Attachment_IB_-_Product_Data_ _Specification_Sheets.pdf

PDF 9 MB Posted

Attached to
Replace Fire Alarm System Federal contract opportunity
Solicitation number
AG-32SD-RFQ-16-MD05
Issued by
Department of Agriculture Agricultural Research Service Central Program Planning Coordination and Support

About this file

Attachment IB - Product Data Specification Sheets

View the file

Other files for this federal contract opportunity

Other files attached to Replace Fire Alarm System, newest first.
File Type Posted
Amendment_01.pdf PDF
Attachment_III_-_Bond_Forms.pdf PDF
AG-32SD-RFQ-16-MD05.pdf PDF
Attachment_II_-_Davis_Bacon-Dona_Ana.pdf PDF
Attachment_IA_-_Stamped_Design_Plan.pdf PDF
Attachment_I_-_Statement_of_Work.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ATTACHMENT IB

Product Data & Specification Sheets

Replace Fire Alarm System

USDA-ARS

Southwestern Cotton Ginning Research Laboratory (SWCGRL)

Mesilla Park, New Mexico

SOL. AG-32SD-RFQ-16-MD05

THIS PAGE IS BLANK

US Agricultural Dept.

Cotton Gin Lab

300 College Ave

Las Cruces NM 88001

Fire Alarm System

Submittal Book

December 16, 2015

By

Dimar Systems, LLC

1581 Tecolote Trail

Las Cruces, NM 88012

Phone: 575-522-1747

US Agricultural Dept.

Cotton Gin Lab

Las Cruces, NM 88001

Submittal Book

TABLE OF CONTENTS Page 1 of 2

1. Fire Alarm Panels

a. ILI‐E3 Series

i. ILI‐MB‐E3 Intelligent Loop Interface‐Main Board

b. DACT‐E3 Digital Communicator Transmitter

c. LCD Keypad DisplayE3 Series 80 Character

d. PM‐9 Power Supply 120 VAC

e. Large Battery Box For 55 AH Batteries

f. E3 SERIES® CABINETS

i. E3BB‐BC/INC Enclosure, Command Center, Black “C” Size

ii. E3ID3‐C Inner Door, Command Center, 2 Slot, “C” Size

iii. E3‐INCC‐CPLATE Command module mounting plate, “C” Size

2. Detectors

a. Velociti® Series Analog, Addressable Photo electronic Smoke Sensor

i. ASD‐PL2F Analog, addressable Photo electronic smoke sensor

b. Velociti® Series Addressable Thermal Sensor

i. ATD‐L2F Addressable thermal sensor, fixed 135° F

c. Intelligent Bases

i. B210LP Flanged mounted base 6.1” diameter

3. Modules

a. MS‐7 Series Fire Alarm Station

i. MA‐7AF Velociti® addressable double action pull station

ii. MS‐7LOB Convention Double Action, Weatherproof Pull Station w/ Back

Box

b. Velociti® Series AMM‐4F addressable monitor module, single circuit, Style D, Class A or Style BC/A and B

c. Safe Fire Detection ThermoCable LHD

TC172(78’C)

TABLE OF CONTENTS Page 1 of 2

4. Notification Devices

a. System Sensor Horn/ Strobe, Wall Mount, Red

P2R

b. System Sensor Horn/ Strobe, Ceiling Mount, Red

PC2R

c. System Sensor Horn/ Strobe, Ceiling Mount, Red Weatherproof

PC2RK

d. System Sensor Horn/ Strobe, Wall Mount, Red Weatherproof

P2RK

e. System Sensor Strobe, Ceiling Mount, Red

SCR

f. CPG Signals Horn/Strobe Explosion Proof

FSEX‐HI‐MOD

5. Power Supplies, Batteries and Surge Protection

a. NAC Expander power supply

i. HPF24S8 8‐amp rated power supply operating at 120VAC/60HZ

b. Batteries

i. BAT‐12700 12 VDC, 7 AH sealed battery

ii. BAT‐12550 12 VDC, 55 AH sealed battery

c. Surge Protection

i. DTK‐120SRD Surge Protector

ii. DTK—2MHLP Series Surge Protector

E3 Series®

Control Panel

Approved

City of Denver

7165-1703:0125 3025415

APPROVED

FM

Reference Certificate of Compliance

VMA-45894-02C

(Revision 1)

FDNY #: 6175

COA # 231-06-E

MEA

Approved

SIGNALING

S1869 1

Class

High Rise Class

City of Chicago

Approved

Features

• IBC Seismic Certified.

• Listed under UL® Standard 864, 9th Edition.

• UL Listed for smoke control (dedicated and non-dedi-cated) when properly configured.

• FM/UL Listed for Pre-action/Deluge use.

• Styles 4, 6, or 7* signaling line circuits.

• Two to 244 SLCs each supporting 159 sensors, 159 modules and 159 addressable sounder bases.

• 625K baud ARCNET communications using wire, fiber, or mixed configurations for installation flexibility.

• High-speed 32 bit processor and 8100 event history log.

• Advanced Boolean logic-based programming such as

AND, OR, NOT, time delay and calendar functions configurable via computer programming.

• Supports up to (16), ASM-16 addressable switch or ANU-48 LED driver modules per ILI-MB-E3/ILI95-MB-E3.

• Two Class A, Style Z or Class B, Style Y, notification appliance circuits rated at 2.0 amps. per circuit.

• Integral city connection.

• Flexible 115,200 baud high speed RS-232 interface.

• 40 character user-defined text per device.

• 15 LCD-SLP displays/annunciators, 6 LCD-E3 displays/ annunciators, 5 LCD-7100/RAN-7100 remote LED annunciators per ILI-MB-E3/ILI95-MB-E3.

*Style 7 wiring requires the use of System Sensor M500X Isolator Modules.

Expandable Emergency Evacuation System

E3 Series Description

The E3 Series® Expandable Emergency Evacuation Sys-tem by Gamewell-FCI is in the forefront of the latest gener-ation of fire alarm control panels. Employing the new high-speed Velociti® sensors, the E3 Series provides previously unattainable polling speed and response together with the flexibility demanded by today’s emergency evacuation sys-tems. In addition to their high-speed polling rate, the Veloc-iti Series of sensors feature bi-polar LEDs that flash green for normal polling, and light red steadily to indicate an alarm.

The E3 Series is equipped with an 80-character LCD-E3 alphanumeric LCD display that allows 40 characters to be user-defined for custom installations. Up to six keyboard LCD displays may also be remotely located. In addition, you can install five of the familiar LCD-7100/RAN-7100 remote displays. The displays show instant system status information and can be connected in any desired area of an installation.

A high-speed 32-bit processor easily tackles a wide array of applications from small office buildings to multi-complex, high-rise installations.

The 64 node networking is made possible by 625K baud/ ARCNET communications using twisted-pair copper cable, fiber-optic cable, or a combination of both. In addition, the Addressable Node Expander (ANX) board expands the network to 122 nodes.

