OVERHAUL DESCRIPTION
FOR OFFICIAL USE ONLY
ITEM NAME POWER SUPPLY, UNINTERRUPTABLE
STOCK NUMBER 6130-01-F10-1749
PART NUMBER UPS1-2.4K-1G-SRNDTI-JS2E-LM
USED ON WMSL CGC2
Items as received by the contractor must be complete and of the proper cited part number. Discrepancies shall be reported to the Coast Guard Contracting Officer.
OVERHAUL REQUIREMENTS:
ACN: 01-F10-1749
OEM PN: UPS1-2.4K-1G-SRNDTI-JS2E-LM (BYPASS FEATURE DISABLED)
LOCKHEED MARTIN ALT PN: 20519797-1
CONVERT TO PN: UPS1-2.4K-1G-SRNDTI-JS2E (**INCLUDES BYPASS FEATURE**)
ITEM: UNINTERRUPTIBLE POWER SUPPLY (UPS)
CAGE: 1BCN7
OEM: NOVA POWER
ESTIMATED REPAIR LEAD TIME: 5 MONTHS
REPAIR REQUIREMENTS: REFER TO REPAIR SPECS DOCUMENT - A COPY WILL BE PROVIDED
TO THE OEM BY THE KS / KO. **SECTION 3.2.4.2 HIGHLIGHTS CONVERSION & REPAIR
INSTRUCTIONS**
ACN: 01-F10-1749, PN: UPS1-2.4K-1G-SRNDTI-JS2E-LM / PN:20519797-1 WILL BE
CONVERTED INTO PN: UPS1-2.4K-1G-SRNDTI-JS2E, NIIN: 01-560-6282 WHICH INCLUDES
THE INTERNAL BYPASS FEATURE.
CG HAS DISCONTINUED USE OF PN: UPS1-2.4K-1G-SRNDTI-JS2E-LM / PN: 20519797-1
AND REQUESTS THAT ALL BE CONVERTED BY OEM ONLY DURING REPAIR PROCESS.
OEM MUST REMOVE ALL OLD PN's AND MARKING FROM BOTH THE UPS AND PACKAGING
BEFORE RETURNING TO SFLC. THE CONVERTED UPS, AND THIER PACKAGING, SHOULD ONLY
REFLECT PN:UPS1-2.4K-1G-SRNDTI-JS2E, NIIN: 01-560-6282 TO ELIMINATE ANY
CONFUSION BETWEEN THE UNITS.
CONVERSION + REPAIR REQUIRES OEM OR AUTHORIZED OEM FACILITY TO REMOVE ALL OLD
PN / SN PLATES, AND REPLACE WITH NEW POST CONVERSION. THIS CANNOT BE DONE BY
A THIRD PARTY / UN-AUTHORIZED REPAIR FACILITY.
CONVERSION + REPAIR WILL ONLY BE EXECUTED BY THE OEM, OR AN AUTHORIZED OEM
REPAIR FACILITY.
THIS IS NOT A ROUTINE REPAIR, THE UPS WILL BE CONVERTED FROM A VERSION WHICH
DOES NOT CURRENTLY INCLUDE THE INTERNAL BYPASS FEATURE, TO A NEWER VERSION
WHICH INCULDES THE INTERNAL BYPASS FEATURE REQUIRED BY THE CG.
NOVA POWER & MDF TECHNOLOGIES ARE THE ONLY AUTHORIZED REPAIR FACILITIES FOR
THIS UPS. THEY'VE ADVISED THEY WILL NOT COVER ANY ISSUES CAUSED BY UN-
AUTHORIZED REPAIR FACILITIES OR NON-OEM PARTS USED. DUE TO THIS, CG WILL NOT
CONSIDER BIDS FROM OTHER SOURCES UNLESS THEY HAVE DOCUMENTATION FROM THE OEM
STATING THEY ARE AN AUTHORIZED OEM REPAIR FACILITY. THIS MUST BE PRESENTED
UP-FRONT TO BE CONSIDERED FOR AWARD, OR RECEIVE RESPOSNE FROM ES / COR TO
DISCUSS POSSIBILITY OF ADDING ADDITIONAL SOURCE OF SUPPLY TO THIS CONVERSION
+ REPAIR.
