528A7-22-160_PHARM-ALT-FINAL SET_03-22-2022.pdf
PDF 16 MB Posted
- Solicitation number
- 36C24222B0038
About this file
This solicitation is for an Alternate Contingency Pharmacy Project at the Veterans Affairs Medical Center located at 800 Irving Ave Syracuse, NY. The scope of work involves mechanical renovations to convert an existing pharmacy dispensary waiting area into a contingency USP800 pharmaceutical compounding suite. Key aspects of the project include demolishing existing mechanical equipment and installing new ductwork, heating coils, hydronic piping, an exhaust fan assembly and associated equipment to service five new spaces for the compounding suite. The period of performance is 180 days, with 60 days for submittals and 120 days for construction. Contractors must submit a detailed schedule and contact information for onsite workers before starting the work. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24222B0038 0004.docx | DOCX document | |
| 36C24222B0038 0003.docx | DOCX document | |
| 36C24222B0038 0002.docx | DOCX document | |
| 36C24222B0038 0001.docx | DOCX document | |
| DBA_Wage_05132022.txt | TXT text file | |
| Specifications.pdf | ||
| 36C24222B0038_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWINGS INDEX
SHEET NO. DRAWING TITLE
GENERAL
1. GI-001 COVER SHEET
ARCHITECTURAL
2. A-001 ARCHITECTURAL ABBREVIATIONS & SYMBOLS (NOT IN CONTRACT)
3. A-101 ARCHITECTURAL FLOOR PLANS & DETAILS (NOT IN CONTRACT)
4. A-501 ARCHITECTURAL DETAILS & SCHEDULES (NOT IN CONTRACT)
FIRE PROTECTION
5. FX-001 FIRE PROTECTION ABBREVIATIONS, SYMBOLS & DETAILS (NOT IN CONTRACT)
6. FX-101 FIRE PROTECTION FLOOR PLANS (NOT IN CONTRACT)
PLUMBING
7. PG-001 PLUMBING ABBREVIATIONS & SYMBOLS (NOT IN CONTRACT)
8. P-101 PLUMBING PLANS & DETAILS (NOT IN CONTRACT)
9. P-501 PLUMBING DETAILS (NOT IN CONTRACT)
MECHANICAL
10. MG-001 MECHANICAL ABBREVIATIONS, SYMBOLS & NOTES
11. MD-101 MECHANICAL DEMOLITION PLANS
12. M-101 MECHANICAL NEW WORK PLANS - 1ST FLOOR
13. M-102 MECHANICAL NEW WORK PLANS - 3RD FLOOR & 2ND FLOOR ROOF
14. M-103 MECHANICAL EXHAUST STACK STRUCTURAL DETAILS
15. M-104 MECHANICAL EXHAUST STACK ELEVATIONS
16. MG-501 MECHANICAL DETAILS
17. MG-601 MECHANICAL SCHEDULES
18. MI-701 CONTROLS DIAGRAMS (NOT IN CONTRACT)
19. MI-702 SEQUENCE OF OPERATIONS & CONTROL POINTS (NOT IN CONTRACT)
ELECTRICAL
20. EG-001 ELECTRICAL ABBREVIATIONS, SYMBOLS & NOTES (NOT IN CONTRACT)
21. E-101 ELECTRICAL DEMOLITION, POWER & LIGHTING PLANS (NOT IN CONTRACT)
22. E-102 ELECTRICAL POWER PLAN - 3RD FLOOR & 2ND FLOOR ROOF (NOT IN CONTRACT)
23. EG-501 ELECTRICAL DETAILS (NOT IN CONTRACT)
AREA OF WORK
1ST FLOOR
KEY PLAN 1ST FLOOR
SCALE: NONE
o n e e i g h t h i n c h o n e f o o t
B
A
C
D
E
F t h r e i c h e s e f o o t o a d o n e h a l f i n c h e e f o o t o c f o t t h r e e q u a r t e r s i n c e f o o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE
VA MEDICAL
CENTER
ENGINEERING
DEPARTMENT
800 IRVING AVE. SYRACUSE, NY 13210
03/22/2022
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-22-160
ALTER PHARMACY WAITING
ROOM FOR ALTERNATE
COMPOUNDING SUITE
S S
Y R
M
S M
S E n g i n e e r i n g P
R O
J E
C T
S A
C T
I V
E
P
R O
J E
C T
S A
A l t e r
P h a r m a c y f o r
A l t
C o m p o u n d i n g
S u i t e D e s i g n
C o n t r a c t D r a w i n g s C
A D
G e n e r a l A
C
O V
E R
S
H T d w g
GI-001
JDAM
COVER SHEET
N
AREA OF WORK
3RD FLOOR &
ROOF
KEY PLAN 3RD FLOOR & ROOF
SCALE: NONE
N
AutoCAD SHX Text DEPARTMENT OF VETERANS AFFAIRS PROJECT NO. 528A7-22-160 VA MEDICAL CENTER BUILDING NO. 1 800 IRVING AVENUE SYRACUSE, NEW YORK 13210
AutoCAD SHX Text
SYRACUSE VAMC ALTER PHARMACY WAITING ROOM FOR ALTERNATE COMPOUNDING SUITE
ARCHITECTURAL ABBREVIATIONS
@ AT
∠ ANGLE
℄ CENTERLINE
[ CHANNEL
┴ PERPENDICULAR
⅊ PLATE
∅ ROUND/DIAMETER
AB ANCHOR BOLT
AFF ABOVE FINISH FLOOR
A/C AIR CONDITIONING
ACC ACCESSIBLE
ACS PNL ACCESS PANEL
ADDM ADDENDUM
ADJ ADJACENT, ADJUSTABLE
AHR ANCHOR(AGE)
ALT ALTERNATE
ALUM ALUMINUM
AMP ACOUSTICAL METAL PANEL
ANNPNL ANNUNCIATOR PANEL
ANOD ANODIZED
ACT ACOUSTICAL CEILING TILE
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
ASB ASBESTOS
ASPH ASPHALT
B/O BOTTOM OF
BE BAKED ON ENAMEL
BEV BEVELED
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BLKT BLANKET
BM BEAM, BENCHMARK
BRG BEARING
BRK BRICK
BSMT BASEMENT
BUR BUILT-UP ROOF
BW BOTH WAYS
CC CONTRACTOR SUPPLIED & INSTALLED
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CMP CORRUGATED METAL PIPE
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CT CERAMIC TILE
CAB CABINET
CH BD CHALKBOARD
CEM CEMENT
CLO CLOSET
CLG CEILING
CLR CLEAR
CMPST COMPOSITE
COL COLUMN
COMB COMBINATION
CONC CONCRETE
CONSTR CONSTRUCTION
CONT CONTINUOUS, CONTINUE
CONT'D CONTINUED
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPRS FL COMPRESSIBLE FILLER
CPT CARPET
CR CARDREADER
CRS COLD ROLLED STEEL
CTG COATING
D DEPTH
DC DOOR CONTROL
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DR DOOR
DEFL DEFLECTION
DIA DIAMETER
DIAG DIAGONAL
DIMEN DIMENSION
DISTR DISTRIBUTION
DL DEAD LOAD
DTL DETAIL
DWG DRAWING
EA EACH
EFTR EXISTING FINISH TO REMAIN
EJ EXPANSION JOINT
EP ELECTRIC PANEL
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMHO ELECTROMAGNETIC HOLD OPEN
ENTR ENTRANCE
EQ EQUAL
EQUIP EQUIPMENT
ESTIM ESTIMATE
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXIST, (E) EXISTING
EXH EXHAUST
EXP EXPOSED, EXPANSION
