580-20-104 - Drawings -R1 - Install Zero Gravity.pdf
PDF 349 KB Posted
- Attached to
- Y1DA--Synopsis Amendment: 580-20-104 Install Zero Gravity System for Cath Lab. Federal contract opportunity
- Solicitation number
- 36C25621Q0111
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 580-20-104 zero gravity -ICRA.pdf | ||
| 580-20-104__lab 1-3.pdf | ||
| 36C25621Q0111 0002.docx | DOCX document | |
| 580-20-104__RFI-01.docx | DOCX document | |
| 580-20-104__32398 Pre Installation Guide-zero-gravity.pdf | ||
| 36C25621Q0111 0001.docx | DOCX document | |
| DOL Wage Determination TX20200253 09_11_2020.txt | TXT text file | |
| Site Visit Instructions for Install Zero Gravity.docx | DOCX document | |
| 36C25621Q0111_1.docx | DOCX document | |
| SF24 BID BOND.pdf | ||
| 580-20-104 - Specifications - Install Zero Gravity.pdf | ||
| 580-20-104 - Scope of Work - Install Zero Gravity.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
THE STRUCTURAL DRAWINGS DEPICT THE STRUCTURE IN ITS FINAL CONSTRUCTED CONFIGURATION.
NEITHER CONSTRUCTION MEANS AND METHODS NOR CONSTRUCTION SAFETY ARE PART OF THE
STRUCTURAL ENGINEER’S EXPERTISE OR SCOPE OF WORK. THE GENERAL CONTRACTOR AND THEIR
SUBCONTRACTORS ARE FULLY RESPONSIBLE FOR THE MEANS AND METHODS USED TO CONSTRUCT
THE STRUCTURE AND FOR FULL COMPLIANCE WITH ALL JOB SAFETY RELATED REGULATIONS AND CONDITIONS AT THE SITE. LIMITED SITE VISITS, IF ANY, BY THE STRUCTURAL ENGINEER ARE SOLELY
TO OBSERVE COMPLETED PARTS OF THE STRUCTURE. THE STRUCTURAL ENGINEER IS NEITHER
QUALIFIED TO OBSERVE NOR COMMENT ON CONSTRUCTION MEANS AND METHODS AND JOB SITE
SAFETY.
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SITE CONDITIONS PRIOR TO
FABRICATION/CONSTRUCTION. NOTIFY STRUCTURAL ENGINEER AND ARCHITECT OF ANY
DISCREPANCIES PRIOR TO FABRICATION/CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR ALL
WORK FITTING AS INTENDED BY THE DRAWINGS AND SPECIFICATIONS.
PRINCIPAL OPENINGS ARE SHOWN ON THE DRAWINGS. SEE ARCHITECTURAL, MECHANICAL AND
ELECTRICAL DRAWINGS FOR OPENINGS, SLEEVES, CURBS, INSERTS, DEPRESSIONS, ETC. NOT SHOWN.
ALL DETAILS ARE TYPICAL UNLESS NOTED OTHERWISE. DETAILS SHALL APPLY TO SIMILAR AND LIKE
CONDITIONS.
SHOP DRAWINGS SHALL BE NEW DRAWINGS PRODUCED BY THE CONTRACTOR, ILLEGIBLE
REPRODUCTIONS OF THE DESIGN DRAWINGS WILL BE REJECTED. ELECTRONIC FILES MAY BE
REQUESTED FROM THE ENGINEER OF RECORD FOR THE PURPOSE OF PREPARING SHOP DRAWINGS.
THE CONTRACTOR WILL BE REQUIRED TO SIGN AN INDEMNITY STATEMENT PRIOR TO TRANSMISSION
OF THE ELECTRONIC FILES TO THE CONTRACTOR. THE USE OF REPRODUCTIONS OF THESE
CONTRACT DRAWINGS BY ANY CONTRACTOR, SUBCONTRACTOR, ERECTOR, FABRICATOR, OR
MATERIAL SUPPLIER IN LIEU OF PREPARATION OF SHOP DRAWINGS SIGNIFIES HIS ACCEPTANCE OF ALL INFORMATION SHOWN HEREIN AS CORRECT, AND OBLIGATES HIMSELF TO ANY JOB EXPENSE, REAL OR IMPLIED, ARISING DUE TO ANY ERRORS OR OMISSIONS THAT MAY OCCUR HEREIN.
MINIMUM SHOP DRAWING SUBMITTAL REQUIREMENTS INCLUDE:
STRUCTURAL STEEL SHOP DRAWINGS
UNISTRUT AND CONNECTION SHOP DRAWINGS AND CALCULATIONS (SEALED BY A
LICENSED PROFESSIONAL ENGINEER)
THIS PROJECT CONSISTS OF A MODIFICATION TO AN EXISTING BUILDING. INFORMATION ON EXISTING
CONDITIONS HAS BEEN TAKEN FROM THE ORIGINAL DESIGN DRAWINGS AND SHOWN ON THESE
DRAWINGS. THESE DRAWINGS WERE ASSUMED TO BE “AS-BUILT” DRAWINGS. EXISTING DIMENSIONS, FRAMING LAYOUT AND MEMBER SIZES WERE DETERMINED BY VISUAL OBSERVATION ONLY WITHOUT
THE REMOVAL OF FINISHES AND THEREFORE THE ACCURACY OF THIS INFORMATION IS NOT
GUARANTEED. IT IS THE CONTRACTOR’S RESPONSIBILITY TO VERIFY ALL EXISTING DIMENSIONS SHOWN ON THESE DRAWINGS AND TO VERIFY THE LOCATION OF ALL FRAMING MEMBERS AND OTHER OBSTRUCTIONS WHICH WILL AFFECT THE WORK. AS PART OF THIS WORK THE CONTRACTOR SHALL PREPARE AN ACCURATE FIELD SURVEY OF THE LOCATION OF ALL STRUCTURAL MEMBERS IN THE WORK AREA PRIOR TO BEGINNING SHOP DRAWINGS AND CONSTRUCTION. THIS SURVEY SHALL BE SUBMITTED TO THE ENGINEER OF RECORD WITH VARIANCES NOTED. CLAIMS FOR ADDITIONAL TIME OR EXTRA COST DUE TO OBSTRUCTIONS AND VARIANCES IN THE LOCATION OF THE STRUCTURAL
MEMBERS WILL NOT BE HONORED AFTER WORK HAS BEGUN ON THE PROJECT.