The basic E3 Series is equipped with an ILI-MB-E3/ILI95- MB-E3 Intelligent Loop Interface-Main Board, ILI-S-E3/ ILI95-S-E3 Intelligent Loop Interface Expansion Board, ANX, and ASM-16 Addressable Switch Module that fea-tures 16 software programmable switches, each accompa-nied by red, green and yellow LEDs that can be programmed to indicate operation of the switches. Addi-tional ASM-16 modules may be added to expand the oper-ation to a plateau previously unimagined.

The Intelligent Loop Interface - Expansion Board (ILI-S-E3/ ILI95-S-E3 provides the E3 Series control panel with two additional electrically isolated signaling line circuits. The layout is similar to the ILI-MB-E3/ILI95-MB-E3 with the exception that a number of components are omitted. It occupies one node on the Broadband network.

E3 Series® and Velociti® are registered trademarks of Honeywell International Inc.

UL® is a registered trademark of Underwriters Laboratories Inc.

GAMEWELL-FCI

12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.

©2015 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0637 Rev. O1 page 1 of 2

E337297 Highlight

E337297 Highlight

Description (Continued) Each ILI-MB-E3/ILI95-MB-E3 can support as many as six-teen ANU-48 LED Driver modules supporting hundreds of LEDs on a 3rd party graphic annunciator for remote annun-ciation. The ANU-48 modules may be installed in any Listed remote annunciator. It can be remotely located via an RS-485 serial interface.

An array of cabinets allows for neat, compact, attractive installations.

Installation The E3 Series expandable emergency evacuation system offers four cabinet size options. A typical cabinet includes a backbox, an inner door, and an outer door. The E3 Series cabinet assembly is a compact 19 3/8” (49 cm) wide wall-mounted enclosure.

Cabinet A includes the following four options:

• Cabinet A1 inner door mounted to the backbox. The backbox houses one NGA module.

• Cabinet A2 inner door mounted to the backbox. The backbox houses one LCD-E3 module.

• Two or three-bay inner door mounted to the backbox.

The backbox typically houses one LCD-E3, or one NGA, and one or two ASM-16 modules.

Cabinet B contains a space for the ILI-MB-E3/ILI95-MB-E3, PM-9/PM-9G modules and batteries set inside the back-box. Additional module options mounted on the backbox include the DACT-E3, and RPT-E3 or ILI-S-E3/ILI95-S-E3/ ANX. The 2-bay inner door houses one LCD-E3 module and one ASM-16 module.

Both Cabinets C and D include the following:

• Pre-assembled outer door that gives visibility to the fire fighter’s phone handset and a microphone voice messaging system.

• Two inner door panel selections that may contain optional modules to meet the facility operation requirements.

In the Cabinet B, C and D backboxes, the ANX appears in the same place as the ILI-MB-E3/ILI95-MB-E3 and PM-9/ PM-9G. For information on the installation instructions for any of the E3 Series cabinets, refer to the E3 Series®

Expandable Emergency Evacuation Installation/Operating Manual Part Number: 9000-0574.

Features (Continued) Velociti® Intelligent Sensor Features:

• Poll 318 devices in less than two seconds.

• Activate up to 159 outputs in less than five seconds.

• LED’s blink associated device address during Walk Test.

• Fully digital, hi-precision protocol.

• Up to 9 levels of sensitivity adjustment.

• Pre-Alarm adjustable between 15 levels for both Alert and Action.

• Day/night automatic sensing adjustment.

• Sensitivity windows:

- Ion .05 to 2% obscuration.

- Photo 1 to 3% obscuration.

- Laser .02 to 2% obscuration.

- MCS Acclimate2F .5 to 4%, also self-adjustable options 1 to 2%, 2 to 3%, and 3 to 4%.

- HARSH 1 to 3% obscuration.

• Drift compensation.

• Each Loop Card has its own integral processor providing maximum survivability on loss of any other component. SLC provides full response on loss of any other system processor.

• Optional programmable switches can be configured to enable, disable or group any combination of output devices.

• Integrated point or Grouped Cross Zoning allows for numerous devices installed at any location to cooperate and determine alarm condition.

• Automatic detector sensitivity testing.

• DIRTY and VERY DIRTY detector maintenance alerts.

Specifications Operating Voltage: 24 VDC Operating Temperature: Not to exceed the range of

32° to 120° F (0 to 49° C) Relative Humidity: Not to exceed 93% non-con-densing at 90° F (32° C)

Ordering Information Part Number Description ILI-MB-E3 Intelligent Loop Interface-Main Board ILI95-MB-E3 Intelligent Loop Interface-Main Board ILI-S-E3 Intelligent Loop Interface-Expansion Board ILI95-S-E3 Intelligent Loop Interface-Expansion Board ANX-SR Addressable Node Expander-Single Ring ANX-MR-FO Addressable Node Expander-Multi-Ring

Fiber Optic ANX-MR-UTP Addressable Node Expander-Multi-Ring

Twisted-pair LCD-E3 LCD-E3, LCD Keypad Display

RPT-E3-FO

RPT-E3-UTP

Network Repeater (fiber and twisted-pair) Network Repeater (twisted-pair only)

DACT-E3 Digital Alarm Communicator Transmitter ANU-48 ANU-48 LED Driver Module ASM-16 Addressable Switch Module NGA LCD Network Graphic Annunciator PM-9 Power Supply Module PM-9G Power Supply Module LCD-7100 Remote LCD Display RAN-7100 Remote LCD Display For additional information on the cabinets, refer to the E3 Series Cabinets data sheet (Part Number: 9020-0649).

Seismic Battery Bracket Kits For information on the types of Seismic Battery Bracket Kits that are available, the Seismic Battery Bracket Kit Part Numbers and the installation instructions, refer to the following documents:

• Seismic Battery Bracket Installation Guide, P/N: 53839

• E3 Series Cabinets Data Sheet, P/N: 9020-0649

GAMEWELL-FCI

12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

9020-0637 Rev. O1 page 2 of 2 www.gamewell-fci.com

E337297 Highlight

E337297 Highlight

E385432 Highlight

E385432 Highlight

E385432

GAMEWELL-FCI

12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.

©2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0610 Rev. J page 1 of 1

DACT-E3

Digital Alarm Communicator Transmitter

APPROVED

FM

City of Chicago

Approved 3025415 Class 1

Class 2 High Rise

7165-1703:0125S1869

SIGNALING

MEA

Approved

FDNY:

COA #6077

City of Denver

Approved

Description The Digital Alarm Communicator Transmitter (DACT-E3) is a digital communications circuit. It is an optional compo-nent of the following systems.

• E3 Series® Expandable Emergency Evacuation System

• S3 Series Small Addressable Fire Alarm Control Panel

The DACT-E3 sends digital signals over the telephone net-work to a central station. This module can be located in the main cabinet or remotely located via a local RS-485 serial interface.

