Attach-2-Drawings Residence-3.pdf
PDF 2 MB Posted
- Attached to
- INKS DAM NFH REMODEL RESIDENCES #2 & Federal contract opportunity
- Solicitation number
- 140F0220R0043
About this file
This set of construction drawings and specifications is for the remodel of Residence #3 at Inks Dam National Fish Hatchery. The project involves demolishing and replacing plumbing, electrical, and sheetrock systems. Plumbing work includes replacing the potable water distribution and sanitary drainage piping. Electrical work consists of a new service entrance, distribution panel, lighting and power upgrades. Sheetrock demolition and replacement is specified along with new insulation. The drawings provide demolition plans, layouts of new systems, schedules and details. The project is to be completed in accordance with all applicable construction codes.
The related federal contract opportunity is for the remodel of Residences #2 and #3 at Inks Dam NFH. The solicitation is for construction services and is issued by the U.S. Fish and Wildlife Service Region 2. No further details are provided in the opportunity description. The set of construction drawings and specifications provides the technical requirements for the remodel work of Residence #3 to support the federal contracting opportunity.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140F0220R0043_Amd_0001.pdf | ||
| Attach-3-Specifications-Residence-2.pdf | ||
| Attach-7-QTRs-2-Lead Paint Findings.pdf | ||
| Attach-9-DBA Min. Wage Rates.pdf | ||
| Attach-5-Price Sheet.xlsx | XLSX spreadsheet | |
| Attach-8-QTRS-3-Lead Paint Findings.pdf | ||
| Attach-4-Specifications-Residenc-3.pdf | ||
| Attach-1-Drawings-Residence-2.pdf | ||
| Sol_140F0220R0043.pdf | ||
| Attach-6-Past Performance and Clauses.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INKS DAM RESIDENCE #3 REHAB DESIGN
ASSET #: 10006240
RESIDENCE #3
RESIDENCE #2
INDEX OF DRAWINGS
C-1 COVER/INDEX OF DRAWINGS
A-1 FLOOR PLAN
A-2 GYPSUM BOARD AND INSULATION PLAN
P-1 PLUMBING NOTES, SYMBOLS AND DETAILS
P-2 PLUMBING DEMO PLAN
P-3 PLUMBING POTABLE WATER PLAN
P-4 PLUMBING SANITARY DRAIN PLAN
E-1 ELECTRICAL SYMBOLS AND DETAILS
E-2 ELECTRICAL DEMO PLAN
E-3 ELECTRICAL PLAN
E-4 GARAGE PLAN
E-5 ELECTRICAL SCHEDULES
100% DESIGN
SUBMITTAL
JULY 31, 2020
AutoCAD SHX Text
FISH AND WILDLIFE SERVICE
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
REGION 2 DIV. OF INFRASTRUCTURE MANAGEMENT
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET 1 OF
AutoCAD SHX Text
CHECKED:
AutoCAD SHX Text
VICINITY MAP
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
OR
AutoCAD SHX Text
RI
AutoCAD SHX Text
ME
AutoCAD SHX Text
RT
AutoCAD SHX Text
PA
AutoCAD SHX Text
DE
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text
NT
AutoCAD SHX Text
TE
AutoCAD SHX Text
IN
AutoCAD SHX Text E
AutoCAD SHX Text
TH
AutoCAD SHX Text
FISH AND WILDLIFE
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text U.S.
AutoCAD SHX Text
U.S. FISH & WILDLIFE SERVICE
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text
FISH AND WILDLIFE
AutoCAD SHX Text
TH
AutoCAD SHX Text
ME
AutoCAD SHX Text
RT
AutoCAD SHX Text
PA
AutoCAD SHX Text
DE
AutoCAD SHX Text
NT
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text
OR
AutoCAD SHX Text
RI
AutoCAD SHX Text
TE
AutoCAD SHX Text
IN
AutoCAD SHX Text E
AutoCAD SHX Text U.S.
AutoCAD SHX Text
APPROVAL SIGNATURES
AutoCAD SHX Text
ANY PRINT ACCOMPANYING THIS INVITATION TO BID MAY BE A REDUCED
AutoCAD SHX Text
REPRODUCTION OF THE WORKING DRAWINGS. IF LINE BELOW DOES NOT
AutoCAD SHX Text
MEASURE SIX INCHES IN LENGTH, THE INDICATED SCALES ARE TO BE
AutoCAD SHX Text
ADJUSTED ACCORDINGLY.
AutoCAD SHX Text
%%UNOTE TO BIDDERS:%%
AutoCAD SHX Text
REGIONAL ENGINEER
AutoCAD SHX Text
ASS'T. REGIONAL DIR.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROGRAM SUPERVISOR
AutoCAD SHX Text
FACILITIES
AutoCAD SHX Text
SAFETY/IND HYGIENIST
AutoCAD SHX Text
CULTURAL RESOURCES
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
BURNET
AutoCAD SHX Text
TX
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
COVER/INDEX OF DRAWINGS
AutoCAD SHX Text
JKB
AutoCAD SHX Text
ARF
AutoCAD SHX Text
DEW
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text C-1
AutoCAD SHX Text
AutoCAD SHX Text N
KITCHEN
UTILITY
ROOM
MECH
ROOM
OFFICE
BEDROOM #2
BEDROOM #1
CLOSET
CLOSET
CLOSET
BATH
CLOSET
LIVING ROOM
4'-7''
3'-4''
6'-8''
7'-0''
8'-9''
2'-4''
6'-9''
2'-5''
2'-5''
2'-3''
2'-3''
3'-0''
3'-10''
3'-10''
3'-10''
FLOOR PLAN
A-1
BEDROOM #1
GENERAL NOTES:
1. DIMENSIONS SHOWN OF EXISTING WALLS ARE
APPROXIMATE.
2. CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CODES
AND REGULATIONS.
3. ALL GYPSUM BOARD WALLS AND WOOD TRIM SHALL
RECEIVE A PROTECTIVE COATING OF PRIMER AND PAINT
AFTER OTHER WORK IS COMPLETED. REFER TO
SPECIFICATION 099600 PROTECTIVE COATINGS FOR
DETAILS.
4. ALL CEILING HEIGHTS ARE 8'-0".
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
JKB
AutoCAD SHX Text
ARF
AutoCAD SHX Text
EWM
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text A-1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Scale in Feet
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Scale in mm
GYPSUM BOARD AND INSULATION PLAN
A-2
GENERAL NOTES:
1. PRIOR TO ANY ELECTRICAL AND PLUMBING DEMOLITION OR
CONSTRUCTION, ALL INDICATED GYPSUM BOARD MUST BE
DEMOLISHED AND REMOVED FROM RESIDENCE.
2. GYPSUM BOARD AND INSULATION SHALL BE DEMOLISHED
FROM ALL CEILINGS, EXTERIOR WALLS AND PAINTED
INTERIOR WALLS. ALL GYPSUM BOARD AND INSULATION
DEBRIS AND DUST MUST BE REMOVED OFF OF HATCHERY
PROPERTY AND PROPERLY DISPOSED OF PRIOR TO
ELECTRICAL AND PLUMBING CONTRACTORS BEGINNING
WORK.
3. A QUALIFIED ASBESTOS ABATEMENT CONTRACTOR SHALL
BE USED DURING DEMOLITION PHASE FOR PROPER SETUP
AND CONTAINMENT.
4. INSTALL NEW R11 INSULATION ON ALL EXTERIOR WALLS
AND APPLY GYPSUM BOARD. INSTALL NEW GYPSUM BOARD
ON INTERIOR WALLS WHERE REMOVED. INSTALL NEW
GYPSUM BOARD ON CEILINGS. MUD, TAPE,SAND AND PAINT
TO MATCH EXISTING CONDITIONS. PAINT ALL PAINTED
WOOD TRIM. ALL COLORS SHALL BE COORDINATED WITH
THE OWNER PRIOR TO PAINTING.
5. REPAIR OR REPLACE WOOD TRIM THAT IS DAMAGED OR
UNUSABLE.
6. BLOW IN NEW R38 INSULATION IN ATTIC TO A MINIMUM
DEPTH OF THE MANUFACTURES RECOMMENDATIONS..
7. CONTRACTOR SHALL PROTECT EXISTING FLOORING DURING
CONSTRUCTION AND SHALL REPAIR NECESSARY DAMAGES
TO RETURN FLOOR TO CONDITIONS BEFORE
CONSTRUCTION.
8. ALL ELECTRICAL AND PLUMBING DEMOLISHED DEBRIS MUST
BE REMOVED OFF OF HATCHERY PROPERTY AND
PROPERLY DISPOSED OF.
CRAWL SPACE
ACCESS
ATTIC
ACCESS
DEMOLISH CEILING
(TYP IN ENTIRE
RESIDENCE)
RETAIN FANS FOR
RE-INSTALLATION
KNOWN LEAD PAINT AND ASBESTOS LOCATIONS:
1. A LEAD-BASED PAINT INSPECTION WAS COMPLETED IN 2000
AND IDENTIFIED THE FOLLOWING FINDINGS;
a. INTERIOR PAINT WAS FOUND IN "GOOD" CONDITION AND
THE AMOUNT OF LEAD IS INDICATIVE OF 1950S OR EARLY
1960S PAINT.
b. EXTERIOR WOOD PAINT ON THE SOFFIT AND ROOF TRIM OF
THE CARPORT WAS IN "POOR" CONDITION AND CONTAINS
MORE THAN 10SQFT OF LBP.
c. EXTERIOR WOOD PAINT ON THE GABLE, SOFFIT AND ROOF
TRIM OF THE SOUTH SIDE OF THE RESIDENCE WAS IN
"POOR" CONDITION AND CONTAINS MORE THAN 10SQFT OF
LBP.
2. AN ASBESTOS SURVEY WAS COMPLETED IN 1999 AND
IDENTIFIED ASBESTOS IN THE FOLLOWING AREAS:
a. WALL SKIM COAT THROUGHOUT RESIDENCE.
b. MECHANICAL ROOM FLOOR TILE.
c. GARAGE SHINGLES.
3. ALL GYPSUM BOARD ON EXTERIOR WALLS SHALL BE
REMOVED. ALL PAINTED GYPSUM BOARD ON INTERIOR
WALLS SHALL BE REMOVED.
4. MECHANICAL ROOM FLOOR TILE WITH ASBESTOS SHALL
REMAIN IN PLACE AND UNDISTURBED.
5. GARAGE SHINGLES WITH ASBESTOS SHALL REMAIN IN PLACE
AND UNDISTURBED.
KITCHEN
UTILITY
ROOM
MECH
ROOM
OFFICE
BEDROOM #2
BEDROOM #1
CLOSET
CLOSET
CLOSET
BATH
CLOSET
LIVING ROOM
DEMOLITION LEGEND
DEMO ALL MATERIAL ON EXTERIOR WALLS FROM FLOOR TO CEILING IN PREPARATION FOR NEW INSULATION.
DEMO ALL PAINTED GYPSUM BOARD ON INTERIOR WALLS SHALL BE REMOVED.
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
JKB
AutoCAD SHX Text
ARF
AutoCAD SHX Text
EWM
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text A-2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Scale in Feet
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PLUMBING NOTES, SYMBOLS AND DETAILS
P-1
WASTE VENT CW HW
LAVATORY
SINK
3"
EXISTING PLUMBING FIXTURE CONNECTION SCHEDULE
2"
3"
2"
TANK TYPE WATER CLOSET
WC-1
SK-1
LAV-1
BATHTUB
3"BT-1
2"
1-1/2"
1-1/2"
1/2"
1/2"
1/2"
1/2"
1/2" 1/2"
3/4"
NG
POTABLE COLD WATER
POTABLE HOT WATER
POTABLE HOT CIRCULATION WATER
NATURAL GAS
FLOOR CLEANOUT
WALL CLEANOUT
BUTTERFLY VALVE
GLOBE VALVE
BALL VALVE
BACKFLOW PREVENTER
DOWN PIPE
VALVE IN RISER
FLOOR DRAIN
ABBREVIATIONS LEGEND GENERAL PLUMBING NOTES
AFF
CFH
CO
CP
DHWR
DHWS
DS
ECR
ECS
ES/EW
ET
EWC
EWH
FCO
FD
FW
GPM
HB
HWR
HWS
LAV
MSB
NG
PW
RPBFP
SD
SH
SK
THW
TMV
TW
U
UW
VTR
WC
WCO
WH
ABOVE FINISHED FLOOR
CUBIC FEET PER HOUR
CLEAN OUT
CIRCULATING PUMP
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER SUPPLY
DRENCH SHOWER
ENGINE COOLING WATER RETURN
ENGINE COOLING WATER SUPPLY
EMERGENCY SHOWER AND EYE WASH
EXPANSION TANK
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FLOOR CLEAN OUT
FLOOR DRAIN
FIRE PROTECTION WATER
GALLONS PER MINUTE
HOSE BIBB
HOT WATER RETURN
HOT WATER SUPPLY
LAVATORY
MOP SERVICE BASIN
NATURAL GAS
POTABLE WATER
REDUCED PRESSURE BACK FLOW PREVENTER
SANITARY DRAIN
SHOWER
SINK
TEMPERED HOT WATER
THERMOSTATIC MIXING VALVE
TEMPERED WATER
URINAL
UTILITY WATER
VENT THROUGH ROOF
WATER CLOSET
WALL CLEAN OUT
WATER HEATER
SANITARY DRAIN
VENT PIPING
CHECK VALVE
DESCRIPTIONID
1. THE ENTIRE PLUMBING SYSTEM SHALL BE IN ACCORDANCE WITH THE
2015 EDITION OF THE INTERNATIONAL PLUMBING CODE AND LOCAL PLUMBING
STATUTES/ORDINANCES.
2. THE PIPING INDICATED ON THESE PLANS ARE DIAGRAMATIC. ALL WORK
SHALL BE COORDINATED WITH ALL OTHER TRADES PRIOR TO
INSTALLATION. SUBCONTRACTOR SHALL COORDINATE ROUTING OF ALL
PIPING WITH EXISTING CONDITIONS AND SHALL PROVIDE ANY NECESSARY
OFFSETS, REROUTING, TEES, ELBOWS, ETC. REQUIRED FOR A COMPLETE
AND COORDINATED INSTALLATION.
3. ALL PLUMBING & PIPING SYSTEMS SHALL BE SUPPORTED AS REQUIRED
BY THE LOCAL CODE REQUIREMENTS AND PER MANUFACTURER'S
RECOMMENDATIONS.
4. ALL PIPING PENETRATIONS THROUGH NEW, EXISTING WALL, OR FLOOR
SHALL BE SEALED TO EQUAL THE RATING OF THE NEW, EXISTING
WALL OR FLOOR.
5. TEST POTABLE WATER SYSTEM UNDER A WATER PRESSURE NOT LESS THAN 1-1/2
TIME THE WORKING PRESSURE, BUT NOT LESS THAN 125 PSI. SEE SPECIFICATION
220000 FOR SPECIFIC TESTING AND REPORTING REQUIREMENTS.
6. TEST THE DRAINAGE AND VENTING SYSTEMS WITH WATER. SEE SPECIFICATION
220000 FOR SPECIFIC TESTING AND REPORTING REQUIREMENTS.
7. TEST GAS PIPING SYSTEM UNDER A PRESSURE NOT LESS THAN 1-1/2 TIME THE
WORKING PRESSURE, BUT NOT LESS THAN 3 PSIG. SEE SPECIFICATION 220000 FOR
SPECIFIC TESTING AND REPORTING REQUIREMENTS.
8. ALL (VTR'S) VENT THRU ROOF PENETRATIONS INDICATED ON PLANS
ARE PRELIMINARY. FINAL LOCATIONS SHALL BE COORDINATED WITH
ALL TRADES.
CLOTHES WASHER
2" 1-1/2"CW-1 1/2" 1/2"
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
SS
AutoCAD SHX Text
DJK
AutoCAD SHX Text
AK
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text P-1
AutoCAD SHX Text
REMOVE EXISTING CAST IRON SANITARY DRAIN INSIDE THE RESIDENCE, 6" FROM THE
INSIDE WALL AND ALL THE WAY TO THE PLUMBING FIXTURES. EXISTING CAST IRON
PIPE RUNS UNDER THE FLOOR IN THE CRAWL SPACE.
REMOVE THE EXISTING GALVANIZED POTABLE WATER LINE FROM THE EXISTING
VALVE VAULT ALL THE WAY TO THE PLUMBING FIXTURES. EXISTING GALVANIZED PIPE
RUNS UNDER THE FLOOR IN THE CRAWL SPACE.
EXISTING KITCHEN SINK TO
REMAIN. REMOVE EXISTING
FAUCET, HOT, AND COLD WATER
PIPING INCLUDING THE ISOLATION
VALVES, AND SANITARY DRAIN.
PLUMBING DEMO PLAN
P-2
EXISTING TOILET TO REMAIN. REMOVE EXISTING
FLASH VALVE, COLD WATER PIPING INCLUDING
THE ISOLATION VALVE, AND SANITARY DRAIN.
EXISTING LAVATORY TO REMAIN. REMOVE
EXISTING FAUCET, COLD WATER PIPING
INCLUDING THE ISOLATION VALVE, AND
SANITARY DRAIN.
EXISTING BATHTUB TO REMAIN. REMOVE
EXISTING FAUCET, COLD WATER PIPING
INCLUDING THE ISOLATION VALVE, AND
SANITARY DRAIN.
WC-1
EXISTING VALVE VAULT
EXISTING 1" GALVANIZED PIPE POTABLE WATER SUPPLY
EXISTING INSTANTANEOUS HOT
WATER HEATER TO REMAIN.
SK-1
LV-1
BT-1
KITCHEN
UTILITY
ROOM
MECH
ROOM
OFFICE
BEDROOM #2
BEDROOM #1
CLOSET
CLOSET
CLOSET
BATH
CLOSET
LIVING ROOM
EXISTING SHUTOFF VALVE TO BE DEMOLISHED
CW-1
REMOVE EXISTING HOT, AND COLD WATER
PIPING INCLUDING THE ISOLATION VALVES, AND
SANITARY DRAIN.
GENERAL SHEET NOTES:
1. ALL WORK SHALL COMPLY WITH THE 2015 INTERNATIONAL
PLUMBING CODE.
2. COORDINATE WITH OWNER TO SHUT OFF MAIN WATER SUPPLY
FOR WORK ON MAIN WATER VALVE.
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
SS
AutoCAD SHX Text
DJK
AutoCAD SHX Text
AK
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text P-2
AutoCAD SHX Text
PLUMBING POTABLE WATER
P-3
GENERAL SHEET NOTES:
1. ALL WORK SHALL COMPLY WITH THE 2015 INTERNATIONAL
PLUMBING CODE.
2. COORDINATE WITH OWNER TO SHUT OFF MAIN WATER SUPPLY
FOR WORK ON MAIN WATER VALVE.
3. RETAIN VALVE IN EXTERIOR VALVE VAULT. REPLACE SUPPLY
PIPING FROM VALVE TO NEW COLD WATER MANIFOLD WITH PEX
TO MATCH EXISTING SIZE. USE DIELECTRIC FITTING AT THE
CONNECTION TO THE EXISTING PIPE.
4. WATER SUPPLY LINE ENTERS CRAWLSPACE AT OR BELOW
EXISTING GROUND LEVEL. RAISE NEW PEX PIPE SUPPLY LINE TO
ABOVE EXISTING GROUND LEVEL AND FEED COLD WATER
MANIFOLD IN MECHANICAL ROOM.
5. ALL NEW POTABLE WATER PIPE SHALL BE PEX PER
SPECIFICATION 220000 PLUMBING PIPING AND SPECIALITIES.
6. PROVIDE PIPE INSULATION ON ALL HOT AND COLD LINES PER
SPECIFICATION 220000 PLUMBING PIPING AND SPECIALTIES.
7. REPLACE TOILET FLUSH VALVE. SEE SPECIFICATION 220000.
8. CLOTHES WASHER SUPPLY PART OF WATER DRAIN ROUGH IN
BOX. INSTALL ROUGH IN BOX AT 42" AFF.
9. IF EXTERIOR HOSE BIBS EXIST ON THE RESIDENCE SUBMIT A
SEPARATE COST PROPOSAL FROM THE BASE BID FOR THEIR
REMOVAL AND REPLACEMENT.
10. INSPECT AND MAKE APPROPRIATE REPAIRS TO ALL ROOF AND
EVE VENTS TO PREVENT WATER AND RODENT ACCESS TO THE
ATTIC SPACES.
11. CONTRACTOR SHALL PROTECT EXISTING FLOORING DURING
CONSTRUCTION AND SHALL REPAIR NECESSARY DAMAGES TO
RETURN FLOOR TO CONDITIONS BEFORE CONSTRUCTION.
KITCHEN
UTILITY
ROOM
MECH
ROOM
OFFICE
BEDROOM #2
BEDROOM #1
CLOSET
CLOSET
CLOSET
BATH
CLOSET
LIVING ROOM
1/2" CW
WC-1
LV-1
BT-1
SK-1
1/2" CW
1/2" HW
ALL NEW POTABLE WATER PIPE SHALL BE PEX PER
SPECIFICATION 220000 PLUMBING PIPING AND SPECIALTIES
CONNECT NEW PEX PIPE TO NEW BALL VALVE
EXISTING POTABLE WATER VALVE VAULT
NEW BRONZE BALL VALVE
EXISTING 1" GALVANIZED PIPE POTABLE WATER SUPPLY
1" PEX PIPE RUNS
UNDER THE FLOOR
IN THE CRAWL
SPACE.
1/2" HW
1/2" DOMESTIC HOT WATER PEX PIPE
RUNS UNDER THE FLOOR IN THE CRAWL
SPACE. (TYP FOR 4)
COPPER DOMESTIC HOT WATER
DISTRIBUTION MANIFOLD
3/4" HW
3/4" CW
COPPER DOMESTIC COLD
WATER DISTRIBUTION MANIFOLD
BALL VALVES (TYP)
EXISTING LBG
INSTANTANEOUS HOT
WATER HEATER
DOMESTIC COLD WATER PEX
PIPE RUNS UNDER THE FLOOR IN
THE CRAWL SPACE. (TYP OF 6)
CW-1
1/2" CW
1/2" HW
NEW REDUCED PRESSURE
BACKFLOW PREVENTER
NEW BRONZE BALL VALVE
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
SS
AutoCAD SHX Text
DJK
AutoCAD SHX Text
AK
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text P-3
AutoCAD SHX Text
PLUMBING SANITARY DRAIN
P-4
GENERAL SHEET NOTES:
1. ALL WORK SHALL COMPLY WITH THE 2015 INTERNATIONAL
PLUMBING CODE.
