This document appears to be a set of drawings and specifications related to a federal contract opportunity to replace the humidification system at the Springfield Armory National Historic Site.
The key details are:
- The contract opportunity is for the SPAR (Springfield Armory) to replace the aged and failing humidification system in Building 13.
- The solicitation number is 140P4324R0048 and is issued by the Department of the Interior National Park Service Northeast Region.
- The drawings provide demolition instructions, protection requirements, utility maintenance guidance, and specification details for the new humidification system.
- The new humidification system will include five steam humidifiers with moisture outputs ranging from 25 to 100 lbs/hr, connected to ductwork with steam dispersion tubes.
- The humidifiers will be controlled with a packaged control system compatible with the site's building management system.
- The drawings also include a detailed humidifier piping detail showing the requirements for the steam supply, condensate drain, and support.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P4324R0048_Amd_0002.pdf | ||
| Sol_140P4324R0048_Amd_0001.pdf | ||
| Amd0001-140P4324R0048_0001.docx | DOCX document | |
| B08_Solit_Clauses_Construction-SPAR_Humidifiers.docx | DOCX document | |
| B08-Attachment_6-Past_Performance_Questionnaire.doc | DOC document | |
| B08_Attachment_7-Limitation_on_Subcontracting_Report_Template.xlsx | XLSX spreadsheet | |
| A04_SPAR_PMIS_259831_HUMIDITY_SYSTEM__SPECS.pdf | ||
| Sol_140P4324R0048.pdf | ||
| M3_0_.pdf | ||
| B08-WD-MA20240003-7_5_24.pdf | ||
| B04-Attachment_2-Tech_Eval_Factors.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. REFER TO ALL DRAWINGS SPECIFICATION FOR GENERAL DESCRIPTION OF AREAS REQUIRING DEMOLITION.
2. REFER TO CONSTRUCTION MANAGER'S INSTRUCTIONS FOR ALL EXISTING EQUIPMENT AND MATERIALS THAT SHALL REMAIN THE PROPERTY
OF THE OWNER.
3. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO BE RETURNED TO THE OWNER, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM SITE AND LEGALLY DISPOSED OF. STORAGE OR SALE OF ITEMS ON THE PROJECT SITE IS PROHIBITED.
4. PROTECTION: ENSURE THE SAFE PASSAGE OF PERSONS IN AND AROUND THE BUILDING DURING DEMOLITION. PREVENT INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY REPAIR DAMAGED PROPERTY TO THE CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE MEASURES TO PREVENT WINDBLOWN DUST.
5. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES SERVING OCCUPIED AREAS WITHOUT FIRST OBTAINING PERMISSION FROM HARVARD FACILITIES.
PROVIDE TEMPORARY SERVICES AS REQUIRED.
6. THESE DRAWINGS ARE DIAGRAMMATIC ONLY AND REFLECT OVERALL SYSTEM REMOVAL. NOT EVERY ITEM OR COMPONENT OF A SYSTEM IS
SHOWN.
7. THIS CONTRACTOR SHALL PROVIDE SHUT DOWN OF SERVICES (BOILERS, AHU, PUMPS, ETC.) AND TRACING OF ALL PIPING WITHIN BASE BID.
HVAC DEMOLITION SPECIFICATION
1. GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO ALL MX.XX SERIES DRAWINGS.
2. DRAWINGS ARE DIAGRAMMATIC, DETERMINE EXACT LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD.
3. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS.
4. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
5. PROVIDE INFORMATION AND HARDWARE AS NECESSARY TO COORDINATE CONCRETE PADS AND STEEL PLATFORMS REQUIRED FOR MECHANICAL
WORK.
6. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH FLASHING REQUIREMENTS.
7. SHEETMETAL FITTINGS SHOWN ARE TO BE PROVIDED. NO SUBSTITUTES SHALL BE ALLOWED WITHOUT PRIOR CONSENT FROM
ARCHITECT/ENGINEER.
8. REFER TO SPECIFICATIONS FOR DUCTWORK CONSTRUCTION CLASSES, SEAL, AND LEAKAGE CLASSES.
9. RUN DUCTS AND PIPING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS. ALL DUCTWORK SHALL BE INSTALLED AS
CLOSE AS POSSIBLE TO WALL AND UNDERSIDE OF BEAMS AND JOISTS.
10. INSTALL THERMOSTATS AT LOCATIONS SHOWN ON PLANS OR AS DIRECTED BY ARCHITECT. MOUNTING HEIGHT AFF SHALL COMPLY WITH ADA.
