RCx_FINAL_REPORT_A.iv.pdf
PDF 530 KB Posted
- Attached to
- Building Automation System Control Upgrades Federal contract opportunity
- Solicitation number
- AG-32SC-S-17-0044
About this file
RCx Final Report A.iv
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_AG-32SC-S-17-0044_Amd_000001.pdf | ||
| Revised_SOW.pdf | ||
| Q&A.pdf | ||
| Past_Performance.pdf | ||
| Brand_Name_-_Siemens_Cntrls_CCRU_BAS_Upgrades_Redacted.pdf | ||
| AG-32SC-S-17-0044.pdf | ||
| RCx_FINAL_REPORT_A.v.pdf | ||
| ARS371.pdf | ||
| RCx_FINAL_REPORT_A.iii.pdf | ||
| RCx_FINAL_REPORT_B.xiii.pdf | ||
| RCx_FINAL_REPORT_B.xiv_and_B.xv.pdf | ||
| Wage_Determination.pdf | ||
| RCx_FINAL_REPORT_A.xix.pdf | ||
| Statement_of_Work.pdf | ||
| Mechanical_Drawings.pdf | ||
| ARS372.pdf | ||
| RCx_FINAL_REPORT_B.iv.pdf | ||
| RCx_FINAL_REPORT_A.ii.pdf | ||
| RCx_FINAL_REPORT_B.i.pdf | ||
| General_Conditions.pdf |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DIFFUSER AND GRILLE TEST REPORT
SYSTEM AHU-1 AREA SERVED AS NOTED
Drawing M-111
Design Final Location No. Size Flow Coefficent VEL CFM Test 1 Test 2 Test 3 VEL CFM Remarks
CVS-149-1 MAX 0.79 100 105 105
MIN 50 50 50
149 AD-1 100 105 105
CVS-152-1 MAX 0.62 700 880 705
MIN 350 350 350
152 1 AD-4 350 350 355
2 AD-4 350 530 350
CVS-120-2 MAX 0.74 200 280 210
MIN 200 280 210
CVS-135-1 MAX 0.67 150 160 160
MIN 75 80 80
135 AD-1 150 160 160
CVS-126-1 MAX 0.67 1420 1380 1385
MIN 710 700 700
126 1 AD-3 350 400 360
2 AD-3 350 320 345
3 AD-3 350 320 340
4 AD-3 350 340 340
CVS-148-1 MAX 0.64 510 660 510 Runs off temperature not CFM
MIN 255 - 260 Runs off temperature not CFM
148 1 AD-2 255 320 260 Runs off temperature not CFM
2 AD-2 255 340 250 Runs off temperature not CFM
CVS-147-1 MAX 0.65 510 670 530 Runs off temperature not CFM
MIN 255 - 260 Runs off temperature not CFM
147 1 AD-2 255 340 265 Runs off temperature not CFM
2 AD-2 255 330 265
CVS-134-1 MAX 0.67 200 210 210
MIN 100 105 105
134 200 210 210
DATE 2/22/2013 TECHNICIAN DAS SYSTEM PAGE 3 OF 10
120 AD-2 200 280
USDA Cereal Crops Survey 12-338 Page 6 of 55
SECTION 10 - TAB REPORT (2013)
joer Rectangle joer Rectangle joer Accepted
Trisha.Vigil Callout A.iv
DIFFUSER AND GRILLE TEST REPORT
SYSTEM RF-2 AREA SERVED AS NOTED
Drawing M-111
Design Final Location No. Size Flow Coefficent VEL CFM Test 1 Test 2 Test 3 VEL CFM Remarks
152 1 AD-11 500 - - DELETED (NOW EF-7)
CABNET 2 75 75 75
CVE 148-1 MAX 0.64 660 655 655 Runs off temperature now.
MIN 660 655 655 Runs off temperature now.
148 1 AD-9 330 330 330 Runs off temperature now.
2 AD-9 330 325 325 Runs off temperature now.
CVE 147-1 MAX 0.64 660 640 640 Runs off temperature now.
MIN 660 640 640 Runs off temperature now.
147 1 AD-9 330 315 315 Runs off temperature now.
2 AD-9 330 325 325 Runs off temperature now.
CVE 146-1 MAX 660 655 655 Runs off temperature now.
MIN 0.62 660 655 655 Runs off temperature now.
146 1 AD-9 330 330 330 Runs off temperature now.
2 AD-9 330 325 325 Runs off temperature now.
CVE 145-1 MAX 0.60 660 710 Runs off temperature now.
MIN Runs off temperature now, not CFM set points.
660 710
1 AD-9 330 355 355
2 AD-9 330 355
CVE 144-1 MAX 0.58 260 260 260
MIN 260 260 260
144 1 AD-8 260 260 260
CVE151-1 MAX 0.60 150 150 150
MIN 150 150 150
151 1 AD-7 150 150 150
CVE-162-1 MAX 0.64 810 820 820
MIN 810 820 820
162 1 AD-12 810 820 820
DATE 2/23/2013 TECHNICIAN DAS SMO SYSTEM PAGE 2 OF 4
USDA Cereal Crops Survey 12-338 Page 16 of 55
SECTION 10 - TAB REPORT (2013)
joer Rectangle joer Rectangle joer Highlight joer Exclamation Point joer Highlight joer Highlight joer Highlight joer Highlight joer Highlight joer Highlight joer Highlight joer Highlight joer Highlight joer Highlight joer Highlight joer Highlight joer Highlight joer Highlight
Trisha.Vigil Callout A.iv