This set of construction drawings and specifications is for the remodel of Residence #3 at Inks Dam National Fish Hatchery. The project involves demolishing and replacing plumbing, electrical, and sheetrock systems. Plumbing work includes replacing the potable water distribution and sanitary drainage piping. Electrical work consists of a new service entrance, distribution panel, lighting and power upgrades. Sheetrock demolition and replacement is specified along with new insulation. The drawings provide demolition plans, layouts of new systems, schedules and details. The project is to be completed in accordance with all applicable construction codes.

The related federal contract opportunity is for the remodel of Residences #2 and #3 at Inks Dam NFH. The solicitation is for construction services and is issued by the U.S. Fish and Wildlife Service Region 2. No further details are provided in the opportunity description. The set of construction drawings and specifications provides the technical requirements for the remodel work of Residence #3 to support the federal contracting opportunity.

View the file

Other files for this federal contract opportunity

Other files attached to INKS DAM NFH REMODEL RESIDENCES #2 &, newest first.
File Type Posted
Sol_140F0220R0043_Amd_0001.pdf PDF
Attach-3-Specifications-Residence-2.pdf PDF
Attach-7-QTRs-2-Lead Paint Findings.pdf PDF
Attach-9-DBA Min. Wage Rates.pdf PDF
Attach-5-Price Sheet.xlsx XLSX spreadsheet
Attach-8-QTRS-3-Lead Paint Findings.pdf PDF
Attach-4-Specifications-Residenc-3.pdf PDF
Attach-1-Drawings-Residence-2.pdf PDF
Sol_140F0220R0043.pdf PDF
Attach-6-Past Performance and Clauses.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INKS DAM RESIDENCE #3 REHAB DESIGN

ASSET #: 10006240

RESIDENCE #3

RESIDENCE #2

INDEX OF DRAWINGS

C-1 COVER/INDEX OF DRAWINGS

A-1 FLOOR PLAN

A-2 GYPSUM BOARD AND INSULATION PLAN

P-1 PLUMBING NOTES, SYMBOLS AND DETAILS

P-2 PLUMBING DEMO PLAN

P-3 PLUMBING POTABLE WATER PLAN

P-4 PLUMBING SANITARY DRAIN PLAN

E-1 ELECTRICAL SYMBOLS AND DETAILS

E-2 ELECTRICAL DEMO PLAN

E-3 ELECTRICAL PLAN

E-4 GARAGE PLAN

E-5 ELECTRICAL SCHEDULES

100% DESIGN

SUBMITTAL

JULY 31, 2020

AutoCAD SHX Text

FISH AND WILDLIFE SERVICE

AutoCAD SHX Text

UNITED STATES DEPARTMENT OF THE INTERIOR

AutoCAD SHX Text

REGION 2 DIV. OF INFRASTRUCTURE MANAGEMENT

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET 1 OF

AutoCAD SHX Text

CHECKED:

AutoCAD SHX Text

VICINITY MAP

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

OR

AutoCAD SHX Text

RI

AutoCAD SHX Text

ME

AutoCAD SHX Text

RT

AutoCAD SHX Text

PA

AutoCAD SHX Text

DE

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text

NT

AutoCAD SHX Text

TE

AutoCAD SHX Text

IN

AutoCAD SHX Text E

AutoCAD SHX Text

TH

AutoCAD SHX Text

FISH AND WILDLIFE

AutoCAD SHX Text

SERVICE

AutoCAD SHX Text U.S.

AutoCAD SHX Text

U.S. FISH & WILDLIFE SERVICE

AutoCAD SHX Text

SERVICE

AutoCAD SHX Text

FISH AND WILDLIFE

AutoCAD SHX Text

TH

AutoCAD SHX Text

ME

AutoCAD SHX Text

RT

AutoCAD SHX Text

PA

AutoCAD SHX Text

DE

AutoCAD SHX Text

NT

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text

OR

AutoCAD SHX Text

RI

AutoCAD SHX Text

TE

AutoCAD SHX Text

IN

AutoCAD SHX Text E

AutoCAD SHX Text U.S.

AutoCAD SHX Text

APPROVAL SIGNATURES

AutoCAD SHX Text

ANY PRINT ACCOMPANYING THIS INVITATION TO BID MAY BE A REDUCED

AutoCAD SHX Text

REPRODUCTION OF THE WORKING DRAWINGS. IF LINE BELOW DOES NOT

AutoCAD SHX Text

MEASURE SIX INCHES IN LENGTH, THE INDICATED SCALES ARE TO BE

AutoCAD SHX Text

ADJUSTED ACCORDINGLY.

AutoCAD SHX Text

%%UNOTE TO BIDDERS:%%

AutoCAD SHX Text

REGIONAL ENGINEER

AutoCAD SHX Text

ASS'T. REGIONAL DIR.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROGRAM SUPERVISOR

AutoCAD SHX Text

FACILITIES

AutoCAD SHX Text

SAFETY/IND HYGIENIST

AutoCAD SHX Text

CULTURAL RESOURCES

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

BURNET

AutoCAD SHX Text

TX

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

COVER/INDEX OF DRAWINGS

AutoCAD SHX Text

JKB

AutoCAD SHX Text

ARF

AutoCAD SHX Text

DEW

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text C-1

AutoCAD SHX Text

AutoCAD SHX Text N

KITCHEN

UTILITY

ROOM

MECH

ROOM

OFFICE

BEDROOM #2

BEDROOM #1

CLOSET

CLOSET

CLOSET

BATH

CLOSET

LIVING ROOM

4'-7''

3'-4''

6'-8''

7'-0''

8'-9''

2'-4''

6'-9''

2'-5''

2'-5''

2'-3''

2'-3''

3'-0''

3'-10''

3'-10''

3'-10''

FLOOR PLAN

A-1

BEDROOM #1

GENERAL NOTES:

1. DIMENSIONS SHOWN OF EXISTING WALLS ARE

APPROXIMATE.

2. CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CODES

AND REGULATIONS.

3. ALL GYPSUM BOARD WALLS AND WOOD TRIM SHALL

RECEIVE A PROTECTIVE COATING OF PRIMER AND PAINT

AFTER OTHER WORK IS COMPLETED. REFER TO

SPECIFICATION 099600 PROTECTIVE COATINGS FOR

DETAILS.

4. ALL CEILING HEIGHTS ARE 8'-0".

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

JKB

AutoCAD SHX Text

ARF

AutoCAD SHX Text

EWM

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text A-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Scale in Feet

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

Scale in mm

GYPSUM BOARD AND INSULATION PLAN

A-2

GENERAL NOTES:

1. PRIOR TO ANY ELECTRICAL AND PLUMBING DEMOLITION OR

CONSTRUCTION, ALL INDICATED GYPSUM BOARD MUST BE

DEMOLISHED AND REMOVED FROM RESIDENCE.

2. GYPSUM BOARD AND INSULATION SHALL BE DEMOLISHED

FROM ALL CEILINGS, EXTERIOR WALLS AND PAINTED

INTERIOR WALLS. ALL GYPSUM BOARD AND INSULATION

DEBRIS AND DUST MUST BE REMOVED OFF OF HATCHERY

PROPERTY AND PROPERLY DISPOSED OF PRIOR TO

ELECTRICAL AND PLUMBING CONTRACTORS BEGINNING

WORK.

3. A QUALIFIED ASBESTOS ABATEMENT CONTRACTOR SHALL

BE USED DURING DEMOLITION PHASE FOR PROPER SETUP

AND CONTAINMENT.

4. INSTALL NEW R11 INSULATION ON ALL EXTERIOR WALLS

AND APPLY GYPSUM BOARD. INSTALL NEW GYPSUM BOARD

ON INTERIOR WALLS WHERE REMOVED. INSTALL NEW

GYPSUM BOARD ON CEILINGS. MUD, TAPE,SAND AND PAINT

TO MATCH EXISTING CONDITIONS. PAINT ALL PAINTED

WOOD TRIM. ALL COLORS SHALL BE COORDINATED WITH

THE OWNER PRIOR TO PAINTING.

5. REPAIR OR REPLACE WOOD TRIM THAT IS DAMAGED OR

UNUSABLE.

6. BLOW IN NEW R38 INSULATION IN ATTIC TO A MINIMUM

DEPTH OF THE MANUFACTURES RECOMMENDATIONS..

7. CONTRACTOR SHALL PROTECT EXISTING FLOORING DURING

CONSTRUCTION AND SHALL REPAIR NECESSARY DAMAGES

TO RETURN FLOOR TO CONDITIONS BEFORE

CONSTRUCTION.

8. ALL ELECTRICAL AND PLUMBING DEMOLISHED DEBRIS MUST

BE REMOVED OFF OF HATCHERY PROPERTY AND

PROPERLY DISPOSED OF.

CRAWL SPACE

ACCESS

ATTIC

ACCESS

DEMOLISH CEILING

(TYP IN ENTIRE

RESIDENCE)

RETAIN FANS FOR

RE-INSTALLATION

KNOWN LEAD PAINT AND ASBESTOS LOCATIONS:

1. A LEAD-BASED PAINT INSPECTION WAS COMPLETED IN 2000

AND IDENTIFIED THE FOLLOWING FINDINGS;

a. INTERIOR PAINT WAS FOUND IN "GOOD" CONDITION AND

THE AMOUNT OF LEAD IS INDICATIVE OF 1950S OR EARLY

1960S PAINT.

b. EXTERIOR WOOD PAINT ON THE SOFFIT AND ROOF TRIM OF

THE CARPORT WAS IN "POOR" CONDITION AND CONTAINS

MORE THAN 10SQFT OF LBP.

c. EXTERIOR WOOD PAINT ON THE GABLE, SOFFIT AND ROOF

TRIM OF THE SOUTH SIDE OF THE RESIDENCE WAS IN

"POOR" CONDITION AND CONTAINS MORE THAN 10SQFT OF

LBP.

2. AN ASBESTOS SURVEY WAS COMPLETED IN 1999 AND

IDENTIFIED ASBESTOS IN THE FOLLOWING AREAS:

a. WALL SKIM COAT THROUGHOUT RESIDENCE.

b. MECHANICAL ROOM FLOOR TILE.

c. GARAGE SHINGLES.

3. ALL GYPSUM BOARD ON EXTERIOR WALLS SHALL BE

REMOVED. ALL PAINTED GYPSUM BOARD ON INTERIOR

WALLS SHALL BE REMOVED.

4. MECHANICAL ROOM FLOOR TILE WITH ASBESTOS SHALL

REMAIN IN PLACE AND UNDISTURBED.

5. GARAGE SHINGLES WITH ASBESTOS SHALL REMAIN IN PLACE

AND UNDISTURBED.

KITCHEN

UTILITY

ROOM

MECH

ROOM

OFFICE

BEDROOM #2

BEDROOM #1

CLOSET

CLOSET

CLOSET

BATH

CLOSET

LIVING ROOM

DEMOLITION LEGEND

DEMO ALL MATERIAL ON EXTERIOR WALLS FROM FLOOR TO CEILING IN PREPARATION FOR NEW INSULATION.

DEMO ALL PAINTED GYPSUM BOARD ON INTERIOR WALLS SHALL BE REMOVED.