EXT EXTERIOR
FC FILE CABINET
FCU FAN COIL UNIT
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FH FIRE HYDRANT
FLG FLOORING
FO FINISHED OPENING
FP FIREPROOFING
F/O FACE OF
FAAP FIRE ALARM ANNUNCIATOR PANEL
FDN FOUNDATION
FIN FINISH(ED)
FIXT FIXTURE
FLASH FLASHING
FLR FLOOR
FM FACTORY MUTUAL
FOW FACE OF WALL
FR FRAME
FRMG FRAMING
FRP FIBERGLASS REINFORCED PLASTIC
PANEL
FRTW FIRE RETARDANT TREATED WOOD
FT FOOT/FEET
FTG FOOTING
FURG FURRING
FURN FURNISHED/FURNITURE
FWC FABRIC WALL COVERING
GB GRAB BAR
GC GENERAL CONTRACTOR
GCT GLAZED CERAMIC TILE
GA GAUGE GALV GALVANIZED
GL GLASS, GLAZING
GWB GYPSUM WALLBOARD
GYP GYPSUM
HT HEIGHT
HC HOLLOW CORE
HM HOLLOW METAL
HCP HANDICAPPED
HDBD HARDBOARD
HDWD HARDWOOD
HDWR HARDWARE
HORIZ HORIZONTAL
HR HOUR
HVAC HEATING / VENTILATING / AIR
CONDITIONING
ICB INTEGRAL COVE BASE
ID INSIDE DIAMETER
INCL INCLUDE(D) (-ING)
INSUL INSULATE(D) (-ION) (-ING)
INT INTERIOR
INV INVERT
JAN JANITOR
JT JOINT LAM LAMINATE(D)
LAV LAVATORY
LF LINEAR FEET
LGMF LIGHT GAUGE METAL FRAMING
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATE(D) (-ION)
LT-GA LIGHT GAUGE
LTG LIGHTING
LVR LOUVER
MACH MACHINE
MATL MATERIAL
MAX MAXIMUM
MC METAL CEILING
MECH MECHANICAL
MET METAL(LIC)
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MKR BD MARKER BOARD
MLDG MOULDING
MMB MEMBRANE
MO MASONRY OPENING
MR MOISTURE RESISTANT
MS
MTD MOUNTED
MTL METAL
MULL MULLION
MW MICROWAVE
NA, N/A NOT APPLICABLE
NAT NATURAL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NPS NOMINAL PIPE SIZE
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
OPH OPPOSITE HAND
OSU OHIO STATE UNIV. (TEST)
P&M PATCH & MATCH
PBD PARTICLE BOARD
PCP PORTLAND CEMENT PLASTER
PCT PORCELAIN CERAMIC TILE
PERIM PERIMETER
PFW POLYPROPYLENE FABRIC WALL
COVERING
PL PLASTIC
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PNL PANEL
P PAINT
PNTD PAINTED
PR PAIR
PREFAB PREFABRICATE(D)
PT PRESSURE TREATED
PTD PAPER TOWER DISPENSER
PTN PARTITION
PVC POLYVINYL CHLORIDE
PVG PAVING
QT QUARRY TILE
QTY QUANTITY
R RADIUS/RISER
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RCT RADIANT CEILING TILE
RD ROOF DRAIN
REF REFERENCE OR REFRIGERATOR
REINF REINFORCE
REQ'D REQUIRED
RESIL RESILIENT
RESIL C RESILIENT CHANNEL
RET RETURN
REV REVISION
RF RAISED RUBBER FLOORING
RM ROOM
RO ROUGH OPENING
RST RESILIENT STAIR TREADS
RTF RESILIENT TILE FLOORING
RUB RUBBER
SC SOLID CORE
SD SOAP DISPENSER
SST STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
SCHED SCHEDULE
SECT SECTION
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
SLNT SEALANT
SND SANITARY NAPKIN DISPENSER
SNDU SANITARY NAPKIN DISPOSAL UNIT SPEC
SPECIFICATION
SPKLR SPRINKLER
SQ SQUARE
SSM SOLID SURFACE MATERIAL
STL STEEL
STD STANDARD
STRUCT STRUCTURAL
SUSP SUSPENDED
SYMM SYMMETRICAL
TREAD T T&G TONGUE & GROOVE
T/CONC TOP OF CONCRETE
T/D TOP OF DECK
T/O TOP OF
T/S, TOS TOP OF STEEL
T/W, TOW TOP OF WALL
TK BD TACK BOARD
TEL TELEPHONE
TMPD TEMPERED
TEMP TEMPERATURE, TEMPORARY
TERM TERMINAL
TER TERRAZZO
THK THICK(NESS)
THRES THRESHOLD
TPD TOILET PAPER DISPENSER
TRANS TRANSOM, TRANSPARENT
TYP TYPICAL
UC or U/C UNDERCUT
UC UNIVERSITY OF CALIFORNIA (TEST)
UL UNDERWRITER'S LABORATORIES (TEST)
UNO UNLESS NOTED OTHERWISE
UR URINAL
VAMC SYRACUSE VA MEDICAL CENTER
VB VINYL BASE
VC VA SUPPLIED & CONTRACTOR INSTALLED
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VNR VENEER
VP VENEER PLASTER
VR VAPOR RETARDER
VSF VINYL SHEET FLOORING (WELDED SEAMS)
VV VA SUPPLIED & INSTALLED
VWC VINYL WALL COVERING
W WIDE
WC WATER CLOSET
WGL WIRE GLASS
WP WATERPROOF
WPT WORK POINT
WR WATER-REPELLENT/RESISTANT
WS WEATHER STRIP
WWF WELDED WIRE FABRIC
W/ WITH
W/O WITHOUT
WDW WINDOW
WD WOOD
XFMR TRANSFORMER
ZA ZONE ALARM
ZVB ZONE VALVE BOX
1A
E
C
A
F
D
B
" METAL STUDS - 20 GA
AT 16" O.C.
1 LAYER
" GWB - TYPE 'X'
BOTH SIDES
W/3" BATT INSULATION
1 HR FIRE-RATED
UL TEST: U-465
STC = 47
" METAL STUDS - 20 GA
AT 16" O.C.
2 LAYERS
" GWB - TYPE 'X'
BOTH SIDES
2HR FIRE-RATED
1 LAYER
" GWB LAMINATE
ADHERED TO EXISTING
PLASTER OR MASONRY
" METAL STUD FURRING -
20 GA AT 16" O.C.
1 LAYER
" GWB - TYPE 'X'
" METAL STUDS - 20 GA
AT 16" O.C.
1 LAYER
" GWB - TYPE 'X'
W/2" BATT INSULATION
8" CMU WALL
2 HR FIRE-RATED
UL TEST: U-618
DIRTT WALLS -
DEMOUNTABLE WALL
PARTITIONS
1 HR FIRE-RATED
UL TEST: U-465
STC = 47
4"
WALL HEIGHT TYPES:
(LETTER DESIGNATION)
CLG CLG
STOP ALL
MATERIAL AT
CEILING
EXTEND ALL
MATERIAL TO
UNDERSIDE OF
STRUCTURE /
SLAB ABOVE
EXTEND GWB
MATERIAL ABOVE
CEILING & BRACE
STUDS AT
STRUCTURE ABOVE,
AS REQUIRED
STOP GWB ABOVE
CEILING ONE SIDE;
EXTEND ALL OTHER
MATERIALS TO
UNDERSIDE OF
STRUCTURE/SLAB
BULKHEAD
CONDITIONS VARY;
SEE DRAWINGS FOR
DETAILS. BRACE
STUDS AT
STRUCTURE ABOVE,
AS REQUIRED
CLG
CLG
VARIES
LOW WALL; SEE
DRAWINGS FOR
HEIGHTS
CLG
4"
2" RIGID OR MINERAL WOOL
R-10 INSULATION (SEE SPEC)
" METAL STUD FURRING -
20 GA AT 16" O.C.
1 LAYER
" GWB - TYPE 'X'
EXISTING PLASTER &
LATH WALL OR MASONRY
EXISTING PLASTER &
LATH WALL OR MASONRY
8" NOMINAL
WALL AND PARTITION TYPES:
(NUMBER DESIGNATION)
4"
EXISTING EXTERIOR WALL
" METAL STUDS - 20 GA
AT 16" O.C.
1 LAYER
" GWB - TYPE 'X'
BOTH SIDES
1 HR FIRE-RATED
UL TEST: U-465
STC = 47
" METAL STUD FURRING -
20 GA AT 16" O.C.
1 LAYER
" GWB - TYPE 'X'
CLG
4"
RAIL- 6" METAL STUDS - 20 GA
"VERTICAL STUD - 20 GA
W/ 5/8" GWB - TYPE 'X' BOTH
SIDES
W/ 3
" BATT INSULATION
PLACE STAGGERED STUDS 2"
APART
2" O.C.