11. EXTERIOR LOUVERS ARE INDICATED FOR LOCATION ONLY.
12. ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN PIPING AND DUCTS (INCLUDING DIVIDED DUCTS) AND TRANSITIONS
AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST.
13. VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED DRAWINGS. VERIFY AND PROVIDE DUCT TRANSITIONS TO FURNISHED
EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DIMENSIONS BEFORE FABRICATION.
14. ACCESS PANELS SHALL BE PROVIDED TO CLEAN COILS AND SERVICE DAMPERS, HEATERS, VALVES AND ALL CONCEALED MECHANICAL
EQUIPMENT.
15. SUPPORT ALL EQUIPMENT, PIPING AND DUCTWORK FROM BUILDING STRUCTURE TO PROVIDE A VIBRATION FREE INSTALLATION. PROVIDE TO GC A LIST OF ALL WEIGHTS AND METHODS OF SUPPORT FOR COORDINATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
16. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED TO THE FIRE ALARM SYSTEM IN ACCORDANCE WITH DIVISION 28 SPECIFICATIONS. MOUNT THE DETECTORS IN DUCTWORK. SMOKE DETECTORS SHALL BE INSTALLED AND WIRED TO THE BAS SYSTEM AND FAN STARTERS FOR SHUTDOWN
IN ACCORDANCE WITH DIVISION 23 SPECIFICATIONS.
17. SMOKE DAMPERS SHALL BE UL555S LISTED.
18. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH NEC, AND DIVISION 26 SPECIFICATIONS.
19. INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. CONTRACTOR SHALL INCREASE SIZE FOR LINER IF APPLICABLE.
20. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, OTHER THAN SPECIFIC RENTED ITEMS IDENTIFIED ON PLANS.
21. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZE ARE NOMINAL.
22. ALL CONDENSATE DRAIN LINES SHALL HAVE A BALL VALVE AND CAPPED.
23. PROVIDE FIRE DAMPERS OR SMOKE/FIRE DAMPERS AND ASSOCIATED ACCESS PANELS WHERE SHOWN ON DRAWINGS IN COMPLIANCE WITH 2018 INTERNATIONAL MECHANICAL CODE. FOR DUCTS THAT PENETRATE FIRE WALLS, FLOORS AND PARTITIONS PROVIDE SLEEVES WHERE PENETRATIONS ARE NOT PERPENDICULAR TO SURFACE PENETRATED. ENCLOSE DAMPERS IN 10 GAUGE STEEL SLEEVE.
24. PROVIDE FLEXIBLE CONNECTIONS ON ALL DUCTS CONNECTING TO FANS AND AIR HANDLING UNITS UNLESS INTERNALLY ISOLATED. ALL DUCTS TO
BE GROUNDED ACROSS FLEXIBLE CONNECTION WITH FLEXIBLE COPPER GROUNDING STRAPS.
25. THE INSIDE OF DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE PAINTED FLAT BLACK.
26. INSULATE PIPING AND DUCTWORK AS SPECIFIED: PERFORM TESTS SPECIFIED BEFORE INSULATING.
27. PROVIDE HANGERS, CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ON PIPING.
28. PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS.
29. PROVIDE AT LEAST THREE-ELBOW SWING FOR PIPE TAKE-OFFS TO TERMINAL EQUIPMENT AND RISERS.
30. ELBOWS IN DUCT SYSTEMS SHALL BE FULL RADIUS (CENTERLINE RADIUS = 1.5 DUCT WIDTH) WHERE SPACE PERMITS. WHERE LIMITED CLEARANCE OCCURS, PROVIDE SHORT RADIUS ELBOW WITH FULL LENGTH SPLITTER VANES PER SMACNA. MITERED (SQUARE) ELBOWS WITH TURNING VANES MAY NOT BE SUBMITTED WITHOUT WRITTEN CONSENT FROM THE ARCHITECT/ENGINEER.
31. ISOLATION VALVES IN PIPING SYSTEMS ARE NOT SHOWN ON PLANS (FOR CLARITY) BUT ARE REQUIRED AT ALL PIPE BRANCHES AND
CONNECTIONS TO EQUIPMENT REFER TO DETAIL SHEETS AND FLOW DIAGRAMS.
32. PITCH PIPING 1 INCH IN 20 FEET MINIMUM IN DIRECTION OF FLOW, TO ALLOW FOR DRAINING
33. MANUAL DAMPERS ARE NOT SHOWN ON THE DRAWINGS IN ORDER FOR DRAWING CLARITY. PROVIDE MANUAL ADJUSTABLE DAMPERS ON EACH LOW PRESSURE SUPPLY, RETURN, AND EXHAUST DUCT TAKE OFF, AND AT EACH TAKE OFF TO REGISTERS, GRILLES AND DIFFUSERS.
