AMENDMENT 04 page 2.docx

DOCX document 14 KB Posted

Attached to
Appalachian Ranger District Construction
Solicitation number
AG-4670-S-11-0052
Issued by

About this file

Amendment 4 page 2

View the file

Other files

File Type Posted
amend 14.pdf PDF
amend 13.pdf PDF
amend 12.pdf PDF
amend 11.pdf PDF
AMEND 10 E11-Revised 8.19.2011.pdf PDF
amend 10.pdf PDF
amend 9.pdf PDF
revised Atch 1 Schedule of Items.xls XLS spreadsheet
SF 30 AMEND 8.doc DOC document
amend 7.pdf PDF
amend 6.pdf PDF
amend 5.pdf PDF
SF 30 AMEND 4.doc DOC document
E11.pdf PDF
M31.pdf PDF
amendment 3.pdf PDF
E21.pdf PDF
amend.pdf PDF
37 SF 30 AMEND 1.doc DOC document
Atch 3 D Section C.pdf PDF
Atch 3C Dwgs Sec S.pdf PDF
Atch 3A Dwgs Sec E.pdf PDF
Atch 3B Dwgs Sec M0.1 to P1.2.pdf PDF
atch 4.pdf PDF
Attch 2 A Specs..pdf PDF
Atch 3 dwgs Sec A.pdf PDF
Attachment 6 Exp Questionaire.doc DOC document
atch 8.pdf PDF
ORCA GUIDE ATCH 9.doc DOC document
RFP_AG-4670-S-11-0052_Constructiondoc.doc DOC document
atch 5.pdf PDF
Atch 1 Schedule of Items.xls XLS spreadsheet
Attch 2. Spec..pdf PDF
Past Performance Questionaire ATch7.doc DOC document
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT 04 8/15/2011 AG-4670-S-11-0052 PAGE 2 OF 2

1. The finish schedule, page A 4.0, shows several areas (104A, 104B, 115, 117,18A, 118B, 119, 120) receiving systems furniture partitions. This is not addressed in the specifications. Is this an owner supplied material to be installed by the GC, or will both the material and installation be handled by the owner? If the desire of the owner is contractor supplied and installed, please provide specifications for this product.

ANSWER: All system furniture and installation is by the Forest Service.

2. Drawing A 1.1 shows the wall types of rooms 104A and 104B as type B, which is defined on page A 3.2 as wood stud with 1/2" GWB. The finish schedule shown on page A 4.0 shows the north and east walls of rooms 104A and 104B as systems furniture. Also, rooms 117, 118, 119 and 120 are shown with type C walls on the wall type plan, but as systems furniture partitions on the finish schedule. Please clarify the desire for wall type and finish.

ANSWER: . There are no walls of system furniture, walls shall be as noted on the floor plans.

3. There are two 2x2 fixtures in room 101 designated C2. Type C2 is a four foot pendant fixture. What type should these fixtures be?

ANSWER: Rm. 101 2x2 fixtures should be type A2

4. There is a 2x2 fixture in room 104 designated C2A. There is no C2A fixture type. Type C, C1 or C2 are 4’ pendant fixtures. What type should this be?

ANSWER: Rm. 101 2x2 fixtures should be type A2

5. There are discrepancies between the electrical lighting drawing and the reflected ceiling plan. For example in room 113 the lighting plan shows 2 fixtures and the ceiling plan shows four. Also in rooms 111 and 110 the lighting plan shows 2x2 fixtures and the ceiling plan shows recessed can lights ANSWER: The Lighting plan over rules the reflected ceiling plan therefore follow the lighting plan.