The DACT-E3 is compatible with digital alarm communica-tor receivers (DACRs) that receive the following signaling formats:

• SIA DC8 • 3+1 2300 Hz

• SIA DCS20 • 4+2 1400 Hz

• Ademco Contact ID • 4+2 2300 Hz

• 3+1 1400 Hz

In addition to the DACT-E3 being compatible with digital signaling formats, the DACT-E3 features numerous for-mats for communication to a central station. As a digital communicator, the DACT-E3 complies with FCC Part 8, Telecommunication Standards for DC and AC Ringer Equivalence.

Installation Instructions The DACT-E3 is adaptable for installation in standard E3 Series and S3 Series System cabinets. Typically, the DACT-E3 module mounts on standoffs on top of the left side of the ILI-MB-E3/ILI95-MB-E3 or SLP (Smart Loop Panel) module. Either unit can be easily connected to the backbox or sub-assembly plate depending on the cabinet module.

Note: For instructions on installing the DACT-E3, refer to the following documents:

• E3 Series Expandable Emergency Evacuation Installa-tion/Operation Manual, P/N:9020-0574

• DACT-E3 Installation Instructions, P/N:9000-0581

• S3 Series (Small Addressable Fire Alarm Control

Panel) UL Listing Document, P/N:LS10005-051GF-E

Specifications Operating Voltage: 24 VDC (from the PM-9/PM-9G power supply) Operating Current: 0.018 amp Alarm Current: 0.018 amp Operating Temperature: 32° to 120° F (0 to 49° C) Relative Humidity: 0 to 93%, non-condensing at

90° F (32° C) E3 Series® and NetSOLO® are registered trademarks of Honeywell International Inc.

UL® is a registered trademark of Underwriters Laboratories Inc.

Features

• Listed under UL® Standard 864, 9th Edition.

• Communicates with the E3 Series, ILI-MB-E3/ILI95-MB-

E3 or S3 Series SLP sub-assembly via RS-485.

• Transmits in a variety of formats (including full

Contact ID).

• Transmits and verifies data to the central station.

• Offers pre-programmed dialing to the central station phone number.

• Performs on and off-hook status to the phone lines.

• Traces proper central station “ACK” and “Kiss-off” tone.

• Activates hang-up and release phone lines.

• Compatible with the IPDACT Internet Communicator.

Ordering Information

Part Number Description DACT-E3 Digital alarm communicator transmitter

DACT-E3

E385432 Highlight

E385432 Highlight

ILI-E3 Series

Intelligent Loop Interface-Main Board

APPROVED

FM

3025415S1869

SIGNALING

City of Chicago

Approved City of Denver

ApprovedClass 1 Class 2 High Rise

7165-1703:0125

FDNY #: 6175

COA # 231-06-E

MEA

Approved

ILI-MB-E3

Features ILI-MB-E3 and ILI-S-E3:

• Listed under UL® Standard 864, 9th Edition.

• Listed under UL Standard UL2572 for Mass Notification.

• Network ready integral 625K baud ARCNET.

• Supports 115.2K baud RS-232.

• Provides signaling line circuits with the following:

- Two Class A, Style 6, 7* or Class B, Style 4 circuits.

- 40 Character user-defined text per device.

- Capacity of 159 sensors, 159 addressable modules and 159 addressable sounder bases per circuit.

• Includes 8100 Event History Log.

*Style 7 wiring requires the use of the System Sensor M500X Isolator Modules.

ILI-MB-E3 Only:

• Automatically adjusts to any NAC End-of-Line Resistor

(EOL) value (1k-55k ohm) for legacy audible/visual appliances.

• Two notification appliance circuits, Class “A”, Style Z or Class B, Style Y rated at 2.0 amps. per circuit.

• RS-485 supporting 16 ASM-16 switch modules and/or ANU-48 LED driver modules.

• Alarm, trouble, and supervisory dry contacts Form “C”, rated at 2 amp. @ 30 VDC (resistive).

• Supports 1 LCD-SLP display via on-board ribbon cable connector.

• RS-485 terminal supports an additional 14 LCD-SLP displays/annunciators, 6 LCD-E3 displays/annunciators, 5 LCD-7100/RAN-7100 remote LED annunciators.

Description

ILI-MB-E3

The Intelligent Loop Interface-Main Board (ILI-MB-E3) is the main interface for the E3 Series® product line. With its state-of-the-art 32 bit RISC processor, this compact “panel on a board” provides a powerful addition to Gamewell- FCI’s single pair conductor solutions. The ILI-E3 Series is used in the following systems.

• E3 Series Expandable Emergency Evacuation System

• E3 Series Combined Fire and Mass Notification System

This intuitive design provides the following features:

• 2 signaling line circuits • auxiliary power output

• local energy city box output • auxiliary relay functions

• 2 notification application circuits

These features, combined with the built-in network and the serial protocols, allow this module to support a host of new and existing products, resulting in a building block approach to the fire alarm panel design.

The ILI-MB-E3 is network ready and occupies 1 of 64 nodes operating at 625K baud. In addition, the Address-able Node Expander (ANX) board expands the network to 122 nodes. When this sub-assembly is integrated with proven Broadband components, the result is a flexible yet powerful integrated audio solution. When the system trans-mits to remote locations, the optional RPT-E3 provides the ILI-MB-E3 with valuable signal boosting and transient pro-tection, as well as connectivity using both wire and fiber-optic cables.

The ILI-MB-E3 provides 2 signaling line circuits and termi-nals for the connections to up to 159 detectors, 159 mod-ules and 159 addressable sounder bases per SLC in Velociti®. In CLIP™ mode, each SLC supports 99 detectors and 99 modules. The RS-485 interface can support a vari-ety of peripheral devices.

The ILI-MB-E3 relay outputs include system alarm, super-visory, and system trouble contacts. The ILI-MB-E3 pro-vides output for a local energy city master box or remote location which is non power-limited. All other wiring is Class 2 power-limited.

CLIP™ is a trademark of System Sensor.

E3 Series®, NetSOLO® and Velociti® are registered trademarks of Honeywell International Inc.

UL® is a registered trademark of Underwriters Laboratories Inc.

GAMEWELL-FCI

12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.

©2015 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0605 Rev. N1 page 1 of 2

E337297 Highlight

E337297 Highlight

E337297 Highlight

E385432 Highlight

ILI-S-E3

ILI-S-E3

The Intelligent Loop Interface - Expansion Board (ILI-S-E3) provides the E3 Series control panel with 2 additional elec-trically isolated signaling line circuits. The layout is similar to the ILI-MB-E3 except a number of components are omit-ted. The ILI-S-E3 occupies one node on the Broadband network. The ILI-S-E3 provides 2 signaling line circuits and terminals for the connections to up to 159 detectors, 159 modules and 159 addressable sounder bases per SLC in Velociti mode. In CLIP mode, each SLC supports 99 detec-tors and 99 modules.