6" METAL STUDS -
20 GA AT 16" O.C.
" GWB - TYPE 'X'
BOTH SIDES.
W/ 3
" BATT
INSULATION
" METAL STUDS -
20 GA AT 16" O.C.
1 LAYER 5/8" GWB-TYPE 'X'
W/ 3
" BATT INSULATION
" METAL STUDS -
20 GA AT 16" O.C.
2 LAYERS
" GWB-TYPE 'X'
BOTH SIDES.
W/ 3 " BATT INSULATION
2 HR FIRE-RATED UL TEST:
U-419 STC = 56
6" CMU WALL
2 HR FIRE-RATED
UL TEST: U-263
6" NOMINAL
" CHANNEL FURRING
1 LAYER
" GWB
EXISTING PLASTER &
LATH WALL OR MASONRY
NOTE:
SYMBOL LIST SHOWN IS FOR GENERAL
REFERENCE ONLY. THE PRESENCE OF A
SYMBOL DOES NOT IMPLY ITS USE ON
THIS PROJECT. REFER TO THE DRAWINGS
FOR SPECIFIC SYMBOLS USED.
CONSTRUCTION LIMIT LINE
DEMOLITION LINE
ELEVATION INDICATOR OR DATUM
CENTER LINE INDICATOR
EXISTING TO REMAIN LINE
FEATURES ABOVE LINE INDICATOR
HIDDEN FEATURES LINE
NEW LINE
PROPERTY LINE
BREAK, ROUND (USER DEFINES SIZE)
BREAK, STRAIGHT (SEE SECTION INDICATORS,
BUILDING, WITH BREAK STANDARDS)
DETAIL INDICATOR
DETAIL INDICATOR
DETAIL INDICATOR FOR SMALL CONDITIONS
DIMENSION LINE
DOOR OPENING AND DOOR MARK NUMBER
TYPICAL DRAWING BLOCK OR DETAIL TITLE
ELEVATION INDICATOR; EXTERIOR
ELEVATION INDICATOR;
INTERIOR, MULTIPLE VIEW
ELEVATION INDICATOR;
INTERIOR, SINGLE VIEW
ARCHITECTURAL SYMBOLS
CENTER LINE
FURNITURE, FIXTURE, & EQUIPMENT INDICATOR
GRAPHIC SCALE;
" = 1'-0"
ROOM NAME AND NUMBER
CG
COLUMN GRID
KEYNOTE
WALL OR PARTITION TYPE:
· NUMBER DESIGNATES WALL CONSTRUCTION TYPE
· LETTER DESIGNATES WALL HEIGHT
FIRE EXTINGUISHER CABINET
CORNER GUARD
NORTH ARROW
EXISTING CONSTRUCTION
TO REMAIN
EXISTING CONSTRUCTION TO
BE REMOVED
NEW CONSTRUCTION
CONCRETE
RIGID INSULATION
BATT INSULATION
V V ITEM - VA SUPPLIED & INSTALLED
VC ITEM - VA SUPPLIED & CONTRACTOR INSTALLED
CC ITEM - CONTRACTOR SUPPLIED & INSTALLED
BUILDING SECTION OR SECTION INDICATOR
DETAIL INDICATOR
MATERIALS LEGEND
D2
A-512
D2
A-512
A-202
A2
10'-0"
A
C B
D
FEC
16'8'4'0
C9XX
D2
A-512
121212
EXISTING DOOR TO REMAIN: IN EXISTING PARTITION
EXISTING DOOR TO BE REMOVED: SEE REMOVAL PLAN
NEW DOOR IN NEW OR EXISTING PARTITION:
SEE DOOR SCHEDULE AND SPECIFICATIONS
C900
CORRIDOR
200 SF
SMOKE BARRIER
1 HR FIRE RATED BARRIER
2 HR FIRE RATED BARRIER
EXIT TRAVEL PATH
NEW SLIDING DOOR (BARN TYPE) AT DIRTT OR GWB
WALLS; SEE DOOR SCHEDULE AND SPECIFICATIONS
CEILING INFORMATION INDICATOR
8'-0"
ACT
CEILING TYPE
CEILING HEIGHT
CMU WALL
A-202
A2
A4
A-201
A4
A-201
A4
A-201
" METAL STUDS - 20 GA
AT 16" O.C.
1 LAYER
" GWB - TYPE 'X'
BOTH SIDES
W/3" BATT INSULATION
W/24" GLASS TRANSOM AT
X'-X" AFF
DRAWING BLOCK TITLE
SCALE: 1/8" = 1'-0"
A-101
DETAIL NUMBER
WHERE DRAWN
NOTE: PROVIDE
" TILE BACKER BOARD IN
LIEU OF GWB IN SPACES WITH TILED WALLS
" METAL STUDS -
20 GA AT 16" O.C.
1 LAYER
" GWB - TYPE 'X'
METAL STUD AND GWB WALL GENERAL NOTE:
USE ONE (1) LAYER OF
" TYPE 'X' MOLD-RESISTANT
GWB WITHIN 5'-0" OF ANY SINK, DRINKING FOUNTAIN
OR BOTTLE FILL STATION EXCEPT IN RESTROOMS
WHERE TILE BACKER BOARD IS BEING USED.
CLG
4"
VARIES
SEE PLANS
G
SOFFIT SIZE &
CONDITIONS VARY;
SEE DRAWINGS
FOR DETAILS.
BRACE STUDS AT
STRUCTURE
ABOVE, AS
REQUIRED
V A
R I E
S
1A o n e e i g h t h i n c e f o o t
B
A
C
D
E
F t h r e e i n c h e e f o o t o n e a n d o l f i n c h e o t o n e i n c e f o o t t h r q u a r t e r s i n o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE
VA MEDICAL
CENTER
ENGINEERING
DEPARTMENT
800 IRVING AVE. SYRACUSE, NY 13210
03/22/2022
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-22-160
ALTER PHARMACY WAITING
ROOM FOR ALTERNATE
COMPOUNDING SUITE
S S
Y R
M
S M
S E n g i n e e r i n g P
R O
J E
C T
S A
C T
I V
E
P
R O
J E
C T
S A
A l t e r
P h a r m a c y f o r
A l t
C o m p o u n d i n g
S u i t e D e s i g n
C o n t r a c t D r a w i n g s C
A D
A r c h i t e c t u r a l A
A
R C
H A
L L d w g
NOT IN CONTRACT-REFERENCE ONLY
A-001
JDAM / DJ
ARCHITECTURAL ABBREVIATIONS &
SYMBOLS
N
A
C105
PHARMACY WAITING
C107
PHARMACY WAITING
B140
PHARMACY
CORRIDOR
SHAFT 9
24'-1" (REF)
R
E F
6'-2" (REF)
4'-2
" (REF)
7'-6" (REF)
R
E F
6'-3" (REF)
R
E F
R
E F
R
E F
R2
R5
R5
R5
R5 R5
R5
R5
R3
R4
R6
R5
R5
17'-10" (REF)
R1
C107
PHARMACY WAITING
B140
PHARMACY
CORRIDOR
SHAFT 9
C105C
HAZ MIX
65 SF
C105
ENTRY
121 SF
C105B
ANTE ROOM
64 SF
C105D
NON-HAZ MIX
71 SF
C105A
GARB
41 SF
10'-2"
6'-11
" (REF)
R
E F
R
E F
ALIGN
A L
I G
N
A L
I G
N
ALIGN
C105
C105C
C105B
C105A
C105D
1A
6A
6A
6A
1A
6A
6A
6'-2" (REF)
11'-3
" (REF)
B140
C107
PHARMACY WAITING
B140
PHARMACY
CORRIDOR
SHAFT 9
C105C
HAZ MIX
65 SF
C105
ENTRY
121 SF
C105B
ANTE ROOM
64 SF
C105D
NON-HAZ MIX
71 SF
C105A
GARB
41 SF
EXISTING 2x4 CEILING
GRID TO REMAIN
7'-5"
GWB-1
7'-5"
GWB-1
7'-5"
GWB-1
7'-5"
ACT-1
7'-5"
ACT-1
PA
C107
PHARMACY WAITING
B140
PHARMACY
CORRIDOR
SHAFT 9
C105C
HAZ MIX
65 SF
C105
ENTRY
121 SF
C105B
ANTE ROOM
64 SF
C105D
NON-HAZ MIX
71 SF
C105A
GARB
41 SF
LAMINAR FLOW
CLASS II
A2 HOOD
CLASS II
B2
HOOD
B E
N C
H
C A
R T
SINK &
EYEWASH
COAT
HOOKS
SEAL GAP BETWEEN HOOD
AND WALL, SEE FINISH
AND LAYOUT NOTE 2
GENERAL ARCHITECTURAL DRAWING NOTES:
1. FOLLOW ALL INFECTION CONTROL PROCEDURES AND TEMPORARY CONSTRUCTION
DEFINED IN PROJECT SPECIFICATION & VA APPROVED ICRA.
2. NEGATIVE PRESSURE MUST BE MAINTAINED 24/7 IN EACH ACTIVE WORK AREA.
3. NO STORAGE IS ACCEPTABLE IN CORRIDORS. ALL MATERIALS MUST BE CONTAINED
IN THE ACTIVE WORK AREA.
4. PROVIDE WALK OFF MATS BY EACH DOOR OUTSIDE EACH ROOM IDENTIFIED AS A
CONSTRUCTION AREA FOR THE DURATION OF THE PROJECT. WALK-OFF MATS
SHALL BE CHANGED WHEN THEY BECOME VISIBLY SOILED OR WHEN REQUESTED
BY THE VAMC COR.
5. ALL EQUIPMENT, CARTS, ETC. MUST BE WIPED DOWN PRIOR TO ENTRY. ONCE IN
AREA CARTS SHOULD BE WIPED DOWN PRIOR TO BE TAKEN OUTSIDE OF THE
CONSTRUCTION AREA.THIS SHALL INCLUDE ALL EQUIPMENT AND CART WHEELS.
6. PROVIDE THOROUGH CLEANING FOLLOWING EACH WORK DAY. ENSURE THE
PROJECT SITE IS CLEANED REGULARLY THROUGHOUT THE WORKING DAY.
7. VERIFY ALL EXISTING CONDITIONS AND ESTABLISHING THE COMPATIBILITY OF ALL
NEW WORK WITH THE EXISTING CONDITIONS.
8. ALL WORK IS BEING DONE ADJACENT TO, AND ABOVE, OCCUPIED SPACE. TAKE
EVERY PRECAUTION TO ELIMINATE THE TRAVEL OF LIQUID, DUST AND DIRT FROM
THE CONSTRUCTION AREA TO THOSE SPACES.
9. TAKE EVERY PRECAUTION TO MINIMIZE DISRUPTION WITH ADJACENT OCCUPIED
SPACE. SCHEDULE AND SEQUENCING OF WORK TO BE COORDINATED WITH VAMC
COR PRIOR TO BEGINNING WORK, AND MODIFIED AS NEEDED DEPENDENT ON
PATIENT COMFORT AND TREATMENT.
10. PATCH ALL SURFACES TO REMAIN EFFECTED BY DEMOLITION OR REMOVAL OF
EXISTING EQUIPMENT & CONSTRUCTION. NEW SURFACES TO BE FILLED, SANDED
SMOOTH & FINISHED TO MATCH ADJACENT SURFACE.
11. MAINTAIN EXISTING UTILITIES INDICATED TO REMAIN, KEEP IN SERVICE, AND
PROTECT AGAINST DAMAGE DURING ALL RENOVATION WORK. COORDINATE
CONSTRUCTION AROUND EXISTING EQUIPMENT, CONDUIT CABLING, ETC. WITH
COR AS REQUIRED TO MAINTAIN CONTINUOUS OPERATION.
12. COORDINATE EXACT LOCATION OF ALL NEW EQUIPMENT TO BE INSTALLED IN
CEILING WITH EXISTING MECHANICAL AND ELECTRICAL WORK TO REMAIN IN PLACE.
13. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL
PROTECTION FOR POLLUTION CONTROL & HAZARDOUS MATERIALS.
14. ALL EXISTING OR NEW PENETRATIONS IN RATED ASSEMBLIES SHALL BE SEALED
WITH UL/FM APPROVED MATERIAL ASSEMBLIES AND PROCEDURES.
15. ALL DIMENSIONS ARE FROM FINISH FACE OF WALL TO FINISH FACE OF WALL.
16. LOCATE ALL NEW DOORS 5" MINIMUM FROM INSIDE CORNER OR SURFACE UNLESS
NOTED OTHERWISE.
17. PROVIDE NON-COMBUSTIBLE BLOCKING AS REQUIRED BEHIND ALL WALLS FOR
PROPER INSTALLATION OF BUMPER GUARDS, WALL MOUNTED EQUIPMENT, WALL
CABINETRY, FIXTURES, ETC.
18. DRAWINGS SHALL NOT BE SCALED AS A BASIS FOR ESTABLISHING DIMENSIONS OR
OTHER INFORMATION.
19. ALL NEW CORRIDOR WALLS MUST HAVE THE SAME FIRE/SMOKE RATING AS THE
WALL THEY ARE MEETING. ALL NEW CORRIDOR WALLS SHALL BE CONSTRUCTED
OF THE SAME MATERIAL THAT THEY ABUT.
o n e e i g h t h i n c e f o o t
B
A
C
D
E
F t h r e e i n c h e e f o o t o n e a n d o l f i n c h e e f o o t o n e i n c e f o o t t h r e e q u a r t e r s i n o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE
VA MEDICAL
CENTER
ENGINEERING
DEPARTMENT
800 IRVING AVE. SYRACUSE, NY 13210
03/22/2022
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-22-160
ALTER PHARMACY WAITING
ROOM FOR ALTERNATE
COMPOUNDING SUITE
S S
Y R
M
S M
S E n g i n e e r i n g P
R O
J E
C T
S A
C T
I V
E
P
R O
J E
C T
S A
A l t e r
P h a r m a c y f o r
A l t
C o m p o u n d i n g
S u i t e D e s i g n
C o n t r a c t D r a w i n g s C
A D
A r c h i t e c t u r a l A
A
R C
H A
L L d w g
NOT IN CONTRACT-REFERENCE ONLY
A-101
JDAM / DJ
ARCHITECTURAL FLOOR PLANS &
DETAILS
N N N
N
ARCHITECTURAL FLOOR PLAN KEYED NOTES:
PATCH EXISTING WALLS AS REQUIRED TO MATCH ADJACENT EXISTING OR NEW WALLS
AND FINISHES. REFER TO FINISHES PLAN, COORDINATE WITH VAMC COR.
INFILL EXISTING REMOVED DOOR WALL OPENING WITH MINIMUM 20 GA. METAL FRAMING
AND
" GYPSUM WALLBOARD. REFER TO ARCHITECTURAL DEMOLITION PLAN AD-101.
MAINTAIN EXISTING WALL FIRE RATING AS REQUIRED. COORDINATE WITH VAMC COR.
OPEN UP EXISTING WALL AS REQUIRED TO INSTALL WALL BLOCKING FOR INSTALLATION
OF NEW WALL-MOUNTED SINK WITH SANITARY AND WATER SUPPLIES AND EYEWASH
BRACKET. COORDINATE WITH VAMC COR AND PLUMBING TRADE.
CEILING PLAN GENERAL NOTES:
1. NO TILE SHALL BE LESS THAN 50% OF THE WIDTH OF A TILE ALONG THE WALL.
2. IN AREAS OF NEW PARTITION WORK WITHIN EXISTING BUILDING: MODIFY EXISTING
GRID AND CEILING TILES AT INTERSECTIONS WITH NEW PARTITIONS. CUT EXISTING
GRID AND CEILING TILES AS NECESSARY TO ACCOMMODATE NEW WORK. PROVIDE
NEW CEILING EDGE TRIM AND RELATED COMPONENTS AS NEEDED TO MATCH AND
COMPLETE EXISTING SYSTEM.
3. IN AREAS OF NEW CEILING WORK WITHIN EXISTING BUILDING: CONTINUE EXISTING
GRID AND CEILING TILES AS SHOWN. USE EXISTING GRID AND TILES FROM AREAS TO
BE REMOVED OR PROVIDE NEW TO MATCH EXISTING. ALIGN NEW GRID WITH EXISTING.
