLLED PARKS NC.. AND AVE NOT TORE COPED.
REPROONCED OR UMO 64 ANY BANNER FOR ANY PURPOSE
YALL'ISOEVER VATHCBT NRTIEN CONSORT CR BRECTICN.
1141111111 Controlled Power, Inc.
17909 BOTHELL EVERET7 HWY. S.E. SUITE #102
BOTHELL, WASHINGTON 98012 USA
PHONE: (425)-485-1778, FAX: (425)-485-065S
h //www.controllecIpowerinc.com
Plot dote: 2013/12/
2 SYNCHRONIZING
AND
LOAD CONTROL GENERATOR
PROTECTIVE
RELAY TO MAIN BUS 2
7705-5241-0
0A OS BC
CTSB-1
GPR2 120
123 20 VOLT BIAS
TO 0914
122 20 6
ISO 150
r-1:11
I 1 151 j
'1091 ITN
j]
E
SPEED BIAS
TO ENGINE
GOVERNOR fl 2 AWG IN
1200A, 5KV
VACUUM CIRCUIT
BREAKER, 250MVA 311 US PT BA -N
CURRENT
'RAViNatRiER
SP.O.IINC.120
CTSB-1
POWER
FACTOR WATT
METER METER
4B1
4C1
4C2
4A2
GENERATOR 2 GENERATOR 2
VOLTAGE FREQUENCY
SENSING SENSING
RELAY RELAY
I ozaI Ifi2E5R I
AMMETER
As TEST SWITCH 1
0-400A SC.
5A RA.
151 0.5-1-0.5
FOR CONTACTS I
SM SHEET.,
In'''. (2) La 149 149 1
SHEET N.
OONT.IS
14110 (,) 08 13 8 10 12 08 07 109
129 9 139 0 0 0 0
1 148 148 2
147 147 1 1
3 6 11 8 111 g
4-YLi".2.4 I
127 127
29 31 33 35
11 112 113 195 1 1 1 2 1 3 195 III 1 2 113 195 102 103 1950
VOLTMETER
VIA
0-5250 Sc
150V RA
P1
I pc
2 112
80- 0 8
195 195
ARB (MOUNTED AT GENERATOR)
CuRRENT
TRWEFORMER
SHORING. Ek00(
CTSB
188 188 43 ---
CYR FM
112 FREQUENCY METER
55-65 HZ
L _ 40 112 40-1 ‘-‘
24VDC
POWER
CCCT
28-1) 28-1 Ill
294 DROOP RES SYNC CHECK
RELAY
1 2 0 0
395 18 - F1
If. • 62 2 -0
DIGITAL
VOLTAGE
REGULATOR
VOLTAGE REGULATOR ALARM
RELAY (DE-ENERGIZED ON ALARM) \R2FR
183 12 1801 141 FROM BUS 2 prf.
7705-5241-D
VOLTAGE REGULATOR FAULT
RELAY (DE-ENERGIZED ON FAULT)
F2
181 (24 143 181
187 187 ,-,1137 26 309 185 POTENTIAL
SENSING
TAGE
SING: 125-249V
186 1 1 1881 1 1/2
500 OHM
1/2 W
VOLT BIAS
TO DSLC-2
OB
OA BC
GENERATOR 2
750 KW, 0.8 PF,
4160 Y, 30
60 H2
130 FLA
86 186 30 4
0 OH
TO BREAKER CONTROL
SCHEMATIC
7705-5420-0
CTSB
NOTE'
1. FOR GENERAL WRING & CONSTRUCTION NOTES, SEE DRAWING No. 7705-3101-0
2 o'
CT-8
AS INSTALLED
SUBMITTAL
12-19-13
10-16-13 A
DESCRIPTION DATE REV.
CT-9 GENERATOR
PROTECTIVE
RELAY
PURCHASE ORDER No. 1136C09P0W-03 CONTROLLED POWER JOB NI 120 x, TITLE GENERATOR 2 AC THREE LINE, SCHEMATIC DIAGRAM
OWN. BY: TRT DATE: 10-16-13 SCALE: NONE
CKD. BY: DLB SHEET: 1 OF 1 DWG. No: 7705-5220-0
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE (EXISTING UNIT)
NOTICE
THE DRAWN.. INFORMATION AND Stf&ECT VATTER HEREOF
ARE THE CONFIDENTIAL SOLE AND EXCLUSVE PROPERTY
OF CONTROLLED POMR. INC.. AND ARE NOT 10 80 COPED,
REPRODUCED OR uSED IN ANY MANN. FOR 911 1061010 *RATS.. IMMO. *RM. CONSENT OR DiRECCO.4,.
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.E. SUITE #102
BOTHELL, WASHINGTON 98012 USA
PHONE: (425)-485-1778. FAX: (425)-485-0658
SYNCHRONIZING
AND
LOAD CONTROL GENERATOR
PROTECTIVE
RELAY TO MAIN BUS 2 CTS8 I/SI C-7 7705-5241-0
220 I 229
I 223 223 22
I 222 1 222 22
GPR
.0
0 I I 288
220 VOLT BIAS
TO UR
250 250 n 220
251 SPEED BIAS
TO ENGINE
GOVERNOR #12 ARC. MIN
1200A, 5KV
VACUUM CIRCUIT
BREAKER, 25014VA
BUS PT BA-N
GENERATOR
FREQUENCY
SENSING
AMMETER
RELAY
same
FOR CUPACTS
ffE SHEET No
0-200A SC.
(:02 10 1)0100 216
5A RA.
259 13 8 10 12 216 0000
257 9
3 4
GENERATOR 3
VOLTAGE
W..01SING
RELAY
POWER
FACTOR
METER
4M WATT
METER
461 TEST SWITCH 1 011/1
FOR CONTACTS
SEE SEP Ho 00 r., 110
GEM Ydri
I52 12006 0.5-1-0.5
4 206 216
CT3 9 7 09 23 259 229 249 229
2 !1 258 I 228 5 248 4 2 216 238
• —cV9—• 4 04 03 4 4A2 247 2 > 0 217 217 227 227 237 257
LO" o 213 [
LI L2 L3 N
?-5)- (?)
211 212 213 295
[3 6 1 8 211 a 3 29 31 33 35
211 295 211 2 2 213 295 AI 212 1 3 295
295 VOLTMETER
vm
0-5250 Sc
150V RA
P1
P2
211 211 201 211
212 212 202 212
7 213 213 203 213 PT-3
B SA SA SA 295 295 295
3 4
(LP
ARB (MOUNTED AT GENERATOR)
CURRENT
TRA20FCRoDIR
DiORTHIG BLOCK 288 288
40-2 40-2
28-2 28-2
F11
212 211 FREQUENCY METER
55-
HZ
CTSB
0 212 5 r, BA
24VDC
POWER
CCCT
10" 211 6
DROOP RES
DIGITAL
VOLTAGE
REGULATOR
SYNC CHECK
RELAY 282
VOLTAGE REGULATOR ALARM
RELAY (DE-ENERGIZED ON ALARM)
F1 40 I 22 I s 6 ss
0 0 0 242 SS 2 02 • 10 F2 212 FROM BUS o VOLTAGE REGULATOR FAULT
RELAY (DE-ENERGIZED ON FAULT)
F2 3 7705-524'
11 243 244
211 211 10 26 50
BR
OA BC
GENERATOR 3
800 KW, 0.8 PF.
4160 Y. 30
60 HZ
139 FLA
POTI
N I' s 0;1.1
6 VOLTAGE
SENSING: 125-249V
VOLT BIAS
TO DSLC-2
4, TO BREAKER CONTROL
SCHEMATIC
7705-5430-0
30 45
CURMENT
ITUNSFORIAER
SNORTe. FROCK 21 222 223 220 else
CT-7
NQ
1. FOR GENERAL WIRING & CONSTRUCTION NOTES, SEE DRAWING No. 7705-3101-
CT-8
12-19-13 AS INSTALLED
SUBMITTAL 10-16-13 CT -9 A
GENERATOR
PROTECTIVE
RELAY
DESCRIPTION DATE REV.
SHDR110 KC. SHOOMNG ELM
CTSB CTSB-2
I 267 I PURCHASE ORDER No. 1136C05P0W-03 CONTROLLED POWER JON No DEBI
TITLE GENERATOR 3 AC THREE LINE. SCHEMATIC DIAGRAM
CT
y LJ
1-12 ARC.