34. PROVIDE CEILING ACCESS PANELS BELOW ALL EQUIPMENT LOCATED ABOVE CEILINGS. EXACT SIZE AND LOCATION SHALL BE COORDINATED IN
FIELD WITH ARCHITECT.
GENERAL NOTESHYDRONIC SYSTEM SPECIFIC ABBREVIATIONSGENERIC HVAC ABBREVIATIONS
AIR SYSTEM SPECIFIC ABBREVIATIONS
GE
FSD
FPI
FLTR
FD
FCU
AC
ACC
ACD
AF
AHU
ALD
ATD
AVS
F F&B
FB
FC
FA
AIR CONDITIONING
AIR COOLED CONDENSER UNIT
AIR FOIL
AIR HANDLING UNIT
AIR VOLUME TRAVERSE STATION
FAN
FACE AND BYPASS
FAN BOX
FORWARD CURVED
FREE AREA
FIRE DAMPER (W/ ACCESS DOOR)
COMBINATION FIRE/SMOKE
DAMPER
FINS PER INCH
FILTER
GENERAL EXHAUST
°F °C Ø
DEGREES FAHRENHEIT
DIAMETER
DEGREES CELSIUS
ACV
AD
ADJ
ADDL
AFF
AFG
ALT
ALUM
AP
ARCH
ATC
ATV
AVG
BAS
BBD
BDT
BF
BFF
BHP
BLDG
BLR
BOD
BOP
BOT
BSMT
BTU
BTUH
C
CA
CF
CL
CLG
CO
COL
COMP
CONC
CONN
CONTR
CORR
CUF
CUH
CYL
CRCU
D
DB
DC
DDC
DIA
DIM
DN
DWG
EA
EAT
EFF
ECUH
ELEC
ELEV
EMER
EMS
ENT
EQUIP
EUH
EXH
EXP
FAS
FOB
FOT
FTR
FCV
FFOP
FG
FLEX
FLR
FLRDR
FP
FPM
FT
FT/SEC
FURN
FVNR
G
GA
GAL
GALV
GC
GND
GPH
GPM
GRD
GWB
H
HCPD
HD
HP
HPG
HR
HZ
HX WRT
WG
WF
WB
W/O W/ W
VTR
VFD
VERT
VEL
V
TYP
TOP
TOD
TEMP
TEL
TEFC
TAV
TA
SUP
SUCT
STL
STDBY
STD
SS
SQFT
SQ
SPECS
SOV
SCH
RPM
RM
R.H.
REQS
REQD
RET
REP
R
PVC
PSIG
PSID
PSIA
PRIM
PR
PRESS
POS
PLBG
PH
PD
PCF
P
OV
OFOI
OFCI
ODP
OD
OC
OB
NTS
NOM
NO.
NO
NIC
NC
NC
N/A
MU
MTD
MIN
MH
MFR
MEZZ
MECH
MCC
MCA
MBH
MAX
M
LVG
LF
LAB
LB
L
KVA
KW
INSUL
IN
ID
AVERAGE
ATMOSPHERIC VENT
AUTOMATIC TEMPERATURE CONTROL
ARCHITECT
ACCESS PANEL
ALUMINUM
ALTERNATE
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
ADDITIONAL
BRITISH THERMAL UNIT PER HOUR
BRITISH THERMAL UNIT
BASEMENT
BOTTOM
BOTTOM OF PIPE
BOTTOM OF DUCT
BOILER
BUILDING
BRAKE HORSEPOWER
BELOW FINISHED FLOOR
BOILER FEED WATER
BLOWDOWN TANK
BOILER BLOW DOWN
BUILDING AUTOMATION SYSTEM
COLD ROOM CONDENSING UNIT
CYLINDER
CABINET UNIT HEATER
CUBIC FEET
CORRIDOR
CONTRACTOR
CONNECTION
CONCRETE
COMPRESSOR
COLUMN
CLEAN-OUT
CEILING
CENTERLINE
CEILING FAN
COMPRESSED AIR
CONVECTOR
DRAIN
DRAWING
DOWN
DIMENSION
DIAMETER
DIRECT DIGITAL CONTROL
DRY COOLER
DRY BULB TEMPERATURE
EXPANSION
EXHAUST
ELECTRIC UNIT HEATER
EQUIPMENT
ENTERING
ENERGY MANAGEMENT SYSTEM
EMERGENCY
ELEVATION
ELECTRICAL
ELECTRIC CABINET UNIT HEATER
EFFICIENCY
ENTERING AIR TEMPERATURE
EACH
FULL VOLTAGE NON-REVERSING
FURNISHED
FEET PER SECOND
FEET
FEET PER MINUTE
FIRE PROTECTION
FLOOR DRAIN
FLOOR
FLEXIBLE
FIBERGLASS
FIREFIGHTERS OVERRIDE PANEL
FLOW CONTROL VALVE
FINNED TUBE RADIATION
FLAT ON TOP