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

JKB

AutoCAD SHX Text

ARF

AutoCAD SHX Text

EWM

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text A-2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Scale in Feet

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PLUMBING NOTES, SYMBOLS AND DETAILS

P-1

WASTE VENT CW HW

LAVATORY

SINK

3"

EXISTING PLUMBING FIXTURE CONNECTION SCHEDULE

2"

3"

2"

TANK TYPE WATER CLOSET

WC-1

SK-1

LAV-1

BATHTUB

3"BT-1

2"

1-1/2"

1-1/2"

1/2"

1/2"

1/2"

1/2"

1/2" 1/2"

3/4"

NG

POTABLE COLD WATER

POTABLE HOT WATER

POTABLE HOT CIRCULATION WATER

NATURAL GAS

FLOOR CLEANOUT

WALL CLEANOUT

BUTTERFLY VALVE

GLOBE VALVE

BALL VALVE

BACKFLOW PREVENTER

DOWN PIPE

VALVE IN RISER

FLOOR DRAIN

ABBREVIATIONS LEGEND GENERAL PLUMBING NOTES

AFF

CFH

CO

CP

DHWR

DHWS

DS

ECR

ECS

ES/EW

ET

EWC

EWH

FCO

FD

FW

GPM

HB

HWR

HWS

LAV

MSB

NG

PW

RPBFP

SD

SH

SK

THW

TMV

TW

U

UW

VTR

WC

WCO

WH

ABOVE FINISHED FLOOR

CUBIC FEET PER HOUR

CLEAN OUT

CIRCULATING PUMP

DOMESTIC HOT WATER RETURN

DOMESTIC HOT WATER SUPPLY

DRENCH SHOWER

ENGINE COOLING WATER RETURN

ENGINE COOLING WATER SUPPLY

EMERGENCY SHOWER AND EYE WASH

EXPANSION TANK

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FLOOR CLEAN OUT

FLOOR DRAIN

FIRE PROTECTION WATER

GALLONS PER MINUTE

HOSE BIBB

HOT WATER RETURN

HOT WATER SUPPLY

LAVATORY

MOP SERVICE BASIN

NATURAL GAS

POTABLE WATER

REDUCED PRESSURE BACK FLOW PREVENTER

SANITARY DRAIN

SHOWER

SINK

TEMPERED HOT WATER

THERMOSTATIC MIXING VALVE

TEMPERED WATER

URINAL

UTILITY WATER

VENT THROUGH ROOF

WATER CLOSET

WALL CLEAN OUT

WATER HEATER

SANITARY DRAIN

VENT PIPING

CHECK VALVE

DESCRIPTIONID

1. THE ENTIRE PLUMBING SYSTEM SHALL BE IN ACCORDANCE WITH THE

2015 EDITION OF THE INTERNATIONAL PLUMBING CODE AND LOCAL PLUMBING

STATUTES/ORDINANCES.

2. THE PIPING INDICATED ON THESE PLANS ARE DIAGRAMATIC. ALL WORK

SHALL BE COORDINATED WITH ALL OTHER TRADES PRIOR TO

INSTALLATION. SUBCONTRACTOR SHALL COORDINATE ROUTING OF ALL

PIPING WITH EXISTING CONDITIONS AND SHALL PROVIDE ANY NECESSARY

OFFSETS, REROUTING, TEES, ELBOWS, ETC. REQUIRED FOR A COMPLETE

AND COORDINATED INSTALLATION.

3. ALL PLUMBING & PIPING SYSTEMS SHALL BE SUPPORTED AS REQUIRED

BY THE LOCAL CODE REQUIREMENTS AND PER MANUFACTURER'S

RECOMMENDATIONS.

4. ALL PIPING PENETRATIONS THROUGH NEW, EXISTING WALL, OR FLOOR

SHALL BE SEALED TO EQUAL THE RATING OF THE NEW, EXISTING

WALL OR FLOOR.

5. TEST POTABLE WATER SYSTEM UNDER A WATER PRESSURE NOT LESS THAN 1-1/2

TIME THE WORKING PRESSURE, BUT NOT LESS THAN 125 PSI. SEE SPECIFICATION

220000 FOR SPECIFIC TESTING AND REPORTING REQUIREMENTS.

6. TEST THE DRAINAGE AND VENTING SYSTEMS WITH WATER. SEE SPECIFICATION

220000 FOR SPECIFIC TESTING AND REPORTING REQUIREMENTS.

7. TEST GAS PIPING SYSTEM UNDER A PRESSURE NOT LESS THAN 1-1/2 TIME THE

WORKING PRESSURE, BUT NOT LESS THAN 3 PSIG. SEE SPECIFICATION 220000 FOR

SPECIFIC TESTING AND REPORTING REQUIREMENTS.

8. ALL (VTR'S) VENT THRU ROOF PENETRATIONS INDICATED ON PLANS

ARE PRELIMINARY. FINAL LOCATIONS SHALL BE COORDINATED WITH

ALL TRADES.

CLOTHES WASHER

2" 1-1/2"CW-1 1/2" 1/2"

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

SS

AutoCAD SHX Text

DJK

AutoCAD SHX Text

AK

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text P-1

AutoCAD SHX Text

REMOVE EXISTING CAST IRON SANITARY DRAIN INSIDE THE RESIDENCE, 6" FROM THE

INSIDE WALL AND ALL THE WAY TO THE PLUMBING FIXTURES. EXISTING CAST IRON

PIPE RUNS UNDER THE FLOOR IN THE CRAWL SPACE.

REMOVE THE EXISTING GALVANIZED POTABLE WATER LINE FROM THE EXISTING

VALVE VAULT ALL THE WAY TO THE PLUMBING FIXTURES. EXISTING GALVANIZED PIPE

RUNS UNDER THE FLOOR IN THE CRAWL SPACE.

EXISTING KITCHEN SINK TO

REMAIN. REMOVE EXISTING

FAUCET, HOT, AND COLD WATER

PIPING INCLUDING THE ISOLATION

VALVES, AND SANITARY DRAIN.