2. INTERCEPT SANITARY DRAINS BELOW FLOOR AND REPLACE
BRANCH AND MAIN LINES WITH PVC PIPE. TRANSITION NEW MAIN
TO EXISTING MAIN SEWER LINE AT 6" INSIDE RESIDENCE SOUTH
WALL.
3. ALL NEW SANITARY DRAINS AND VENTS SHALL BE POLYVINYL
CHLORIDE (PVC), GRAVITY PIPE ASTM D2665/D1785.
4. SLOPE DRAINAGE PIPING 1/4" PER LINEAR FOOT OF DRAIN PIPE.
5. CLOTHES WASHER DRAIN PART OF WATER SUPPLY ROUGH IN
BOX. INSTALL DRAIN P-TRAP AT 12" AFF AND ROUGH IN BOX AT
42" AFF.
KITCHEN
UTILITY
ROOM
MECH
ROOM
OFFICE
BEDROOM #2
BEDROOM #1
CLOSET
CLOSET
CLOSET
BATH
CLOSET
LIVING ROOM
WC-1
LV-1
BT-1
SK-1
CO
CO
3" SD
1 1/2" V
2" VTR
2" SD
1 1/2" V
2" SD
1 1/2" V
P-TRAP
3" SD
4" SD
4" SD
1 1/2" VTR
4" SD
1 1/2" V
EXISTING LPG
INSTANTANEOUS HOT
WATER HEATER
NEW 4" SANITARY DRAIN POLYVINYL
CHLORIDE (PVC), GRAVITY DWV PIPE, ASTM
D2665/D1785, SCH 40
EXISTING 4" CAST IRON SANITARY DRAIN.
3" SD
4" SD
1 1/2" V
2" SD
P-TRAP
P-TRAP
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
SS
AutoCAD SHX Text
DJK
AutoCAD SHX Text
AK
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text P-4
AutoCAD SHX Text
ELECTRICAL SYMBOLS & DETAILS
E-1
OVER COUNTER DUPLEX 5-20R RECEPTACLE
OVER COUNTER DUPLEX 5-20R RECEPTACLE
W/ INTEGRAL GROUND FAULT
WEATHERPROOF DUPLEX 5-20R
RECEPTACLE W/ INTEGRAL GROUND FAULT
220V RECEPTACLE
1-GANG LINE VOLTAGE SWITCH W/OCCUPANCY SENSOR
3-WAY LINE VOLTAGE SWITCH
SMOKE ALARM
CABLE RECEPTACLE
ELECTRICAL LEGEND
# CIRCUIT NUMBER
CARBON MONOXIDE DETECTOR
# CIRCUIT NUMBER
TRANSFER SWITCH
ENCLOSURE (IF REQ)
NEUTRAL
BUS
GROUND
LUG
SERVICE ENTRANCE
DEVICE ENCLOSURE
NEUTRAL
DISCONNECTING
LINK
GROUNDING ELECTRODE
CONDUCTOR TO GROUNDING
ELECTRODE, #4 AWG
NEUTRAL
BUS
NEUTRAL
CONDUCTOR
GROUND BUS
GROUND LUG
SERVICE NEUTRAL
RACEWAY
DUCTBANK GROUND
CONDUCTOR (IF REQ'D)
E-300
SERVICE GROUNDING
REV 010119
NON-SEPARATELY DERIVED SOURCE
3/4"x10' COPPER
CLAD GROUND ROD
FINISH GRADE
EXOTHERMIC
WELD
GROUND CABLE
#4 AWG
NOTE:
1. ELECTRICAL SAMPLE DETAIL.
ES351
BURIED GROUND ROD
REV 010119
INSTALLATION
X a
GF
WP
GF
GF
J G
F
WP
T R
T R
GF
J G
F
WP
T R
T R
DUPLEX 5-20R RECEPTACLE #
CIRCUIT NUMBER
1-GANG LINE VOLTAGE
SWITCH x SWITCH LEG
LIGHT FIXTURE
X FIXTURE TYPE
# CIRCUIT NUMBER
x SWITCH LEG
LIGHT
SWITCH
RECEPTACLE
(EQUIPMENT AREAS, WET
AND CORROSIVE AREAS)
RECEPTACLE OR
TELEPHONE/COMPUTER
(OFFICE AREAS)
DOOR FRAME TRIM
12" MAX
E-450
OUTLET BOX MOUNTING
REV 010119
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
JKB
AutoCAD SHX Text
ARF
AutoCAD SHX Text
KES
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text E-1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text
OS
x
ELECTRICAL DEMOLITION PLAN
E-2
GENERAL NOTES:
1. COORDINATE WITH LOCAL POWER COMPANY TO
DISCONNECT POWER TO EXISTING SERVICE PRIOR TO
WORK.
2. DEMOLISH ALL RECEPTACLES, SWITCHES, LIGHT FIXTURES
AND FANS ON INTERIOR AND EXTERIOR OF RESIDENCE.
RETAIN FANS FOR REINSTALLATION IN ORIGINAL
LOCATIONS.
3. DEMOLISH EXISTING SERVICE PANELS CONDUIT AND
JUNCTION BOXES DOWNSTREAM OF EXISTING METER. NEW
MAIN PANEL WILL BE INSTALLED INSIDE RESIDENCE. SEAL
ALL HOLES WITH PAINTABLE WATERPROOF SEALANT AND
PAINT TO MATCH RESIDENCE EXTERIOR.
4. DEMOLISH ALL EXISTING RECEPTACLES, SWITCHES,
INTERIOR OR EXTERIOR PULL BOXES NOT LOCATED IN
ATTIC OR CRAWL SPACES AND WIRING. REMOVE FANS AND
RETAIN TO BE RE-INSTALLED DURING CONSTRUCTION.