FLAT ON BOTTOM
FIRE ALARM SYSTEM
GYPSUM WALL BOARD
GRADE (GROUND LEVEL)
GALLONS PER MINUTE
GALLONS PER HOUR
GROUND
GENERAL CONTRACTOR
GALVANIZED
GALLONS
GAUGE
GAS
HEAT EXCHANGER
HERTZ
HOUR
HIGH PRESSURE GAS
HORSEPOWER
HEAD
HANDICAPPED
HEIGHT
WITH RESPECT TO
WATER GAUGE
WIDE FLANGE
WET BULB TEMPERATURE
WITHOUT
WITH
WIDTH
VENT THROUGH ROOF
VARIABLE FREQUENCY DRIVE
VERTICAL
VELOCITY
VENT
TYPICAL
TOP OF PIPE
TOP OF DUCT
TEMPERATURE
TELEPHONE
TOTALLY ENCLOSED FAN COOLED
THERMOSTATIC AIR VENT
THROW-AWAY
SUPPLY
SUCTION
STEEL
STANDBY
STANDARD
STAINLESS STEEL
SQUARE FEET
SQUARE
SPECIFICATIONS
REVOLUTIONS PER MINUTE
ROOM
RELATIVE HUMIDITY
REQUIREMENTS
REQUIRED
RETURN
REPRESENTATIVE
REHEAT
SCHEDULE
SOLENOID OPERATED VALVE
POLYVINYL CHLORIDE
POUNDS PER SQUARE INCH GAUGE
POUNDS PER SQUARE INCH DIFFERENTIAL
POUNDS PER SQUARE INCH ABSOLUTE
PRIMARY
PRESSURE REFERENCE
PRESSURE
PROVIDED BY OTHER SECTION(S)
PLUMBING
PHASE
PRESSURE DROP
POUNDS PER CUBIC FOOT
PERIMETER HEAT
OUTLET VELOCITY
OWNER FURNISHED OWNER INSTALLED
OWNER FURNISHED CONTRACTOR INSTALLED
OPEN DRIP PROOF
OUTSIDE DIAMETER
ON CENTER
OCTAVE BAND
NOT TO SCALE
NOMINAL
NUMBER
NORMALLY OPEN
NOT IN CONTRACT
NOISE CRITERIA
NORMALLY CLOSED
NOT APPLICABLE
MAKEUP WATER
MOUNTED
MINIMUM
MANHOLE
MANUFACTURER
MEZZANINE
MECHANICAL
MOTOR CONTROL CENTER
MINIMUM CIRCUIT AMPS
THOUSAND BRITISH THERMAL UNITS PER HOUR
MAXIMUM
ONE THOUSAND
LEAVING
LINEAR FEET
LABORATORY
POUND
LENGTH
KILOVOLT AMPERE
KILOWATT
INSULATION
INCHES
INSIDE DIAMETER
BDD
BI
BC
BSD
BACKDRAFT DAMPER
BACKWARD INCLINED
BLOWER COIL
BIOSEAL DAMPER
CC
CD
CFM
CG
COOLING COIL
CUBIC FEET PER MINUTE
CEILING DIFFUSER
CEILING GRILLE
CREF CHILLER ROOM EXHAUST FAN
CU CONDENSING UNIT
DIFF
DWDI DOUBLE WIDTH DOUBLE INLET
DIFFUSER
DWSI
DX DIRECT EXPANSION
DOUBLE WIDTH SINGLE INLET
EF
EG
EHC
EHU
ERU
ER
ERHC
ESP
EXHAUST FAN
EXHAUST GRILLE
ELECTRICAL HEATING COIL
EXHAUST AIR HANDLING UNIT
ENERGY RECOVERY UNIT
EXHAUST REGISTER
ELECTRIC REHEAT COIL
EXTERNAL STATIC PRESSURE
WMS
VVR
VVE
VV
VD
WIRE MESH SCREEN
VARIABLE VOLUME RETURN AIR TERMINAL BOX
VARIABLE VOLUME EXHAUST AIR TERMINAL BOX
VARIABLE VOLUME SUPPLY AIR TERMINAL BOX
VOLUME DAMPER
UC UNDERCUT DOOR
TSP
TR
TG
TF
TOTAL STATIC PRESSURE
TRANSFER
TRANSFER GRILLE
TRANSFER FAN
TEF DEDICATED TOILET EXHAUST FAN
TE TOILET EXHAUST
SWSI
SWDI
SV
SR
SP
SM
SGD
SG
SFD
SF
SEF
SDET
SD
SCR
SATT
SA
SINGLE WIDTH SINGLE INLET
SINGLE WIDTH DOUBLE INLET