PLUMBING DEMO PLAN

P-2

EXISTING TOILET TO REMAIN. REMOVE EXISTING

FLASH VALVE, COLD WATER PIPING INCLUDING

THE ISOLATION VALVE, AND SANITARY DRAIN.

EXISTING LAVATORY TO REMAIN. REMOVE

EXISTING FAUCET, COLD WATER PIPING

INCLUDING THE ISOLATION VALVE, AND

SANITARY DRAIN.

EXISTING BATHTUB TO REMAIN. REMOVE

EXISTING FAUCET, COLD WATER PIPING

INCLUDING THE ISOLATION VALVE, AND

SANITARY DRAIN.

WC-1

EXISTING VALVE VAULT

EXISTING 1" GALVANIZED PIPE POTABLE WATER SUPPLY

EXISTING INSTANTANEOUS HOT

WATER HEATER TO REMAIN.

SK-1

LV-1

BT-1

KITCHEN

UTILITY

ROOM

MECH

ROOM

OFFICE

BEDROOM #2

BEDROOM #1

CLOSET

CLOSET

CLOSET

BATH

CLOSET

LIVING ROOM

EXISTING SHUTOFF VALVE TO BE DEMOLISHED

CW-1

REMOVE EXISTING HOT, AND COLD WATER

PIPING INCLUDING THE ISOLATION VALVES, AND

SANITARY DRAIN.

GENERAL SHEET NOTES:

1. ALL WORK SHALL COMPLY WITH THE 2015 INTERNATIONAL

PLUMBING CODE.

2. COORDINATE WITH OWNER TO SHUT OFF MAIN WATER SUPPLY

FOR WORK ON MAIN WATER VALVE.

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

SS

AutoCAD SHX Text

DJK

AutoCAD SHX Text

AK

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text P-2

AutoCAD SHX Text

PLUMBING POTABLE WATER

P-3

GENERAL SHEET NOTES:

1. ALL WORK SHALL COMPLY WITH THE 2015 INTERNATIONAL

PLUMBING CODE.

2. COORDINATE WITH OWNER TO SHUT OFF MAIN WATER SUPPLY

FOR WORK ON MAIN WATER VALVE.

3. RETAIN VALVE IN EXTERIOR VALVE VAULT. REPLACE SUPPLY

PIPING FROM VALVE TO NEW COLD WATER MANIFOLD WITH PEX

TO MATCH EXISTING SIZE. USE DIELECTRIC FITTING AT THE

CONNECTION TO THE EXISTING PIPE.

4. WATER SUPPLY LINE ENTERS CRAWLSPACE AT OR BELOW

EXISTING GROUND LEVEL. RAISE NEW PEX PIPE SUPPLY LINE TO

ABOVE EXISTING GROUND LEVEL AND FEED COLD WATER

MANIFOLD IN MECHANICAL ROOM.

5. ALL NEW POTABLE WATER PIPE SHALL BE PEX PER

SPECIFICATION 220000 PLUMBING PIPING AND SPECIALITIES.

6. PROVIDE PIPE INSULATION ON ALL HOT AND COLD LINES PER

SPECIFICATION 220000 PLUMBING PIPING AND SPECIALTIES.

7. REPLACE TOILET FLUSH VALVE. SEE SPECIFICATION 220000.

8. CLOTHES WASHER SUPPLY PART OF WATER DRAIN ROUGH IN

BOX. INSTALL ROUGH IN BOX AT 42" AFF.

9. IF EXTERIOR HOSE BIBS EXIST ON THE RESIDENCE SUBMIT A

SEPARATE COST PROPOSAL FROM THE BASE BID FOR THEIR

REMOVAL AND REPLACEMENT.

10. INSPECT AND MAKE APPROPRIATE REPAIRS TO ALL ROOF AND

EVE VENTS TO PREVENT WATER AND RODENT ACCESS TO THE

ATTIC SPACES.

11. CONTRACTOR SHALL PROTECT EXISTING FLOORING DURING

CONSTRUCTION AND SHALL REPAIR NECESSARY DAMAGES TO

RETURN FLOOR TO CONDITIONS BEFORE CONSTRUCTION.

KITCHEN

UTILITY

ROOM

MECH

ROOM

OFFICE

BEDROOM #2

BEDROOM #1

CLOSET

CLOSET

CLOSET

BATH

CLOSET

LIVING ROOM

1/2" CW

WC-1

LV-1

BT-1

SK-1

1/2" CW

1/2" HW

ALL NEW POTABLE WATER PIPE SHALL BE PEX PER

SPECIFICATION 220000 PLUMBING PIPING AND SPECIALTIES

CONNECT NEW PEX PIPE TO NEW BALL VALVE

EXISTING POTABLE WATER VALVE VAULT

NEW BRONZE BALL VALVE

EXISTING 1" GALVANIZED PIPE POTABLE WATER SUPPLY

1" PEX PIPE RUNS

UNDER THE FLOOR

IN THE CRAWL

SPACE.

1/2" HW

1/2" DOMESTIC HOT WATER PEX PIPE

RUNS UNDER THE FLOOR IN THE CRAWL

SPACE. (TYP FOR 4)

COPPER DOMESTIC HOT WATER

DISTRIBUTION MANIFOLD

3/4" HW

3/4" CW

COPPER DOMESTIC COLD

WATER DISTRIBUTION MANIFOLD

BALL VALVES (TYP)

EXISTING LBG

INSTANTANEOUS HOT

WATER HEATER

DOMESTIC COLD WATER PEX

PIPE RUNS UNDER THE FLOOR IN

THE CRAWL SPACE. (TYP OF 6)

CW-1

1/2" CW

1/2" HW

NEW REDUCED PRESSURE

BACKFLOW PREVENTER

NEW BRONZE BALL VALVE

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

SS

AutoCAD SHX Text

DJK

AutoCAD SHX Text

AK

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text P-3

AutoCAD SHX Text

PLUMBING SANITARY DRAIN

P-4

GENERAL SHEET NOTES:

1. ALL WORK SHALL COMPLY WITH THE 2015 INTERNATIONAL

PLUMBING CODE.