Installation Typically, the ILI-MB-E3 or ILI-S-E3 can be mounted in the following E3 Series cabinets:

• Cabinet B and D, backbox

• Cabinet B, B-Slim-E3 sub-assembly plate

• Cabinet C, E3-ILI-C sub-assembly plate

• Cabinet C, E3-INCC-C sub-assembly plate

• Cabinet C, E3-INX-C sub-assembly plate

• Cabinet D, E3-INCC-D sub-assembly plate

• Cabinet D, E3-INX-D sub-assembly plate

For instructions on the installation of the ILI-MB-E3 or ILI-S-E3, refer to the following documents:

• E3 Series® Expandable Emergency Evacuation

Installation/Operation Manual, Part Number: 9000-0574

• ILI-MB-E3 Installation Instructions, Part Number: 9000-0579

• ILI-S-E3 Installation Instructions, Part Number: 9000-0569

For information on the ILI95-MB-E3 and ILI95-S-E3, refer to the ILI95-E3 Series Data Sheet, Part Number, 9021-60336.

For information on the ANX, refer to the ANX Data Sheet, Part Number, 9021-60497.

Specifications

ILI-MB-E3

Operating Current: 0.081 amp Alarm Current: 0.150 amp max.

ILI-S-E3

Operating Current: 0.118 amp Alarm Current: 0.119 amp ILI-MB-E3 and ILI-S-E3 Operating Voltage: 24 VDC FWR (from the PM-9/

PM-9G Power Supply).

Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 0 to 93%, non-condensing at 90° F (32° C) Supervised Class 2 Power-Limited SLC 40 Ohms maximum line impedance

0.5 µf maximum line capacitance

Ordering Information

Part Number Description ILI-MB-E3 Intelligent Loop Interface-Main Board ILI-S-E3 Intelligent Loop Interface-Expansion Board

GAMEWELL-FCI

12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

9020-0605 Rev. N1 page 2 of 2 www.gamewell-fci.com

E337297 Highlight

E385432 Highlight

Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.

©2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0606 Rev. I page 1 of 1

LCD-E3

LCD Keypad Display

APPROVED

FM

City of Chicago

Approved City of Denver

Approved3025415 Class 1 Class 2 High Rise

S1869

SIGNALING

7165-1703:0125 Approved

MEA

FDNY:

COA #6077

Description The LCD-E3 provides the main panel display of the E3 Series® Expandable Emergency Evacuation System with indicating LEDs and operating switches. Up to six (6), LCD-E3 displays may be locally or remotely located from the panel via a local RS-485 bus of the E3 Series, ILI-MB- E3/ILI95-MB-E3 or the S3 Series, SLP (Smart Loop Panel) sub-assembly.

The LCD-E3 includes an LCD display for the system status and the following switches and LED indicators:

Switches

• Alarm acknowledge • System reset/lamp test

• Trouble acknowledge • Function buttons:

- menu/back

- back space/edit

- OK

• Signal silence • 12 button keypad

LED Indicators

• AC Power On (green) • Power Fault (yellow)

• Alarm (red) • Ground Fault (yellow)

• Supervisory (yellow) • System Silenced (yellow)

• System Trouble (yellow)

Installation Options The LCD-E3 is adaptable for installation in any of the following E3 Series System cabinets.

Cabinet Part Number

• “A” size cabinet, inner door E3ID2-A

• “A2” flush cabinet E3BB-FLUSH-LCD

• “A2” size cabinet, inner door E3ID-A2

• “B” size cabinet, inner door E3ID2-B

• B-Slim cabinet, outer door E3BB-RBSLIM

• 7200 B Retrofit, inner door 7200-B-RETROFIT

• IF600 Retrofit, outer door IF600-RETROFIT

• “C” size cabinet, inner door E3ID2-C

• 600XL Retrofit, inner door 600XL-RETROFIT

• 7200 C Retrofit, inner door 7200-C-RETROFIT

• “D” size cabinet, inner door E3ID2-D

Specifications Operating Voltage: 24 VDC FWR

(from PM-9 power supply) Operating Current: 0.024 amp Alarm Current: 0.028 amp Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 0 to 93%, non-condensing at

90° F (32° C) E3 Series® is a registered trademark of Honeywell International Inc.

LCD-E3

Features

• Listed under UL Standard 864, 9th Edition.

• Provides an 80-character display of system events together with indicating LEDs and control switches.

• The E3 Series, ILI-MB-E3/ILI95-MB-E3 or S3 Series, SLP can support up to six LCD-E3 displays, any or all of which may be remotely located via the RS-485 serial interface.

• Offers a legible backlit LED display, with low power con-sumption.

Ordering Information

Part Number Description LCD-E3 LCD keypad display

E385432 Highlight

E385432 Highlight

E385432 Highlight

Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.

©2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0555 Rev. O page 1 of 1

PM-9

PM-9 Power Supply

S1869 Vol. 14 S1949 Vol. 19

APPROVED

FM

3017416 7165-1703:0125 Approved

City of

DENVER

Approved

Class 1 Class 2 High Rise

Chicago City of

SIGNALING

FDNY:

COA #6077

MEA

Approved

Description

The Gamewell-FCI, PM-9 Power Supply is a switching power supply that provides 9 amperes of filtered and regu-lated 24 VDC (nominal). It provides the power to the INX Transponder assembly and all of the E3 Series compo-nents. It is a component of the following systems.

• E3 Series® Expandable Emergency Evacuation System

• E3 Series Combined Fire and Mass Notification System

• E3 Series Broadband Voice Evacuation System

• NetSOLO® System

The PM-9 has an internal battery charging circuit capable of maintaining up to 55 A/H batteries. This module is designed for use with the Gamewell-FCI distributed audio networks.

Installation Typically, the PM-9 Module can be mounted in the follow-ing E3 Series cabinets:

• Cabinet B and D, backbox

• Cabinet C, INX-E3 sub-assembly plate

• Cabinet C, INCC-E3 sub-assembly plate

• Cabinet D, E3-INX-D Plate

• Cabinet D, E3-ILI-D Plate

For information on the installation of the PM-9, refer to the following documents:

• E3 Series Expandable Emergency Evacuation

Installation/Operating Manual, P/N: 9000-0574

• PM-9 Installation Instructions, P/N: 9000-0548

• Mass Notification System Manual, P/N:LS10013-000GF-E

Specifications

Input Voltage: 120 VAC 60 Hz @ 3.5 A. max.

Output Voltage: 24 VDC (nominal) FWR Output Current: 9 amperes Output Current: 1 ampere battery charging current Alarm Current: 0.050 amp Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 0 to 93% (non-condensing) at

90° F (32° C) Dimensions: 10 1/2” W x 5” H x 2” D

(27 x 13 x 5 cm)

E3 Series® and NetSOLO® are registered trademarks of Honeywell International Inc.

UL® is a registered trademark of Underwriter’s Laboratories Inc.

Features

• Listed under UL® Standard 864, 9th Edition.

• Listed under UL Standard UL2572 for Mass

Notification.

• Includes 9 ampere, filtered, regulated power supply.

• Provides 1 ampere battery charging current.

• Offers energy and space saving switching technology.

• Contains an integral battery charger capable of recharging up to 55 AH batteries.

(Batteries not furnished).