BUILDING CODE: INTERNATIONAL BUILDING CODE, 2018
DEAD LOAD:
ANY CHANGES IN CONSTRUCTION MATERIALS FROM THOSE SHOWN ON
THE STRUCTURAL DRAWINGS SHALL BE REPORTED BY THE CONTRACTOR
TO THE STRUCTURAL ENGINEER FOR VERIFICATION OF LOAD CARRYING
CAPACITY OF THE STRUCTURE.
LIVE LOAD:
ROOF: 20 PSF
STAIRS, EXITWAYS: 100 PSF
CLINICAL SPACE: 80 PSF
PARTITION: 20 PSF
CORRIDORS: 100 PSF (1ST FLOOR)/ 80 PSF (ABOVE 1ST FLOOR)
LOBBIES: 100 PSF
OFFICE: 50 PSF
LIGHT STORAGE: 125 PSF
MECHANICAL: 150 PSF
HANDRAILS: 50 PLF / 200 POUNDS IN ANY DIRECTION
LIVE LOAD REDUCTIONS HAVE BEEN APPLIED IN ACCORDANCE WITH THE
BUILDING CODE, UNLESS NOTED OTHERWISE.
WIND LOAD:
INTERNATIONAL BUILDING CODE, 2018 EDITION
VELOCITY (ULT) : 152 MPH THREE SECOND GUST
EXPOSURE: B
RISK CATEGORY: IV
INTERNAL PRESSURE COEFFICIENT, Gcpi: +/- 0.18
SEISMIC LOAD:
RISK CATEGORY: IV
SEISMIC IMPORTANCE FACTOR (I): 1.5
MAPPED SPECTRAL RESP ACCEL (Ss/S1): 0.286g/0.081g
SITE CLASS: D
SPECTRAL RESPONSE COEFF (Sds/Sd1): 0.299g/0.129g
SEISMIC DESIGN CATEGORY: C
SNOW LOAD:
GROUND SNOW LOAD (Pg): N/A
STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL DESIGN, DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO
ALLOWABLE STRENGTH DESIGN (ASD) ACCORDING TO THE LATEST AISC SPECIFICATION.
2. ALL WELDING SHALL CONFORM TO THE STANDARDS OF THE LATEST EDITION OF THE STEEL
CONSTRUCTION MANUAL OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, AND THE
AMERICAN WELDING SOCIETY ANSI/AWS D1.1 STRUCTURAL WELDING CODE-STEEL. WELDING OF
REINFORCING BARS SHALL COMPLY TO THE AMERICAN WELDING SOCIETY AWS D.1.4. SHORT
CIRCUIT TRANSFER FOR THE GAS METAL ARC WELDING PROCESS IS NOT PERMITTED.
3. ELECTRODES FOR ALL FIELD AND SHOP WELDING SHALL BE CLASS E70XX. ELECTRODES FOR MOMENT CONNECTIONS SHALL BE CLASS E7018 WITH A CHARPY TOUGHNESS OF AT LEAST 20 FT-
LBS AT -20 DEGREES FAHRENHEIT.
4. ALL STRUCTURAL STEEL ROLLED SHAPES SHALL CONFORM TO ASTM A992, AND ALL ANGLES, BARS, CHANNELS AND PLATES SHALL CONFORM TO ASTM A36. ALL SQUARE AND RECTANGULAR TUBE (Fy 46KSI) SHALL CONFORM TO ASTM A500 GRADE B AND ROUND PIPES (Fy 36KSI) SHALL CONFORM TO ASTM A53 GR B. ALL COLD-FORMED GIRTS AND PURLINS SHALL CONFORM TO ASTM A570M GR. 55.
5. ALL STRUCTURAL STEEL DETAILS AND CONNECTIONS SHALL CONFORM TO STANDARDS OF AISC.
DOUBLE CONNECTIONS THROUGH COLUMN WEBS, BEAMS THAT FRAME OVER THE TOP OF
COLUMNS, AND BEAM TO BEAM CONNECTIONS SHALL HAVE A BEAM ERECTION SEAT OR A
STAGGERED CONNECTION WITH AT LEAST ONE INSTALLED BOLT REMAINING IN PLACE TO
SUPPORT THE FIRST BEAM WHILE THE SECOND BEAM IS BEING ERECTED.
6. TYPICAL CONNECTIONS ARE INDICATED ON THE DRAWINGS.
7. IT IS THE INTENTION OF THE PLANS AND SPECIFICATIONS THAT SHOP CONNECTIONS BE WELDED
OR BOLTED AND THAT FIELD CONNECTIONS BE BOLTED, UNLESS NOTED OTHERWISE ON THE
DRAWINGS.
8. ALL TYPICAL BEAM SIMPLE CONNECTIONS SHALL BE STANDARD DOUBLE ANGLE OR SINGLE ANGLE
FRAMED BEAM CONNECTIONS. SHEAR TAB CONNECTIONS MAY BE USED AT LOCATIONS WHERE
DOUBLE ANGLE CONNECTIONS ARE NOT POSSIBLE. SEATED BEAM CONNECTIONS SHALL NOT BE
USED UNLESS INDICATED ON THE DRAWINGS PROVIDE FULL DEPTH SHEAR TAB IF BEAM FRAMES
ON ONLY ONE SIDE OF A GIRDER.
9. ALL MISCELLANEOUS WELDS (FIELD OR SHOP) SHALL BE MINIMUM SIZE FILLET ALL AROUND IN
ACCORDANCE WITH AISC 360. WELDING OF CONTINUOUS MEMBERS SHALL BE A MINIMUM OF 2
INCHES OF 3/16 INCH FILLET STITCH WELDS AT 12 INCHES O.C., STAGGERED EACH SIDE, UNLESS
OTHERWISE NOTED. COLUMN BASE PLATES, CAP PLATES AND STIFFENER PLATES SHALL BE
WELDED ALL AROUND.
10. PROVIDE ALL NECESSARY HOLES IN MISCELLANEOUS STRUCTURAL STEEL MEMBERS FOR
ATTACHMENT OF NON-STRUCTURAL ITEMS (IE: HOLES FOR WINDOW HEAD ANCHORS), SEE
ARCHITECTURAL DRAWINGS FOR REQUIREMENTS.
11. SPLICING OF STRUCTURAL STEEL MEMBERS WHERE NOT DETAILED IS PROHIBITED WITHOUT PRIOR
APPROVAL OF THE STRUCTURAL ENGINEER.
14. ALL CONNECTION BOLTS FOR STRUCTURAL STEEL MEMBERS SHALL CONFORM TO ASTM F3125, GRADE A325, TYPE 1 EXCEPT WHERE NOTED OTHERWISE. MINIMUM SIZE SHALL BE 3/4 INCH
DIAMETER UNLESS NOTED OTHERWISE. BOLTS SHALL BE DIRECT TENSION INDICATING BOLTS
CONFORMING TO ASTM F3125, GRADE F1852 WITH HARDENED WASHERS UNDER THE NUT AND
SACRIFICIAL SPLINES. HEX NUTS SHALL CONFORM TO ASTM A563 AND WASHERS SHALL CONFORM
TO ASTM F436.
15. SHOP BOLTED CONNECTIONS ARE PERMISSIBLE IF SUFFICIENT BOLT CLEARANCE IS AVAILABLE FOR TIGHTENING OF HIGH STRENGTH BOLTS. CLEARANCES SHALL BE IN ACCORDANCE WITH TABLE 7-15 AND 7-16 OF THE FOURTEENTH EDITION OF THE AISC STEEL CONSTRUCTION MANUAL. ALL
STEEL MEMBERS AND ASSEMBLIES SHALL BE SHOP FABRICATED TO THE GREATEST EXTENT
POSSIBLE. TRUSSES SHALL BE FULLY SHOP ASSEMBLED. FIELD SPLICES FOR SHIPPING SHALL ONLY BE AS APPROVED BY THE ENGINEER OF RECORD. THE STEEL FABRICATOR AND THE STEEL
ERECTOR SHALL COORDINATE THE SHOP FABRICATION, SHIPPING AND ERECTION OF ALL
STRUCTURAL MEMBERS AND ASSEMBLIES.
16. THE GENERAL CONTRACTOR AND THEIR SUBCONTRACTOR’S SHALL COMPLY TO OSHA 29 CFR 1926
SUBPART R, SAFETY STANDARDS FOR STEEL ERECTION.
17. AS SCOPE AND PERFORMANCE DOCUMENTS, THE DRAWINGS AND SPECIFICATIONS DO NOT
INDICATE OR DESCRIBE ALL OF THE WORK REQUIRED FOR THE PERFORMANCE AND COMPLETION
OF THIS WORK. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE FABRICATION AND
INSTALLATION OF ALL MISCELLANEOUS METAL ITEMS INDICATED, DESCRIBED, OR IMPLIED ON THE STRUCTURAL AND/OR THE ARCHITECTURAL DRAWINGS. MISCELLANEOUS STEEL ITEMS, WITHIN AN ASSEMBLY AND NOT ATTACHED TO THE STRUCTURE, ARE THE RESPONSIBILITY OF THE GENERAL
CONTRACTOR AND THEIR SUBCONTRACTORS WHETHER THEY ARE SHOWN OR NOT SHOWN ON
THE ARCHITECTURAL OR STRUCTURAL DRAWINGS. SUCH ASSEMBLIES INCLUDE BUT ARE NOT
LIMITED TO, EXTERIOR AND INTERIOR WALL ASSEMBLIES, CEILING ASSEMBLIES, PARTITION
ASSEMBLIES, SHELF AND CABINET ASSEMBLIES AND ALL OTHER SIMILAR ASSEMBLIES. ANY
MISCELLANEOUS METAL ITEMS INDICATED ON THE ARCHITECTURAL DRAWINGS AND NOT SHOWN
ON STRUCTURAL DRAWINGS SHALL BE A MINIMUM OF L4x4x1/2”, C7x9.8, 3/8” PLATE OR HSS4x4x3/8”
UNLESS OTHERWISE APPROVED BY THE STRUCTURAL ENGINEER.
STRUCTURAL TESTING AND INSPECTIONS
SPECIAL INSPECTIONS
SPECIAL INSPECTION WORK AND THE FINAL LETTER OF COMPLIANCE HAVE NOT BEEN
INCLUDED IN THE STRUCTURAL ENGINEER OF RECORD’S SCOPE OF SERVICES. PER IBC
CHAPTER 17, THE OWNER IS RESPONSIBLE FOR OBTAINING THE SERVICES OF THE SPECIAL
INSPECTOR AND THE TESTING LABORATORY. SPECIAL INSPECTIONS CAN BE PROVIDED BY AN
INDEPENDENT SPECIAL INSPECTOR APPROVED BY THE BUILDING AUTHORITY OR BY THE
ENGINEER OF RECORD. THE SPECIAL INSPECTION WORK DOES NOT INCLUDE THE TESTING
LABORATORY SERVICES AS CALLED FOR ON THE DRAWINGS. ARRANGEMENTS FOR SPECIAL
INSPECTIONS SHOULD BE MADE PRIOR TO THE COMMENCEMENT OF CONSTRUCTION. THE
CONTRACTOR IS RESPONSIBLE FOR NOTIFYING THE OWNER IF SPECIAL INSPECTIONS ARE
REQUIRED ON THE APPROVED PERMIT DRAWINGS AND FOR NOTIFYING THE TESTING
LABORATORY AND SPECIAL INSPECTOR IN A TIMELY MANNER PRIOR TO PROCEEDING WITH
CONSTRUCTION OPERATIONS. THE CONTRACTOR SHALL NOT PROCEED WITH ANY WORK
REQUIRING INSPECTIONS WITHOUT THE TESTING LABORATORY’S OR SPECIAL INSPECTOR’S
PRESENCE. THE STRUCTURAL ENGINEER WILL NOT PROVIDE A FINAL LETTER OF COMPLIANCE
AFTER THE WORK IS COMPLETE UNLESS THEY HAVE PERFORMED THE SPECIAL INSPECTIONS.
STRUCTURAL STATEMENT OF SPECIAL INSPECTIONS
INCLUDED HERE ARE SPECIAL INSPECTIONS REQUIRED FOR THE STRUCTURAL ELEMENTS FOR
THIS PROJECT. REFERENCE STATEMENT OF SPECIAL INSPECTIONS BY ARCHITECT AND OTHER
CONSULTANTS FOR SPECIAL INSPECTION DETAILS OF NON-STRUCTURAL ITEMS REQUIRED BY
IBC AND PROVIDED IN THE SPECIFICATIONS.
PER IBC 1704.2.4, THE STRUCTURAL SPECIAL INSPECTOR SHALL KEEP RECORDS OF ALL
STRUCTURAL INSPECTIONS AND SHALL FURNISH INSPECTION REPORTS TO THE OWNER AND
THE STRUCTURAL REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE (SRDP).
DISCOVERED DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR
FOR CORRECTION. IF SUCH DISCREPANCIES ARE NOT CORRECTED, THE DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF THE OWNER AND THE SRDP. THE SPECIAL INSPECTION
PROGRAM DOES NOT RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES.
A FINAL REPORT OF SPECIAL INSPECTION DOCUMENTING COMPLETION OF ALL SPECIAL
INSPECTIONS, TESTING AND CORRECTION OF ANY DISCREPANCIES NOTED IN THE INSPECTIONS
SHALL BE SUBMITTED TO THE OWNER AND THE SRDP PRIOR TO THE ISSUANCE OF A
CERTIFICATE OF OCCUPANCY AND USE.
CONTRACTOR RESPONSIBILITY
PER IBC 1704.4, EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A MAIN WIND-
OR SEISMIC FORCE-RESISTING SYSTEM, DESIGNATED SEISMIC SYSTEM OR A WIND- OR
SEISMIC-RESISTING COMPONENT LISTED IN THE STATEMENT OF SPECIAL INSPECTIONS SHALL
SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND THE
OWNER PRIOR TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT. THE
CONTRACTOR'S STATEMENT OF RESPONSIBILITY SHALL CONTAIN ACKNOWLEDGEMENT OF
AWARENESS OF THE SPECIAL REQUIREMENTS CONTAINED IN THE STATEMENT OF SPECIAL
INSPECTIONS.
STRUCTURAL SCHEDULE OF SPECIAL INSPECTIONS
QUALIFICATIONS OF INSPECTORS AND TESTING TECHNICIANS
THE QUALIFICATIONS OF ALL PERSONNEL PERFORMING SPECIAL INSPECTION AND TESTING
ACTIVITIES ARE SUBJECT TO THE APPROVAL OF THE OWNER. THE CREDENTIALS OF ALL
INSPECTORS AND TESTING TECHNICIANS SHALL BE PROVIDED TO THE SPECIAL INSPECTOR
FOR THEIR RECORDS.
KEY FOR MINIMUM QUALIFICATION OF INSPECTION AGENTS
WHEN THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE OR SPECIAL
INSPECTOR OF RECORD DEEMS APPROPRIATE THAT THE INDIVIDUAL PERFORMING THE
STIPULATED TEST OR INSPECTION HAVE A SPECIFIC CERTIFICATION, LICENSE OR EXPERIENCE
AS INDICATED BELOW. SUCH REQUIREMENT SHALL BE LISTED BELOW AND SHALL BE CLEARLY
IDENTIFIED WITHIN THE SCHEDULE UNDER THE AGENT QUALIFICATION DESIGNATION.
• PE/SE STRUCTURAL ENGINEER – A LICENSED SE OR PE SPECIALIZING IN THE DESIGN OF
BUILDING STRUCTURES
• PE/GE GEOTECHNICAL ENGINEER – A LICENSED PE SPECIALIZING IN SOIL MECHANICS
AND FOUNDATIONS
• EIT ENGINEER IN TRAINING – A GRADUATE ENGINEER WHO HAS PASSED THE
FUNDAMENTALS OF ENGINEERING EXAM
• ETT EXPERIENCED TESTING TECHNICIAN – AN EXPERIENCED TESTING TECHNICIAN
WITH A MINIMUM OF 5 YEARS EXPERIENCE WITH THE STIPULATED TEST OR INSPECTION
AMERICAN WELDING SOCIETY (AWS) CERTIFICATION
• AWS-CWI CERTIFIED WELDING INSPECTOR
• AWS/AISC-SSICERTIFIED STRUCTURAL STEEL INSPECTOR
PERIODIC, CONTINUOUS, OBSERVE, PERFORM, AND DOCUMENT ARE DEFINED AS IN THE SPECIFIC
REFERENCE STANDARD.
SPECIAL CASES
1. PER IBC 1705.1.1, SPECIAL INSPECTIONS AND TESTS SHALL BE REQUIRED FOR PROPOSED WORK THAT IS, IN THE OPINION OF THE BUILDING OFFICIAL, UNUSUAL IN ITS NATURE SUCH AS:
A. MATERIALS AND SYSTEMS REQUIRED TO BE INSTALLED IN ACCORDANCE WITH ADDITIONAL
MANUFACTURER'S INSTRUCTIONS THAT PRESCRIBE REQUIREMENTS NOT CONTAINED IN IBC
OR IN STANDARDS REFERENCED BY IBC.
B. UNUSUAL DESIGN APPLICATIONS OF MATERIALS DESCRIBED IN IBC.
C. CONSTRUCTION MATERIALS AND SYSTEMS THAT ARE ALTERNATIVES TO MATERIALS AND
SYSTEMS PRESCRIBED BY THIS CODE.
STRUCTURAL STEEL TESTING
1. PER IBC 1705.2, SPECIAL INSPECTIONS AND TESTS OF STEEL CONSTRUCTION SHALL BE
PERFORMED.
2. CERTIFY WELDERS FOR THE WELD TYPES IN THE PROJECT AND CONDUCT INSPECTIONS AND
TESTS AS REQUIRED, AS A MINIMUM, WELDERS SHALL BE AISC CERTIFIED. RECORD TYPES AND
LOCATIONS OF DEFECTS FOUND IN WORK. RECORD WORK REQUIRED AND PERFORMED TO
CORRECT DEFICIENCIES.
3. VISUALLY INSPECT 100% OF ALL FILLET WELDS.
4. ALL WELDS THAT FAIL SHALL BE REWELDED AND RETESTED UNTIL THEY PASS THE TEST. TEST
TWO ADDITIONAL WELDS AT THE CONTRACTOR’S EXPENSE FOR EVERY WELD FAILURE.
5. BOLTS SHALL BE VISUALLY INSPECTED WHEN TWIST-OFF SPLINES ARE USED, OTHERWISE
BOLTS SHALL BE SNUG TIGHT.
SCHEDULE OF SPECIAL INSPECTIONS
VERIFICATION / INSPECTION BOLTING INSPECTIONS
IBC SECTION 1705.2, AISC 360,
LATEST EDITION
EXTENT
OBSERVE,
PERFORM
COMMENTS
AGENT
PE/GE, EIT,
OR ETT
PERFORM
ETT
ETT
OBSERVE ETT
MANUFACTURER'S CERTIFICATIONS
AVAILABLE FOR FASTENER MATERIALS
CORRECT FASTENERS SELECTED FOR
THE JOINT DETAIL (GRADE, TYPE, BOLT
LENGTH IF THREADS ARE TO BE
EXCLUDED FROM SHEAR PLANE)
FASTENERS MARKED IN ACCORDANCE WITH
ASTM REQUIREMENTS
CORRECT BOLTING PROCEDURE SELECTED
FOR JOINT DETAIL
CONNECTING ELEMENTS, INCLUDING THE
APPROPRIATE FAYING SURFACE CONDITION
AND HOLE PREPARATION, IF SPECIFIED,
MEET APPLICABLE REQUIREMENTS
PRE-INSTALLATION VERIFICATION TESTING
BY INSTALLATION PERSONNEL OBSERVED
AND DOCUMENTED FOR FASTENER
ASSEMBLIES AND METHODS USED
PROTECTED STORAGE PROVIDED FOR
BOLTS, NUTS, WASHERS AND OTHER
FASTENER COMPONENTS
PERFORM ETT
ETT
ETT
ETT
ETT
INSPECTIONS PRIOR TO BOLTING
INSPECTIONS DURING BOLTING
FASTENER ASSEMBLIES PLACED IN ALL
HOLES AND WASHERS AND NUTS ARE
POSITIONED AS REQUIRED
JOINT BROUGHT TO THE SNUG-TIGHT
CONDITION PRIOR TO THE PRETENSIONING
OPERATION
FASTENER COMPONENT NOT TURNED BY
THE WRENCH PREVENTED FROM ROTATING
FASTENERS ARE PRETENSIONED IN
ACCORDANCE WITH THE RCSC
SPECIFICATION, PROGRESSING
SYSTEMATICALLY FROM THE MOST RIGID
POINT TOWARD THE FREE EDGES
INSPECTIONS AFTER BOLTING
DOCUMENT ACCEPTANCE OR REJECTION
OF BOLTED CONNECTIONS
TABLE N5.6-1
TABLE N5.6-1
TABLE N5.6-1
TABLE N5.6-1
TABLE N5.6-1
TABLE N5.6-1
TABLE N5.6-1
TABLE N5.6-2
TABLE N5.6-2
TABLE N5.6-2
TABLE N5.6-2
TABLE N5.6-3
ETT
ETT
ETT
ETT
OBSERVE
OBSERVE
OBSERVE
OBSERVE
OBSERVE
OBSERVE
OBSERVE
OBSERVE
OBSERVE
SCHEDULE OF SPECIAL INSPECTIONS
VERIFICATION / INSPECTION INSPECTION PRIOR TO WELDING
IBC 2018 SECTION 1705.2, AISC 360-16
EXTENT
OBSERVE,
PERFORM
COMMENTS
AGENT
PE/GE, EIT,
OR ETT
WELDING PROCEDURE SPECIFICATIONS
(WPSs) AVAILABLE
PERFORM ETT
PERFORM TABLE N5.4-1 ETT
OBSERVE ETT
ETT
CHECK WELDING EQUIPMENT
MANUFACTURER CERTIFICATIONS FOR
WELDING CONSUMABLES AVAILABLE
TABLE N5.4-1
MATERIAL IDENTIFICATION (TYPE/GRADE) TABLE N5.4-1
WELDER IDENTIFICATION SYSTEM OBSERVE TABLE N5.4-1 ETT
FIT-UP OF GROOVE WELDS (INCLUDING
JOINT GEOMETRY)
• JOINT PREPARATION
• DIMENSIONS (ALIGNMENT, ROOT
OPENING, ROOT FACE, BEVEL)
• CLEANLINESS (CONDITION OF
STEEL SURFACES)
• TACKING (TACK WELD QUALITY
AND LOCATION)
• BACKING TYPE AND FIT (IF
APPLICABLE)
OBSERVE TABLE N5.4-1 ETT
CONFIGURATION AND FINISH OF ACCESS
HOLES OBSERVE TABLE N5.4-1 ETT
FIT-UP OF FILLET WELDS
• DIMENSIONS (ALIGNMENT, GAPS
AT ROOT)
• CLEANLINESS (CONDITION OF
STEEL SURFACES)
• TACKING (TACK WELD QUALITY
AND LOCATION)
OBSERVE TABLE N5.4-1
ETTOBSERVE TABLE N5.4-1
WELDER QUALIFICATION RECORDS AND
CONTINUITY RECORDS
FIT-UP OF CJP GROOVE WELDS OF HSS
T-, Y, AND K-JOINTS WITHOUT BACKING
(INCLUDING JOINT GEOMETRY)
• JOINT PREPARATION
• DIMENSIONS (ALIGNMENT, ROOT
OPENING, ROOT FACE, BEVEL)
• CLEANLINESS (CONDITION OF
STEEL SURFACES)
• TACKING (TACK WELD QUALITY
AND LOCATION)
• BACKING TYPE AND FIT (IF
APPLICABLE)
OBSERVE TABLE N5.4-1 ETT
OBSERVE TABLE N5.4-1 ETT
SCHEDULE OF SPECIAL INSPECTIONS
VERIFICATION / INSPECTION INSPECTION DURING WELDING
IBC 2018 SECTION 1705.2, AISC 360-16
EXTENT
OBSERVE,
PERFORM
COMMENTS
AGENT
PE/GE, EIT,
OR ETT
PERFORM
ETT
OBSERVE ETT
OBSERVE ETT
ETT
OBSERVE TABLE N5.4-2 ETT
OBSERVE ETT
CONTROL AND HANDLING OF WELDING
CONSUMABLES
• PACKAGING
• EXPOSURE CONTROL
NO WELDING OVER CRACKED TACK WELDS
PLACEMENT AND INSTALLATION OF STEEL
HEADED STUD ANCHORS
ENVIRONMENTAL CONDITIONS
• WIND SPEED WITHIN LIMITS
• PRECIPITATION AND
TEMPERATURE
WPS FOLLOWED
• SETTINGS ON WELDING
EQUIPMENT
• TRAVEL SPEED
• SELECTED WELDING MATERIALS
• SHIELDING GAS TYPE/FLOW RATE
• PREHEAT APPLIED
• INTERPASS TEMPERATURE
MAINTAINED (MIN/MAX)
• PROPER POSITION (F,V,H,OH)
WELDING TECHNIQUES
• INTERPASS AND FINAL CLEANING
• EACH PASS WITHIN PROFILE
LIMITATIONS
• EACH PASS MEETS QUALITY
REQUIREMENTS
OBSERVE TABLE N5.4-2
TABLE N5.4-2
TABLE N5.4-2
TABLE N5.4-2
TABLE N5.4-2
SCHEDULE OF SPECIAL INSPECTIONS
VERIFICATION / INSPECTION INSPECTION AFTER WELDING
IBC 2018 SECTION 1705.2, AISC 360-16
EXTENT
OBSERVE,
PERFORM
COMMENTS
AGENT
PE/GE, EIT,
OR ETT
PERFORM
ETT
ETT
ETT
OBSERVE
TABLE N5.4-3 ETT
OBSERVE ETT
WELDS CLEANED
WELDS MEET VISUAL ACCEPTANCE
CRITERIA
• CRACK PROHIBITION
• WELD / BASE-METAL FUSION
• CRATER CROSS SECTION
• WELD PROFILES
• WELD SIZE
• UNDERCUT
• POROSITY
TABLE N5.4-3
TABLE N5.4-3
TABLE N5.4-3
TABLE N5.4-3
SIZE, LENGTH, AND LOCATION OF WELDS
ARC STRIKES
K - AREA
WELD ACCESS HOLES IN ROLLED HEAVY
SHAPES AND BUILT-UP HEAVY SHAPES
BACKING REMOVED AND WELD TABS
REMOVED (IF REQUIRED)
REPAIR ACTIVITIES
DOCUMENT ACCEPTANCE OR REJECTION
OF WELDED JOINT OR MEMBER
NO PROHIBITED WELDS HAVE BEEN ADDED
WITHOUT THE APPROVAL OF THE EOR
PERFORM
PERFORM
PERFORM
PERFORM
PERFORM
PERFORM
PERFORM
TABLE N5.4-3 ETT
TABLE N5.4-3 ETT
ETTTABLE N5.4-3
ETTTABLE N5.4-3
ETTTABLE N5.4-3
STRUC ABBREVIATIONS
+/- PLUS OR MINUS
ADDNL ADDITIONAL
ADJ ADJACENT
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ARCH ARCHITECT OR ARCHITECTURAL
B/W BETWEEN
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOD BOTTOM OF DECK
BOS BOTTOM OF STEEL
CF COLD FORMED
CFMF COLD-FORMED METAL FRAMING
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLR CLEAR/CLEARANCE
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CTR CENTER
db DIA OF REINF BAR, DIA OF BOLT
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DIA DIAMETER
DIAG DIAGONAL
DWL DOWEL
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EW EACH WAY
EXIST EXISTING
EXT EXTERIOR
FLR FLOOR
FND FOUNDATION
FS FAR SIDE
FTG FOOTING
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SECTION
IF INSIDE FACE
INT INTERIOR
JST JOIST
K KIPS (1000 LBS)
LCE COMPRESSION EMBEDMENT LENGTH
LCS COMPRESSION LAP SPLICE LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LTE TENSION EMBEDMENT LENGTH
LTS TENSION LAP SPLICE LENGTH
LW LIGHTWEIGHT
MANUF MANUFACTURER
MTL METAL
NIC NOT IN CONTRACT
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OCEW ON CENTER, EACH WAY
OF OUTSIDE FACE
OH OPPOSITE HAND
OPP OPPOSITE
PAF POWDER ACTUATED FASTENER
PEMB PRE-ENGINEERED METAL BUILDING
PL PLATE
PLF POUNDS PER LINEAL FOOT
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
RE: OR REF REFER TO
REINF REINFORCING
REQD REQUIRED
SIM SIMILAR
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STL STEEL
SW SHEAR WALL
SYM SYMMETRIC
T&B TOP AND BOTTOM
TOC TOP OF CONCRETE
TOD TOP OF DECK
TOS TOP OF STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WP WORK POINT
WWF WELDED WIRE FABRIC
H2B, INC.
TEXAS FIRM REGISTRATION NO. 8856
1225 N LOOP W, SUITE 800
HOUSTON, TX 77008
713.864.2900
P
LO
T T
E D
O N
F
IL
E
N A
M E
SCALE:
DESIGNED BY :
DRAWN BY :
AS SHOWN
VA PROJECT No. :
09-18-2020
/1
/2
:4
:5
P M
C U s e rs \z a c k e ry .f e rg u s o n
\D o c u m e n ts
\M A
D V
A M
C Z e ro
G ra v it y A n a ly s is
R
S T
R C e n tr a l_
Z a c k e ry .F e rg u s o n A
N N
A .r v t
SA-001
STRUCTURAL GENERAL NOTES
ZERO GRAVITY SYSTEM FOR CATH LAB
MEDVAMC HOUSTON, TEXAS
CCM
ZAF
580-20-104
REV DESCRIPTION DATE
0 ISSUE FOR PERMIT 09/18/2020
1/4
1/4
Le v
Le v
"S " S
PA
CI
NG
(N
D" D
IA
A3
-N
B
OL
TS
VARIABLES:
Lev = 1 1/2" D = 3/4"
N = PER TABLE
S = 3"
BEAM N
W8, W10 2
NOTES:
3" DIM. TYP. EXCEPT AS
RECOMMENDED BY AISC FOR W8 &
SMALLER BEAMS OR FOR LARGER
BEAMS.
FACE OF : BEAM WEB, COL. FLG.,
OR COL. WEB
.1
L 3 ½ x 3 ½ x 5/16 " DBL
ANGLE CONN (GA = 4
½" MIN)
MI
N3"
EXIST W18
OR W21
EXISTING 4 1/2" CONC
ON METAL DECK (VIF)
EXISTING W18x35 OR W16x26
NEW CONT
L3x3x1/4 EA SIDE
FULL LENGTH OF
EXIST BEAM
1/4"
3/16" MIN
1/4"3 1/2" @
12" OC
3 1/2" @
12" OC
EXISTING 4 1/2" CONC
ON METAL DECK (VIF)
EXISTING W16
4th FLOOR
3/16" MIN
V.
I.F
1'
- 4
1/ 8"
V.
I.F
7'
- 1
1 7 /8"
EXIST
4th FLOOR
NEW HSS4x4
BETWEEN EXIST
HANGER RODS
EXIST C6 CHANNELS
SPACING VARIES
EQUIPMENT
EXIST CONC ON
METAL DECK (4 3/8"
TOTAL V.I.F.)
UNISTRUT SUPPLIER
PROVIDE CHANNEL NUT
TO SUPPORT 1.8K (ASD)
LOAD
+/- 2' - 0"
P5001 BETWEEN
EXIST UNISTRUT IN
CEILING @ 2'-0" OC
(5 TOTAL, V.I.F.)
+/- 9'-6" CEILING
TO 3rd FF BELOW COORD w/ EXIST
AND EQUIP MANUF.
UNISTRUT P1652S
BEAM CLAMP w/ 3/4"Ø
THREADED ROD
3/4"x6"x0'-11" CAP PLATE w/ (4) 3/4"Ø
BOLTS
C6 - SEE PLANSEE DETAIL 6 THIS
SHEET FOR CONN
TO HSS 4x4 HANGER
3/4"Ø DIA BOLT
IN VERT. SLOTTED
HOLE
L4x4x3/8" EA SIDE
OF HANGER
MI
N.
1/2
1'
- 0
T.O. INTERSTITIAL
6" FLOOR PURLIN
L5x5x5/16" BRACE @ 4'-0" OC
EXIST W18
WELD ANGLE
ALL AROUND
EXIST
W BEAM
EXIST
W BEAM
EXIST 4 1/2"
CONC ON METAL
DECK (VIF)
3/16" MIN
C6 -
SEE PLAN 3/16" MIN.
3/16" MIN.
HSS 4x4 HANGER
- SEE PLAN
EXISTING 4 1/2" CONC
ON METAL DECK (VIF)
NEW W10x22
3/16" MIN
V.
I.F
1'
- 4
1/ 8"
V.
I.F
7'
- 1
1 7 /8"
EXIST
4th FLOOR
NEW HSS4x4
BETWEEN EXIST
HANGER RODS
EQUIPMENT
UNISTRUT SUPPLIER
PROVIDE CHANNEL NUT
TO SUPPORT 1.8K (ASD)
LOAD
+/- 2' - 0"
P5001 BETWEEN
EXIST UNISTRUT IN
CEILING @ 2'-0" OC
(5 TOTAL, V.I.F.)
+/- 9'-6" CEILING
TO 3rd FF BELOW COORD w/ EXIST
AND EQUIP MANUF.
3/4"x6"x0'-11" CAP PLATE w/ (4) 3/4"Ø
BOLTS
C6 - SEE PLAN
L3x3x5/16" X 0'-6"
EA SIDE OF HSS
4x4 w/ (2) 1/2"Ø
HILTI KWIK BOLT 3
w/ 2" EMBEDMENT
SEE DETAIL 6 THIS
SHEET FOR CONN
TO HSS 4x4 HANGER
3/4"Ø DIA BOLT
IN VERT. SLOTTED
HOLE
T.O. EXIST
INTERSTITIAL 6"
FLOOR PURLIN
1'
- 0
MI
N.
1/2
UNISTRUT P1652S
BEAM CLAMP w/ 3/4"Ø
THREADED ROD1
H2B, INC.
TEXAS FIRM REGISTRATION NO. 8856
1225 N LOOP W, SUITE 800
HOUSTON, TX 77008
713.864.2900
PL
OT
TE
D
ON
FI
LE
N
AM
E:
SCALE:
DESIGNED BY :
DRAWN BY :
AS SHOWN
VA PROJECT No. :
10/15/2020
/1
6/
1:
:0
AMC
:\U se rs
\e lb a.
du qu e\
D oc um en ts \M
AD
VA
M C
Z er o G ra vi ty A na ly si s_
R
_S
TR
_C en tra l_ el ba
.d uq ue .rv t
SA-050
TYPICAL DETAILS - STEEL
ZERO GRAVITY SYSTEM FOR CATH LAB
MEDVAMC HOUSTON, TEXAS
CCM
ZAF
580-20-104
NTS1 DOUBLE ANGLE CONNECTION
NTS2 EXIST WF REINF. DETAIL
NTS4
EQUIPMENT SUPPORT DETAIL - CATH
LAB #1
NTS3 BOTTOM FLANGE BRACING DETAIL
NTS6 CHANNEL TO HSS HANGER CONN
NTS5
EQUIPMENT SUPPORT DETAIL - CATH
LAB #3
REV DESCRIPTION DATE
1 BEAM CLAMP REVISION 10/15/2020
G G
22 21 20 19
H H
J J
K K
W21X50 W21X50 W21X50
W18X35W21X62
W21X62 W18X35
W18X35W21X62
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W21X57
W21X62
W21X62
V .I.
F
V .I.
F
V .I.
F
V.I.F.
36' - 6"
V.I.F.
36' - 6"
V.I.F.
36' - 6"
W21X44
W18X35
W21X44
W18X40
W18X40
W21X44
W21X44
W21X44
W21X44
W21X44
W21X50
W21X50
W18X35
W18X35
W18X35
W18X35
W18X35
W18X35
W18X35
W18X35
W18X35
W18X35
W18X35
W18X35
W16X26
W16X31
W16X31
W18X35
W18X35
W18X35
W18X35
W18X35
W18X35
W16X26
W16X26
W16X26
TYP
4' - 6"
TYP
4' - 6"
7' - 9" 9"
1' - 6"
6"
W
X
W
X
C10X15.3
W
X
W
X
W
X
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
E X
E X
E X
E X
E X
E X
E X
E X E X
E X
E X E X
E X
E X E X
E X E
X
E X
E X
E X
E X
SB-100
H.5 H.5
J.5 J.5
G.2 G.2
5'
W 10X12
W 10X12
W 10X12
W 10X12
W 10X12
W 10X12
W 10X12
W 10X12
EX
EX
EX
EX
EX
EX
EX
EX
SB-100
W
X
W
X
W
X
6' - 1" 6' - 1"
3 3
N E
W
N E
W
N E
W
TYP
FOR LOWER CEILING
SCHEMATIC PLAN
FOR LOWER CEILING
SCHEMATIC PLAN
C6x8.2
BELOW
3 3
TYP
4' - 6" 10' - 0"
6' - 1"
TYP
3' - 0 1/2"
TYP
3' - 0 1/2"
10' - 0" 4' - 6"
3' - 0 1/2"
V.I.F.
6' - 1"
C6x8.2
BELOW
GENERAL SHEET NOTES
A. REFERENCE SHEET SA-001 FOR STRUCTURAL GENERAL NOTES AND SA-050 FOR
TYPICAL STRUCTURAL DETAILS. REVIEW NOTES & DETAILS FOR APPLICABILITY.
B. SEE EQUIPMENT MANUFACTURER DRAWINGS FOR DETAILS & DIMENSIONS NOT
SHOWN.
C. EXISTING CONDITIONS AND DIMENSIONS SHALL BE CONFIRMED BY THE
CONTRACTOR. CONTRACTOR SHALL CONTACT ENGINEER OF RECORD WITH ANY
FIELD DISCREPANCIES.
FRAMING PLAN NOTES:
1. EXISTING 4 1/2" TOTAL THICK CONCRETE SLAB ON METAL DECK - GC TO FIELD
VERIFY.
2. EXISTING 3/4" DIA HANGERS SUPPORTING INTERSTITIAL FLOOR BELOW. GC
COORD EXISTING FRAMING LOCATIONS.
3. NEW HSS 4x4x3/8" HANGERS BETWEEN EXISTING HANGER RODS ON EXISTING
W16/NEW W10. SEE DETAIL 4 & 5/SA-050.
4. BRACE BOTTOM FLANGE OF EXISTING W18x35 TO ADJACENT EXISTING BEAMS WITH L5x5x5/16" @ 4'-0" OC. SEE PLAN FOR EXTENTS. SEE DETAIL .
5. REINFORCE EXISTING W18x35 AND W16x26 WITH (2) L3x3x1/4" AT BOTTOM
FLANGE - SEE DETAIL ./2 SA-050
/3 SA-050
H
H.5
V.I.F.
3' - 2"
TYP - V.I.F.
6 SPCS @ 2'-2"
V.I.F.
1' - 2"
V.I.F.
3' - 0"
NEW EQUIP - COORD
LOCATION w/ EXISTING
AND EQUIP MANUF.
EXISTING UNISTRUTS
INSTALLED FOR EXIST
EQUIPMENT SUPPORT
(TYP)
NEW UNISTRUT
P5001 BETWEEN
EXIST CEILING
UNISTRUTS (TYP)
K
NEW EQUIP - COORD
LOCATION w/ EXISTING
AND EQUIP MANUF.
EXISTING UNISTRUTS
INSTALLED FOR EXIST
EQUIPMENT SUPPORT
(TYP)
NEW UNISTRUT
P5001 BETWEEN
EXIST CEILING
UNISTRUTS (TYP)
5'
5'
O F
E X
IS
T
E Q
U
IP
V.I.F.
3' - 8"
V.I.F.
2' - 3"
TYP - V.I.F.
6 SPCS @ 2'-0"
V.I.F.
11 3/4"
V.I.F.
1' - 11 5/8"
V.I.F.
2' - 5 1/2"
H2B, INC.
TEXAS FIRM REGISTRATION NO. 8856
1225 N LOOP W, SUITE 800
HOUSTON, TX 77008
713.864.2900
P
LO
T T
E D
O N
F
IL
E
N A
M E
SCALE:
DESIGNED BY :
DRAWN BY :
AS SHOWN
VA PROJECT No. :
09-18-2020
/1
/2
:4
:0
P M
C U s e rs \z a c k e ry .f e rg u s o n
\D o c u m e n ts
\M A
D V
A M
C Z e ro
G ra v it y A n a ly s is
R
S T
R C e n tr a l_
Z a c k e ry .F e rg u s o n A
N N
A .r v t
SB-100
OVERALL 4TH FLOOR FRAMING
PLAN
ZERO GRAVITY SYSTEM FOR CATH LAB
MEDVAMC HOUSTON, TEXAS
CCM
ZAF
580-20-104
1/8" = 1'-0"
PARTIAL 4TH FLOOR FRAMING PLAN
1 : 60
CATH LAB #1 - ENLARGED FRAMING
PLAN
1 : 60
CATH LAB #3 - CEILING EQUIPMENT
SUPPORT SCHEMATIC
REV DESCRIPTION DATE
| Sheets |
| SA-001 - STRUCTURAL GENERAL NOTES |
| SA-050 - TYPICAL DETAILS - STEEL |
| SB-100 - OVERALL 4TH FLOOR FRAMING PLAN |
File details come from the government source that posted it. Updated .