Mechanical_Drawings.pdf
PDF 7 MB Posted
- Attached to
- Building Automation System Control Upgrades Federal contract opportunity
- Solicitation number
- AG-32SC-S-17-0044
About this file
Mechanical Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_AG-32SC-S-17-0044_Amd_000001.pdf | ||
| Revised_SOW.pdf | ||
| Q&A.pdf | ||
| Past_Performance.pdf | ||
| Brand_Name_-_Siemens_Cntrls_CCRU_BAS_Upgrades_Redacted.pdf | ||
| AG-32SC-S-17-0044.pdf | ||
| RCx_FINAL_REPORT_A.v.pdf | ||
| RCx_FINAL_REPORT_B.iv.pdf | ||
| RCx_FINAL_REPORT_A.ii.pdf | ||
| RCx_FINAL_REPORT_B.i.pdf | ||
| General_Conditions.pdf | ||
| RCx_FINAL_REPORT_B.xiv_and_B.xv.pdf | ||
| Wage_Determination.pdf | ||
| RCx_FINAL_REPORT_A.xix.pdf | ||
| Statement_of_Work.pdf | ||
| ARS372.pdf | ||
| RCx_FINAL_REPORT_A.iv.pdf | ||
| ARS371.pdf | ||
| RCx_FINAL_REPORT_A.iii.pdf | ||
| RCx_FINAL_REPORT_B.xiii.pdf |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Trisha.Vigil Callout A.i
Trisha.Vigil Callout A.vii
Trisha.Vigil Callout B.xi
Trisha.Vigil
B.xii
B.iii
Trisha.Vigil Callout B.iv
Trisha.Vigil Callout B.xiv and B.xv
Trisha.Vigil
B.ii
B.vi
Line
A.xxiv
A.viii Return fan shall be slowed down to match airflow of supply fan
Trisha.Vigil Callout A.x
Trisha.Vigil Callout B.ix Implement a program that controls the exhaust fans (EF-1 and EF-2) in which there is one lead fan, one lag fan, and one standby fan. The new static pressure setpoint for EF-1 and EF-2 will be - 2.85" H2O. When the one lead fan cannot keep up with the load demand, the lag fan will start and the bypass dampers will operate in parallel with the lead fan bypass dampers. With both the lead and lag fans operating, once the load drops to the point where the bypass dampers are 100% open, the lag fan will be shut down again. As before, the standby fan shall be put in place of either the lead or lag fan in the event of a fan failure. During unoccupied times only the lead fan will operate.
A.xi
Trisha.Vigil Callout A.xii
Trisha.Vigil Line
Trisha.Vigil Callout A.xii
Trisha.Vigil Line
Trisha.Vigil Callout B.vii
Trisha.Vigil Callout A.vi
Trisha.Vigil Line
Trisha.Vigil Line
Trisha.Vigil Callout A.xiv
Trisha.Vigil Callout B.viii
Trisha.Vigil Callout B.xvi
A.xxvi. Program a 1 deg F deadband.
Trisha.Vigil
B.x Setpoint to be reduced to 55 deg F (typ x33)
A.xxv (typ. x4)
| M-001 |
| M-110 |
| M-111 |
| M-112 |
| M-113 |
| M-120 |
| M-121 |
| M-210 |
| M-310 |
| M-410 |
| M-411 |
| M-412 |
| M-500 |
| M-501 |
| M-502 |
| M-503 |
| M-610 |
| M-611 |
| M-612 |
| M-613 |
| M-710 |
| M-810 |
| M-811 |
| M-812 |