Ordering Information

Part Number Description PM-9 Power supply 29229 AC Line Filter Kit

PM-9

E337297 Highlight

E337297 Highlight

Batteries - Battery Cabinet

12 Volt - Sealed Lead Acid Rechargeable

Features

• Long life

• Completely sealed

• Charge and discharge in any position

• Low self discharge

• Maintenance Free

Ordering Information

Part Number Description 1100-0653 BC-1 Battery Cabinet, Beige 1100-0654 BC-1R Battery Cabinet, Red 100-2910A B-1.9R Sealed lead calcium battery, 1.9AH

100-2311A B-7R Sealed lead calcium battery, 7 AH 100-2010A B-17R Sealed lead calcium battery, 17

AH

100-2610A B-31 Sealed lead calcium battery, 31 AH 100-2710A B-55 Sealed lead calcium battery, 55AH

G a m e w e ll-F C I G a m e w e ll-F C I

G a m e w e ll-F C I G a m e w e ll-F C I

B C -1 C a b in e t

B -1 .9 R B -7 R

B -1 7 R B -3 1 , B -5 5 Description

Battery Cabinet The Model BC Battery Cabinet is UL Listed and finished in textured red or beige to match the various Gamewell-FCI control panels. The cabinet will house up to four (4) model B-31 or two (2) model B-55 batteries.

The heavy duty cabinet, constructed of 16 gauge steel, is phosphate treated and primed with zinc chromate prior to painting. Knockouts are located at each end of the cabinet.

The cabinet features a hinged, locked cover which is keyed alike with Gamewell-FCI control panels.

Batteries The rechargeable batteries are of sealed lead calcium maintenance-free construction with a fully gelled electrolyte in a polypropylene case. These batteries will not leak or spill even if left upside down for extended periods of time.

Electrical Specifications

Nominal voltage: 12 volts Charging voltage Float 13.5 - 13.8 VDC Cycle 14.4 - 14.8 VDC Operating Temperature Range

Discharge -76° F to +122° F (-60° C to +50° C)

Charge -4° F to +122° F (-20° C to +50° C)

GAMEWELL-FCI

12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.

©2009 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0357 Rev. G1 page 1 of 2

E385432 Highlight

E385432 Highlight

Model B-1.9R

Model B-17R

Model B-7R

Models B-31, B-55

GAMEWELL-FCI

12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

9020-0357 Rev. G1 page 2 of 2 www.gamewell-fci.com

Model Capacity (20 hr. rate) Terminal Type Dimensions Weight B-1.9R 1.9 AH Faston tab “.187" series 7" L x 2.6" H x 1.34" W

(17.78 cm L x 6.6 cm H x 3.4 cm W)

1.9 lbs. (0.86 kg)

B-7R 7 AH Faston tab “.187" series 5.95" L x 3.95" H x 2.6" W (15.11 cm L x 10.03 cm H x 6.6 cm W)

5.75 lbs. (2.61 kg)

B-17 17 AH Terminal posts w/5 mm nut and bolt connectors

7.13" L x 6.57" H x 2.99" W (18.11 cm L x 16.69 cm H x 7.59 cm)

13.2 lbs. (5.99 kg)

B-31R 31 AH “L” blade w/6.4 mm hole 7.75" L x 7.3" H x 5.1" W (19.69 cm L x 18.54 cm H x 12.95 cm)

24 lbs. (10.89) kg

B-55 55 AH “L” blade w/6.4 mm hole at negative, 8.9 mm sq. cutout at positive

10.25" L x 8.75" H x 6.8" W (26.04 cm L x 22.23 cm H x 17.27 cm W)

39 lbs. (17.69 kg)

BC-1 22" L x 10" H x 8.81" W (55.88 cm L x 25.4 cm H x 23.38 cm W)

19 lbs. (8.62 kg)

E385432 Highlight

E385432 Highlight

Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.

©2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0649 Rev. Q page 1 of 4

E3 Series®

Cabinets

Cabinets for the E3 Series®

SIGNALING

S1869 VMA-45894-01C

City of Denver

Approved1

City of Chicago

Approved Class Class High Rise

FDNY:

COA#-6077

MEA

Approved

3025415

APPROVED

FM

7165-1703:0125

Description

E3 Series® and FocalPoint® are a registered trademark of Honeywell International Inc.

Lexan® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.

The E3 Series® Expandable Emergency Evacuation Sys-tem by Gamewell-FCI offers several cabinet size options.

These cabinet options allow for neat, sturdy, attractive installations. The E3 Series cabinet assembly is a com-pact, wall-mounted enclosure. A typical cabinet includes a backbox and an outer locking door. In addition, there are several inner door choices and mounting plates to accom-modate a variety of E3 sub-assemblies.

Each cabinet backbox includes mounting patterns for plates to aid the installer in arranging and securing the sub-assemblies to the backbox. Backbox knockouts are also positioned at numerous points to allow a conduit access into the enclosure.

Four Annunciator Cabinet sizes provide maximum flexibility that can meet any application.

• Cabinet A or AA offers 2 slot and 3 slot options to accommodate either of the following configurations:

- Cabinet A or AA, 2 slot allows space for one

LCD-E3 and one NGA or one ASM-16/ANU-48.

- Cabinet A1 or AA, 3 slot provides space for either one

NGA and two ASM-16s or three ASM-16s/ANU-48s.

• Cabinet A1 houses one NGA or one ASM-16/ANU-48.

• Cabinet A2 accommodates a single LCD-E3 display.

E3BB-RBSlim or B-Slim contains the 600 Series cabinet.

Cabinet B includes a mounting plate that contains a space for the ILI-MB-E3/ILI95-MB-E3, PM-9/PM-9G sub-assem-blies and batteries set inside the backbox. Additional sub-assembly options mounted on the backbox include the DACT-E3 and RPT-E3. The 2 slot inner door houses the following options:

• one LCD-E3 module and

• either one ASM-16/ANU-48 or one NGA module

Both C and D size Command Center cabinets house a vari-ety of E3 Broadband sub-assemblies in multiple configura-tions that provide a solution to a wide range of applications.

Two flexible inner door panel selections are available for C and D size Command Center cabinets that may contain a fire fighter’s phone handset, a microphone, and optional modules to meet the facility operation requirements.

(*Note: See Inner Door and Backbox Mounting Capacities on page 3 and 4).

Features

• IBC Seismic Certified.

• 16-gauge steel backbox.

• Removable outer and inner doors.

• Inner door bonding strap used to provide electrical continuity for grounding.

• Backbox and door ground studs provide positive grounding. 180° opening door with full clearance.

• Available in either black or red.

• Lexan® windows appear on the doors of most cabinets, except the Cabinet “C” and “D” INX cabinets and the INX CAB-B cabinet which contain louvered doors.

• 90° opening door with zero clearance.

• Keylock with quarter turn latch.

• Trim Ring accessories available.