2. INTERCEPT SANITARY DRAINS BELOW FLOOR AND REPLACE

BRANCH AND MAIN LINES WITH PVC PIPE. TRANSITION NEW MAIN

TO EXISTING MAIN SEWER LINE AT 6" INSIDE RESIDENCE SOUTH

WALL.

3. ALL NEW SANITARY DRAINS AND VENTS SHALL BE POLYVINYL

CHLORIDE (PVC), GRAVITY PIPE ASTM D2665/D1785.

4. SLOPE DRAINAGE PIPING 1/4" PER LINEAR FOOT OF DRAIN PIPE.

5. CLOTHES WASHER DRAIN PART OF WATER SUPPLY ROUGH IN

BOX. INSTALL DRAIN P-TRAP AT 12" AFF AND ROUGH IN BOX AT

42" AFF.

KITCHEN

UTILITY

ROOM

MECH

ROOM

OFFICE

BEDROOM #2

BEDROOM #1

CLOSET

CLOSET

CLOSET

BATH

CLOSET

LIVING ROOM

WC-1

LV-1

BT-1

SK-1

CO

CO

3" SD

1 1/2" V

2" VTR

2" SD

1 1/2" V

2" SD

1 1/2" V

P-TRAP

3" SD

4" SD

4" SD

1 1/2" VTR

4" SD

1 1/2" V

EXISTING LPG

INSTANTANEOUS HOT

WATER HEATER

NEW 4" SANITARY DRAIN POLYVINYL

CHLORIDE (PVC), GRAVITY DWV PIPE, ASTM

D2665/D1785, SCH 40

EXISTING 4" CAST IRON SANITARY DRAIN.

3" SD

4" SD

1 1/2" V

2" SD

P-TRAP

P-TRAP

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

SS

AutoCAD SHX Text

DJK

AutoCAD SHX Text

AK

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text P-4

AutoCAD SHX Text

ELECTRICAL SYMBOLS & DETAILS

E-1

OVER COUNTER DUPLEX 5-20R RECEPTACLE

OVER COUNTER DUPLEX 5-20R RECEPTACLE

W/ INTEGRAL GROUND FAULT

WEATHERPROOF DUPLEX 5-20R

RECEPTACLE W/ INTEGRAL GROUND FAULT

220V RECEPTACLE

1-GANG LINE VOLTAGE SWITCH W/OCCUPANCY SENSOR

3-WAY LINE VOLTAGE SWITCH

SMOKE ALARM

CABLE RECEPTACLE

ELECTRICAL LEGEND

# CIRCUIT NUMBER

CARBON MONOXIDE DETECTOR

# CIRCUIT NUMBER

TRANSFER SWITCH

ENCLOSURE (IF REQ)

NEUTRAL

BUS

GROUND

LUG

SERVICE ENTRANCE

DEVICE ENCLOSURE

NEUTRAL

DISCONNECTING

LINK

GROUNDING ELECTRODE

CONDUCTOR TO GROUNDING

ELECTRODE, #4 AWG

NEUTRAL

BUS

NEUTRAL

CONDUCTOR

GROUND BUS

GROUND LUG

SERVICE NEUTRAL

RACEWAY

DUCTBANK GROUND

CONDUCTOR (IF REQ'D)

E-300

SERVICE GROUNDING

REV 010119

NON-SEPARATELY DERIVED SOURCE

3/4"x10' COPPER

CLAD GROUND ROD

FINISH GRADE

EXOTHERMIC

WELD

GROUND CABLE

#4 AWG

NOTE:

1. ELECTRICAL SAMPLE DETAIL.

ES351

BURIED GROUND ROD

REV 010119

INSTALLATION

X a

GF

WP

GF

GF

J G

F

WP

T R

T R

GF

J G

F

WP

T R

T R

DUPLEX 5-20R RECEPTACLE #

CIRCUIT NUMBER

1-GANG LINE VOLTAGE

SWITCH x SWITCH LEG

LIGHT FIXTURE

X FIXTURE TYPE

# CIRCUIT NUMBER

x SWITCH LEG

LIGHT

SWITCH

RECEPTACLE

(EQUIPMENT AREAS, WET

AND CORROSIVE AREAS)

RECEPTACLE OR

TELEPHONE/COMPUTER

(OFFICE AREAS)

DOOR FRAME TRIM

12" MAX

E-450

OUTLET BOX MOUNTING

REV 010119

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

JKB

AutoCAD SHX Text

ARF

AutoCAD SHX Text

KES

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text E-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text

OS

x

ELECTRICAL DEMOLITION PLAN

E-2

GENERAL NOTES:

1. COORDINATE WITH LOCAL POWER COMPANY TO

DISCONNECT POWER TO EXISTING SERVICE PRIOR TO

WORK.

2. DEMOLISH ALL RECEPTACLES, SWITCHES, LIGHT FIXTURES

AND FANS ON INTERIOR AND EXTERIOR OF RESIDENCE.

RETAIN FANS FOR REINSTALLATION IN ORIGINAL

LOCATIONS.

3. DEMOLISH EXISTING SERVICE PANELS CONDUIT AND

JUNCTION BOXES DOWNSTREAM OF EXISTING METER. NEW

MAIN PANEL WILL BE INSTALLED INSIDE RESIDENCE. SEAL

ALL HOLES WITH PAINTABLE WATERPROOF SEALANT AND

PAINT TO MATCH RESIDENCE EXTERIOR.