4. PROVIDE CAULK BETWEEN WALL AND CEILING GRID.
5. IF NECESSARY, RELOCATED SPRINKLER HEADS TO BE LOCATED IN THE CENTER OF
THE GRIDS.
6. CEILING GRID SHALL BE INSTALLED PER ASTM C636 / C636M, "STANDARD PRACTICE
FOR INSTALLATION OF METAL CEILING SUSPENSION SYSTEMS FOR ACOUSTICAL TILE
AND LAY-IN PANELS".
DEMOLITION / REMOVALS KEYED NOTES:
REMOVE MASONRY, PLASTER AND/OR DRYWALL/FRAME SYSTEM AND WINDOW FRAME
AND GLAZING. PATCH/REPAIR ANY FLOOR AND/OR CEILING SUBSTRATE DAMAGED BY
REMOVAL. PREPARE EXISTING SUBSTRATE TO REMAIN TO RECEIVE NEW FINISH WORK.
INFILL SLAB WITH CONCRETE TO FLUSH WITH EXISTING. ALL WALL MOUNTED
ACCESSORIES SHALL BE REMOVED. CONSULT WITH VAMC COR PRIOR TO REMOVAL TO
DETERMINE WHAT ACCESSORIES TO SALVAGE.
REMOVE DOOR, HOLLOW METAL DOOR FRAME, HARDWARE AND ALL ASSOCIATED
FASTENERS IN THEIR ENTIRETY. INFILL CONC SLAB TO BE LEVEL WITH ADJACENT FLOOR
SURFACES. PATCH AND REPAIR ANY DAMAGE ASSOCIATED WITH REMOVAL OF EXISTING
DOOR. PREPARE WALLS TO RECEIVE NEW FINISH WORK. COORDINATE DOOR REMOVAL
AND REPLACEMENT WITH VAMC COR.
REMOVE EXISTING FLOORING, UNDERLAYMENT, ADHESIVE, VCT AND MASTIC FROM FLOOR
SUBSTRATE, REMOVE WALL BASE AND ANY ADHESIVES OR RESIDUE. PATCH AND REPAIR
ANY DAMAGE ASSOCIATED WITH REMOVALS AND PREPARE EXISTING SUBSTRATE TO
RECEIVE NEW FINISH WORK.
REMOVE ACOUSTICAL CEILING TILE CEILING, ASSOCIATED GRID AND SUPPORT HANGERS.
PATCH AND REPAIR ANY DAMAGE ASSOCIATED WITH REMOVAL. PREPARE WALLS TO
RECEIVE NEW FINISH WORK AT ANY EXISTING WALLS THAT ARE TO REMAIN.
WALL TO REMAIN, ALL WALL MOUNTED ACCESSORIES AND FINISHES SHALL BE REMOVED
AND DISPOSED OF. CONSULT WITH VAMC COR PRIOR TO REMOVAL TO DETERMINE WHAT
ACCESSORIES TO SALVAGE.
REMOVE EXISTING SOLID SURFACE COUNTER AND SUPPORT SYSTEM AT TRANSACTION
WINDOW. TRANSACTION WINDOW, INTERIOR COUNTER AND PASS-THROUGH BOX TO
REMAIN. PATCH AND REPAIR WALL AS REQUIRED.
R1
R2
R3
R4
R5
R6
GENERAL DEMOLITION AND REMOVAL NOTES:
1. THE DEMOLITION AND ALTERATION NOTES ON THIS PLAN SHALL NOT BE DEEMED TO
BE ALL-INCLUSIVE. PRIOR TO THE START OF DEMOLITION INSPECT AND ASSESS
EACH AREA TO FULFILL THE DESIGN INTENT OF THE WORK INDICATED BY THE
PROJECT DOCUMENTS.
2. VERIFY ALL CONDITIONS AND DIMENSIONS WITHIN THE PROJECT LIMITS AND NOTIFY
THE VAMC COR IMMEDIATELY OF ANY DEVIATION FROM PROJECT DOCUMENTS
NECESSITATED BY FIELD CONDITIONS OR ITEMS NOT COVERED.
3. DASHED LINES ON DEMOLITION PLANS REPRESENT WALLS, DOORS, SOFFITS,
CEILINGS, CASEWORK, ETC. TO BE REMOVED.
4. FOR ALL SURFACES SCHEDULED TO REMAIN, PATCH, MATCH SURFACES DISTURBED
BY DEMOLITION OR REMOVAL OF EQUIPMENT OR UTILITIES. PROVIDE PATCHING TO
MATCH ADJACENT WORK IN FINISH, STRUCTURAL QUALITIES, COURSING OF
MASONRY AND OTHER CHARACTERISTICS. PATCH SURFACES TO COMPLY WITH FIRE
RATINGS, SMOKE-TIGHT RATINGS, ACOUSTICAL CRITERIA AND OTHER
PERFORMANCE CRITERIA INDICATED. PREPARE SURFACES AS NECESSARY TO
PROVIDE A PROPER SUBSTRATE FOR SPECIFIED FINISH. REFINISH ENTIRE SURFACE
CORNER TO CORNER TO PROVIDE AN EVEN FINISH. ALL WORK SHALL REFLECT
HIGHEST LEVEL OF INDUSTRY STANDARDS FOR EACH TRADE.
5. ALL DEMOLITION SHALL BE PERFORMED IN A SAFE AND ACCEPTABLE MANNER TO
ALL AUTHORITIES HAVING JURISDICTION AND THE SYRACUSE VAMC. A FIRE WATCH
SHALL BE PROVIDED AS REQUIRED BY SYRACUSE VAMC AND APPLICABLE CODES.
6. PROVIDE TEMPORARY FIRE-RATED BARRIERS/DUST PROTECTION AS REQUIRED BY
CONSTRUCTION RISK ASSESSMENT AND ILSM. REVIEW LOCATIONS OF TEMPORARY
PARTITIONS/DUST PROTECTION WITH VAMC COR PRIOR TO START OF WORK.
7. HAZARDOUS MATERIAL NOTE: STOP WORK AND INFORM VAMC COR IMMEDIATELY OF
ANY HAZARDOUS MATERIAL ENCOUNTERED OR THOUGHT TO BE HAZARDOUS. VAMC
COR SHALL INSTRUCT ON HOW TO PROCEED.
8. ALL WORK SHALL BE DONE IN PROTECTED SPACE. NO DUST, DIRT OR LIQUID SHALL
TRAVEL FROM CONSTRUCTION AREA TO ADJACENT AREAS. TEMPORARY ICRA
PARTITIONS SHALL BE ERECTED PRIOR TO COMMENCING WORK.
9. PRIOR TO ANY DEMOLITION, COORDINATE BRACING AND MAINTAIN THE STRUCTURAL
INTEGRITY OF THE REMAINING ELEMENTS OF THE BUILDING AND ITS SYSTEMS AS
REQUIRED.
10. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL
PROTECTION FOR POLLUTION CONTROL. THOROUGHLY CLEAN ADJACENT AREAS OF
DUST, DIRT AND DEBRIS CAUSED BY DEMOLITION WORK. BEFORE NEW WORK
BEGINS, RETURN ADJACENT AREAS TO CONDITION FOUND PRIOR TO START OF
DEMOLITION WORK.
11. REVIEW ALL ITEMS TO BE DEMOLISHED WITH VAMC COR TO IDENTIFY ANY ITEMS TO
BE SALVAGED PRIOR TO START OF DEMOLITION.
12. PREPARE FLOOR SLABS AS ONE CONTINUOUS SLAB WITH NO COLD JOINTS SO
FINISH FLOORS ARE FLUSH WITH EACH OTHER AND PREPARED TO ACCEPT NEW
FINISH. FLOOR SLAB TO BE FLUSH AND CONTINUOUS THROUGHOUT AND
COMPLETED PRIOR TO WALL INSTALLATION.
13. MAINTAIN ACCESS TO EXITS AND EXIT STAIRS AT ALL TIMES. FIRE ALARM AND
SMOKE DETECTION SYSTEM SHALL REMAIN OPERATIONAL AT ALL TIMES. PROTECT
SMOKE DETECTORS AS REQUIRED AND IN CONFORMANCE WITH CODES AND LOCAL
AUTHORITIES HAVING JURISDICTION.