VARIABLE VOLUME SUPPLY AIR TERMINAL BOX
SUPPLY REGISTER
STATIC PRESSURE
SHEETMETAL
SLIDE GATE DAMPER
SUPPLY GRILLE
COMBINATION AUTOMATIC SMOKE/FIRE
DAMPER WITH ACCESS DOOR
SUPPLY FAN
SMOKE EXHAUST FAN
SMOKE DETECTOR
SMOKE DAMPER
SCREEN
SOUND ATTENUATOR
SUPPLY AIR
RV
RS
RR
RLF
RL
RHC
RG
RF
RD
RA
RETURN AIR VALVE/BOX
REFRIGERANT SUCTION
RETURN REGISTER
RELIEF
REFRIGERANT LIQUID
REHEAT COIL
RETURN GRILLE
RETURN FAN
REFRIGERANT DISCHARGE (HOT GAS)
RETURN AIR
PHC PREHEAT COIL
OED
OBD
OAI
OA
OPEN END DUCT
OPPOSED BLADE DAMPER
OUTSIDE AIR INTAKE
OUTSIDE AIR
LVDR
LUVR
LD
LAT
LOUVERED DOOR
LOUVER
LINEAR DIFFUSER
LEAVING AIR TEMPERATURE
IH INTAKE HOOD
HU
HV
HRU
HPU
HEPA
HC
HUMIDIFIER
HEATING & VENTILATING UNIT
HEAT RECOVERY UNIT
HEAT PUMP UNIT
HIGH EFFICIENCY PARTICULATE AIR FILTER
HEATING COIL
GWCE
GH
GLASS WASH CENTER EXHAUST
GRAVITY HOOD
GEF GENERAL EXHAUST FAN
AIR SEPARATOR
AUTOMATIC AIR VENTAAV
AS
CH
CHEM
CHW
CHWR
CHWS
DOV
ET
EWT
GR
GS
GHW
GHWR
GHWS GLYCOL HOT WATER SUPPLY
GLYCOL HOT WATER RETURN
GLYCOL HOT WATER
GLYCOL SUPPLY
GLYCOL RETURN
ENTERING WATER TEMPERATURE
EXPANSION TANK
DRAIN OFF VALVE
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CHILLED WATER
CHEMICAL FEED
CHILLER
HB
HCR
HCS
HRC
HW
HOSE BIBB CONN W/CHAINED CAP
HOT WATER
HEAT RECOVERY COIL - GLYCOL
HOT OR COLD WATER SUPPLY (DUAL TEMP)
HOT OR COLD WATER RETURN (DUAL TEMP)
UV
TDH
S(XXX)
RHWR
RHWS
T(XXX)
RHW
RH
RHP
PCHWS
PCHWR
PROCHW
PHX
PC
P
OS&Y
UNIT VENTILATOR
TOTAL DYNAMIC HEAD
TERTIARY (SYSTEM DEPENDENT PREFIX)
SECONDARY (SYSTEM DEPENDENT PREFIX)
REHEAT HOT WATER RETURN
REHEAT HOT WATER SUPPLY
REHEAT HOT WATER
REHEAT
RADIANT HEATING PANEL
PROCESS CHILLED WATER SUPPLY
PROCESS CHILLED WATER RETURN
PROCESS CHILLED WATER
PLATE HEAT EXCHANGER
PUMPED CONDENSATE
PUMP
OUTSIDE STEM AND YOKE
NET POSITIVE SUCTION HEAD
MANUAL AIR VENTMAV
NPSH
LWT
HWUH
HWS
HWR
HWRHC
HWPHC
HWHC
HWCUH HOT WATER CABINET UNIT HEATER
HOT WATER HEATING COIL
HOT WATER PREHEAT COIL
HOT WATER REHEAT COIL
HOT WATER RETURN
HOT WATER SUPPLY
HOT WATER UNIT HEATER
LEAVING WATER TEMPERATURE
VV SUPPLY VAV BOX
ADJUSTABLE
ACCESS DOOR
AUTOMATIC CONTROL VALVE
UH UNIT HEATER
SCHW SECONDARY CHILLED WATER
AIR TERMINAL DEVICE
ACOUSTICAL LINED DUCTWORK
AUTOMATIC CONTROL DAMPER
HR
HZ
HX HEAT EXCHANGER
HERTZ
HOUR
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
MECHANICAL LEGEND
M0.1 REPLACE HUMIDIFICATION SYSTEM
SPRINGFIELD ARMORY NATIONAL HISTORIC SITE
259831
ELS
ELS
HACEC
MAY 8, 2024