E3 Series® Cabinets

Ordering Information Part Number Description Cabinet “A” & “AA” Size Dimensions: 19 1/4” W x 10” H x 3” D

(49 W x 25 H x 7.6 D cm) E3BB-BA Enclosure, Black, “A” Size E3BB-RA Enclosure, Red, “A” Size E3BB-BAA Enclosure, Black, “AA” (LOC) Size E3BB-RAA Inner Door, AA Plate, Enclosure, Red, “AA” (LOC) Size E31D2-TA Inner Door, 2 Slots, “AA” Size

(INCC-TEL & ASM-16)

E3ID2-A Inner Door, 2 Slots, “A” Size

(LCD-E3 & ASM-16)

E3ID3-A Inner Door, 3 Slots, “A” Size

(NGA, ASM-16 and MIC) Cabinet “A1” & “A2” Size:

Dimensions: 8 3/4” W x 10” H x 4 1/2” D

(22.2 W x 25 H x 7.6 D cm) E3BB-BA1 Assy, Backbox, Remote Enclosure, A1

Size, Black (include inner door) E3BB-RA1 Remote Enclosure, A1 Size, Red

(include inner door) E3BB-BA2 Remote Enclosure, A2 Size, Black

(include inner door) E3BB-RA2 Remote Enclosure, A2 Size, Red

(include inner door) Flush Cabinet A1 Annunciators:

E3BB-FLUSH-LCD CAB A2 Remote Flush LCD ANN with

Keyswitch operation E3BB-FLUSH-NGA CAB A2 Remote Flush NGA ANN with

Password protected Cabinet “B-Slim” Size: (Retrofit Kits) Dimensions: 14” W x 20” H x 4 1/2: D

(35.5 W x 50.8 H x 11 D cm) E3BB-RBSLIM Assy, Enclosure, B-SLIM, Red with

Backplate and LCD-E3 Keyswitch plate.

IF600-RETROFIT Door and Cab mounting plates, disable key switch and door lock (PK-625) for E3 Series upgrade.

Cabinet “B” Size:

Dimensions: 19 3/8” W x 19 3/8” H x 4 1/2” D

(49 W x 49 H x 11 D cm) E3BB-BB Assy, Backbox Enclosure, Black,“B” Size E3BB-RB Assy, Backbox Enclosure, Red, “B” Size E3ID2-B Inner Door, 2 Slots, “B” Size 1100-0460 INX-Transponder 19” (cm) Backbox with

Door, Black.

Dimensions: 19 3/8” W x 19 3/8” H x 4 1/2” D

(49 W x 49 H x 11.43 D cm) Cabinet “C” Size:

Dimensions: 19 3/8” W x 30” H x 4 1/2” D

(49 W x 76 H x 11 D cm) E3BB-BC/INCC Enclosure, Command Center, Black, “C” Size E3BB-RC/INCC Enclosure, Command Center, Red, “C” Size E3ID2-C Assy, Inner Door, Command Center, 2- Bay “C” Size E3ID3-C Assy, Inner Door, Command Center, 3-Bay “C” Size E3BB-BC/INX Assy, Transponder, Black, “C” Size E3BB-RC/INX Assy, Transponder, Red, “C” Size

Ordering Information (Continued) Part Number Description Cabinet “C” Size (Continued) E3-INCC-CPLATE Command Center module mounting plate, “C” Size E3-INX-CPLATE Transponder module mounting plate, “C” Size E3-ILI-CPLATE Intelligent loop module mounting plate “C” Size Cabinet “D” Size:

Dimensions: 19 3/8” W x 41” H x 4 1/2” D

(49 W x 104 H x 11 D cm) E3BB-BD/INCC Enclosure, Command Center, Black, “D” Size E3BB-RD/INCC Enclosure, Command Center, Red, “D” Size E3ID2-D Assy, Inner Door, 2-Bay, “D” Size E3ID3-D Assy, Inner Door, 3-Bay, “D” Size E3BB-BD/INX Enclosure, Transponder, Black “D” Size E3BB-RD/INX Enclosure, Transponder, Red, “D” Size E3-INCC-D-PLATE Command Center module mounting plate, “D” Size E3-INX-D-PLATE Transponder module mounting plate, “D”

Size Optional Extender Plates AM-50 Plate AM-50 Extender Plate FPT-GATE-3-EXT FPT-GATE-3 Extender Plate Optional Accessories 1100-0450 Command Center,blank plate,single size E3-BP Inner door panel, blank, double size 90375 PM-9/PM-9G Adapter Plate Kit, Hardware E3-TRIMKIT-A Trim kit for “A”/”AA” size enclosure, black E3-TRIMKIT-A1 Trim kit for “A1” size enclosure, black E3-TRIMKIT-A2 Trim kit for “A2” size enclosure, black E3-TRIMKIT-B Trim kit for “B” size enclosure, black E3-TRIMKIT-C Trim kit for “C” size enclosure, black E3-TRIMKIT-D Trim kit for “D” size enclosure, black

Bulk Amplification Part Number Description AA-100 100 W Audio Amplifier, @70.7 VRMS with 120 VAC.

AA-120 120 W Audio Amplifier, @25 VRMS with 120 VAC.

ACT-1 Audio coupling transformer, for audio systems w/multiple supplies.

FCI-CHG-120 Battery Charger, 25-120 A/H Gel cell.

FCI-LBB Battery box, accommodates batteries up to 55 A/H, (Black).

Cabinet C:

FCI-DR-C4B Large Battery Backbox, Blank door, lock

& keys, for backbox accepting 3 chassis, (Black).

FCI-DR-C4BR Blank door, lock & keys, for backbox accepting 3 chassis, (Red).

SBB-C4 Backbox, 3 chassis, (Black) Cabinet D:

FCI-DR-D4B Blank door, lock & keys, for backbox accepting 4 chassis, (Black) FCI-DR-D4BR Blank door, lock & keys, for backbox accepting 4 chassis, (Red) SBB-D4 Backbox, 4 chassis, (Black)

GAMEWELL-FCI

12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

9020-0649 Rev. Q page 2 of 4 www.gamewell-fci.com

E364472 Highlight

E364472 Highlight

E364472

Seismic Battery Bracket Kits Part Number Description 90516 7100-Slim 7 A/H Seismic Battery Bracket Kit

E3 B-Slim 7 A/H Seismic Battery Bracket Kit 90517 7100-Slim 12 A/H Seismic Battery Bracket Kit

E3 B-Slim 12 A/H Seismic Battery Bracket Kit 90518 E3 CAB-B 7 A/H Seismic Battery Bracket Kit

E3 CAB-C 7 A/H Seismic Battery Bracket Kit E3 CAB-D 7 A/H Seismic Battery Bracket Kit NetSOLO NS-INX 7 A/H Seismic Battery Bracket Kit NetSOLO 7100 7 A/H Seismic Battery Bracket Kit

90519 E3 CAB-C (INX only) 12 A/H Seismic Battery Bracket Kit E3 CAB-D (INX only) 12 A/H Seismic Battery Bracket Kit NetSOLO NS-INX 12 A/H Seismic Battery Bracket Kit

90520 E3 CAB-B 18 A/H Seismic Battery Bracket Kit E3 CAB-C 18 A/H Seismic Battery Bracket Kit E3 CAB-D 18 A/H Seismic Battery Bracket Kit

Retrofit Kits For information on the Gamewell and 7200 Retrofit Kits, refer to the following Data Sheets.