5. DEMOLISH AC POWER WHIP IN PREPARATION FOR NEW AC
DISCONNECT AND WHIP.
6. TEST EXISTING GROUND ROD (UNDER EXISTING MAIN
DISTRIBUTION PANEL) FOR RESISTANCE TO GROUND AT OR
BELOW 25 OHMS. IF RESISTANCE IS LOWER THAN
THRESHOLD, IT CAN BE USED AS PART OF NEW SERVICE
GROUNDING ELECTRODE SYSTEM. IF RESISTANCE IS
HIGHER THAN 25 OHMS, DISCONNECT AND DRIVE NO LESS
THAN 6" BELOW GRADE.
7. DEMO CONDUIT AND WIRE TO GARAGE. NEW CONDUIT AND
WIRE WILL BE INSTALLED IN SAME APPROXIMATE LOCATION.
8. CONTRACTOR SHALL PROTECT EXISTING FLOORING DURING
CONSTRUCTION AND SHALL REPAIR NECESSARY DAMAGES
TO RETURN FLOOR TO CONDITIONS BEFORE
CONSTRUCTION.
9. DEMO ALL EXTERIOR PHONE AND COAXIAL CABLES. AS
WELL AS THE DEVICES ON WHICH THEY TERMINATE INSIDE
THE RESIDENCE. SEAL ALL HOLES WITH PAINTABLE
WATERPROOF SEALANT AND PAINT TO MATCH RESIDENCE
EXTERIOR.
CRAWL SPACE
ACCESS
ATTIC
ACCESS
EXISTING PANEL(MAIN BREAKER ONLY)
(EXISTING METER ABOVE PANEL)
EXISTING
BREAKER
PANEL
CONDUIT TO
GARAGE
EXISTING
GROUND ROD
KITCHEN
UTILITY
ROOM
MECH
ROOM
OFFICE
BEDROOM #2
BEDROOM #1
CLOSET
CLOSET
CLOSET
BATH
CLOSET
LIVING ROOM
GF
GF
WP
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
JKB
AutoCAD SHX Text
ARF
AutoCAD SHX Text
KES
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text E-2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Scale in Feet
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Scale in mm
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL PLAN
E-3
CRAWL SPACE
ACCESS
ATTIC
ACCESS
GROUND ROD
(TYP)
IBT
MAIN DISTRIBUTION
PANEL
RANGE HOOD
30A FUSED
DISCONNECT
AC CONDENSER
UNIT
FURNACE
SHEET NOTES:
INSTALL NEW 200A SERVICE DISCONNECT BELOW EXISTING
UTILITY METER. CONNECT WITH 3#3/0 CONDUCTOR.
INSTALL INTERSYSTEM TERMINATION BONDING DEVICE WITH
NOT LESS THAN THREE TERMINALS AND CONNECT TO THE
GROUNDING ELECTRODE CONDUCTOR WITH #6AWG COPPER
CONDUCTOR.
CONNECT NEW MAIN DISTRIBUTION PANEL TO SERVICE
DISCONNECT WITH 3#3/0, 1#4G. CONNECT GROUNDING
ELECTRODE CONDUCTOR TO GROUND RODS NEAR
DISCONNECT WITH PERMANENT CADWELD EXOTHERMIC
WELDED CONNECTIONS.
TEST EXISTING GROUND ROD (UNDER EXISTING MAIN
DISTRIBUTION PANEL) FOR RESISTANCE TO GROUND AT OR
BELOW 25 OHMS. IF RESISTANCE IS LOWER THAN THRESHOLD,
IT CAN BE USED AS PART OF NEW SERVICE GROUNDING
ELECTRODE SYSTEM. IF RESISTANCE IS HIGHER THAN 25 OHMS,
DISCONNECT AND DRIVE NO LESS THAN 6" BELOW GRADE. A
MINIMUM OF TWO GROUND RODS, SPACED NO CLOSER THAN 6'
ARE REQUIRED, WITH A TOTAL SYSTEM RESISTANCE OF NO
MORE THAN 25 OHMS. OTHER SYSTEM GROUNDING METHODS
ARE PERMITTED PER THE 2017 NEC, BUT A MINIMUM OF TWO
GROUND RODS ARE REQUIRED PER THIS CONTRACT.
INSTALL NEW 30A FUSED DISCONNECT AND REFEED AC
CONDENSER WITH 2#10, 1#10G.
ALL NON-FAN LIGHT SWITCHES SHALL INCORPORATE
OCCUPANCY SENSORS COMPATIBLE WITH LED LIGHTING.
RUN NEW 3/4" EMT CONDUIT FROM ATTIC OF RESIDENCE TO
GROUND IN SAME LOCATION OF EXISTING 1/2" CONDUIT
FEEDING GARAGE. TRANSITION TO PVC CONDUIT, SAWCUT
PAVING AND RUN NEW GARAGE FEED IN SAME APPROXIMATE
LOCATION AS EXISTING FEED. FEED NEW 30A SUBPANEL WITH
3#8, 1#8G IN 1" CONDUIT.
CONNECT RG6 CABLE FROM COMMERCIAL COMMUNICATIONS
TERMINAL ON EXTERIOR OF RESIDENCE TO INTERIOR
COMMUNICATIONS PANEL. CONNECT TO INDIVIDUAL ROOMS
USING PASSIVE COAXIAL SPLITTER BOX MANUFACTURED FOR
THE NUMBER OF DEVICES ATTACHED. LABEL EXTERIOR AND
ROOM RG6 CABLES INSIDE COMMUNICATIONS BOX. CONNECT
COPPER PHONE CABLE FROM COMMERCIAL TERMNIAL ON
EXTERIOR OF HOUSE TO COMMUNICATIONS BOX. LAND PHONE
CABLE ON A PHONE TERMINATION BLOCK AND CONTINUE CABLE
TO LIVING ROOM PHONE RECEPTACLE.