DWN. BY: TRT DATE: 10-16-13 SCALE: NONE
CKD. BY: DB SHEET: 1 OF 1 DWG. No: 7705-5230-D (EXISTING UNIT)
JOB: BURTON CONSTRUC110N INC., VA PUGET SOUND HEALTHCARE
NOTICE
THE DRAVARDS, 1.020011.1 AND SUEttEDT VATTER HEREOF
ARE THE CD.2100111., SOU .0 DMUS. PROPERTY
OF CONIRWED PONER. NC. AND ARE tiOT TORE COP..
REPRODULED OR USED 0 MY UAW. FOR ANY PURPOSE
WHATDDEVER 0120.11 RATTER 0010111 OR MEMO!,
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. SE. SUITE #102
BOTHELL. WASHINGTON 98012 USA
PHONE: (425)-485-1778, FAX: (425)-485-0658
http://www.contraedpower;nc.com L igi1111 4.11.0 99A411
Plot Hate: 2013/12/
2 MASTER SYNCHRONIZING
AND LOAD CONTROL
C)— 69 cp— A98
ASS 05— AS
OWN. BY: TRT DATE: 10-16-13 SCALE: NONE
CKO. BY: DLB SHEET: 1 OF 1 DWG. No: 7705-5240-D
II215R
XIS
1/2.195.
SS-63 HZ
1200 RA
FOR MM...
SEE 41MI N.
022E28 5/2513
FOR /CIE
II! SW N.
L L/N
-C1)-
601 6-95
L1 L2 L3 N
501 603
602 1 6-95
4 3
5 6 7 8 =
601 I 603
607 I 6-95
TO UTILITY SOURCE 2 prs
7705-5241-5
12-19-13
10-27-13
A 10-16-13
REV. DATE
24 VDC MASTER POWER
BREAKER CLOSE
RELAY
BREAKER OPEN
RELAY
(2
UAM
D089
R o ni '----- 00090C., 0090
0093 00
:i
992: 5092
0094 00094e
BUS 2 POTENTIAL
395 7705-5241-0
UTILITY 2 WRIT( 2 UTILITY 2 UTILITY 2
VOLT VOLTAGE SENSING FREQUENCY FREQUENCY
METER RELAY SENSING RELAY METER
1)2- FIB
0-S250 SC.
1. RA
LT Tn
601 6-95
NOTICE
THE DRAVANGS. RiFORDADON ARO NN PCT NATTER HEREOF
ARE THE COHNDENTIAL, 501£ ENCLUSINE PROM,
OF CONTROLLED POWER. INC. AND ARE NOT TO BE COPED,
REPRODUCED OR USED IN ANY WANNER FOR ANT PURPOSE
WHATSOEVER 015005 0161140 CONSENT OR DIRECTION
'la
UllUTY 2 BREAKER
CLOSE CIRCUIT
umny 1 BREAKER
OPEN CIRCUIT
U1 OSR
U2OSR
UTILITY 2 BREAKER
OPEN CIRCUIT
6151lik
1. FOR GENERAL WIRING & CONSTRUCTION NOTES, SEE DRAWING No. 7705-3101-I
AS INSTALLED
CORRECT MSLC-2 TERMINAL NUMBERS
SUBMITTAL
DESCRIPTION
PURCHASE ORDER No. 1136CONPOW-03 CONTROLLED POWER 308 Nc
TITLE MASTER SYNCHRONIZING & LOAD CONTROL, SCHEMATIC DIA(
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.C. SUITE #102
BOTHELL, WASHINGTON 98012 USA
PHONE: (425)-485-1778, FAX: (425)-485-0658
http://www.controlledpowerinc.com
Plot dote: 2013/12/
RUN
U-UNLOAD
SF-RAISE
SP-LOWER
V-RAISE
V-LOWER
"0
FROM PLC OUTPUTS
IN MASTER SECTION
7705-5343-0
TO UTILITY 1 CTS
7705-5241-0
6D8
281 2112
247 695
608 695
609 2111 2112 -0 0
SA
TO UTIUTY 2 CTS
7705-5241-0
AUXILIARY AUXILIARY AUXILIARY
CURRENT CURRENT CURRENT
TRANSFORMER TRANSFORMER TRANSFORMER
Ised 61XCI CXCI 25A-1
BA
5, 5.5 ra 5, 5.5
WE
5, 5.5
CURRENT
TRA.NSFORYOR
S7CLITND
CTSB
507 595
1111 1112 0 0
1111 1112 0 0
161 -21 595
501 5-95
L L/N
501 5-95
25A-2
ONARENT
INANDNINER
NNIRTPD LUC.
CTSB
254-3 caw, 11LL BLOCH
CTSB
UTILITY 1 UTILITY 1 UTILITY 1 UTILITY 1
FREQUENCY VOLTAGE SENSING FREQUENCY VOLT
METER RELAY SENSING RELAY METER
LLIoIM U1VSR UIEDR
SS-6.1
120/ roe MOW'S FM CORMS FOR 00.11/CIS SEE SW W. SEF ft. SI SW NI.
1151 05. 02)69 NH CA 0 4 a (0)69
5 6 7 8 = ? 0 ? 0
501 503
502 5-95
100 sgs
TO UTILITY SOURCE 1
7705-5241-0
U2SX
I 0
1512 602
,o
1513 0 0 603
7 1 11
1595 6-95
08 07 706
06 05 706
04 03 706
29 31 33 35
1511 1513 1512 1295
UTILITY 1 BREAKER
CLOSE CIRCUIT
cp— ATE
U1CR
510 5
.1
--- 112 -HOLD
U2CSR U2
CR
g? 520 521
A7E d>.-ATB 1 1 m U1CSR 1.11CSR
*9 505
UBCR
TO SUBSTATION
SOURCE 1
OA or--) : '! AC
TO SUBSTATION
SOURCE 1
MA MB MC
TO MASTER
SECTION
SYNCHRONIZING
7705-5240-13
TO UTILITY SECTION
METERING & RELAYING
(BY CUTLER HAMMER)
— — — OA
TO GEN 1, 2 & 3
MANUAL SYNC
SCOPE & DSLC-2
7705-5210, 5220, &
TO MAIN BUS 2
METERING & RELATING
(BY CUTLER HAMMER)
BUS 2 POTENTIAL
TO MSLC-2
7705-5240-0
TO OTHER FEEDERS & LOADS
(SEE CUTLER-HAMMER DWG No. )
TO GENERATOR 3
7705-5230-0
Plot dote: 201 3/1 2/
-c) BA 7 TO MASTER
SECTION
SW4CHRONIZING
7705-5240-0 r — — — 1-) • 8
UTILITY 1
PT-1
I
LIZII.C
.B
F I 0 ....17-1r _________= 2917 -11=Ill g_zil II :6;
, OA
4F F :
\ 2Vle
I
I0 PT
-2, I I
PT-3 9 2019
9 — N 26 26
II 4
1VI8 6
' 1111
PT-3
TO UTILITY SECTION
METERING & RELATING
(BY CUTLER HAMMER)
F 1V1 B 6
(.)AC -0
x2
IVO 6 F) N
351 35:
52....la
12D0A, 5KV
— VACUUM CIRCUIT
BREAKER, 250MVA
22=02
12008, 5XV
VACUUM CIRCUIT
BREAKER. 250MVA
CuM:01 CoRRENT
IRANSFCRAER
9.ORTNO
CTSB
SrORTM SOX
CUB CTS8
F - 1 Cl
1-#C31 y 0A
1- 1 2-AC31
,./ OA 0A(r)
TO UTILITY SECTION
mB METERING & RELAYING MIL)
(BY CUTLER HAMMER)
0A,( ) 0
1 TO UTIUTY SECTION
, 03 METERING & RELAYING089)
`. (BY CUTLER HAMMER)
I
9 0C oC,)
2-AC32
I
1-AC32
019 TO MASTER
SECTION
ASS crs 7705-5240-D
70 MASTER
SECTION
ASS crs 7705-5240-0
2-AC33 1.) BC
1-8C33 oC 00 •c
2-AC10 _c) N
1-AC10 y
395 )
3 BUS BUS 1
:mom.
PT-1
F
II
TO MAIN BUS 1
METERING & RELAYING
(BY CUTLER HAMMER)
2.22.1
VACUUM CIRCUIT
BREAKER, 250MVA
5KV, 1200A, MAIN BUS 1 5KV, 1200A, MAIN BUS 2
I rt, oA OR oc OA MB 0C
NOTE.
1. FOR GENERAL WRING & CONSTRUCTION NOTES, SEE DRAWING No. 7705-3101-1 oA oe oc
0 OTHER FEEDERS & LOADS
(SEE CUTLER-HAMMER DWG No.
oA MB oc
TO GENERATOR 1
7705-5210-6
RA MB
TO GENERATOR 2
7705-5220-D
12-19-13 AS INSTALLED
SUBMITTAL 10-16-13 A
DESCRIPTION DATE REV.
PURCHASE ORDER No 1136CONPOW-03 CONTROLLED POWER JOB 1:1, TITLE MAIN BUS & UTILITY AC THREE LINE, SCHEMATIC DIAGRAM
DWN. BY: TRT DATE: 10-16-13 SCALE: NONE
CIO. BY: DB SHEET: 1 OF 1 DWG. No: 7705-5241-0
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
NOTICE
THE CRAYANOS, INfORMAIICN AND SUBJECT 1IATIER HEREOF ARE DiE CONFIDENRAL SO. EXCLUSivE PROPERTY
OF CONTROLLED POACH. NC.. AND ARE NOT TO BE COPED.
REPRe.it, OR USED N ANY LOANER FOR ANT PURPOSE
WHATSOEVER WTHDUT WITTEN CONSENT CR OREM..
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.E. SUITE #102
BOTHELL. WASHINGTON 98012 USA
PHONE: (425)-485-1778, FAX: (425)-485-0658
http: //www.controlledpowerinc.torn
SI
2 GENERATOR 1 2490C SUPPLY
8-
1;1128 CONTINUED FROM LOWER LEFT
24 A
ECS1 GlSRR
9 • I I ? oUlt0o)
8641 E1FR
72 726
• • 54
G1CPFR
(24
E1FR
E1FRX
E1RR
G1CR
AUTO START
RELAY
TRIP AUG
RELAY
GEN RUNNING
RELAY
RUN
RELAY
AUTO
RELAY
40 7 EMCP 3.3 PANEL
AT ENGINE/GENERATOR
CONTROL POWER FAIL
RELAY
GSC 77
01658 G1VSR G1FSR G1FSR
° I ° 74 9 9 (0.176 9 I I , 76 it la (0,ER)
(v..)
(29.0 86
ENGINE FAULT
RELAY
RO5
9 ENGINE
FAULT
49 49 28
ENGINE FAULT
RELAY AUG.
(24vac)
UlTOLTD so U1T1R 85 4
RO6
ENGINE fa_
RUNNING
RANGE 0-30 28 2 UNIT 1 TEST ONLINE TIMER
TIME DELAY PICK UP SET 0 30
INOTES
NOTES
ENGINE RUN 64
RELAY
(2900C
G1SIR
GPR1/R3
81 28 GEN 1 START INHIBIT
GOVERNOR CONTROL
RELAY
66 RELAY
ES
2A
DIGITAL SYNCHRONIZER
& LOADING CONTROLLER
pac-2, 64 40
ENGINE
SHUTOFF
4 28
4C!
00375 28
DRS
SNARE BASELOAD
00375 so
00375
DI2
ENGINE START ID_
AND RUN
187 7c6
, L.0 , 2
188 67 0 cwto, 40 J_ o 187
SU
SS 193 BUS
01 • 0 • 10
UIRR
0„,,,) 32 33
G1RR
00369
D 1 1 0
00369 RH 00369
00370 00370 71
00370 7
GOB 74
a_L_o 003710
Al
TO PLC OUTPUTS
7705-5311-0
00371
2896 48
BREAKER OPEN
RELAY
BREAKER CLOSE
RELAY
0 TO MASTER DC CONTROL
7705-5340-0
CONDMJED ON GRAINS No 7705-5311-D UNE No. 2
NOTE:
1. FOR GENERAL WIRING & CONSTRUCTION NOTES, SEE DRAWING No. 7705-3101-1
12-19-13
10-27-13
10-16-13
AS INSTALLED
CORRECT 0SLC-2 TERMINAL NUMBERS
SUBMITTAL A
DESCRIPTION DATE REV.
PURCHASE ORDER No. 1136CONPOW-03 CONTROLLED POWER JOB N, TITLE GENERATOR 1 DC CONROL, SCHEMATIC DIAGRAM
OWN. BY: TRT DATE: 10-16-13 SCALE: NONE
CKD. BY: DLB SHEET: 1 OF 1 DWG, No: 7705-5310-D
CONTINUED AT UPPER RIGHT
28 JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY SE. SUITE #102
BOT1IELL WASHINGTON 98012 USA
PHONE: (425)-485-1778, FAX: (425)-485-0658
http://www.controlledpowerinc.corn
• LAI *ii* 100
NOTICE
THE ORAI.miDS. INFORMARCN AND SUB-COT mATTER HEREOF ARE BiE ODNFIDENTIAL, SOLE AND FM:UMW PROPERTY OF CONTR.]. PO.R, ft.C. AND ARE NOT TO BE COPIED, REPRODUCED OR OS. IN ANY MANNER FOR ANy PuRPOSE wHATSCEvER vATHOoT vii,TTEN CONSENT OR ORECTIC.N
( 4)
CONTINUED FROM LOWER LEFT 2 CONTINUED FROM DRAWING No. 7705-5310-0 LINE No.