14. PRIOR TO DEMOLITION, PERFORM A THOROUGH ABOVE-CEILING INSPECTION FOR
EXISTING SERVICES THAT ARE TO REMAIN AND NOTIFY VAMC COR IMMEDIATELY OF
ANY CONFLICTS WITH INSTALLATION OF NEW WORK.
15. MAINTAIN 60" MINIMUM CLEARANCE AT ALL CORRIDORS AT ANY GIVEN TIME.
16. ENSURE THAT THE SMOKE AND FIRE BARRIER IS FULLY MAINTAINED THROUGHOUT
THE DURATION OF THE PROJECT. THIS IS TO INCLUDE FILLING ANY EXISTING
OPENINGS WITHIN THE SMOKE AND FIRE BARRIER.
EQ
EQ
2'x4' SUSPENDED ACOUSTIC CEILING
SUSPENDED ACOUSTIC CEILING
(W/FALSE JOINT)
2'x2' SUSPENDED ACOUSTIC CEILING
GWB CEILING; SEE DETAIL
SUPPLY AIR DIFFUSER
RETURN OR EXHAUST AIR GRILLE
NEW CEILING PENDANT SPRINKLER HEAD
FIRE ALARM SMOKE DETECTOR
CAN (RECESSED & SEMI-RECESSED)
LIGHT FIXTURES
LED LIGHT FIXTURE (2'x2')
SUSPENDED FLUORESCENT OR
LED LIGHT FIXTURE
SUSPENDED LIGHT FIXTURE
BELOW CEILING
LAYOUT INSTRUCTIONS:
EQ = EQUAL SPACES
OCCUPANCY / MOTION SENSOR
CEILING LEGEND
L3
LED LIGHT FIXTURE (2'x2')
NIGHT LIGHT (NL), LIFE SAFETY (LS)
OR EMERGENCY (E) CIRCUIT
LED LIGHT FIXTURE (2'x4')
WIRELESS ACCESS POINT (WAP)
UPRIGHT OR EXISTING SPRINKLER HEAD
EXIT SIGN
P.A. SPEAKER
WAP
PA
M
L1
L2
L1
LS
FINISHES & LAYOUT PLAN GENERAL NOTES:
1. REFER TO MATERIALS LEGEND AND FINISH SCHEDULE ON A-501 FOR ROOM FINISHES.
2. FABRICATE AND INSTALL TRIM PIECE TO INSTALL AT FINISHED WALL AND CLASS II B2
HOOD IN ROOM C105C TO FILL GAP BETWEEN WALL AND HOOD. SEAL TRIM AT WALL
WITH CAULK. COORDINATE WITH VAMC PROJECT COR.
ARCHITECTURAL DEMOLITION FLOOR PLAN
SCALE: 1/4" = 1'-0"
ARCHITECTURAL FLOOR PLAN
SCALE: 1/4" = 1'-0"
REFLECTED CEILING PLAN
SCALE: 1/4" = 1'-0"
FINISHES & LAYOUT FLOOR PLAN
SCALE: 1/4" = 1'-0"
SUSPENDED DRYWALL CEILING (TYPE GWB-1)
WITH CROSS CHANNEL
SCALE: NONE
ROOM DATA
SCALE: NONE
AutoCAD SHX Text
MAIN TEE SPLICE
AutoCAD SHX Text
FIRE EXPANSION NOTCH
AutoCAD SHX Text
CROSS CHANNEL
AutoCAD SHX Text
GYPSUM PANEL
AutoCAD SHX Text
MAIN TEE
AutoCAD SHX Text
12 GA. HANGER WIRE
DRYWALL SCREW (TYP)
5"
TYPE 'B' DOOR
ARMOR PLATE IF
SPECIFIED (SEE
DOOR SCHEDULE)
WSF-1; MANNINGTON MERSTICK 725 COVE STICK
FRP-1; WALL PROTECTION FRP PANEL FROM
SUB-FLOOR TO CEILING
(ROOM C105C & C105D, SEE FINISH SCHEDULE)
WSF-1; MANNINGTON 022 COVE CAP
WSF-1 FLOOR SYSTEM
(SEE FINISH SCHEDULE)
SUB-FLOOR
GWB-1; METAL STUD & GWB WALL (TYP)
o n e e i g h t h i n c e f o o t
B
A
C
D
E
F t h r c h e e f o o t o d o n e h a l f i n c h e e f o o t o o t t h r e e q u a r t e r s i n c e f o o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE
VA MEDICAL
CENTER
ENGINEERING
DEPARTMENT
800 IRVING AVE. SYRACUSE, NY 13210
03/22/2022
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-22-160
ALTER PHARMACY WAITING
ROOM FOR ALTERNATE
COMPOUNDING SUITE
S S
Y R
M
S M
S E n g i n e e r i n g P
R O
J E
C T
S A
C T
I V
E
P
R O
J E
C T
S A
A l t e r
P h a r m a c y f o r
A l t
C o m p o u n d i n g
S u i t e D e s i g n
C o n t r a c t D r a w i n g s C
A D
A r c h i t e c t u r a l A
A
R C
H A
L L d w g
NOT IN CONTRACT-REFERENCE ONLY
A-501
JDAM / DJ
ARCHITECTURAL DETAILS &
SCHEDULES
DOOR SCHEDULE
SCALE: NONE
DOOR TYPE LEGEND
SCALE: NONE
PARTITION FRAMING FOR DOORS
SCALE: NONE
FINISH SCHEDULE
SCALE: NONE
MATERIALS LEGEND
SCALE: NONE
DOOR HEAD & JAMB DETAILS
SCALE: NONE
WSF-1 FLOOR COVE BASE DETAIL
SCALE: NONE
AutoCAD SHX Text NOTE 1: OMIT BRACE WHEN "D" DIMENSION IS LESS THAN 2'-0" [610mm] FOR GYP. WALLBD. OR 16" [400mm] FOR PLASTER PARTITION.
AutoCAD SHX Text [152mm]
AutoCAD SHX Text
%%USECTION B
AutoCAD SHX Text VERTICAL STUDS @ 2'-0" [610mm] MAX. W/GYPSUM WALLBD. 1'-4" [406mm] W/GYPSUM LATH & PLASTER DOUBLE STUDS FOR SUPPORTING CONC. BACKER BOARD.
AutoCAD SHX Text PROVIDE CONTINUOUS BRACING WHEN STUDS EXCEED 10'-0" [3048mm] & ARE FINISHED BOTH SIDES
AutoCAD SHX Text
JAMB ANCHOR CLIPS 3 PER SIDE-COORDINATE W/HINGE REINFORCEMENT.
AutoCAD SHX Text
DETAIL D
AutoCAD SHX Text
SEE NOTE 1
AutoCAD SHX Text 12" [13mm] CONSTRUCTION JOINT
AutoCAD SHX Text
RUNNER BTWN STUDS
AutoCAD SHX Text
SEE DOOR SCHEDULE
AutoCAD SHX Text
SHIM AS REQ'D.
AutoCAD SHX Text
SEC. B
AutoCAD SHX Text
GYPSUM WALLBD. PANELS
AutoCAD SHX Text
CONTROL JOINT
AutoCAD SHX Text
ISOMETRIC OF CONSTR. JT.
AutoCAD SHX Text
ELEVATION AT DOOR FRAME
AutoCAD SHX Text
PROVIDE SOUND DEADENING WHERE REQ'D
AutoCAD SHX Text
SANITARY STOP
AutoCAD SHX Text
METAL DOOR FRAME
AutoCAD SHX Text
METAL ANCHOR CLIP
AutoCAD SHX Text
SHIM AS REQ'D.
AutoCAD SHX Text
DETAIL C
AutoCAD SHX Text [13mm]
AutoCAD SHX Text
JAMB ANCHOR
AutoCAD SHX Text
SECTION A
AutoCAD SHX Text
DOUBLE STUDS
AutoCAD SHX Text
DETAIL C
AutoCAD SHX Text
JAMB ANCHORS (FURNISHED WITH FRAME) DETAIL D
AutoCAD SHX Text
MET. DOOR FRAME
AutoCAD SHX Text 12" [13mm]
AutoCAD SHX Text [13mm]
AutoCAD SHX Text
CRIPPLE STUD; DO NOT ANCHOR TO BEARING STUD
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text [19mm]
AutoCAD SHX Text
WIDTH
AutoCAD SHX Text
STUD
AutoCAD SHX Text
MINUS 3/16"
AutoCAD SHX Text [5mm]
AutoCAD SHX Text
JAMB DEPTH
AutoCAD SHX Text
3/4" MIN.