REQUIREMENT PER FAR 6.302-1 CLAUSE: OEM AUTHORIZED DISTRIBUTORS ONLY. MUST
SHOW PROOF VIA LETTER FROM OEM PRIOR TO AWARD. APPLIES TO BIDDING COMPANY -
SEE JOTFOC.
SPECS:
3U-HIGH
FITS MOST 19" RACKMOUNT APPLICATIONS
23" DEEP, STEEL CHASSIS
FEATURES: 14 MINUTES RUN TIME AT 50% RATED LOAD
DIMENSIONS: 5 1/4" H X 19" W X 23" D
WEIGHT: 135 LBS
- PER LMCO DRAWING # 20519797-1 (REV E). INCLUDES CT-09A-2 SNMP OPTION AND
NO BATTERY PACK
- THIS MODEL LACKS AN INTERNAL BYPASS AND HAS A DIFFERENT BATTERY PACK FROM
SIMILAR UPS MODELS. **CONVERSION REQUIRED TO CORRECT DISABLED BYPASS AND
BATTERY PACK DIFFERENCES**
PACKAGING SPECS:
1.) MIL-STD-20731E - REFER TO METHOD 10. PACKAGING SHOULD BE APPROPRIATE TO
PART SIZE, WEIGHT, AND MUST WITHSTAND MULTIPLE WORLDWIDE SHIPMENTS IN VARIOUS
SHIPPING CONDITIONS / CLIMATES. PART MUST BE APPROPRIATELY SECURED, AND
CUSHIONED BY FOAM OR BUBBLE WRAP TO PREVENT EXCESSIVE MOVEMENT AND DAMAGE
DURING SHIPPING.
1.A) ELECTROSTATIC DISCHARGE (ESD) ITEMS TO COMPLY WITH METHOD 41, PARAGRAPH
3.7; 5.2.4.1 & TABLE J-IA IAW MIL-PRF-81705E (**ONLY IF APPLICABLE TO PART**)
2.) INDIVIDUALLY PACKAGED AND LABELED IAW MIL-STD-129P CH.4, REQUIRED ID
MARKING EX: PARAGRAPH 4.1 FIGURE 1 - MARKINGS SHALL COMPLY WITH PACK TYPE /
MATERIALS AS REFERENCED IN DOCUMENT. LABELS: IAW MIL-STD-129P W/ CHANGE 4,
PARAGRAPH 4.1 IDENTIFICATION MARKINGS; BARCODING IS NOT REQUIRED. (PG.21).
2.A) VISIBLY MARK / LABEL ALL ELECTRONIC EQUIPMENT WITH "STORE INDOORS ONLY"
WARNING. ITEMS THAT ARE NOT INDIVIDUALLY PACKAGED, AND / OR LABELED WITH THE
REQUIRED FORMAT WILL BE RETUREND TO THE VENDOR FOR REPACKAGING.
END USE: MULTIPLE SYSTEMS & LOCATIONS ON WMSL CUTTERS
TECH / KS/ KO INFO:
MDF's FOB DESTINATION CHARGES ARE INCLUDED IN THE REPAIR COST. (EST ~$150 EA)
THIS IS A CONVERSION + REPAIR FROM A UPS THAT LACKS AN INTERNAL BYPASS
FEATURE, TO A UPS THAT INCLUDES THE INTERNAL BYPASS FEATURE UNDER NIIN: 01-
560-6282.
PLEASE ONLY CONTACT MDF FOR RFQ's, THEY ARE NOVA's PARTNER COMAPNY AND ASSIST
WITH THE RMA & PACKAGING PROCESS. ALL UPS WILL BE SHIPPED TO & FROM MDF, AND
MDF WILL COORDINATE SHIPMENT TO OEM: NOVA FOR REPAIRS.
NOVA IS THE SOLE DESIGNER AND REPAIR FACILITY FOR THESE UPS, BUT MDF PROVIDES
THE QUOTES AND ASSIST WITH THE LOGISTICS.