9021-60678 Gamewell Retrofit Kits Data Sheet 9021-60733 7200 Retrofit Kits Data Sheet

Specifications Inner Door Mounting Capacity Number Components Cabinet A E3ID2-A, Cabinet A, Inner Door, 2 Slots

1 LCD-E3 Display and

1 ASM-16/ANU-48

E3ID2-TA Assembly, Door, Inner, TEL-E3

E3ID3-A, Cabinet A, Inner Door, 3 Slots 1 NGA or ASM-16 2 ASM-16s/ANU-48s

Cabinet AA 1 Microphone

Cabinet A1 E3ID-A1 Cabinet A1, Inner Door, (Included with Box)

1 NGA or ASM-16 Cabinet A2 E3ID-A2 Cabinet A2, Inner Door, (Included with Box)

1 LCD-E3

Cabinet B E3ID2-B, Cabinet B, Inner Door, (Included with Box)

1 LCD-E3 Display and one ASM-16/ANU-48 1 NGA and one ASM-16/ANU-48

B-Slim Cabinet 1 LCD-E3 Display and one RPT-E3 or one

DACT-E3

1 ILI-MB-E3 or one ILI95-MB-E3 1 PM-9 or one PM-9G

Inner Door Mounting Capacity (Cont’d) Number Components Cabinet C E3ID2-C, Cabinet C, Inner Door, 2 Slots

1 LCD-E3 Display and 5 Any combination of ASM-16/ANU-48, NGA or

Microphone Assemblies 1 Telephone Assembly

E3ID3-C, Cabinet C, Inner Door, 3 Slots 7 Any Combination of ASM-16/ANU-48, NGA, or

Microphone Assemblies 1 Telephone Assembly

Cabinet D E3ID2-D, Cabinet D, Inner Door, 2 Slots

1 LCD-E3 Display 11 Any Combination of ASM-16/ANU-48, or NGA or Microphone and 1 Telephone Assembly

E3ID3-D, Cabinet D, Inner Door, 3 Slots 13 Any Combination of ASM-16/ANU-48, NGA or

Microphone Assemblies 1 Telephone Assembly

Backbox Mounting Capacity Number Components E3BB-BAA, Enclosure, “AA’ (LOC) Size, Black

1 INI-VG Series Voice Gateway E3BB-BA, A1 Size Box/Door, Black

1 RPT-E3 Network Repeater E3BB-BB, B Size Box/Door, Black

1 PM-9/PM-9G Power Supply 1 ILI-MB-E3/ILI95-MB-E3 and 1 Additional ILI-MB-E3/ILI95-MB-E3

Loop Interface or ANX or 1 DACT-E3 Digital Communicator and 1 RPT-E3 Network Repeater

INX CAB-B Mounting Plate 1 PM-9 or PM-9G

1 INI-VGX

4 AM-50 Series amplifiers

E3-INCC-C Plate 1 PM-9/PM-9G Power Supply 1 INI-VG Series Voice Gateway 1 ILI-MB-E3/ILI95-MB-E3 Loop Interface and 1 Additional ILI-MB-E3/ILI95-MB-E3/ANX Loop

Interface or 1 DACT-E3 Digital Communicator and 1 RPT-E3 Network Repeater 1 Optional AM-50 or FPT-GATE-3 Extender Plate

GAMEWELL-FCI

www.gamewell-fci.com 9020-0649 Rev. Q page 3 of 4

Backbox Mounting Capacity Number Components E3-ILI-C Plate

1 PM-9/PM-9G Power Supply 1 ILI-MB-E3 or ILI95-MB-E3 2 Additional ILI-MB-E3/ILI95-MB-E3 or ILI-S-E3

/ILI95-S-E3 or ANX

1 DACT-E3

1 RPT-E3

1 Optional FPT-GATE-3 Extender Plate

E3-INX-C Plate 1 PM-9/PM-9G Power Supply with one PM-9/

PM-9G Adapter Plate 1 INI-VGX Voice Gateway

1 ILI-MB-E3 Loop Interface and

1 Additional ILI-MB-E3/LI95-MB-E3/ANX

1 DACT-E3 Digital Communicator and

1 RPT-E3 Network Repeater 4 AM-50 Series Amplifier 1 Optional FPT-GATE-3 Extender Plate

E3-INCC-D Plate 1 PM-9/PM-9G Power Supply 1 ILI-MB-E3 or ILI95-MB-E3 4 Additional ILI-E3 Series or ILI95-E3 Series or

ANX

1 DACT-E3 Digital Communicator 1 RPT-E3 Network Repeater 1 INI-VG Series 1 Optional AM-50 or FPT-GATE-3 Extender Plate

E3-INX-D Plate 1 PM-9/PM-9G Power Supply 1 ILI-MB-E3 or ILI95-MB-E3 1 DACT-E3 Digital Communicator 1 RPT-E3 Network Repeater 1 INI-VG Series 4 AM-50 Series Amplifier 1 Optional FPT-GATE-3 Plate

Backbox Mounting Capacity Number Components E3BB-BD, D Size Box/Command Center (Voice), Black

1 PM-9/PM-9G Power Supply 1 INI-VG Series Voice Gateway 4 ILI-MB-E3/ILI95-MB-E3/ANX Loop Interface and 1 Additional ILI-MB-E3/ILI95-MB-E3/ANX Loop

Interface or 1 DACT-E3 Digital Communicator and 1 RPT-E3 Network Repeater 1 Optional FPT-GATE-3 Plate

E3BB-BD, D Size Box/Command Center, Black 1 PM-9/PM-9G Power Supply 7 ILI-MB-E3/ILI95-MB-E3/ANX Loop Interface and 1 Additional ILI-MB-E3/ILI95-MB-E3/ANX Loop

Interface or 1 DACT-E3 Digital Communicator and 1 RPT-E3 Network Repeater 1 Optional FPT-GATE-3 Extender Plate

Optional Extender Plates AM-50 Extender Plate

1 AM-50-25 or AM-50-70 FPT-GATE-3 Extender Plate

1 FocalPoint® Gateway

1 PNET-1

GAMEWELL-FCI

9020-0649 Rev. Q page 4 of 4 www.gamewell-fci.com

12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.

©2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0617 Rev. J page 1 of 2

Velociti® Series

ASD-PL2F, ASD-PTL2F

and ASD-PL2FR

Analog, Addressable Photoelectronic Smoke Sensor

APPROVED

FM

3023594

SIGNALING

7272-1703:0121S1913

MEA

Approved

FDNY

COA #:219-02-E

Vol.VI

Description

The Gamewell-FCI Velociti® Series, analog address-able plug-in smoke sensors with integral communica-tion provide features that surpass conventional sensors. Sensitivity can be programmed in the con-trol panel software, and is continuously monitored and reported to the panel. Point ID capability allows each sensor’s address to be set, providing exact locations for selective maintenance when the cham-ber contamination reaches an unacceptable level.

The ASD-PL2F photoelectric sensor’s unique optical sensing chamber is engineered to sense smoke pro-duced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixed-tem-perature thermal sensing on the ASD-PTL2F model.