EXISTING GARAGE
FEEDER CONDUIT
GENERAL NOTES:
1. INSTALLATION SHALL BE IN ACCORDANCE TO THE 2017 NEC,
INCLUDING ALL APPLICABLE LOCAL ORDINANCES. WIRING
AND DETAILS IN COMMONLY DESCRIBED IN CODE MAY NOT
BE SHOWN ON PLANS BUT ARE APPLICABLE PER CODE
REQUIREMENTS.
2. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS
FOR ELECTRICAL CONSTRUCTION.
3. ALL INTERIOR ELECTRICAL CABLE SHALL BE TYPE NM.
4. COORDINATE EXACT LOCATION OF ALL LIGHTING FIXTURES
WITH EQUIPMENT, DUCTWORK AND PIPING.
5. ALL CIRCUITING; 2#12, 1#12G UNLESS NOTED OTHERWISE
ON THE DRAWINGS OR IN THE SPECIFICATIONS.
6. CIRCUIT 1,3 TO AC SHALL BE FED WITH 2#10, 1#10G.
7. CIRCUIT 9,11 TO DRYER SHALL BE FED WITH 2#10, 1#10G.
8. CIRCUIT 19, 21 TO OVEN SHALL BE FED WITH 2#8, 1#8G.
9. CIRCUIT 22, 28 TO GARAGE SHALL BE FED WITH 3#8, 1#8G.
10. ARRANGE WITH AUTHORITIES AND UTILITY COMPANIES FOR
PERMITS, FEES AND SERVICE CONNECTIONS, VERIFYING
LOCATIONS AND ARRANGEMENT AND PAYING ALL
CHARGES, INCLUDING INSPECTIONS.
11. COORDINATE WORK WITH ARCHITECTURAL FEATURES AND
COORDINATE WORK SO THAT INTERFERENCE BETWEEN
CONDUITS, LIGHTING, EQUIPMENT, PLUMBING WORK AND
BUILDING STRUCTURE WILL BE AVOIDED.
12. ALL RACEWAYS AND EQUIPMENT SHALL BE INSTALLED AND
GROUNDED IN ACCORDANCE WITH THE 2017 EDITION OF
THE NEC AND APPLICABLE LOCAL CODES.
13. THE CONTRACTOR SHALL PROVIDE PULLBOXES WHERE
REQUIRED TO MAKE A WORKABLE INSTALLATION.
14. ALL RECEPTACLES IN OUTDOOR AND ANTICIPATED WET
AREAS SHALL BE GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLES WITH WEATHERPROOF, IN-USE COVERS.
15. FOR LIGHTING AND RECEPTACLE SYSTEMS, ONLY CIRCUIT
NUMBERS ARE SHOWN. CONTRACTOR SHALL PROVIDE ALL
NECESSARY CONDUITS, WIRES, FITTINGS, JUNCTION BOXES
AND ALL NECESSARY COMPONENTS TO MAKE THE
ELECTRICAL INSTALLATION COMPLETE AND OPERATIONAL.
CIRCUIT LOADING SHALL BE AS INDICATED IN THE PANEL
SCHEDULES. ALL CIRCUITS SHALL INCLUDE GROUND WIRE.
16. MULTI-WIRE BRANCH CIRCUITS USING ONE COMMON
GROUNDED OR "SHARED" NEUTRAL CONDUCTOR ARE NOT
PERMITTED.
17. ALL CONDUCTORS SHALL BE COPPER. ALUMINUM BRANCH
CIRCUITS OR FEEDER CONDUCTORS ARE NOT PERMITTED.
18. RECEPTACLES IN KITCHEN, LIVING ROOM, BEDROOMS AND
OFFICE SHALL BE TAMPER-RESISTANT.
19. SURGE PROTECTIVE DEVICE (SPD) SHALL BE INSTALLED IN
PANELBOARD.
20. CONTRACTOR SHALL PROTECT EXISTING FLOORING
DURING CONSTRUCTION AND SHALL REPAIR NECESSARY
DAMAGES TO RETURN FLOOR TO CONDITIONS BEFORE
CONSTRUCTION.
21. CONNECT COMMUNICATIONS OUTLETS TO
COMMUNICATIONS PANEL WITH RG6 CABLE. COIL CABLE
INSIDE PANEL FOR FUTURE TERMINATION.
COMMUNICATION
PANEL
19,21
GF
GF
GF
9,11
USB TYPE A
USB TYPE A
USB TYPE A
USB TYPE A
USB TYPE A
b
F
USB TYPE A
USB TYPE A
GF
GF
200A SERVICE
DISCONNECT
CABLE AND PHONE BOX
CABLE AND PHONE BOX
PHONE AND CABLE
RECEPTACLE
c
4 4 a
A a
A a
C a
A b
GS
a c b a a a b
E b a b
E b a b
A a
E b
A a
E b a b a c b ab a b
A a
12 12
A a
A a
A a
A a
A a
A a
A a
A a
A a
A c
A c
GF
A a
A a
A a
A a
A a
A a
A a
GF
WP
GF
GF
A a
A a
A a
A a
A a
A a
GF
WP
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
JKB
AutoCAD SHX Text
ARF
AutoCAD SHX Text
KES
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text E-3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Scale in Feet
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Scale in mm
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text c
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text a
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OS
AutoCAD SHX Text
AutoCAD SHX Text
CCT
OS
GARAGE PLAN
E-4
GENERAL NOTES:
1. INSTALLATION SHALL BE IN ACCORDANCE TO THE 2017 NEC,
INCLUDING ALL APPLICABLE LOCAL ORDINANCES. WIRING
AND DETAILS IN COMMONLY DESCRIBED IN CODE MAY NOT
BE SHOWN ON PLANS BUT ARE APPLICABLE PER CODE
REQUIREMENTS.
2. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS
FOR ELECTRICAL CONSTRUCTION.
3. COORDINATE EXACT LOCATION OF ALL LIGHTING FIXTURES
WITH EQUIPMENT, DUCTWORK AND PIPING.
4. ALL CIRCUITING; 2#12, 1#12G UNLESS NOTED OTHERWISE
ON THE DRAWINGS OR IN THE SPECIFICATIONS.
5. COORDINATE WORK WITH ARCHITECTURAL FEATURES AND
COORDINATE WORK SO THAT INTERFERENCE BETWEEN
CONDUITS, LIGHTING, EQUIPMENT, PLUMBING WORK AND
BUILDING STRUCTURE WILL BE AVOIDED.
6. ALL RACEWAYS AND EQUIPMENT SHALL BE INSTALLED AND
GROUNDED IN ACCORDANCE WITH THE 2017 EDITION OF
THE NEC AND APPLICABLE LOCAL CODES.
7. THE CONTRACTOR SHALL PROVIDE PULLBOXES WHERE
REQUIRED TO MAKE A WORKABLE INSTALLATION.
8. ALL RECEPTACLES IN OUTDOOR AND ANTICIPATED WET
AREAS SHALL BE GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLES WITH WEATHERPROOF, IN-USE COVERS.
9. FOR LIGHTING AND RECEPTACLE SYSTEMS, ONLY CIRCUIT
NUMBERS ARE SHOWN. CONTRACTOR SHALL PROVIDE ALL
NECESSARY CONDUITS, WIRES, FITTINGS, JUNCTION BOXES
AND ALL NECESSARY COMPONENTS SHOWN OR NOT
SHOWN ON THE DRAWINGS, TO MAKE THE ELECTRICAL
INSTALLATION COMPLETE AND OPERATIONAL. CIRCUIT
LOADING SHALL BE AS INDICATED IN THE PANEL
SCHEDULES. ALL CIRCUITS SHALL INCLUDE GROUND WIRE.
10. MULTI-WIRE BRANCH CIRCUITS USING ONE COMMON
GROUNDED OR "SHARED" NEUTRAL CONDUCTOR ARE NOT
PERMITTED.
11. ALL CONDUCTORS SHALL BE COPPER. ALUMINUM BRANCH
CIRCUITS OR FEEDER CONDUCTORS ARE NOT PERMITTED.
12. RUN NEW 1" EMT CONDUIT FROM ATTIC OF RESIDENCE TO
GROUND IN SAME LOCATION OF EXISTING 1/2" CONDUIT
FEEDING GARAGE. TRANSITION TO PVC CONDUIT, SAWCUT
PAVING AND RUN NEW GARAGE FEED IN SAME
APPROXIMATE LOCATION AS EXISTING FEED. FEED NEW
30A SUBPANEL WITH 3#8, 1#8G IN 1" CONDUIT.
NEW SUBPANEL
DEMO ALL EXISTING CONDUIT,
RECEPTACLES, SWITCHES
AND LIGHT FIXTURES
1 FLOOR PLAN
1/2" = 1' - 0"
2 ELECTRICAL DEMO PLAN
1/2" = 1' - 0"
3 ELECTRICAL PLAN
1/2" = 1' - 0" b
NOTE: ALL WIRE IN GARAGE SHALL BE TYPE XHHW AND RUN
IN NEW CONDUIT.
b
MPC-1
MPC-1
MPC-1
MPC-1
MPC-1
MPC-1
MPC-1
MPC-1
MPC-2
C a
MPC-2
C a
D
MCP-2
b a
D
MCP-2
a b
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
JKB
AutoCAD SHX Text
ARF
AutoCAD SHX Text
KES
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text E-4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Scale in Feet
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL SCHEDULES
E-5
GENERAL NOTES:
1. CIRCUIT BREAKERS IN BEDROOMS, LIVING ROOM, OFFICE
AND PORCH SHALL BE ARC-FAULT TYPE.
2. CIRCUIT BREAKER FOR DISHWASHER SHALL BE GFCI TYPE.
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
INKS DAM
AutoCAD SHX Text
INKS DAM RESIDENCE #3 REHAB DESIGN
AutoCAD SHX Text
JKB
AutoCAD SHX Text
ARF
AutoCAD SHX Text
KES
AutoCAD SHX Text 7/31/20
AutoCAD SHX Text E-5
AutoCAD SHX Text
| Residence #3-Cover |
| Sheets and Views |
| Cover |
| Residence #3-Floor Plan |
| Sheets and Views |
| Floor Plan |
| Residence #3-Sheetrock and Insulation Plan |
| Sheets and Views |
| GYPSUM BOARD AND INSULATION Plan |
| Residence #3 - Plumbing Notes Symbols and Details |
| Sheets and Views |
| Plumbing General Notes symbols and Details |
| Residence #3 - Plumbing-Demo Plan |
| Sheets and Views |
| Plumbing Demo Plan |
| Residence #3 - Plumbing-Potable Water Plan |
| Sheets and Views |
| Plumbing Plan - Water |
| Residence #3 - Plumbing Sanitary Drain Plan |
| Sheets and Views |
| Plumbing Plan - Waste |
| Residence #3-Electrical Symbols and Details |
| Sheets and Views |
| Electrical Symbols and Details |
| Residence #3-Electrical Demo Plan |
| Sheets and Views |
| Electrical Demo Plan |
| Residence #3-Electrical Plan |
| Sheets and Views |
| Electrical Plan |
| Residence #3-Garage Plan |
| Sheets and Views |
| Garage Plan |
| Residence #3-Schedules |
| Sheets and Views |
| Schedules |
File details come from the government source that posted it. Updated .