24VDC DISCRETE OUTPUT MODULE
PART No. ICS93ADL740 RACK No. 4, SLOT No. 3
24VDC DISCRETE INPUT MODULE
PART No. IC69311110L845
RACK 4, SLOT No. 1
ADDRESS
GENERATOR 1
ANNUNaATOR 4
ADDREsa
GIASR 28
4 28
00345
00346
00347
00349
00350
00351
00352
00353
00354
00355
00356
00357
00358
00359
00360
10161
10 0 ENGINE START 02 510161
EIRR
ENGINE RUNNING
10162 olio ENGINE START COMMAND
LIGHT
20 03 810162 X 00345
X 90346
00347
X 00348
% 00349
X 00350
X 00351
X 00352
12 •
ENGINE RUNNING
LIGHT
CATERPILLAR 010 MODULE
234-0275
LOW COOLANT TEMP ALARM
LIGHT
40 40 HIGH COOLANT TEMP ALARM
LIGHT Nee
CAN24,_
1D1T T I
CAN2-1 I 119
HIGH COOLANT TEMP TRIP
LIGHT
EMCP 3.3
J1939 CAN 2 BUS D-, y cA,r,4 L 2 ,d_
• 11
LOW al PRESSURE ALARM
LIGHT
LOW at. PRESSURE TRIP
UGHT
10163 SPN - 110 GEN 1 LOW WATER
ETA' - 17 TEMPERATURE WARNING
OVER CRANK
LIGHT
04 8 10163
X 10164
X 10165
X 10166
OR 8 )0167
OH 510168
0 10 5 10169
0 11 8)0170
10164 SPN - 110 GEN 1 1110-1 WATER
FBI - 15 TEMPERATURE WARNING
20 0 05
10165 SPN - 110 GEN 1 8I0-1 WATER
FBI - 0 TEMPERATURE SHUTOFF
OVER SPEED
LIGHT
06 X 00353
X 00354
X 00355
X 00356
X 00357
X 00358
X 00359
X 00360
10166 SPN - 100 GEN 1 SHE LOW CIL
FBI - 17 PRESSURE WARNING 0 1
C-.1 MO-1 37
UNIT NOT IN AUTO
LIGHT
07 1
10167 100 GEN 1 LOW OIL
1 PRESSURE SHUTOFF
SPN -
FBI -
ENGINE CONTROL PANEL FAILURE
LIGHT C-5 NO-5 10
10168 SPN - 1664 GEN 1 OVERCRANK
SHUTOFF
ENGINE FAULT
LIGHT
C-6 NO-6 20 FBI- 31
10169 SPN -
FBI -
190 GEN 1 OVERSPEED
0 SHUTOFF < 0 1
29 C-7 N.0
UNIT LOCKOUT
LIGHT
10170 SPN- ?
FBI -
NOT IN AUTO (SPARE)
UGHT
1 70
LOW FUEL LEVEL ALARM
UGHT
1 71
40 10171
BATTERY CHARGER ALARM
LIGHT
1 0 12 X 10171
0 13 X 10172
0 14 X 10173
0 15 X 10174
0 16 X 10175
0 17 X 10176
E1FR
40 10172
ENGINE FAULT
VOLTAGE REGULATOR ALARM
VOLTAGE REGULATOR FAILURE
BREAKER MODE AUTO
ENGINE CONTORL SWITCH AUTO
BRIAR
40 10173 24VDC DISCRETE OUTPUT MODULE
PART No. ICS931AD4.740 RACK No, 4, SLOT No. 4
0 1 0
WIER
40 10174
0 1 1 0 9 5 ANNIFcS
BMS
I 10400)
40 28 10175 10 0
ECS
° I I 0 (04101 31 35
00361
00362
00363
00364
00365
00366
00367
00368
40 10176 (SPARE)
LIGHT
X 00361
X 00362
X 00363
X 00364
X 00365
X 00366
X 00367
X 00368 aa
(SPARE)
LIGHT
(SPARE)
LIGHT
PROTECTIVE RELAY ALARM
LIGHT
24VDC DISCRETE INPUT MODULE
PART No. IC693MDL646
RACK 4, SLOT No. 2
ADDRESS
PROTECTIVE RELAY TRIP
LIGHT
ENGINE LOCKOUT
10177 PROTECTIVE RELAY FAILURE
UGHT
02 8 10177
X 10178
4 X 10179
5 X 10180
X 10181
07 8 )0182
0 8 5 )0183
0 9 5)8184
010 510185
0 11 X 10186
0 12 X 10187
013 510188
0 14 5 10189
015 8 10190
0 16 X 10191
0 17 X 10192
LOW FUEL LEVEL ALARM
€ 1 03 3
VOLTAGE REGULATOR ALARM
LEL 10179
_75_ VOLTAGE REGULATOR FAILURE
UGHT
RCA
_ 0_
BATTERY CHARGER ALARM 0--(3-4° -OH I-0-
1220_
13 0
14 0
40 0 . _____ 11 181
10182
10183
GPR1/R5
40 0184
GPR1/R4
10185
00369
RUN
PF CONTROL
LOAD/UNLOAD
GEN 1 START/RUN
X 00369
X 00370
00371
X 00372
00373
00374
X 00375
X 00376
00370 0 DSLC-2
00371
NOTE.
I. FOR GENERAL WIRING A CONSTRUCTION NOTES. SEE DRAWING No. 7705-310
PROTECTIVE RELAY ALARM
PROTECTIVE RELAY TRIP
PROTECTIVE RELAY FAILURE
RELAY
UNIT 1 TEST TIMING
RELAY
GPR1/R6
10186
VOLTAGE REGULATOR 1
FAILURE RELAY AUG AS INSTALLED
SUBMITTAL
12-19-13
BASE LOAD MODE 10-16-13 A
DESCRIPTION DATE REV. 28 00376
GEN 1 EXCITATION DISABLE
RELAY PURCHASE ORDER No. 1136CONPOW-03 CONTROLLED POWER J08 No
TITLE GENERATOR 1 DC CONTROL, SCHEMATIC DIAGRAM
LIB
ARB
4 10190
LAMP TEST
HORN SILENCE
ALARM RESET
HSB DWN. BY: TRT DATE: 10-16-13 SCALE: NONE
4 10191
CONTINUED ON DRAWING No. 7705-531
CKD. BY: DLB SHEET: 1 OF 1 DWG. No: 7705-5311-D 40 (+) 4 10192 0
L _
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
NOTICE
DiE DRAM.. INIFORIOATION ARO soexct 1AATIER HEREOF
ARE TOE COWDEN'', SOLE ARO EXCLUSVE PROPERTY
OF CONTROLLED PO., INC.. AND ARE NOT TO RE COPED,
REPROX10,0 OR USED iN ANT MANNER FOR ANY PURPOSE VeriAlSOBER WHO, WRITTEN CONSENT CR DREClION.
r1111111 Ligi1111 44‘•
10,19IF
Controlled Power, Inc.
17909 BOTHELL EvERETT HWY. SE. SLATE #102
BOTHELL, WASHINGTON 98012 USA
PHONE: (425)-485-1778. FAX: (425)-485-0658
htto://www.controdedpowerinc.00rn
CONTINUED AT UPPER RIO-IT
40 28 twEN.o.
(-1 (4)
28 GENERATOR 2 24VDC SUPPLY 2
AUTO START
RELAY
TRIP AUG
RELAY
GUN RUNNING
RELAY
RUN
RELAY
AUTO
RELAY
24 ±
-1711 F13
(05e)
G2CPER
a CONTROL POWER FAIL
RELAY
AUTO START
ENGINE SHUTDOWN
7 EMCP-II PANEL
AT ENGINE/GENERATOR
8 GSC
33 57
START 0-111-
INPUT
23 SP1
SHUTDOWN 0-11I-
INPUT To.
62 12 494.0
U2TOLTD
63 13
E2RR
6 28
U2TTR
? I
28 UNIT 2 TEST ONLINE TIMER RANGE 0-30 MINUTES BO
T 0 30 MINUTES
40 RA4-16
CRANK
TERMINATE
OUTPUT
ENGINE RUN
RELAY
TIME DELAY PICK UP 64 14
CAR2/R3
8 GEN 2 START INHIBIT
RELAY
68-22 6 16 FAULT fp—EY
OUTPUT
ENGINE FAULT
RELAY DIGITAL SYNCHRONIZER
& LOADING CONTROLLER
40 163
(04
17 DC-2
0 0 ENGINE FAULT
RELAY AUG.
66 28
48 1 28
88 28
(.) 08' 4' attia N. BASELOAD
00143
— T3
763 00143 40 RU-24
20 RUN 0-0--
OUTPUT
GOVERNOR CONTROL
RELAY LINER LCS
NI/ ,86
(5 1- 73 1 0008
_L 13 17
SS
a 186 g 40
187 7c! 40
° Ni "3
S116
RELAY BOARD ASSY BMS 67 188 40 8 n 18
CIM
RELAY
R1-R9
23 DATA LINK
'2U2RR
00137 I 9
? 1
19 40 40 28 12 a) 24
00137
, 013, 71 0 yeTis
<, 00137
PLC
LOW COOLANT
TEMP ALARM
00138 R9 76
TO PLC OUTPUTS
SHEET No. (9) C4 001, 8 72
0 .99
00139X 74 0 ref.
GUB
G2ORX
0 - J4, 0
I "
PLC
LOW OIL
PRESS ALARM
00139
189A
BREAKER OPEN
RELAY
RUM 29
190 29
RELAY
DRIVER
MODULE
50 BREAKER CLOSE
RELAY
PLC
SYSTEM NOT
IN AUTO
11 12 30
67 51 0258 (1) 3 2 31 5202/8
91 40
?<° 1-".>> 8)
31:12 32
PLC
HIGH COOLANT
TEMP FAULT
53 TEMPORARILY
JUMPER FOR LOCAL
RELAY LAMP TEST
(1) R6 5 411) a)
ED12 34
JUMPER TO
DISABLE EMCP II
RELAY LAMP TEST
PUSH BUTTON
2-28 2-40 55 TO MASTER DC CONTROL
7705-5240-0
PLC
LOW OIL
PRESS FAULT
(D11 35
5 56 0 10 9 36 28 40
(4)
CD 9 37
PLC
OVERCRANK
FAULT
se 88 (D 8 R4
NOTE:
1. FOR GENERAL WRING & CONSTRUCTION NOTES. SEE DRAWING No. 7705-3101-
1:17 7 121:17 39
60 PLC
OVERSPEED
FAULT
CD 6 13 (D 40
co, 5
R3 12-19-13 AS INSTALLED
CORRECT DSLC-2 TERMINAL NUMBERS
SUBMITTAL
14 (1) 41
10-27-13
10-16-13 A 92 42
DESCRIPTION REV. DATE PLC
HIGH COOLANT
TEMP ALARM
93 PURCHASE ORDER No. 1136CONPOW-03 CONTROLLED POWER JOB Nc 43 R2
TITLE GENERATOR 2 DC CONTROL, SCHEMATIC DIAGRAM
PLC
EMCP II
FAULT
OWN. BY: TRT DATE: 10-16-13 SCALE: NONE
96 46 CKD. BY: DB SHEET: 1 OF 1 DWG. No: 7705-5320-0
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
48 CONTINUED AT UPPER RIGHT
NOTICE
THE DRAWN.. INFORPARON SUPECT MATTER HEREOF
ARE DIE CONPOENTI.I. SOU AND ExCLUSVE FROPERTY Of CONIROUED INC, AND ARE NOT TO BE COPED.
REPRODUCED CD USED IN *81 088500 FOR ANY PURPOSE
RHATSOEVER RIPOUT 09,T1E5 0005058 (80 OREODON.
IM
LI II
Controlled Power, Inc.
17909 BOTHELL EWRETT HWY. SE. SUITE #102
BOTHELL. WASHINGTON 98012 USA
PHONE: (425)-485-1778. FAX. (425)-485-0658
Otto: thtww.COntrolledpowerinc.COm
99 49
100 50
Ott
24VDC DISCRETE OUTPUT MODULE
PART No. IC093MOL740 RACK No. 2, SLOT No. 3
GENERATOR 2
ANN 980 ATOR 24VDC DISCRETE INPUT MODULE
PART No. 1C693MDI.845 RACK 2, SLOT No. 1
ADORFG4
ADDRFs9
10 0
G2ASR
II?
2 10065 00113
90114
00115
00116
00117
00118
00119
00120
00121
00122
00123
00124
00125
00126
00127
00128 o ENGINE START
7 ENGINE RUNNING
8 LOW COOLANT TEMP ALARM
9 HIGH COOLANT TEMP ALARM •
10 HIGH COOLANT TEMP FAULT
it LOW OIL PRESSURE ALARM
12 LOW OIL PRESSURE FAULT
13 OVERCRANK ALARM
14 OVERSPEED FAULT
15 ENGINE NOT IN AUTO ALARM
16 ENGINE CONTROL PANEL FAULT
17 ENGINE FAULT
18 VOLTAGE REGULATOR ALARM
19 VOLTAGE REGULATOR FAILURE
ENGINE START COMMAND
LIGHT
02 0I0065
03 010066
O 4 010067
O 5 010068
O 6 010069
O 7 X 10070
O R 010071
OH 010072
010 0 10073
Oil 010074
012 010075
013 010076
014 010077
015 010078
016 010079
0 17 0 10080
X 00113
X 00114
X 00115
00116
X 00117
X 00118
X 00119
X 00120
E2RR 28
ENGINE RUNNING
40 10066
12 8 LIGHT
LCTA
28 40 10067 olio LOW COOLANT TEMP ALARM
LIGHT
HCTA
011 0 34 25
28 10068
HIGH COOLANT TEMP ALARM
LIGHT
HCTF
40 28
II 22 23
HIGH COOLANT TEMP TRIP
LIGHT
LOW OIL PRESSURE ALARM
LIGHT
LOW OIL PRESSURE TRIP
LOPA
40 10070
(Hi 0 .1 .7
LOPE
II ° 25 26
so 10071
UGHT
40 28
OVERCRANK
LIGHT
10072
OS
I I
SNA
II
28 40 10073 20 0
28 40 10074
OVERSPEED
LIGHT
00121
X 00122
X 00123
X 00124
O 00125
O 00126
O 00127
X 00128
EMCPF
0 11 0 I 37 38
40 28
10075
UNIT NOT IN AUTO
UGHT
E2FR
40 10076
ENGINE CONTROL PANEL FAILURE
LIGHT 10 6
VR2AR
40 0 11 0 ENGINE FAULT
LIGHT 2 5
VR2FR
? I1 ?
10078
UNIT LOCKOUT
LIGHT
20 BREAKER MODE AUTO
10079 0 I
ECS
i 2 (1111)
(SPARE)
LIGHT (-101 70
21 ENGINE CONTORL SWITCH AUTO
10080
LOW FUEL LEVEL ALARM
LIGHT
BATTERY CHARGER ALARM
LIGHT
28 ENGINE LOCKOUT
24VDC DISCRETE OUTPUT MODULE
PART No. ICS93MDL740 RACK No. 2, SLOT No. 4
ADORER%
24VDC DISCRETE INPUT MODULE
PART No. IC603111DL646
RACK 2, SLOT No. 2
ADDRF%
00129
(SPARE)
LIGHT
X 00129
X 00130
00131
X 00132
X 00133
X 00134
0 00135
X 00136
I 0 10081
10082
LFL 10083
—0-2- 00134 0
C7-2-0 °°85
10087
00130
(SPARE)
LIGHT
O 2 010081
1 X 10082
4 010083
5 010084
6 0 10085
7 X 10086 a 010087
09 0 10088
010 0 10089
0 11 % 10090
0 12 %I0091
013 l0092
0 14 0 10093
010 0 10094
0 16 z 10095
017 010096
40 00131
(SPARE)
LIGHT
LOW FUEL LEVEL ALARM
00 32
PROTECTIVE RELAY ALARM
LIGHT
8CA
BATTERY CHARGER ALARM —o -
1 o 00133
PROTECTIVE RELAY TRIP
LIGHT
00134
PROTECTIVE RELAY FAILURE
UGHT
28 00135
VOLTAGE REGULATOR ALARM
LIGHT 24
• VOLTAGE REGULATOR FAILURE
LIGHT
00136 34 84
GPR2/R5
2<<H1--3 ( ,):
GPR2/R4
40 28 10088 28
PROTECTIVE RELAY ALARM
PROTECTIVE RELAY TRIP
PROTEC11VE RELAY FAILURE
20 0
12 0
13 0
40 10089 00137
RUN
PF CONTROL
LOAD/UNLOAD
GEN 2 START/RUN
RELAY
X 00137
X 00138
X 00139
000140
X 00141
X 00142
X 00143
X 00144
GPR2/R6
40 10090 00138 TO OSIC-2 87
00139
02066
28 00140
NOTE;
1. FOR GENERAL WRING & CONSTRUCTION NOTES, SEE DRAWING No. 7705-3101-0
It U2T1R
• UNIT 2 TEST TIMING
LTI3
O 0
VR2FRX RELAY
28 10094 00142
VOLTAGE REGULATOR 2
FAILURE RELAY AUG
LAMP TEST
HORN SILENCE •
ALARM RESET
HSB
0 0
AS INSTALLED
SUBMITTAL
12-19-13
PM) 40 10095 00143 BASE LOAD MODE TO DSLC-2 10-16-13 A 180 92
ARB
O 0
DESCRIPTION DATE REV. 40 10096 00144
PURCHASE ORDER No. 1136C00P0W-03 CONTROLLED POWER JOB Nt
TITLE GENERATOR 2 DC CONTROL, SCHEMATIC DIAGRAM
DWN. BY: TRT DATE: 10-16-13 SCALE: NONE
CKD. BY: DLB 28
(- 1
(A)
SHEET: 1 OF 1 28
DWG. No: 7705-5321-0
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
NOTICE
THE ORMENCS, IWO... AND SUBJECT NATION NEREOP
ARE THE CONE10.11, SOLE ANO EXCLUSYC PROPERTY
Of CONTROLLED POPPER, IND. AND ME Vol 10 60 COP., REPROCOCED OR USED IN ANY LIANMR FCR ANY PURPOSE
EINATSOCY. WPM. WRITER CONSENT OR 0100(004.
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.E. SUITE #102
BOTHEU— WASHINGTON 98012 USA
PHONE: (425)-485-1778. FAG, (425)-485-0658
h1113://www.confrolledpotve6m.com I/ I
404.
l'et
MINIM 8MMOIMM,..
Plot dote, 2013/12/
GENERATOR 3 2451)C SUPPLY
AUTO START
RELAY
TRIP AUG
RELAY
GEN RUNNING
RELAY
RUN
RELAY
AUTO
RELAY
24 54
F13
7 EMCP-II PANEL
AT ENGINE/GENERATOR
G3CPER
40 40 28 CONTROL POWER FAIL
RELAY
AUTO START
ENGINE SHUTDOWN
28 IA
GSC 8
G3ASR
33 57
START
INPUT
28 28
8603 1 28
SHUTDOWN
INPUT
TERIRNAARE<-1 89
OUTPUT
UNIT 3 TEST ONUNE TIMER
11ME DELAY PICK UP ENGINE RUN
RELAY
G3SIR
GPR3/R3
0 I F.
RM-22 6
FAULT 0--E-
OUTPUT
2 81 GEN 3 START INHIBIT
RELAY ENGINE FAULT
RELAY DIGITAL SYNCHRONIZER
& LOADING CONTROLLER
ES
(2401101
40 1 63
DSLC-2
0 0 2 40
ENGINE FAULT
RELAY AUG.
6c, 28 00191 y
BASELOAD
00191
— 763!..z 4c! 28 00191 40
RUN
OUT
0---a
PUT
GOVERNOR CONTROL
RELAY
70 5090/ L.CZ RAGE
40 86
6016R
40 T -1 87 D
68 28 as
RELAY BOARD ASSY
MS
SS TS1-18 90
DATA LINK (11)-1-
n 8 I 40 01 k 32
CIM
RELAY
R1-R9
9, (i)
R
I
00185 40 28
0 I 0 74
00185 6C!1
00186 7( 31
00185
00186
PLC
LOW COOLANT
TEMP ALARM R9
TO PLC OUTPUTS
SHEET No. 84 00186 72
GUB
001878 74 0
G3ORX
trd r) 1 r) o
89A 4c7 ) cenr
90 g
PLC
LOW OIL
PRESS ALARM
00187
ROM BREAKER OPEN
RELAY
RELAY
DRIVER
MODULE
PLC
SYSTEM NOT
IN AUTO
BREAKER CLOSE
RELAY
52G3/o
? <E1
6 70
91 40
PLC
HIGH COOLANT
TEMP FAULT
TEMPORARILY
.A/MPER FOR LOCAL
RELAY LAMP TEST
JUMPER TO
DISABLE EMCP II
RELAY LAMP TEST
PUSH BUTTON
3-28 3-40 3-28 e TO MASTER DC CONTROL e
7705-5340-0
9 a)
10 ED
IT ED
' 3 0
PLC
LOW OIL
PRESS FAULT n, PLC
OVERCRANK
FAULT
NOTE:
1. FOR GENERAL WIRING & CONSTRUCTION NOTES, SEE DRAWING No, 7705-31C 89
PLC
OVERSPEED
FAULT
AS INSTALLED
CORRECT DSLC-2 TERMINAL NUMBERS
SUBMITTAL
12-19-13
10-27-13
10-16-13 A 92
ON
DESCRIPTION PLC
HIGH COOLANT
TEMP ALARM
DATE REV.
PURCHASE ORDER No. 1136CONPOW-03 CONTROLLED POWER JOB N:
TITLE GENERATOR 3 DC CONTROL, SCHEMATIC DIAGRAM
PLC
EMCP II
FAULT
OWN. BY: TRT DATE: 10-16-13 SCALE: NONE
CKD. BY: DLB SHEET: 1 OF 1 DWG. No: 7705-5330-0
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
CONTINUED AT UPPER RIGHT
NOTICE
IRE DRAWINGS, 0109061100 000 SIBJEGT RARER HEREOF
ARE TIE CONFIDEBRAl. 100 0110 EXCLUSVE PROPERTY
OF CONTROLLED POWER. INC. MD ARE NOT TO BE COPED.
REPRODUCED CR USED IN ANY WANNER FOR ANY PURPOSE
WHATSOEVER ARTNIDOT MITTEN CONSENT OR 00E0I100
mita 11.11111
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.E. SUITE #102
BOTHELL, WASHINGTON 98012 USA
PHONE: (425)-485-1778, FAX: (425)-485-0658
http, //www.controlledpowerinc.com
Plot date: 2013/12/
LHIE No
(A)
40 28
24VDC DISCRETE OUTPUT MODULE
PART No. IC1193MDL740 RACK No. 3, SLOT No. 3
6 ENGINE START
7 ENGINE RUNNING
8 LOW COOLANT TEMP ALARM
HIGH COOLANT TEMP ALARM
10 HIGH COOLANT TEMP FAULT
11 LOW OIL PRESSURE ALARM
12 LOW OIL PRESSURE FAULT
13 OVERCRANK ALARM
14 OVERSPEED FAULT
15 ENGINE NOT IN AUTO ALARM
16 ENGINE CONTROL PANEL FAULT
17 ENGINE FAULT
18 VOLTAGE REGULATOR ALARM
19 VOLTAGE REGULATOR FAILURE
20 BREAKER MORE AUTO
21 ENGINE CONT. SWITCH AUTO
24VDC DISCRETE INPUT MODULE
PART No. ICI193MDL645
RACK 3, SLOT No. 1 ADoRrsq GENERATOR 3
ANNUNCIATOR ADDRFeS 28 10113 4
02 810113
03 810114
0 4 810115
05 810116
06 810117
07 810118
0 8 8 10119
09 810120
0 10 X 10121
0 11 X 10122
0 12 X 10123
0 13 X 10124
0 14 X 10125
0 15 X 10126
18 X 10127
17 X 10128
0 1 10
08%1 28
ENGINE START COMMAND
LIGHT
X 00161
X 00162
X 00163
X 00164
X 00165
X 00166
X 00167
X 00168
28 00162
ENGINE RUNNING
UGHT
28 00163
LOW COOLANT TEMP ALARM
LIGHT
59 4
00, 28 00164
HIGH COOLANT TEMP ALARM
LIGHT
00165
HIGH COOLANT TEMP TRIP
LIGHT
LOW OIL PRESSURE ALARM
UGHT
LOW OIL PRESSURE TRIP
UGHT
00168
OVERCRANK
LIGHT
OVER SPEED
LIGHT
P. C0169
X 00170
X 00171
X 00172
X 00173
X 00174
X 00175
0 00176
UNIT NOT IN AUTO
UGHT
ENGINE CONTROL PANEL FAILURE
LIGHT
ENGINE FAULT
LIGHT
00073
00174
00175
00178
UNIT LOCKOUT
LIGHT
16 0 70
(SPARE)
LIGHT
080 LOW FUEL LEVEL ALARM
UGHT
18 0
BATTERY CHARGER ALARM
LIGHT
24VDC DISCRETE OUTPUT MODULE
PART No. IC893MDL740 RACK No. 3, SLOT No. 4
24VDC DISCRETE INPUT MODULE
PART No. 1C693MDL645
RACK 3, SLOT No. 2 miArcs
AfX2.6666 28 28
10 0
(EA WC)
ENGINE LOCKOUT
I 0
10129 0 2 810129
IP
28 (SPARE)
LIGHT
00177 X 00177
X 00178
X 00179
X 00180
X 00181
X 00182
X 00183
X 00184
0_ 101. 00
3 810130
LFL 10131
BCA
4 810131
28 (SPARE)
LIGHT
00178 3 0
28 (SPARE)
LIGHT
LOW FUEL LEVEL ALARM
BATTERY CHARGER ALARM
I 5 X 10132
28 PROTECTIVE RELAY ALARM
LIGHT
(3_____
1(11
6 810133
28 PROTECTIVE RELAY TRIP
LIGHT
28 PROTECTIVE RELAY FAILURE
UGHT
10134 7 810134
• VOLTAGE REGULATOR ALARM 10135
a 8 10135 84 LIGHT
GPR2/R5
10136
PROTECTIVE RELAY ALARM
T7 --/ 1-3 2 0 9 X 10136
GPR2/R4 4 10137
PROTECTIVE RELAY TRIP
1-3 ix) 0 10 % 10137
GPR2/R6
PROTECTIVE RELAY FAILURE 1-36)
10138
0 II 8 10138
10_ 913/_ 0 12 X 10139
(3 10140 013 810140
<-.) 141 014 810141
LTB
28 VOLTAGE REGULATOR FAILURE
UGHT 85
NOTE.
1. FOR GENERAL WIRING & CONSTRUCTION NOTES, SEE DRAWING No. 7705-310 28
RUN
Pr CONTROL
LOAD/UNLOAD
GEN 3 START/RUN
RELAY
X 00185
X 00186
X 00087
X 00188
X 00189
X 00190
X 00191
X 00192
10142 LAMP TEST 0 0 la 10142
UNIT 3 TEST TIMING
RELAY
AS INSTALLED
SUBMITTAL
12-19-13 Et 10143
HORN SILENCE • 0 0 ls 8 10143
ARB
40 _I_ 1014.4
ALARM RESET • 0 0 17 810144
VOLTAGE REGULATOR 3
FAILURE RELAY AUG
10-16-13 A
DESCRIPTION DATE REV, BASE LOAD MODE 00191 .TO DSLC-2 180 PURCHASE ORDER No, 113600NP0W-03 CONTROLLED POWER JOB No
TITLE GENERATOR 3 DC CONTROL, SCHEMATIC DIAGRAM 00192 0
OWN. BY: TRT DATE: 10-16-13 SCALE: NONE
CKD. BY: DLB 28
SHEET: 1 OF 1 DWG. No: 7705-5331-D 28
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
NOTICE
THE ORMAN.. MORN/MON AND SUILECT LIMIER HEREOF
ARE THE CONFIDENTIAL. SOLE MO MAUS. PROPERTY
CF CONTROLLED PRIER. INC. AND ME NOT TO BE 00060.
REPRODUCED OR USED PI ANY WANNER FOR ANY PURPOSE
WHATSOEVER PAINCLIT MITTEN CONSENT CR DIRECTION
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.E. SUITE 4102
BOTHELL, WASHINGTON 98012 USA
PHONE: (425)-485-1778, FAX: (425)-485-0658
http://www.0001FOIIOdPR*orino.0090
PURCHASE ORDER No. 6CONPO -03 CONTROLLED POWER 308 NV
(-0
5-9
CONTINUED FROM 7705 5340-0
24VDC DISCRETE INPUT MODULE
IC693MDL645
RACK 0, SLOT No. 4
MMUS
1000, a
57 UTILITY 1 AUTO MORE 91CD-
'02 X 10001
- 9
10002
03 X 10002
58 UTILITY 1 BREAKER OPEN
02019
10003 I 0
59 UTILITY 1 LOCKED OUT
UNIT 2 START INHIBIT 11I( ID - (:)---9----0 - 1
04 X 10003
5202/ 9 161304
UNIT 2 BREAKER CLOSED
6 OS % 10004
10005
UTILITY 1 OK
G2RR
10006
° 1
-06 X 10005
UNIT 2 DEN RUNNING
UTILITY 2 AUTO MODE
10 6
7 X 10006
10007
UTIUTY 2 BREAKER OPEN
U2TOLTD
0 X 10007
UNIT 2 TEST 111.1EOUT
10008
UTILITY 2 LOCKED OUT
9-
9 11 9 OR 015008
G2CPFR
15 DEN 2 CONTROL POWER
FAILURE
1C009 oIl o
9 5 0 10 010009
66 UTILITY 2 OK
Dl SIR
UNIT 1 START INHIBIT
67 TIE BREAKER AUTO MODE
11 X 10010
-9
5201/o
18 UNIT I BREAKER CLOSED
TIE BREAKER OPEN
(I(E • Is 12 X 10011
10012
G1RR
.0 13 7. 10012
UNIT 1 DEN RUNNING
0 1 1-0 lo 6 14 X 10013
10014 0
SYSTEM MODE AUTO
01101.10
015 010014
22 UNIT 1 TEST T1MEOUT
10015
UllUTY TRANSFER MODE
9 119
61CPER
0 16 0 10015
CLOSE TRANSITION
DEN 1 CONTROL POWER
FAILURE
10016
9 1 19 6 017 015016
24VDC DISCRETE INPUT MODULE
IC6931ADL646 76
RACK 0, SLOT No.
ADORFTYY
10017 10017
0 02 0
10018
6 03 X 10018
53SIR
30 UNIT 3 START INHIBIT
10019
19 6 04 O 10019
31 UNIT CLOSED 3 BREAKER
52133 10020
9<<- 11- )2 OS 7. 10020
10021
03049
06 X 10021
33 RUNNING
10022
UNIT 3 DEN
° 9 1 19 07 X 10022
.(z. )022.___0 8 0 10023
U3TOLID
5 UNIT 3 TEST 11MEOUT
10024
9 5 9 X 10024
6 DEN 3 CONTROL POWER
FAILURE
ea
G3CPER
10025
0 10 X 10025
7 DEN 1 DEMAND LEAD
10026
-c)
0 11 X 10026
38 DEN 2 & 3 DEMAND LEAD
3 10027
LTI3
X 10027
39 10028
39 LAMP TEST
BUTTON
0 0
HSB
0 13 10028
39 10029
HORN SILENCE
0 0
AR
I B
014 X 10029
39 10030
ALARM RESET
0 0-
0 15 X 10030
WS 2
B&S 1 & 2
10031 10031
TEST BUS 2
0 16
39 10032
43 TEST BUS 1 & 2
(3 0 17 X 10032
CONTINUED UPPER RIGHT
39 39
4 98
4 99
10-16 SUB ITTA
ONTINUED AT LOWER LEFT
24VDC DISCRETE INPUT MODULE
ICNI3MDLI:145
RACK 0, SLOT No. 6
UlAM
1003, ADDRESS
-OHIO
% 10033
U152/6
_01 Fc, X 10034
U186
10_ 03 5 4 X 10035
_01 Fa_
10_ 0 ___11/3_06
X 10036
HVU1RR (13),
00.37
X 10037 9!
U2AM
100.3...0
X 101338
U252/0
- OH
% 10039 p I O 9
-OHI O
X I0040
11-0-
_ o _KL .,_ 0(741
TO O 10041
HVU2RR
X 10042
TBAM
-0-H
10_..0 043 12 X 10043
71752/9
% 10044
10_ 00 45 14 Z 10045 1
-0--I 10
X 10046
UTMS 10047
X 10047 9 1 19 OPEN
0 16 fAUF01
Op y am.
10046
113048
0 17
I. FOR GENERAL WIRING & CONSTRUCTION NOTES. SEE DRAWING No. 7705-3101-0
12 9- 3 AS INSTALLED
REV DATE DESCRIPTION
TITLE MASTER DC CONTROL, SCHEMATIC DIAGRAM
SCALE: NONE DATE 10-16-13 OWN. BY: TRT
CONTINUED ON 7705-5342 D
DWG, No: 7705-5341-0 SHEET: 1 OF 1 CKO. BY: DLB 28
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
NOTICE
191E DRAWN., RitORRIAllON ANO SLELIECT NATTER MERV, ARE 111E COWDENTIAL, SCSE AND EXO_USYS PROPERTY
OF CONTROLLED PONCA. P.. AND ARE NOT TO BE COPED.
REPRCOUCE0 OR U4-13 91 ANT MANNER FOR ANY PURPOSE
9NATSO,ER INTHOJT %Ran& C.5E10 OR ORECDON
INI11111
I/ I 41.
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.E. SUITE #102
BOTHELL, WASHINGTON 98012 USA
PHONE: (425)-485-1778. FAX: (425)-485-0658
http://www.controIledpowerinc.corn
28 28
CONTINUED FROM LOWER LEFT CONTINUED FROM 7705 5341 D 2
24VDC DISCRETE OUTPUT MODULE
IC8931ADL740
RACK No. 0, SLOT No. 10
24VDC DISCRETE OUTPUT MODULE
IC893MDL740
RACK No. 0, SLOT No. 8
ADDRESS ADDRESS
28 28 39 39 39 39 28 28
10 100
00033 28
UAMR
00001 28
UTILITY 1 OPEN
RELAY
20 % 00033
% 00034
00035
% 00036
% 00037
00038
% 00039
% 00040
UTIUTY AUTO MODE
RELAY
00301
00002
00003
% 00004
% 00005
% 00006
00007
00008 90
20 0
X 00009 120
00010 130
00011 140
800002 ISO
500013 160
800014 170
00015 080
00016 190
7 3 U CR G2ORX
(44 00030 28 UTILITY I CLOSE
RELAY
• GENERATOR 2 BREAKER OPEN
RELAY AUG U20R 03088
00035
UTILITY 2 OPEN • GENERATOR 3 BREAKER OPEN
RELAY AUG
8206 RELAY
(24 200) 00036 28 UTIUTY 2 CLOSE
RELAY • GENERATOR 1 BREAKER OPEN
RELAY AUG
10 c, 0444621 28 00037
• TIE BREAKER OPEN
'MGR RELAY
FBR
(24 00038 28 TIE BREAKER CLOSE
RELAY • 00 FAULT BEACON
RELAY
G2SX ABR
(24 4201 28 00039 00007 28 GEN 2 SOURCE AUG
RELAY (NOT USED)
00 • ALARM BEACON
RELAY
G3SX
28 (24 00040
GEN 3 SOURCE AUG
RELAY (NOT USED)
• 14
28 28 28 200 15
UISX • 28 00041
UTILITY 1 SOURCE AUG
RELAY
% 00041
% 00042
% 00043
% 00044
% 00045
00046
% 00047
% 00048
• 16 66
U2SX
24 28 00042
• UTIUTY 2 SOURCE AUX
RELAY
1.3 • 17 67
F3CR • .24 02) 28 00043
FEEDER 3 CLOSE 18 t4 F3OR RELAY
(24 28 00044
• FEEDER 3 OPEN
RELAY
LEICSR
(24 1001 28 00045
• UTILITY I CLOSE SELECT
RELAY
16 • 20 UlOSR
(04009 28 02046
• UTILITY 1 OPEN SELECT
RELAY
U2CSR
28 00047
UTILITY 2 CLOSE SELECT
RELAY
18 22
U20SR
UTILITY 2 OPEN SELECT
RELAY
25 75
24VDC DISCRETE OUTPUT MODULE
26 1C8911910L740
RACK No. 0, SLOT No. 9
41 re 4=10 :r .
73:,, 41 .1.( r
FEEDER 5 CLOSE 79
RELAY
I 28
ADDRESS
10 0
2 00017
To Loom--
TO FEEDER 3
CLOSE LOGIC
SHEET No.
F5BCR
15800 2P
% 00017
% 00018
% 00019
% 00020
00021 60
880022 70
500023 80
500024 90
500025 120
00026 1.30
800027 140
00028 150
40029 160
500030 170
00031 180
500032 190
FEEDER 5 OPEN
RELAY
F2BCR F3OR 9B-11
79B-9 1 9
(24 C0019
TO FEEDER 3
OPEN LOGIC
SHEET No.
FEEDER 2 CLOSE
RELAY
F2BOR
(2 ) 00020 28
32 FEEDER 2 OPEN
RELAY
(24
F58R
35 TO FEEDER 5
CLOSE LOGIC
SHEET No.
36 86
28 28
15800
TO FEEDER 5
OPEN LOGIC
SHEET No.
c..), 1 °
All
F28CR
TO FEEDER 2
CLOSE LOGIC
A7A SHEET No.
F2BOR
A9
I TO FEEDER 2 94 I 0 (
OPEN LOGIC
A11 , SHEET No.
1. FOR GENERAL WIRING & CONSTRUCTION NOTES, SEE DRAWING No. 71U5-3101-
12-19-13 AS INSTALLED
SUBMITTAL 10-16-13 42
DESCRIPTION REV. DATE
43 PURCHASE ORDER No. 1136C0NP0W-03 CONTROLLED POWER JOB NI
TITLE MASTER DC CONTROL, SCHEMATIC DIAGRAM
j
OWN. BY: TRT DATE: 10-16-13 SCALE: NONE
CONTINUED ON 7705-5343-0 46
28 CKD. BY: DB SHEET: 1 OF 1 DWG. No: 7705-5342-0
47 CONTINUED UPPER RIGHT
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE 39
Controlled Power, Inc. NOTICE INFORMATICti AND SUBJECT WAIT. HEREC, PAL SOLE MO EXCLUSIVE PROPERTY
PO.R. INC,. 000 ARE NOT 00 00 04000.
OR USED Pi ANT MANNER MR ANT PURPOSE
14TROJT ARMEN CONSENT OR ORECT1ON.
17909 BOTHELL EVERETT HWY. S.E. SUITE #IO2
BOTHELL, WASHINGTON 98012 USA
PHONE: (425)-485-1778, FAX: (425)-485-0658
hltp://www.controlledpowerine.com
50 100
12-19-13 AS INSTALLED
SUBMITTAL
DATE DESCRIPTION
SHEET: 1 OF 1 DWG. No: 7705-5343-D
DATE: 10-16-13 SCALE: NONE
GEN 2 & 3 NOT READY
UGHT
GEN 1 NOT READY
UGHT
SYSTEM NOT IN AUTO
US/IT
LOSS OF UTILITY HV-1
LIGHT
LOSS OF UTILITY HV-2
LJGHT
GEN 2 OR 3 CONTROL POWER FAIL
LIGHT
GEN 1 CONTROL POWER FAIL
US/IT
HORN
PLC FAILURE
RELAY
00065 46.
00069
00066 (MVO ,a, R 4 2
3 0 28
4 0--- 6.----L-----0
000 .0t
5 00068 '$985) xis P /3 28
XI,
6 0
) ,a......,G 7 OW. 00070 28 .
00076
7 /
(24' .) 71 8 00 ITCY
00072 (24496) \ / 0 28
20 0 28 28
00073 4.cx 28
12 0 \ 10
00074 (24WCY W 28
TI/
14 0 00( 84̀ 5 .1i s P .M) 28
/\ 12 (1moc) ; Js. SR
16 0 00077
13 / \
WW1
500080 190
NOV.
1. FOR GENERAL WIRING & CONSTRUCTION NOTES, SEE DRAYANG No. 7705-3101-I
PURCHASE ORDER No. 1136CONPOW-03 CONTROLLED POWER JOB (4(
TITLE MASTER DC CONTROL, SCHEMATIC DIAGRAM
OWN. BY: TRT
JOB: BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
REV.
10-16-13
CKD. BY: DB
NOTICE
WE DRAWN., RSCRIAATION AND 041180 HEREOF
ARE 115E COWOENTIAL. SOU AND EXCLUSIVE PROPERTY
US CCNIRIX.LEO POAER. INC. AND ARE HOT 10 80 CONED
REPRODUCED OR USED ANY MANNER FOR ANY PURPOSE
wrIATSCORR %MOUT AR,TTEN CONSENT OR ORECRON.
MI1111/
•ligiiiIIIII
*TO
*et
ConhlgecliDbmmel; Inc.
17909 BOTHELL EVERETT HWY. Si. SUITE 8102
8061ELL, WASHINGTON 98012 USA
PHONE (425)-485-1778. FAX: (425)-485-0658
http://www.controlledpowerinc.corn
UK
GEN 2 & 3 ON-LOAD 64
US/IT
GEN 1 ON-LOAD
US/IT
TRANSFER TO UTILITY HV-1 ACTIW 67
US/IT
TRANSFER TO UTILITY HV-2 ACTIVE
US/IT
TRANSFER TO UTILITY 99-1 FAILURE 69
UGHT
TRANSFER TO UTILITY HV-2 FAILURE 70
LIGHT
UTILITY LOCKOUT 71
LJGHT
PLC ALARM
US/IT
PLC FAILURE
US/IT
39 28
CONTINUED FROM 7705 5342 D
24VDC DISCRETE OUTPUT MODULE
10693111DL740
RACK No. 1, SLOT NO. 1
A9DRERS
MASTER ANNUNCIATOR PANEL--..„
1/4
00078 (24161)
17 0 15 / \
(2.1901 079 18 0 C/0 0.0 0 l'IXTOC.Is
&lb!, 24VDC DISCRETE OUTPUT MODULE
IC89SIADL740
RACK No. 1, SLOT No. 2
ADDREKS
2 28
(T)
00081 20
5 00082 30
500083 4 0
500084 5 0
00085 60
5 00086 70
580087 80
SC 00088 90
500089 120
500090 130
500091 140
500082 150
800093 160
5 00094 170
X 00095
TO MSLC-2
7705-5240-0
HORN
FROM SHEET (5) F3
00065
X 00066
X 00067
% 00068
X 00069
X 00070
X 00071
X 00072
O TT
X 00073
X 00074
X 00075
X 00076
% 00077
% 00078
X 00079
PLCFR
X 00096
00089 RUN -7
00090 UNLOAD
00091 SET PT-RAISE
00092 SET PT-LOWER e
00093 VOLT RAISE -)
00094 WU LOWER
U2FSR
U1VSR
U2VSR
MF2
FOR
UNE NJ.
GEN 2 GEN 3 GEN 1
2-40 3-40 5-40
VUTRR
(24
HVU2RR
HIGH VOLTAGE
UTILITY I RUNNING
RELAY
28 413 HIGH VOLTAGE
UTILITY 2 RUNNING
RELAY
28 28
NOTE.
I. FOR GENERAL WIRING & CONSTRUCTION NOTES, SEE DRAWING No, 7705-3101—I
420 TBOR 421
TIE BREAKER
OPEN CIRCUIT
A
12-19-13
10-16-13
AS INSTALLED
SUBMITTAL
SE BREAKER TRIP (6 CI 05F
SCALE: NONE DATE 10-16-13 DWN, BY: TRT
DWG. No: 7705-5340-0 SHEET: 1 OF 1 CKD. BY: DLB
GEN 2 GEN 3 GEN I
2-28 3-28 5-28
CONTINUED FROM LOWER LEFT
TO REMOTE ANNUNCIATOR — — —
7705-5351-0
ETHERNET SWITCH 1
NOTICE
TIE ORANNICS. INFORUADON AND SUBJECT NATTER HEREOF
ARE THE CONFIDENNAL DOSE ANIS Exaxsow PROPERTY
OF CONTROUDO PORTF, INC.. AND ARE NOT TO BE °SPRED.
REPRODUCE() OR USED IN AM MANNER FOR ANY PuRPOSE
IIIMATSOEVER WNW, WRITTEN CONSENT OR ',RECD.
Controlled Power, Inc.
17909 BOTHELL EVERETT HWY. S.E. SUITE 8102
BOTHELL. WASHINGTON 98012 USA
PHONE: (425)-485-1778, FAX: (425)-485-0658
http://www.controlleapowerinc.corn
Plot dote: 2013/12/1
1411111111 ihvo
/PE*
RI
U2VSR U2FSR
410 9 4
FSR U1VSR
401 40
21 10871„
ABR
SAT
SRI
SA1 I
BEACON
BEACON
0 AMBER
FAULT
BEACON
ALARM
BEACON
SRI
0 RED
24 IOC FROM GENERATORS 1 — 2 — 3
7705-5310, 5320, 5330-0
125VDC CONTROL POWER
FROM SVATCHGEAR BUS
I 0G
GE FANUC
125 VDC
POWER SUPPLY
RACK 0
GE FANUC
125 VDC
POWER SUPPLY
RACK 1
SE FANUC
125 VDC
POWER SUPPLY
RACK 9
GE FANUC
125 VDC
POWER SUPPLY
BACK 3 _ I
GE FANUC
125 I.EIC
POWER SUPPLY
RASZE...1 _
VII POWER
U2— VM./P
VIA POWER
ETHERNET SWITCH 2
CONTINUED ON 7705-5341—D
XXI BURTON CONSTRUCTION INC., VA PUGET SOUND HEALTHCARE
24VDC
OUTPUT
125VDC
INPUT
125P
TB2-11
125N 125N
125N
U1-91.1/P88
CONTINUED…