4. DEMOLISH ALL EXISTING RECEPTACLES, SWITCHES,

INTERIOR OR EXTERIOR PULL BOXES NOT LOCATED IN

ATTIC OR CRAWL SPACES AND WIRING. REMOVE FANS AND

RETAIN TO BE RE-INSTALLED DURING CONSTRUCTION.

5. DEMOLISH AC POWER WHIP IN PREPARATION FOR NEW AC

DISCONNECT AND WHIP.

6. TEST EXISTING GROUND ROD (UNDER EXISTING MAIN

DISTRIBUTION PANEL) FOR RESISTANCE TO GROUND AT OR

BELOW 25 OHMS. IF RESISTANCE IS LOWER THAN

THRESHOLD, IT CAN BE USED AS PART OF NEW SERVICE

GROUNDING ELECTRODE SYSTEM. IF RESISTANCE IS

HIGHER THAN 25 OHMS, DISCONNECT AND DRIVE NO LESS

THAN 6" BELOW GRADE.

7. DEMO CONDUIT AND WIRE TO GARAGE. NEW CONDUIT AND

WIRE WILL BE INSTALLED IN SAME APPROXIMATE LOCATION.

8. CONTRACTOR SHALL PROTECT EXISTING FLOORING DURING

CONSTRUCTION AND SHALL REPAIR NECESSARY DAMAGES

TO RETURN FLOOR TO CONDITIONS BEFORE

CONSTRUCTION.

9. DEMO ALL EXTERIOR PHONE AND COAXIAL CABLES. AS

WELL AS THE DEVICES ON WHICH THEY TERMINATE INSIDE

THE RESIDENCE. SEAL ALL HOLES WITH PAINTABLE

WATERPROOF SEALANT AND PAINT TO MATCH RESIDENCE

EXTERIOR.

CRAWL SPACE

ACCESS

ATTIC

ACCESS

EXISTING PANEL(MAIN BREAKER ONLY)

(EXISTING METER ABOVE PANEL)

EXISTING

BREAKER

PANEL

CONDUIT TO

GARAGE

EXISTING

GROUND ROD

KITCHEN

UTILITY

ROOM

MECH

ROOM

OFFICE

BEDROOM #2

BEDROOM #1

CLOSET

CLOSET

CLOSET

BATH

CLOSET

LIVING ROOM

GF

GF

WP

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

JKB

AutoCAD SHX Text

ARF

AutoCAD SHX Text

KES

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text E-2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Scale in Feet

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Scale in mm

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL PLAN

E-3

CRAWL SPACE

ACCESS

ATTIC

ACCESS

GROUND ROD

(TYP)

IBT

MAIN DISTRIBUTION

PANEL

RANGE HOOD

30A FUSED

DISCONNECT

AC CONDENSER

UNIT

FURNACE

SHEET NOTES:

INSTALL NEW 200A SERVICE DISCONNECT BELOW EXISTING

UTILITY METER. CONNECT WITH 3#3/0 CONDUCTOR.

INSTALL INTERSYSTEM TERMINATION BONDING DEVICE WITH

NOT LESS THAN THREE TERMINALS AND CONNECT TO THE

GROUNDING ELECTRODE CONDUCTOR WITH #6AWG COPPER

CONDUCTOR.

CONNECT NEW MAIN DISTRIBUTION PANEL TO SERVICE

DISCONNECT WITH 3#3/0, 1#4G. CONNECT GROUNDING

ELECTRODE CONDUCTOR TO GROUND RODS NEAR

DISCONNECT WITH PERMANENT CADWELD EXOTHERMIC

WELDED CONNECTIONS.

TEST EXISTING GROUND ROD (UNDER EXISTING MAIN

DISTRIBUTION PANEL) FOR RESISTANCE TO GROUND AT OR

BELOW 25 OHMS. IF RESISTANCE IS LOWER THAN THRESHOLD,

IT CAN BE USED AS PART OF NEW SERVICE GROUNDING

ELECTRODE SYSTEM. IF RESISTANCE IS HIGHER THAN 25 OHMS,

DISCONNECT AND DRIVE NO LESS THAN 6" BELOW GRADE. A

MINIMUM OF TWO GROUND RODS, SPACED NO CLOSER THAN 6'

ARE REQUIRED, WITH A TOTAL SYSTEM RESISTANCE OF NO

MORE THAN 25 OHMS. OTHER SYSTEM GROUNDING METHODS

ARE PERMITTED PER THE 2017 NEC, BUT A MINIMUM OF TWO

GROUND RODS ARE REQUIRED PER THIS CONTRACT.

INSTALL NEW 30A FUSED DISCONNECT AND REFEED AC

CONDENSER WITH 2#10, 1#10G.

ALL NON-FAN LIGHT SWITCHES SHALL INCORPORATE

OCCUPANCY SENSORS COMPATIBLE WITH LED LIGHTING.

RUN NEW 3/4" EMT CONDUIT FROM ATTIC OF RESIDENCE TO

GROUND IN SAME LOCATION OF EXISTING 1/2" CONDUIT

FEEDING GARAGE. TRANSITION TO PVC CONDUIT, SAWCUT

PAVING AND RUN NEW GARAGE FEED IN SAME APPROXIMATE

LOCATION AS EXISTING FEED. FEED NEW 30A SUBPANEL WITH

3#8, 1#8G IN 1" CONDUIT.

CONNECT RG6 CABLE FROM COMMERCIAL COMMUNICATIONS

TERMINAL ON EXTERIOR OF RESIDENCE TO INTERIOR

COMMUNICATIONS PANEL. CONNECT TO INDIVIDUAL ROOMS

USING PASSIVE COAXIAL SPLITTER BOX MANUFACTURED FOR

THE NUMBER OF DEVICES ATTACHED. LABEL EXTERIOR AND

ROOM RG6 CABLES INSIDE COMMUNICATIONS BOX. CONNECT

COPPER PHONE CABLE FROM COMMERCIAL TERMNIAL ON

EXTERIOR OF HOUSE TO COMMUNICATIONS BOX. LAND PHONE

CABLE ON A PHONE TERMINATION BLOCK AND CONTINUE CABLE

TO LIVING ROOM PHONE RECEPTACLE.