SHELF LIFE CD 0
ACN: 01-F10-1749
OEM PN: UPS1-2.4K-1G-SRNDTI-JS2E-LM (BYPASS FEATURE DISABLED)
LOCKHEED MARTIN ALT PN: 20519797-1
CONVERT TO PN: UPS1-2.4K-1G-SRNDTI-JS2E (**INCLUDES BYPASS FEATURE**)
ITEM: UNINTERRUPTIBLE POWER SUPPLY (UPS)
CAGE: 1BCN7
OEM: NOVA POWER
ESTIMATED REPAIR LEAD TIME: 5 MONTHS
REPAIR REQUIREMENTS: REFER TO REPAIR SPECS DOCUMENT - A COPY WILL BE PROVIDED
TO THE OEM BY THE KS / KO. **SECTION 3.2.4.2 HIGHLIGHTS CONVERSION & REPAIR
INSTRUCTIONS**
ACN: 01-F10-1749, PN: UPS1-2.4K-1G-SRNDTI-JS2E-LM / PN:20519797-1 WILL BE
CONVERTED INTO PN: UPS1-2.4K-1G-SRNDTI-JS2E, NIIN: 01-560-6282 WHICH INCLUDES
THE INTERNAL BYPASS FEATURE.
CG HAS DISCONTINUED USE OF PN: UPS1-2.4K-1G-SRNDTI-JS2E-LM / PN: 20519797-1
AND REQUESTS THAT ALL BE CONVERTED BY OEM ONLY DURING REPAIR PROCESS.
OEM MUST REMOVE ALL OLD PN's AND MARKING FROM BOTH THE UPS AND PACKAGING
BEFORE RETURNING TO SFLC. THE CONVERTED UPS, AND THIER PACKAGING, SHOULD ONLY
REFLECT PN:UPS1-2.4K-1G-SRNDTI-JS2E, NIIN: 01-560-6282 TO ELIMINATE ANY
CONFUSION BETWEEN THE UNITS.
CONVERSION + REPAIR REQUIRES OEM OR AUTHORIZED OEM FACILITY TO REMOVE ALL OLD
PN / SN PLATES, AND REPLACE WITH NEW POST CONVERSION. THIS CANNOT BE DONE BY
A THIRD PARTY / UN-AUTHORIZED REPAIR FACILITY.
CONVERSION + REPAIR WILL ONLY BE EXECUTED BY THE OEM, OR AN AUTHORIZED OEM
REPAIR FACILITY.
THIS IS NOT A ROUTINE REPAIR, THE UPS WILL BE CONVERTED FROM A VERSION WHICH
DOES NOT CURRENTLY INCLUDE THE INTERNAL BYPASS FEATURE, TO A NEWER VERSION
WHICH INCULDES THE INTERNAL BYPASS FEATURE REQUIRED BY THE CG.
NOVA POWER & MDF TECHNOLOGIES ARE THE ONLY AUTHORIZED REPAIR FACILITIES FOR
THIS UPS. THEY'VE ADVISED THEY WILL NOT COVER ANY ISSUES CAUSED BY UN-
AUTHORIZED REPAIR FACILITIES OR NON-OEM PARTS USED. DUE TO THIS, CG WILL NOT
CONSIDER BIDS FROM OTHER SOURCES UNLESS THEY HAVE DOCUMENTATION FROM THE OEM
STATING THEY ARE AN AUTHORIZED OEM REPAIR FACILITY. THIS MUST BE PRESENTED
UP-FRONT TO BE CONSIDERED FOR AWARD, OR RECEIVE RESPOSNE FROM ES / COR TO
DISCUSS POSSIBILITY OF ADDING ADDITIONAL SOURCE OF SUPPLY TO THIS CONVERSION
+ REPAIR.
REQUIREMENT PER FAR 6.302-1 CLAUSE: OEM AUTHORIZED DISTRIBUTORS ONLY. MUST
SHOW PROOF VIA LETTER FROM OEM PRIOR TO AWARD. APPLIES TO BIDDING COMPANY -
SEE JOTFOC.
SPECS:
3U-HIGH
FITS MOST 19" RACKMOUNT APPLICATIONS
23" DEEP, STEEL CHASSIS
FEATURES: 14 MINUTES RUN TIME AT 50% RATED LOAD
DIMENSIONS: 5 1/4" H X 19" W X 23" D
WEIGHT: 135 LBS
- PER LMCO DRAWING # 20519797-1 (REV E). INCLUDES CT-09A-2 SNMP OPTION AND
NO BATTERY PACK
- THIS MODEL LACKS AN INTERNAL BYPASS AND HAS A DIFFERENT BATTERY PACK FROM
SIMILAR UPS MODELS. **CONVERSION REQUIRED TO CORRECT DISABLED BYPASS AND
BATTERY PACK DIFFERENCES**
PACKAGING SPECS:
1.) MIL-STD-20731E - REFER TO METHOD 10. PACKAGING SHOULD BE APPROPRIATE TO
PART SIZE, WEIGHT, AND MUST WITHSTAND MULTIPLE WORLDWIDE SHIPMENTS IN VARIOUS
SHIPPING CONDITIONS / CLIMATES. PART MUST BE APPROPRIATELY SECURED, AND
CUSHIONED BY FOAM OR BUBBLE WRAP TO PREVENT EXCESSIVE MOVEMENT AND DAMAGE
DURING SHIPPING.
