Bill of Materials Revised June 26, 2022

*All changes are highlighted in yellow

Provide 3,500 feet of 2 AWG 3/C 15KV type MP-GC power cable with class B copper conductors, Ethylene Propylene Rubber (EPR) 133% insulation level, copper tape shield, with ground and ground check, and mold cured Chlorinated Polyethylene (CPE) jacket (jacket color Orange).

Cable must be MSHA approved and meet the following specifications:

• ASTM B3 Soft or Annealed Copper Wire

• ASTM B8 Concentric-Lay-Stranded Copper Conductors

• ASTM B496 Compact Round Concentric-Lay-Stranded Copper Conductors

• ICEA S-75-381/NEMA WC 58 Portable and Power Feeder Cables for use in Mines and Similar

Applications

Provide the cable manufacturer’s data sheet and drawing for the cable being offered.

Cable shall be tested in accordance with ICEA S-75-381 section 4.10 and applicable sections of section 6.

Provide the manufacturer’s test reports and a certificate of cable testing after the electrical cable is manufactured. The electrical cable will be shipped after acceptance of the testing results.

Cable is intended to be used for underwater service in shallow water (max 36 foot depth).

Cable shall be provided as one continuous length on one spool, with an acceptable length variance of +/-5%.