EXISTING GARAGE

FEEDER CONDUIT

GENERAL NOTES:

1. INSTALLATION SHALL BE IN ACCORDANCE TO THE 2017 NEC,

INCLUDING ALL APPLICABLE LOCAL ORDINANCES. WIRING

AND DETAILS IN COMMONLY DESCRIBED IN CODE MAY NOT

BE SHOWN ON PLANS BUT ARE APPLICABLE PER CODE

REQUIREMENTS.

2. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS

FOR ELECTRICAL CONSTRUCTION.

3. ALL INTERIOR ELECTRICAL CABLE SHALL BE TYPE NM.

4. COORDINATE EXACT LOCATION OF ALL LIGHTING FIXTURES

WITH EQUIPMENT, DUCTWORK AND PIPING.

5. ALL CIRCUITING; 2#12, 1#12G UNLESS NOTED OTHERWISE

ON THE DRAWINGS OR IN THE SPECIFICATIONS.

6. CIRCUIT 1,3 TO AC SHALL BE FED WITH 2#10, 1#10G.

7. CIRCUIT 9,11 TO DRYER SHALL BE FED WITH 2#10, 1#10G.

8. CIRCUIT 19, 21 TO OVEN SHALL BE FED WITH 2#8, 1#8G.

9. CIRCUIT 22, 28 TO GARAGE SHALL BE FED WITH 3#8, 1#8G.

10. ARRANGE WITH AUTHORITIES AND UTILITY COMPANIES FOR

PERMITS, FEES AND SERVICE CONNECTIONS, VERIFYING

LOCATIONS AND ARRANGEMENT AND PAYING ALL

CHARGES, INCLUDING INSPECTIONS.

11. COORDINATE WORK WITH ARCHITECTURAL FEATURES AND

COORDINATE WORK SO THAT INTERFERENCE BETWEEN

CONDUITS, LIGHTING, EQUIPMENT, PLUMBING WORK AND

BUILDING STRUCTURE WILL BE AVOIDED.

12. ALL RACEWAYS AND EQUIPMENT SHALL BE INSTALLED AND

GROUNDED IN ACCORDANCE WITH THE 2017 EDITION OF

THE NEC AND APPLICABLE LOCAL CODES.

13. THE CONTRACTOR SHALL PROVIDE PULLBOXES WHERE

REQUIRED TO MAKE A WORKABLE INSTALLATION.

14. ALL RECEPTACLES IN OUTDOOR AND ANTICIPATED WET

AREAS SHALL BE GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLES WITH WEATHERPROOF, IN-USE COVERS.

15. FOR LIGHTING AND RECEPTACLE SYSTEMS, ONLY CIRCUIT

NUMBERS ARE SHOWN. CONTRACTOR SHALL PROVIDE ALL

NECESSARY CONDUITS, WIRES, FITTINGS, JUNCTION BOXES

AND ALL NECESSARY COMPONENTS TO MAKE THE

ELECTRICAL INSTALLATION COMPLETE AND OPERATIONAL.

CIRCUIT LOADING SHALL BE AS INDICATED IN THE PANEL

SCHEDULES. ALL CIRCUITS SHALL INCLUDE GROUND WIRE.

16. MULTI-WIRE BRANCH CIRCUITS USING ONE COMMON

GROUNDED OR "SHARED" NEUTRAL CONDUCTOR ARE NOT

PERMITTED.

17. ALL CONDUCTORS SHALL BE COPPER. ALUMINUM BRANCH

CIRCUITS OR FEEDER CONDUCTORS ARE NOT PERMITTED.

18. RECEPTACLES IN KITCHEN, LIVING ROOM, BEDROOMS AND

OFFICE SHALL BE TAMPER-RESISTANT.

19. SURGE PROTECTIVE DEVICE (SPD) SHALL BE INSTALLED IN

PANELBOARD.

20. CONTRACTOR SHALL PROTECT EXISTING FLOORING

DURING CONSTRUCTION AND SHALL REPAIR NECESSARY

DAMAGES TO RETURN FLOOR TO CONDITIONS BEFORE

CONSTRUCTION.

21. CONNECT COMMUNICATIONS OUTLETS TO

COMMUNICATIONS PANEL WITH RG6 CABLE. COIL CABLE

INSIDE PANEL FOR FUTURE TERMINATION.

COMMUNICATION

PANEL

19,21

GF

GF

GF

9,11

USB TYPE A

USB TYPE A

USB TYPE A

USB TYPE A

USB TYPE A

b

F

USB TYPE A

USB TYPE A

GF

GF

200A SERVICE

DISCONNECT

CABLE AND PHONE BOX

CABLE AND PHONE BOX

PHONE AND CABLE

RECEPTACLE

c

4 4 a

A a

A a

C a

A b

GS

a c b a a a b

E b a b

E b a b

A a

E b

A a

E b a b a c b ab a b

A a

12 12

A a

A a

A a

A a

A a

A a

A a

A a

A a

A c

A c

GF

A a

A a

A a

A a

A a

A a

A a

GF

WP

GF

GF

A a

A a

A a

A a

A a

A a

GF

WP

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

JKB

AutoCAD SHX Text

ARF

AutoCAD SHX Text

KES

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text E-3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Scale in Feet

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Scale in mm

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text c

AutoCAD SHX Text

OS

AutoCAD SHX Text

OS

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text a

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

OS

AutoCAD SHX Text

OS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

OS

AutoCAD SHX Text

OS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

OS

AutoCAD SHX Text

AutoCAD SHX Text

CCT

OS

GARAGE PLAN

E-4

GENERAL NOTES:

1. INSTALLATION SHALL BE IN ACCORDANCE TO THE 2017 NEC,

INCLUDING ALL APPLICABLE LOCAL ORDINANCES. WIRING

AND DETAILS IN COMMONLY DESCRIBED IN CODE MAY NOT

BE SHOWN ON PLANS BUT ARE APPLICABLE PER CODE

REQUIREMENTS.

2. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS

FOR ELECTRICAL CONSTRUCTION.

3. COORDINATE EXACT LOCATION OF ALL LIGHTING FIXTURES

WITH EQUIPMENT, DUCTWORK AND PIPING.

4. ALL CIRCUITING; 2#12, 1#12G UNLESS NOTED OTHERWISE

ON THE DRAWINGS OR IN THE SPECIFICATIONS.

5. COORDINATE WORK WITH ARCHITECTURAL FEATURES AND

COORDINATE WORK SO THAT INTERFERENCE BETWEEN

CONDUITS, LIGHTING, EQUIPMENT, PLUMBING WORK AND

BUILDING STRUCTURE WILL BE AVOIDED.

6. ALL RACEWAYS AND EQUIPMENT SHALL BE INSTALLED AND

GROUNDED IN ACCORDANCE WITH THE 2017 EDITION OF

THE NEC AND APPLICABLE LOCAL CODES.

7. THE CONTRACTOR SHALL PROVIDE PULLBOXES WHERE

REQUIRED TO MAKE A WORKABLE INSTALLATION.

8. ALL RECEPTACLES IN OUTDOOR AND ANTICIPATED WET

AREAS SHALL BE GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLES WITH WEATHERPROOF, IN-USE COVERS.

9. FOR LIGHTING AND RECEPTACLE SYSTEMS, ONLY CIRCUIT

NUMBERS ARE SHOWN. CONTRACTOR SHALL PROVIDE ALL

NECESSARY CONDUITS, WIRES, FITTINGS, JUNCTION BOXES

AND ALL NECESSARY COMPONENTS SHOWN OR NOT

SHOWN ON THE DRAWINGS, TO MAKE THE ELECTRICAL

INSTALLATION COMPLETE AND OPERATIONAL. CIRCUIT

LOADING SHALL BE AS INDICATED IN THE PANEL

SCHEDULES. ALL CIRCUITS SHALL INCLUDE GROUND WIRE.

10. MULTI-WIRE BRANCH CIRCUITS USING ONE COMMON

GROUNDED OR "SHARED" NEUTRAL CONDUCTOR ARE NOT

PERMITTED.

11. ALL CONDUCTORS SHALL BE COPPER. ALUMINUM BRANCH

CIRCUITS OR FEEDER CONDUCTORS ARE NOT PERMITTED.

12. RUN NEW 1" EMT CONDUIT FROM ATTIC OF RESIDENCE TO

GROUND IN SAME LOCATION OF EXISTING 1/2" CONDUIT

FEEDING GARAGE. TRANSITION TO PVC CONDUIT, SAWCUT

PAVING AND RUN NEW GARAGE FEED IN SAME

APPROXIMATE LOCATION AS EXISTING FEED. FEED NEW

30A SUBPANEL WITH 3#8, 1#8G IN 1" CONDUIT.

NEW SUBPANEL

DEMO ALL EXISTING CONDUIT,

RECEPTACLES, SWITCHES

AND LIGHT FIXTURES

1 FLOOR PLAN

1/2" = 1' - 0"

2 ELECTRICAL DEMO PLAN

1/2" = 1' - 0"

3 ELECTRICAL PLAN

1/2" = 1' - 0" b

NOTE: ALL WIRE IN GARAGE SHALL BE TYPE XHHW AND RUN

IN NEW CONDUIT.

b

MPC-1

MPC-1

MPC-1

MPC-1

MPC-1

MPC-1

MPC-1

MPC-1

MPC-2

C a

MPC-2

C a

D

MCP-2

b a

D

MCP-2

a b

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

JKB

AutoCAD SHX Text

ARF

AutoCAD SHX Text

KES

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text E-4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Scale in Feet

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL SCHEDULES

E-5

GENERAL NOTES:

1. CIRCUIT BREAKERS IN BEDROOMS, LIVING ROOM, OFFICE

AND PORCH SHALL BE ARC-FAULT TYPE.

2. CIRCUIT BREAKER FOR DISHWASHER SHALL BE GFCI TYPE.

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

INKS DAM

AutoCAD SHX Text

INKS DAM RESIDENCE #3 REHAB DESIGN

AutoCAD SHX Text

JKB

AutoCAD SHX Text

ARF

AutoCAD SHX Text

KES

AutoCAD SHX Text 7/31/20

AutoCAD SHX Text E-5

AutoCAD SHX Text

Residence #3-Cover
Sheets and Views
Cover
Residence #3-Floor Plan
Sheets and Views
Floor Plan
Residence #3-Sheetrock and Insulation Plan
Sheets and Views
GYPSUM BOARD AND INSULATION Plan
Residence #3 - Plumbing Notes Symbols and Details
Sheets and Views
Plumbing General Notes symbols and Details
Residence #3 - Plumbing-Demo Plan
Sheets and Views
Plumbing Demo Plan
Residence #3 - Plumbing-Potable Water Plan
Sheets and Views
Plumbing Plan - Water
Residence #3 - Plumbing Sanitary Drain Plan
Sheets and Views
Plumbing Plan - Waste
Residence #3-Electrical Symbols and Details
Sheets and Views
Electrical Symbols and Details
Residence #3-Electrical Demo Plan
Sheets and Views
Electrical Demo Plan
Residence #3-Electrical Plan
Sheets and Views
Electrical Plan