The Velociti® Series use a communication protocol that substantially increases the speed of communica-tion between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concen-trates on the single device. The net effect is a response speed up to five times greater than earlier designs.

Velociti® is a registered trademark of Honeywell International Inc.

UL® is a registered trademark of Underwriters Laboratories Inc.

Ordering Information

Part Number Description ASD-PL2F Analog, addressable photoelectronic smoke sensor ASD-PTL2F Analog, addressable photoelectronic smoke sensor with thermal sensing ASD-PL2FR Analog, addressable photoelectronic smoke sensor used with the DNR duct base when the remote test is required.

Features

• Sleek, low-profile design.

• Visual rotary, decimal switch addressing (01-159).

• Built-in functional test switch activated by an external magnet.

• Bicolor LEDs flash green whenever the sensor is addressed, and light steady red on alarm.*

• Optional relay, isolator, or sounder bases.

• Low standby current.

• Analog addressable communication.

• Stable communication technique with noise immunity.

• Optional remote, single-gang LED Indicator (RA100Z).

• Compatible with Gamewell-FCI analog addressable panels.

Note: *Only the red LED is operative in panels that do not operate in Velociti® mode.

ASD-PL2FRASD-PL2F/ASD-PTL2F

E364472 Highlight

9020-0617 Rev. J page 2 of 2 www.gamewell-fci.com

Installation ASD-PL2F plug-in sensors use a separate base to simplify installation, service, and maintenance. A special tool allows maintenance personnel to plug-in and remove sensors without using a ladder.

Mount the base on a box which is at least 1.5" (3.8 cm) deep. Suitable mounting base boxes include:

• 4.0" (10.2 cm) square box.

• 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box.

• Single-gang box (except relay or isolator bases).

• With B200S or B200SR base, mounted on a 4.0"

(10.2 cm) octagonal or square box.

• With B224RB or B224BI base, mounted on a 3.5"

(8.9 cm) octagonal box, or a 4.0" (10.2 cm) octagonal or square box.

NOTE: Because of the inherent supervision provided by the SLC, end-of-line resistors are not required.

Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring.

Sensor Spacing

Gamewell-FCI recommends that the spacing sensors be used in compliance with NFPA 72.

Specifications

ASD-PL2F, ASD-PTL2F, ASD-PL2FR:

Dimensions: 2.1” (5.1 cm) height Diameter: 4.1” (10.4 cm) installed in the B501 base 6.1” (15.5 cm) installed in the B210LP base Shipping Weight: 5.2 oz. (147 g) Operating Temperature:

ASD-PL2F:

32° F to 120° F (0° C to 49° C)

ASD-PTL2F:

32° F to 100° F (0° C to 38° C)

UL®-Listed Velocity Range:

0-4000 ft./min. (1,219.2 m/min.), suitable for installation in ducts.

Relative Humidity: 10-93% (non-condensing)

Thermal Ratings: Fixed-temperature setpoint 135° F (57° C)

Electrical Specifications

Voltage Range: 15 – 32 volts DC peak Standby Current: (max. avg.): .0003 A @ 24 VDC

(One communication every 5 seconds with LED blink enabled).

Maximum Alarm- Current: .0065 A @ 24 VDC (LED) lit).

Bases and Options B501 Plug-in sensor base without flange Dimensions: 4.1” (10.4 cm) diameter B210LP Flanged mounting base Dimensions: 6.1” (15.5 cm) diameter B210LPBP Flanged mounting base bulk pack Dimensions: 6.1” (15.5 cm) diameter

B224RB

Relay Base

Plug-in sensor base with auxiliary relay, SPDT, rated 2 amps @ 30 VDC (resistive).

Screw terminals:

Up to 14 AWG (2.0 mm2) 2 coil latching relay 1 Form C contact UL/CSA Rating:

0.9 A @ 125 VAC, inductive

0.9 A @ 110 VDC, inductive

3 A @ 30 VDC, resistive

Dimensions: 6.1” (15.5 cm) diameter Maximum: 25 devices between isolator bases.

B200S Intelligent sensor sounder base Dimensions: 6.875” (17.5 cm) diameter B200SR Standard sounder base, UL 8649th

Edition compliant, ULC Listed Dimensions: 6.875” (17.5 cm) diameter RA100Z Remote LED Annunciator BCK-200 Black detector covers (box of 10) DNR Duct smoke housing

Velociti® Series

ATD-L2F, ATD-RL2F

Addressable Thermal Sensor

APPROVED

FM

3023594

SIGNALING

7270-1703:0115S2332

MEA

Approved

219-02-E Vol.VI

An ISO 9001-2000 Company

Features

• Sleek, low-profile design

• Visual rotary switch addressing

• Built-in functional test switch activated by an external magnet

• Bicolor LEDs flash green whenever the sensor is addressed, and light steadily red on alarm*

• Optional relay, isolator, or sounder bases

• Low standby current

• Addressable communication

• Stable communication technique with noise immunity

• Optional remote, single-gang LED accessory

(RA-100Z)

• Suitable for installation in ducts

Note: *Only the red LED is operative in panels that do not operate in Velociti® mode.

ATD-L2F

Description

The Gamewell-FCI Velociti® Series, addressable plug-in thermal sensors with integral communication provide fea-tures that surpass conventional sensors. Point ID capabil-ity allows each sensor’s address to be set, providing exact locations for pinpointing alarm locations and for selective maintenance. ATD thermal sensors use an innovative thermistor sensing circuit to produce 135°F/57°C fixed-temperature (ATD-L2F). The ATD-RL2F provides a combi-nation 15°/minute rate-of-rise with 135° fixed thermal detection that is included in a low-profile package. The ATD-HL2F provides fixed high-temperature detection at 190°F/88°C. These thermal sensors provide cost-effective, addressable property protection in a variety of applica-tions.

The Velociti® Series uses a communication protocol that substantially increases the speed of communication between the sensors and Gamewell-FCI analog address-able fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and identifies the single device with the status change.

The net effect is response speed up to five times greater than earlier designs.

Installation ATD plug-in sensors use a separate base to simplify instal-lation, service, and maintenance. A special tool allows maintenance personnel to plug-in and remove sensors without using a ladder.

Mount the base on a box which is at least 1.5" (3.8 cm) deep. Suitable mounting base boxes include:

• 4.0" (10.2 cm) square box.

• 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box.

• Single-gang box (except relay or isolator base).

• With B200S or B200SR base, mounted on a 4.0"

(10.2 cm) octagonal or square box.

• With B224RB or B224BI base, mounted on a 3.5" (8.9

cm) octagonal box, or a 4.0" (10.2 cm) octagonal or square box.

NOTE: Because of the inherent supervision provided by the SLC, end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring.

Velociti® and E3 Series® are registered trademarks of Honeywell International Inc.

UL® is a registered trademark of Underwriters Laboratories Inc.

ULC® is a registered trademark of Underwriters Laboratories Canada Inc.

GAMEWELL-FCI

12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.

©2011 by…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .