This document is a salient characteristics specification for an outdoor hazardous material storage building to be delivered to the 309th Aerospace Maintenance and Regeneration Group (AMARG). The building requirements include external dimensions not to exceed 30' width x 10' height x 10' length, with specified internal working dimensions of 28' x 8'3" x 8'. The structure must be fully assembled prior to shipment and feature a 5' x 6'8" personnel door with 1.5-hour fire rating, a 3' x 5' heavy-duty steel access ramp, R19 insulation, and two-hour rated wall construction.

The building must include comprehensive safety and operational features including: a dry chemical fire suppression system, explosion-proof lighting, liquid spill detection system, climate control system operating between 45-80 degrees, 1,200 CFM exhaust/intake system, Allen Bradley PLC controls, and pre-wired electrical components meeting NEC standards. Additional requirements specify a 10-year warranty, UL listed electrical components, NFPA 30 compliant ventilation, static electricity grounding system, and direct hookup capability to the existing Monaco Fire Alarm System. The structure must be delivered with engineering stamped drawings and owner's manual.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS

For

OUTDOOR HAZARDOUS MATERIAL STORAGE BUILDING

1.0. SCOPE OF EQUIPMENT:

All proposed products shall meet or exceed the following specifications outlined in this Salient Characterizes. All items shall be delivered to the 309th Aerospace Maintenance and Regeneration Group (AMARG) – FOB DESTINATION

1.1. PRODUCT PERFORMANCE SPECIFICATION:

Hazardous Material Storage Building must meet the following minimum specifications:

Hazardous Material Storage Building Build Requirements and Dimensions: Not to Exceed Overall Dimensions

(NTE)

• Hazardous Material Storage Building must be fully Assembled Prior to Shipment.

• Externial Dimensions:

o Width: 29′ (NTE 30′) o Height: 10′ (NTW 10′) o Length: 9′ (NTE 10′)

• Internal Dimensions:

o Working Width: 28′ o Working Height: 8′ 3″ o Working Length: 8′

• Personnel Door Access Arrangement:

o (1) 5′ (W) x 6′ 8″ (H) o 1.5-hour fire rated U.L. classified and labeled.

o Automatic door closure o Keyed locking mechanism.

• Access Ramp:

o (1) 3′ W x 5′ L Ramp o One-piece heavy-duty steel fabrication without welding points, non-corrosive.

o 6:1 ratio run to rise 12″ (H) x 70-1/2″ (L) x 33″ (W) o White polyurethane paint with 2” wide grip tape at 4″ intervals.

Hazardous Material Storage Build Requirements:

• Panel/Frame Construction Finish:

o Interior Finish: Chemical-resistant coating in white, semi-gloss finish.

o Exterior Finish: Weather-resistant coating in champagne (or equal), satin-gloss.

• R19 Insulation.

• Base Design:

o Heavy-duty tube construction.

• Wall Panel Design:

o Two-hour rated construction consisting of ASTM A653.

o Explosion Relief Vent Panels:

Must be designed to release at a maximum internal pressure of 20 PSF.

Each panel shall be weather-stripped and safely hinged to the rear wall.

Explosion relief panel openings must be equipped with security bars and held in place with Factory Mutual Research Corporation (FMRC) approved explosion relief fasteners.

• Roof/Ceiling Design:

o Two-hour rated construction consisting of ASTM A653

• Floor Design:

o Grating shall be 1′ Steel bar grating painted black.

o Floor load: 300 PSF.

• Panel/Frame Construction Material: 18 Gauge Thickness.

• Panel/Frame Construction Support: Formed Steel Structure.

• Light Build/Design:

o Light Quantity: (4) ea.

o Incandescent Explosion Proof Ceiling Mounted Light with

Guard.

• Fire Suppression System Design in Accordance With (IAW)

National Fire Protection Agency (NFPA):

o Dry Chemical Fire Suppression System built and installed.

o Fire Suppression System: Pre-piped prior to shipment.

• Liquid Spill Detection System: explosion proof float switch, vertically mounted microswitch, 10-amp rating - resistive 3-amp, inductive 30 volts.

• Explosion Safety Design: Sidewall (Outdoor).

Hazardous Material Storage Exhaust/Intake Build Requirement:

• Exhaust Ductwork:

o Total Exhaust CFM: 1,200 o Exhaust Duct Building Penetration: Roof.

• Intake Ductwork:

o Total Supply CFM: 1,200.

o Intake Design: Ceiling Plenum.

Hazardous Material Storage Building Climate System:

• Climate Control System shall be a Packaged Unit

• Climate Control System shall operate between 45° and 80°.

• Thermostat Controlled Cooling System:

o 4 ton or manufacture recommendations.

o Condensing pipe must Pre-Piped Prior to Shipment.

• Thermostat Controlled Heating System:

o Emergency Heater (Electric Heat – 19KW or manufacture recommendations) when temperature falls below 50-degree.

Electrical Controls Build Requirement:

• Equipment Control Operation: Insight (Allen Bradley PLC) or equivalent.

• Equipment Pressure Control System: Auto Balance.

• Enclosure Design: Outdoor Rated Enclosure Included (NEMA 4).

• Storage Building Wiring must be Pre-Wired Prior to Shipment.

Safety and Additional Requirements:

• Hazardous Material Storage Building must come with a Structurally Engineering Stamped Drawings.

• Hazardous Material Storage Building must come with an Owner’s Manual.

• Hazardous Material Storage Building must come with a 10-Year warranty.

• All Electrical Components Must Be U.L. Listed and Meet National Electrical Codes (NEC).

• Ventilation System must meet or exceed the minimum requirements of National Fire Protection Agency (NFPA) 30 and the IFC.

• Control Panel Components: National Electrical Manufacturers Association (NEMA).

• Static Electricity Bonding/Grounding System/bar on the Interior wall and exterior grounding connection.

• Fire alarm System Must Direct Hook up to Existing Monaco Fire Alarm System.

SALIENT CHARACTERISTICS
For
OUTDOOR HAZARDOUS MATERIAL STORAGE BUILDING
1.1. PRODUCT PERFORMANCE SPECIFICATION: