564-22-407 Base-1-AI 101.pdf

PDF 771 KB Posted

Attached to
Z2DA--CON | 564-22-407 | NRM REPLACE CHEMO HOOD IV ROOM
Solicitation number
36C25622R0058
Issued by

View the file

Other files

File Type Posted
36C25622R0058 0001.docx DOCX document
564-22-407 Base-1-MH 101.pdf PDF
36C25622R0058_1 Chemo Hood.docx DOCX document
SOW 564-22-407 Relocate Chemo Hood .docx DOCX document
Wage Determination AR20210035.txt TXT text file
564-22-407 Specifications.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

T

EM

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

97 8654321

Location

Date Checked Drawn

Project Title

Office of Facilities

Management

Project Number

Building Number

Drawing Number

Dwg. of

Drawing Title

Approved: Project Director

ARCHITECT / ENGINEERS:CONSULTANTS:Date:Revisions:

GHN Project Number 21-511.00 564-21-407Pharmacy Chemo Hood Relocation

Veterans Affairs Medical Ctr

Fayetteville, AR300 S. Jefferson Avenue, Suite 301, Springfield, MO 65806

GHN ARCHITECTS ENGINEERS

T. 417-869-0719 F. 417-869-3044 o n e si xt e e n th in c h o n e fo o t

KEY PLAN NTS

Jun 8, 2021

1LDC DMF

CEILING AND FINISHES

REPAIR AND MODIFICATIONS

1-AI 101

Scale: 1/4" = 1'-0"

PARTIAL FLOOR PLAN

1-AI 101

Scale: 1/4" = 1'-0"

PARTIAL REFLECTED CEILING PLAN

1-AI 101

ARCHITECTURAL KEYED NOTES

REMOVE AND PROPERLY DISPOSE OF EXISTING 24”x24” CEILING

ACCESS DOOR. PREP OPENING FOR NEW CEILING ACCESS DOOR.

FURNISH AND INSTALL ONE NEW 304 STAINLESS STEEL

AIRTIGHT/WATERTIGHT CEILING ACCESS DOOR (ACUDOR

MODEL NUMBER ADWT-SS1616). ACCESS DOOR SHALL BE

INSTALLED WITH NORTH AND WEST SIDE OF FRAME MOUNTED

FLUSH WITH FACE OF NORTH AND WEST WALLS; WITH

CONTINUOUS EXPOSED STAINLESS STEEL PIANO HINGE ON

WEST SIDE.

REMOVE AND PROPERLY DISPOSE OF EXISTING 24”x24” CEILING

ACCESS DOOR. PREP OPENING FOR NEW CEILING ACCESS DOOR.

FURNISH AND INSTALL ONE NEW 304 STAINLESS STEEL

AIRTIGHT/WATERTIGHT CEILING ACCESS DOOR (ACUDOR

MODEL NUMBER ADWT-SS2424). ACCESS DOOR SHALL BE

INSTALLED WITH SOUTH SIDE OF FRAME MOUNTED FLUSH

WITH FACE OF SOUTH WALL; WITH CONTINUOUS EXPOSED

STAINLESS STEEL PIANO HINGE ON SOUTH SIDE.

RELOCATE ONE EXISTING (YELLOW) ¾” EMT CONDUIT AND

CONTROL WIRING ABOVE CEILING TO AVOID INTERFERENCE

WITH LOCATION OF NEW STAINLESS STEEL BSC EXHAUST DUCT.

PATCH/REPAIR DAMAGED CEILING TO MATCH ADJACENT

MATERIALS AND FINISHES.

PAINT CEILING COMPLETE (PREP, PRIME ONE COAT AND FINISH

PAINT TWO COATS ENTIRE CEILING). PAINT SHALL BE SHERWIN

WILLIAMS MACROPOXY 646, COLOR TO MATCH EXISTING.

REMOVE AND PROPERLY DISPOSE OF EXISTING 24”x24” CEILING

ACCESS DOOR. PREP OPENING FOR NEW CEILING ACCESS DOOR.

FURNISH AND INSTALL ONE NEW 304 STAINLESS STEEL

AIRTIGHT/WATERTIGHT CEILING ACCESS DOOR (ACUDOR

MODEL NUMBER ADWT-SS2424). ACCESS DOOR SHALL BE

INSTALLED WITH NORTH AND EAST SIDE OF FRAME MOUNTED

FLUSH WITH FACE OF NORTH AND EAST WALLS; WITH

CONTINUOUS EXPOSED STAINLESS STEEL PIANO HINGE ON

NORTH SIDE.

RELOCATE EXISTING PASS-THROUGH WITH VERTICAL

CENTERLINE 28” TO EAST WALL. MAINTAIN EXISTING

HORIZONTAL CENTERLINE 55-1/2” AFF. VERIFY EXACT LOCATION

WITH VHSO ENGINEERING. PATCH WALL TO MATCH EXISTING.

PATCH/REPAIR DAMAGED WALL TO MATCH ADJACENT

MATERIALS AND FINISHES (INCLUDING BUT NOT LIMITED TO

5/8” FIRE CODE DRYWALL, METAL STUDS AND TRACK).

PAINT WALL COMPLETE (PREP, PRIME ONE COAT AND FINISH

PAINT TWO COATS ENTIRE WALL). PAINT SHALL BE SHERWIN

WILLIAMS MACROPOXY 646, COLOR TO MATCH EXISTING.

REMOVE AND PROPERLY DISPOSE OF ONE EXISTING PASS

THROUGH AND STAINLESS-STEEL SIDE AND HEAD FRAME IN

29”x79-1/4” OPENING.

RELOCATE EXISTING EMERGENCY POWER RECEPTACLE AT

HORIZONTAL CENTERLINE 18” AFF, AND MAINTAIN EXISTING

VERTICAL CENTERLINE AT 15-1/2” TO WEST WALL.

FURNISH AND INSTALL ONE NEW CLEAN AIR PRODUCTS

PASS-THROUGH CABINET MODEL CAP18WFB-SST-18Wx18Hx18D

WITH HORIZONTAL CENTERLINE AT 55-1/2” AFF AND VERTICAL

CENTERLINE AT 42” TO WEST WALL.

PATCH AND REPAIR WELDED SEAM FLOORING AND INTEGRAL

COVE BASE. MATCH ADJACENT SURFACES AND FINISHES.

PROVIDE INFECTION CONTROL PRECAUTIONS/

CONTAINMENT SYSTEM AS REQUIRED (BY VHSO)

INFECTION CONTROL REPRESENTATIVE FOR ALL AREAS

OUTSIDE THE LIMIT OF WORK.

MAINTAIN EXIT AT ALL TIMES DURING CONSTRUCTION.

EXISTING DOORS/PARTITIONS TO REMAIN IN PLACE

DURING CONSTRUCTION TO SERVE AS A TEMPORARY

BARRIER.

IC1

IC2

IC3

EXISTING EXITS TO BE MAINTAINED DURING CONSTRUCTION.

PROVIDE TEMPORARY PROTECTION AS REQUIRED TO

MAINTAIN EGRESS AND SAFE PASSAGE FROM THE BUILDING.

PROVIDE HEPA EXHAUST FANS OPERATION TO KEEP SPACE

WITHIN THE PROJECT AREA UNDER NEGATIVE PRESSURE AS

LOCATIONS AND CONDITIONS DICTATE.

PROVIDE TEMPORARY PROTECTION WHILE WORKING IN THE

SPACES, BELOW OR ABOVE THE AREA OF DEMOLITION.

PROVIDE BARRIERS AND TEMPORARY PARTITIONS TO

PROTECT OCCUPANTS FROM PHYSICAL HAZARD AND NOISE

OF ALL DEMOLITION WORK AND FOR INFECTION CONTROL.

GENERAL I.C.R.A. NOTES

I.C.R.A. KEYNOTES

IC2

IC2

IC2

IC3

IC3

IC3

IC1

IC1

1.

2.

3.

4.

8 9

78 9

4 5

4 5

IC1

AutoCAD SHX Text

EXIT

AutoCAD SHX Text

PLAN NORTH

AutoCAD SHX Text

TRUE NORTH

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text

CLEAN

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text 1219-01

AutoCAD SHX Text

INTRAVENOUS

AutoCAD SHX Text

CLEAN ROOM

AutoCAD SHX Text 1224-01

AutoCAD SHX Text

ANTEROOM/

AutoCAD SHX Text

CLEAN STORAGE

AutoCAD SHX Text 1223-01

AutoCAD SHX Text

ONCOLOGY

AutoCAD SHX Text

CLEAN ROOM

AutoCAD SHX Text 1222-01

AutoCAD SHX Text

ANTEROOM/

AutoCAD SHX Text

CLEAN ROOM

AutoCAD SHX Text 1221-01

AutoCAD SHX Text

CHANGING

AutoCAD SHX Text

ROOM

AutoCAD SHX Text 1220-01

AutoCAD SHX Text

CLEAN

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text 1219-01

AutoCAD SHX Text

INTRAVENOUS

AutoCAD SHX Text

CLEAN ROOM

AutoCAD SHX Text 1224-01

AutoCAD SHX Text

97 SF

AutoCAD SHX Text

ANTEROOM/

AutoCAD SHX Text

CLEAN STORAGE

AutoCAD SHX Text 1223-01

AutoCAD SHX Text

61 SF

AutoCAD SHX Text

ONCOLOGY

AutoCAD SHX Text

CLEAN ROOM

AutoCAD SHX Text 1222-01

AutoCAD SHX Text

76 SF

AutoCAD SHX Text

ANTEROOM/

AutoCAD SHX Text

CLEAN ROOM

AutoCAD SHX Text 1221-01

AutoCAD SHX Text

61 SF

AutoCAD SHX Text

CHANGING

AutoCAD SHX Text

ROOM

AutoCAD SHX Text 1220-01

AutoCAD SHX Text

51 SF

Sheets and Views
1-AI 101
VP2
VP3
VP5
VP6

File details come from the government source that posted it. Updated .