Questions Asked:
1) What size air handler?
a) Trane
b) Model NO:LPCAA21F2F0ED000000000KBEA000000000000
c) Serial No: T07F49773
d) Rated Voltage: 460 HZ: 60 PH: 3
e) Maximum overcurrent protection: 45 AMPS
f) Blower Motor: 20.30 FLA 15 HP
g) Max inlet Water Temp. 200 f (93 c)
h) Max water pressure: 300 PSIG (14 BAR)
2) How much water damage to ceiling tiles and drywall can you see?
a) Water damager was all round the unit. At least 20 ceiling tiles of damage (possibly more) and about a 10’x10’ area of dry wall was damaged (could be more)
3) Are there any busted lines that you have noticed do to the freeze?
a) There were busted pipes in other area. Vendor also needs to be aware, we had to secure these pipes and unsecuring them will also need to happen.