1.A) ELECTROSTATIC DISCHARGE (ESD) ITEMS TO COMPLY WITH METHOD 41, PARAGRAPH
3.7; 5.2.4.1 & TABLE J-IA IAW MIL-PRF-81705E (**ONLY IF APPLICABLE TO PART**)
2.) INDIVIDUALLY PACKAGED AND LABELED IAW MIL-STD-129P CH.4, REQUIRED ID
MARKING EX: PARAGRAPH 4.1 FIGURE 1 - MARKINGS SHALL COMPLY WITH PACK TYPE /
MATERIALS AS REFERENCED IN DOCUMENT. LABELS: IAW MIL-STD-129P W/ CHANGE 4,
PARAGRAPH 4.1 IDENTIFICATION MARKINGS; BARCODING IS NOT REQUIRED. (PG.21).
2.A) VISIBLY MARK / LABEL ALL ELECTRONIC EQUIPMENT WITH "STORE INDOORS ONLY"
WARNING. ITEMS THAT ARE NOT INDIVIDUALLY PACKAGED, AND / OR LABELED WITH THE
REQUIRED FORMAT WILL BE RETUREND TO THE VENDOR FOR REPACKAGING.
END USE: MULTIPLE SYSTEMS & LOCATIONS ON WMSL CUTTERS
TECH / KS/ KO INFO:
MDF's FOB DESTINATION CHARGES ARE INCLUDED IN THE REPAIR COST. (EST ~$150 EA)
THIS IS A CONVERSION + REPAIR FROM A UPS THAT LACKS AN INTERNAL BYPASS
FEATURE, TO A UPS THAT INCLUDES THE INTERNAL BYPASS FEATURE UNDER NIIN: 01-
560-6282.
PLEASE ONLY CONTACT MDF FOR RFQ's, THEY ARE NOVA's PARTNER COMAPNY AND ASSIST
WITH THE RMA & PACKAGING PROCESS. ALL UPS WILL BE SHIPPED TO & FROM MDF, AND
MDF WILL COORDINATE SHIPMENT TO OEM: NOVA FOR REPAIRS.
NOVA IS THE SOLE DESIGNER AND REPAIR FACILITY FOR THESE UPS, BUT MDF PROVIDES
THE QUOTES AND ASSIST WITH THE LOGISTICS.
WARRANTY:
X
OVERHAUL DESCRIPTION
A. Standard Manufacturer's Warranty
B. Item being repaired as an "onboard repair" or a "system stock" item and will be put into inventory. NOT FOR IMMEDIATE INSTALLATION.
Contractor must guarantee item against defects that lead to failure for days after installation for a period of up to two (2) years after delivery to Coast Guard.
GOVERNMENT ACCEPTANCE:
Acceptance will be made at destination by a Government representative.
Acceptance will be contingent upon the representative's verification of no damage in transit, correctness and completeness of order and contractor's conformance to preservation/packaging, packing and marking requirements.
PACKAGING AND MARKING FOR SHIPMENT:
X
A. Each unit shall be packed individually in it's own wooden box which shall be capable of providing adequate protection to the item during multiple shipments. Mark each box in legible black print lettering with the following information:
NATIONAL STOCK NUMBER
ITEM NAME
PART NUMBER
GOVERNMENT ORDER NUMBER
6130-01-F10-1749
POWER SUPPLY, UNINTERRUPTABLE
UPS1-2.4K-1G-SRNDTI-JS2E-LM
PRESERVATION / PACKAGING:
A. Each unit shall be individually preserved and wrapped for protection against deterioration for a period of two (2) years minimum.
X B. See Attachments
B. See Attachments
And the words: "Coast Guard SFLC Material, Condition "A"