AutoCAD SHX Text
OF
DN
UP
W
CO
MAV
AAV
PT
E
FM
S
OR
OR
OR
R w
GATE VALVE
BALL VALVE
BALL VALVE WITH MEMORY STOP (BALANCING VALVE)
BALL VALVE WITH HOSE BIBB, CAP & CHAIN (DRAIN VALVES)
BUTTERFLY VALVE
BUTTERFLY VALVE WITH MEMORY STOP (BALANCING VALVE)
GLOBE VALVE
PRESSURE REDUCING VALVE
CHECK VALVE
STRAINER W/BALL VALVE, HOSE BIBB & CAP (GATE VALVE FOR STEAM)
SOLENOID VALVE
AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR
AUTOMATIC CONTROL VALVE, TWO POSITION ACTUATOR
THREE WAY AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR
THREE WAY AUTOMATIC CONTROL VALVE, TWO POSITION ACTUATOR
AUTOMATIC FLOW CONTROL VALVE (PRESSURE INDEPENDENT)
COMBINATION FLOWMETER/SHUT OFF/BALANCING VALVE (CIRCUIT SETTER)
FLOW MEASURING DEVICE
FLOW SWITCH
SAFETY RELIEF VALVE
UNION OR FLANGE (AS INDICATED BY PIPE SIZE - SEE SPEC.)
BLIND FLANGE
END CAP
PRESSURE GAUGE WITH GAUGE CLOCK
PRESSURE/TEMPERATURE WELL
AUTOMATIC AIR VENT WITH ISOLATION VALVE
MANUAL AIR VENT
REDUCER (ECCENTRIC-FLAT ON BOTTOM OR FLAT ON TOP)
REDUCER (CONCENTRIC)
FLEXIBLE CONNECTION
EXPANSION JOINT
PIPE GUIDE
ANCHOR
RISE (SINGLE LINE - PLAN VIEW)
DROP (SINGLE LINE - PLAN VIEW)
VALVE IN VERTICAL
TOP TAKEOFF
BOTTOM TAKEOFF
PIPE BREAK (SINGLE LINE)
WATER METER DIAL TYPE
DIRT LEG
CLEAN-OUT FOR CONDENSATE DRAIN
RISE (DOUBLE LINE - PLAN VIEW)
DROP (DOUBLE LINE - PLAN VIEW)
PIPE BREAK (DOUBLE LINE)
DIRECTION OF FLOW IN PIPE
PITCH PIPE UP IN DIRECTION OF FLOW
PITCH PIPE DOWN IN DIRECTION OF FLOW
NEW WORK
SUPPLY LINES
RETURN LINES
PIPING LEGENDDUCTWORK
SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE
ROUND SUPPLY
DUCT UP
SUPPLY
DUCT UP
ROUND SUPPLY
DUCT DN
SUPPLY DUCT
DOWN
STANDARD RADIUS
ELBOW
( R = W )
SUPPLY/RETURN
EXHAUST
SPLIT TAKE-OFF
W/ BRANCH DAMPERS
SUPPLY
BULLHEAD SPLIT
SUPPLY
CEILING DUCT
GOOD FOR
RING DUCT
TAKEOFF TO
MTD DIFF/GRILLE
W/BRANCH TAKE-OFF
VOLUME DAMPER
CEILING DUCT
MTD DIFF/GRILLE
W/BRANCH TAKE-OFF
VOLUME DAMPER
OPEN END
DUCT W/VD &
1/2"x1/2" WMS
FLEXIBLE
DUCT
RISE/DROP
RISE/DROP
ROUND RETURN OR
EXHAUST
DUCT UP
RETURN/EXHAUST
DUCT UP
RETURN/EXHAUST
DUCT DOWN
ROUND RETURN OR
EXHAUST DUCT
DN
HORIZONTAL
OFFSET
SUPPLY/RETURN
/EXHAUST
RISE OR DROP
SUPPLY/RETURN/
EXHAUST
RING
DUCT
90° TAKE-OFF W/BRANCH TAKE-OFF
VOLUME DAMPER (VD IN LOW PRESSURE
SYSTEMS ONLY)
BULLHEAD CONVERGE
RETURN/EXHAUST
W/BRANCH TAKE-OFF
VOLUME DAMPER
SIDEWALL DUCT MTD
REGISTER/GRILLE
W/BRANCH TAKE-OFF
VOLUME DAMPER
SUPPLY SIDEWALL
LINEAR DIFFUSER
(W/ 1" INTERNALLY
LINED SM PLENUM)
BRANCH CONN
W/VD FOR EVERY
4' OF LINEAR
SUPPLY CEILING
LINEAR DIFFUSER (W/
1" INTERNALLY LINED
SM PLENUM) BRANCH
CONN W/VD FOR
EVERY 4' OF LINEAR BOOT
BY LD
MFR
AVS AIR VOLUME TRAVERSE STATION
WITH ACCESS DOOR
ROOF EXHAUST FAN
SHOWN ON ROOF
ROOF EXHAUST FAN
SHOWN ON FLOOR PLAN
RETURN OR EXHAUST
AIR FLOW
SUPPLY AIR FLOW
STANDARD 4-WAY BLOW
SUPPLY DIFFUSER
BLANKED FOR 3-WAY BLOW
SUPPLY DIFFUSER
BLANKED FOR 2-WAY BLOW
SUPPLY DIFFUSER
BLANKED FOR 1-WAY BLOW
SUPPLY DIFFUSER
ALTERNATE CFM LOCATION
DESIGN CFM
(200) A(200)
SYMBOL DESIGNATES ASSOCIATED
SYSTEM OR SERVICE (ie HWS)
REFER TO DRAWINGS ( ) FOR
CONTINUATION XXX
SMOKE DETECTOR
PRESSURE TRANSMITTER
HUMIDITY INDICATOR
TEMPERATURE INDICATOR
HUMIDITY SENSOR
TEMPERATURE SENSOR
HUMIDISTAT
THERMOSTATSECTION DESIGNATION SHEET NUMBER
DETAIL DESIGNATION SHEET NUMBER
REVISION NUMBER
DIFFUSER, GRILLE, REGISTER LETTER
DESIGNATOR
CALL OUT SYMBOLS
M.XX
M.XX
SDET
P
MI
TI
MS
TS
C CARBON DIOXIDE SENSOR
MATCHLINE
BDD BACKDRAFT DAMPER
FSD COMBINATION SMOKE/FIRE
DAMPER W/ACCESS DOOR
SGD SLIDE GATE DAMPER
VD MANUAL VOLUME DAMPER
(OBD IN DIFFUSER)
ACD AUTOMATIC CONTROL DAMPER
W/ACCESS DOOR
SD AUTOMATIC SMOKE DAMPER
W/ACCESS DOOR
FD FIRE DAMPER W/ ACCESS DOOR
X PIPE ANCHOR FOR EXPANSION LOOP
PIPE GUIDE FOR EXPANSION LOOP
EQUIPMENT TAG SYMBOLS & ABBREVIATIONS
RH
VFD
C
C
C
VARIABLE FREQUENCY DRIVE
UNIT HEATER
CABINET HEATER
COOLING COIL
REHEAT COIL
OPPOSED BLADE DAMPER
PARALLEL BLADE DAMPER
W/ MODULATING ACTUATOR
W/ MODULATING ACTUATOR
W/ TWO POSITION ACTUATOR
BACKDRAFT DAMPER
PARALLEL BLADE DAMPER
W/ TWO POSITION ACTUATOR
OPPOSED BLADE DAMPER
ROOF FAN
FLOW DIAGRAM AND CONTROL DIAGRAM EQUIP SYMBOLS
C
H
HEATING COIL
FILTER BANK
INLINE CENTRIFUGAL FAN
CENTRIFUGAL FAN
PUMP
UPBLAST CENTRIFUGAL FAN
TAG
NO
TAG
NO
EXPANSION TANK
AIR SEPARATOR
CHEMICAL FEED SYSTEM
AIR TERMINAL BOX WITH
REHEAT COIL
AIR TERMINAL BOX
AAV
NOTE: REFER TO SCHEDULES FOR EQUIPMENT SPECIFIC DATA
OCCUPIED MAX CFM
UNOCCUPIED CFM
TERMINAL BOXVAV/VAVE
XXX
XXX
OCCUPIED MAX GPM
TERMINAL BOXVAV/VAVE
XXX
PUSH BUTTONPB
RF SHIELDED ROOM
EQUIPMENT NOT
REQUIRING
ELECTRIC SERVICE
EQUIPMENT
REQUIRING
ELECTRIC SERVICE
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
MECHANICAL LEGEND
M0.2 REPLACE HUMIDIFICATION SYSTEM IN
SPRINGFIELD ARMORY NATIONAL HISTORIC SITE
259831
ELS
ELS
HACEC
MAY 8, 2024
AutoCAD SHX Text
AIR VALVE
HUMIDIFIER SCHEDULE
UNIT
NO. SERVICE LOCATION
MOISTURE
OUTPUT
(LBS/HR)
UNIT EAT
DB (°F) RH %
UNIT LAT MANUFACTURER
MODEL NUMBER
(AS STANDARD)
REMARKS
SSH-1 ARSENAL 25 62.2 52.8 85 28
MAX
AIRFLOW
(CFM)
ARSENAL
BASEMENT
HUMIDIFICATION CONTROL VALVE AND STEAM TRAP BY MANUFACTURER
PROVIDE HIGH LIMIT HUMIDISTAT AND DUCT PRESSURE SWITCH
SSH-2
SSH-3
ARSENAL ARSENAL
BASEMENT
ARSENAL ARSENAL
BASEMENT
25 CONDAIR
EL-0102115
100 5430
SSH-4
SSH-5
ARSENAL ARSENAL
BASEMENT
ARSENAL ARSENAL
BASEMENT
100 7370
100 5210
DB (°F) RH %
HZPHASEVOLTS
MAX CUR
AMP
RATED
AMP
GAS TYPE
NATURAL
GAS
NATURAL
GAS
NATURAL
GAS
STEAM
INJECTION
LOCATION
DUCTWORK
DUCTWORK
DUCTWORK
DUCTWORK
AHU-4
3 PROVIDE ALUMINUM DRIP PANS IN DUCTS WITH 1" LIP BEFORE AND AFTER DISPERSION TUBE WITH ACCESS DOORS IN SIDE DUCT.
4 CONTRACTOR CONFIRM EXISTING EQUIPMENT SIZE AND DUCTWORK SIZE BEFORE PURCHASING EQUIPMENT
CONDAIR
EL-0102082518 601
CONDAIR
GS-100-CS
CONDAIR
GS-100-CS
CONDAIR
GS-100-CS
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
85 28
85 28
85 28
85 28
65.7 54.8
62.3 52.8
66.8 55.4
62.2 52.8
STEAM HUMIDIFIER PIPING1
SCALE: NTS
DRAIN LINE TO AIR
GAP FUNNEL.
CONNECT TO
EXISTING DRAIN LINE.
1/2" DOMESTIC COLD
WATER CONNECTION.
SS OR ALUM. DRAIN PAN
8 FT LONG TOTAL
SECTION LENGTH
INSULATED ON OUTSIDE
DRAIN PAN WATER SEAL (2")
3/4" DRAIN DOWN TO
NEAREST INDIRECT
WASTE
FURNISH SUPPORT
BRACKET AND PLATE
ON BOTH ENDS
NOTES:
1. PROVIDE DUCT PRESSURE SWITCH & HIGH LEVEL
HUMIDISTAT.
2. STEAM SUPPLY PIPING FROM HUMIDIFIER TO DISPERSION
TUBES SHALL BE SIZED AS PER THE MFR'S
RECOMMENDATIONS AND PROVIDED BY THE MFR,
INSTALLED BY THE CONTRACTOR.
3. HUMIDIFIER SHALL HAVE SCR CONTROL (0-100%)
4. MFR IS RESPONSIBLE FOR PROVIDING PACKAGED
CONTROL SYSTEM COMPATIBLE WITH THAT OF THE BASE
BUILDING MANAGEMENT SYSTEM.
5. MOUNT UNIT PER MFR'S RECOMMENDATIONS.
6. PROVIDE P-TRAP EVERY 15' AND RUN TO CONDENSATE
DRAIN.
6" WATER SEAL
CONDENSATE LINE
STEAM DISTRIBUTOR
STEAM DISCHARGE PORTS
FOR HUMIDIFIER SECTION PROVIDE STAINLESS
STEEL OR ALUMINUM DUCT EXTENDING 2 FT
UPSTREAM & 6 FT DOWNSTREAM OF HUMIDIFIER.
BOTTOM OF DUCT SHALL BE SEAMLESS OR
WELDED LIQUID TIGHT TO ACT AS DRAIN PAN
MINIMUM 2 INCH DEPTH.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
MECHANICAL SCHEDULES AND DETAIL
M3.0 REPLACE HUMIDIFICATION SYSTEM
SPRINGFIELD ARMORY NATIONAL HISTORIC SITE
259831
ELS
ELS
HACEC
MAY 8, 2024
| M.00 |
| M0.1 |
| M0.1 (2) |
| M0.2 |
| M0.2 (2) |
| M1.1 |
| M1.2 |
| M3.0 |
| M3.0 (2) |