AutoCAD SHX Text [19mm]
AutoCAD SHX Text
3/4" MIN.
AutoCAD SHX Text [19mm]
AutoCAD SHX Text
WIDTH
AutoCAD SHX Text
STUD
AutoCAD SHX Text
FRAME FACE
AutoCAD SHX Text
MINUS 3/16
AutoCAD SHX Text [5mm]
AutoCAD SHX Text
MINUS 3/16
AutoCAD SHX Text
FRAME FACE
AutoCAD SHX Text [5mm]
AutoCAD SHX Text 12"MIN. [13mm]
AutoCAD SHX Text 5/8"MAX. [16mm]
AutoCAD SHX Text
3/4" MIN.
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text
UNO
AutoCAD SHX Text
AS SCHED
AutoCAD SHX Text
WIDTH
AutoCAD SHX Text `8"
AutoCAD SHX Text 2"
AutoCAD SHX Text `8"
AutoCAD SHX Text `8"
AutoCAD SHX Text `8"
AutoCAD SHX Text
MTL STUDS SINGLE OR DOUBLE LAYER & GWB PER PARTITION SCHEDULE
AutoCAD SHX Text
CERAMIC TILE FINISH WHERE REQUIRED
AutoCAD SHX Text
CORNER PTN WHERE APPLICABLE
AutoCAD SHX Text
DOUBLE STUD SEALANT (TYP)
AutoCAD SHX Text
HM FRAME W/MIN 3 ANCHORS PER JAMB
AutoCAD SHX Text
HEAD-FRAME
AutoCAD SHX Text
JAMB-FRAME
AutoCAD SHX Text AT DOOR FRAME UNITS WIDER THAN 5'-0", PROVIDE & INSTALL 18 GA. FLAT STRAP X-BRACING FROM JACK STUDS
AutoCAD SHX Text
SEE PTN TYPES FOR THROAT DIM
SEE PTN TYPES FOR THROAT DIM
F F
TAMPER SWITCH
CHECK VALVE
SPRINKLER DRAIN PIPING
FIRE PROTECTION PIPING MAIN
GROUND FACE UNION OR FLANGES
PRESSURE GAUGE
FIRE PROTECTION LEGEND
ISOLATION VALVE
INSPECTORS TEST FITTING
RECESSED PENDENT SPRINKLER HEAD-NEW
SPRINKLER HEAD TO REMAIN-EXISTING
SIDEWALL SPRINKLER HEAD
WATERFLOW SWITCH
ABV CLG ABOVE THIS CEILING
AFF ABOVE FINISHED FLOOR
BLW FLR BELOW THIS FLOOR
BOP BOTTOM OF PIPE
BOS BOTTOM OF STEEL
COR CONTRACTING OFFICER'S
REPRESENTATIVE
DN DOWN
(E), EXIST EXISTING
EC ELECTRICAL CONTRACTOR
FC FIRE PROTECTION CONTRACTOR
FDC FIRE DEPARTMENT CONNECTION
FHC FIRE HOSE CABINET
FHV FIRE HOSE VALVE
FLR FLOOR
FP FIRE PROTECTION
GC GENERAL CONTRACTOR
INV INVERT
MAX MAXIMUM
MIN MINIMUM
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
PC PLUMBING CONTRACTOR
R RISER / RADIUS
SP STANDPIPE
SPKLR SPRINKLER
TOP TOP OF PIPE
TOS TOP OF STEEL
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
VAMC SYRACUSE VA MEDICAL CENTER
VIF VERIFY IN FIELD
EXISTING PIPING TO BE REMOVED
EXISTING FIRE PROTECTION PIPING
SPRINKLER HEAD TO BE REMOVED
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
SMOKE BARRIER
AREA OF WORK BOUNDARY
1. FIRE PROTECTION SPRINKLER INSTALLATION SHALL MEET THE REQUIREMENTS OF THE
FOLLOWING:
NFPA 13 AND 14, 2019 EDITION AND NFPA 101 2018 EDITION.
LOCAL AND STATE REGULATIONS AND IBC 2018 EDITION.
DVA FIRE PROTECTION DESIGN MANUAL; SEVENTH EDITION; REVISED DECEMBER, 2015.
2. SPRINKLERS SHALL BE FM APPROVED QUICK RESPONSE IN ALL AREAS EXCEPT WHERE
SPECIFICALLY PROHIBITED, IN COMPLIANCE WITH VA GUIDELINES AND NFPA REQUIREMENTS.
3. SPRINKLERS THROUGHOUT THE BUILDING TO BE ORDINARY TEMPERATURE RATED.
4. SPRINKLER PIPE SIZES AND SPRINKLER HEAD LOCATIONS SHALL BE HYDRAULICALLY
CALCULATED. SPRINKLER HEADS INDICATED ON DRAWINGS ARE FOR DESIGN COORDINATION AND
BUDGETARY PRICING ONLY.
5. PIPE HANGERS INCLUDING SEISMIC PROTECTION TO BE INSTALLED AS REQUIRED BY NFPA FOR
SUPPORTING SPRINKLER PIPING. NO OTHER PIPING AND/OR DEVICES ARE TO BE ATTACHED TO
THE SPRINKLER PIPE.
6. PIPING SHALL NOT BE LOCATED IN ANY ELECTRICAL ROOMS/CLOSETS OR TELECOMMUNICATION
ROOMS/CLOSETS UNLESS THOSE PIPES SERVE ONLY THAT SPACE.
7. ALL SPRINKLER PIPE TO MAINTAIN A 6'-0" MIN VERTICAL CLEARANCE FROM TOP OF ELECTRICAL
CONTROL PANELS AND SWITCHGEARS/TRANSFORMERS.
8. PROVIDE SPRINKLER ZONE FLOOR CONTROL VALVE ASSEMBLY CONSISTING OF CONTROL VALVE, CHECK VALVE, FLOW SWITCH, TAMPER SWITCH, SELF-CONTAINED TEST AND DRAIN ASSEMBLY
AND PRESSURE GAGE, ON THE SPRINKLER MAIN BRANCH SERVING EACH FLOOR.
9. INSTALL PIPING SO THAT VALVES ARE ACCESSIBLE AND STEMS EXTEND VERTICALLY UP. ALL
CONTROL VALVES SHALL BE EQUIPPED WITH TAMPER SWITCHES.
10. ALL WATER FLOW SWITCHES MUST BE ISOLATED BY MEANS OF A FITTING OR UNION ON BOTH
SIDE TO FACILITATE REMOVAL AND SERVICE OF THE FLOW SWITCH.
11. THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE THE QUANTITY OF SPRINKLER HEADS AS
REQUIRED TO MAINTAIN THE MINIMUM COVERAGE REQUIRED BY NFPA 13 IN ALL AREAS OF THE
BUILDING.
12. FIRE PROTECTION CONTRACTOR SHALL INSPECT ALL EXISTING FIRE PROTECTION MAINS TO BE
REUSED AND REPLACE ANY THAT ARE DAMAGED, CORRODED OR OTHERWISE COMPROMISED.
COORDINATE ANY FINDINGS WITH THE COR.
13. COORDINATE THE EXACT LOCATION OF ALL SPRINKLER HEADS, PIPING, EQUIPMENT AND DEVICES
WITH ARCHITECTURAL DRAWINGS AND THE RESPECTIVE DRAWINGS OF PIPING, DUCTWORK,
DIFFUSERS, BEAMS, LIGHTS, ETC. THIS CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF
THESE COMPONENTS IN THE FIELD AND DOCUMENT ON THEIR SUBMITTALS.
14. PROVIDE COMPLETE AND FUNCTIONAL FIRE PROTECTION SYSTEMS FOR THE PROJECT. THE
SYSTEMS SHALL CONFORM TO THE SPECIFICATIONS AND AS SHOWN ON DRAWINGS. ITEMS OR
WORK NOT SHOWN OR SPECIFIED, BUT REQUIRED FOR COMPLETE SYSTEMS, SHALL BE PROVIDED
AND CONFORM TO ACCEPTED TRADE PRACTICES. THE DRAWINGS AND SPECIFICATIONS ARE
PRESENTED TO DEFINE SPECIFIC SYSTEM REQUIREMENTS AND SERVE TO EXPAND ON THE
PRIMARY CONTRACT REQUIREMENTS OF PROVIDING COMPLETE SYSTEMS. THE DRAWINGS ARE
DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT AND ROUTING OF THE SYSTEMS
INCLUDED IN THIS CONTRACTORS WORK.
15. THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE ORIGINAL BUILDING
DRAWINGS AND FIELD SURVEY INFORMATION COMPILED BY THE ENGINEERING DESIGN TEAM FOR
THE PURPOSE OF ENGINEERING DESIGN CONCEPT. EXISTING CONDITIONS ARE SHOWN AS
ACCURATELY AS POSSIBLE. THERE IS THE POSSIBILITY THAT CONDITIONS SHOWN ARE NOT
EXACTLY AS EXISTING. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, LOCATIONS, SIZES AND CONDITIONS AT THE SITE AND DOUMENT THAT ON THEIR SUBMITTALS.
16. THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING THAT ALL RULES AND REGULATIONS, INCLUDING THOSE WHICH MAY BE ISSUED BY THE OWNER, ARE BEING OBSERVED, PARTICULARLY
WORKPLACE SAFETY AND THE CONDUCT OF ALL THOSE EMPLOYED DIRECTLY AND INDIRECTLY BY
HIM ON THE PREMISES, AND THE OWNER'S EMPLOYEES WHO MAY BE IMPACTED OR AFFECTED BY
CONSTRUCTION ACTIVITIES. THE CONTRACTOR WILL INSTALL SIGNAGE, BARRIERS, AND OTHER
MEANS TO PROVIDE WARNING AND PERSONNEL SAFETY. PLACEMENT OF THESE ITEMS WILL BE
COORDINATED WITH THE OWNER AND HIS ONGOING OPERATIONS AND WILL PROMPTLY BE
RESTORED WHEN WORK IN A PARTICULAR AREA HAS BEEN COMPLETED.
17. CONTRACTOR SHALL MAKE ALL NECESSARY SUBMISSIONS AND OBTAIN ALL NECESSARY PERMITS
AND APPROVALS PRIOR TO STARTING FABRICATION AND CONSTRUCTION.
FIRE PROTECTION GENERAL NOTES
1. SYSTEM TYPE: WET PIPE
2. SPRINKLER HEAD SPACING AND PIPE SIZING SHALL BE:
a. TOILET ROOMS, TESTING AND OFFICE AREAS; LIGHT HAZARD (0.10 GPM/SQ.FT. OVER 1500
SQ.FT, 225 SQ.FT. PER SPRINKLER HEAD)
b. STORAGE ROOMS; ORDINARY GROUP II HAZARD (0.20 GPM/SQ.FT. OVER 1500 SQ.FT, 130 SQ.FT.
PER SPRINKLER HEAD)
3. PROVIDE FOR AN ADDITIONAL WATER ALLOWANCE OF 250 GPM FOR INSIDE AND OUTSIDE HOSE
STREAMS TO THE SPRINKLER HYDRAULIC REQUIREMENTS.
4. THE CALCULATED DEMAND INCLUDING HOSE STREAM REQUIREMENTS SHALL FALL NO LESS THAN
10 PERCENT BELOW THE AVAILABLE WATER SUPPLY.
5. SYSTEM SHALL BE DESIGNED ON A HYDRAULICALLY CALCULATED BASIS UTILIZING THE AREA
DENSITY METHOD PER NFPA 13 BY THE SPRINKLER CONTRACTOR. CALCULATIONS AND SHOP
DRAWINGS SHALL BE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE
STATE OF NEW YORK.
6. SPRINKLER PIPE SIZES SHALL BE DETERMINED BY HYDRAULIC CALCULATIONS BASED ON EXISTING
FIRE PUMP HYDRAULIC FLOW TEST DATA (SEE VAMC-SYRACUSE FMS TO VERIFY MOST CURRENT
PUMP TEST DATA PRIOR TO START OF WORK):
DATE: JUNE 18, 2021
· SUCTION PRESSURE: 40 PSIG
· DISCHARGE PRESSURE: 170 PSIG
· MEASURED NET PRESSURE: 130 PSIG
· NET PRESSURE AT RATED RPM: 127.8 PSIG
· OBSERVED FLOW: 1004 GPM
· FLOW AT RATED RPM: 995.3 GPM
FIRE PROTECTION DESIGN CRITERIA
PROVIDE SUPPORT IF
ARM EXCEEDS 24"
SPRINKLER HEAD TO
BOTTOM OF DECK
PER
NFPA-13
F I E
L D
M E
A S
U R
E
BRANCH LINE
1"
QUICK RESPONSE
RECESSED
SPRINKLER HEAD
BRANCH LINE
F I E
L D
M E
A S
U R
E
CEILING
REDUCER 1" x
1"
REDUCER
1" x
FHC
FIRE HOSE CABINET
FS
TS
TYPICAL DROP PENDANT SPRINKLER DETAIL
SCALE: NONE
TYPICAL UPRIGHT SPRINKLER DETAIL
SCALE: NONE
QUICK RESPONSE
UPRIGHT SPRINKLER
W/SPRINKLER GUARD
INTERIOR WALL PENETRATION DETAIL
SCALE: NONE
MARK DESCRIPTION
1 MINIMUM 2
" THICKNESS OF MINIMUM 4 PCF MATERIAL WOOL BATT INSULATION FIRMLY
PACKED INTO OPENING AS A PERMANENT FORM RECESSED A MINIMUM OF
" FROM BOTH
SURFACES OF WALL.
2 FILL VOID WITH SEALANT A MINIMUM OF
" THICKNESS APPLIED WITHIN THE ANNULUS, FLUSH
WITH BOTH SURFACES OF WALL ASSEMBLY. AT POINT OF CONTACT BETWEEN THROUGH
PENETRANT AND WALL, A MINIMUM
" DIAMETER BEAD OF FILL MATERIAL SHALL BE APPLIED
AT THE CONCRETE/THROUGH PENETRANT INTERFACE ON BOTH SURFACES OF WALL.
3 PIPE SLEEVE (NOT REQUIRED FOR EXISTING CORE DRILLED WALLS).
4 WALL.
5 ESCUTCHEON PLATE FLUSH AGAINST WALL AND OF SIZE TO COMPLETELY COVER OPENING.
PROVIDE FOR EXPOSED PIPING IN FINISHED SPACES.
2 HR RATING: UL #C-AJ-1240 OR APPROVED EQUAL.
1 HR RATING: UL #C-AJ-1240 OR APPROVED EQUAL.
NOTE:
FOR GYPSUM BOARD WALLS; PROVIDE UL #W-L-1033 OR APPROVED EQUAL FOR 2 HR AND 1 HR RATINGS.
FIRE PROTECTION ABBREVIATIONS
FIRE PROTECTION DETAILS
PIPE HANGER INSTALLATION & SCHEDULE
SCALE: NONE
12"
6" THRU 8"
HANGER ROD SCHEDULE
" THRU 3"
PIPE SIZE
UP TO 2"
4" AND 5"
" DIA.
" DIA.
ROD SIZE
2"
" 11'
10'
HANGER ROD SPACING
1"
PIPE SIZE
9'
8'
7'
MAX. ALLOWABLE
SPACING
3" THRU 8"
12'
10" & 12" 15'
NOTE: FLEXIBLE
SPRINKLER HEAD
CONNECTIONS
PERMITTED, SEE
DETAIL 2
HANGER ROD
LOCKING NUT
SUPPORT NUT
CLEVIS HANGER
PIPE
QUICK RESPONSE
RECESSED
SPRINKLER HEAD
BRANCH LINE
F I E
L D
M E
A S
U R
E
CEILING
ADJUSTABLE HUB
FULLY BRAIDED,
CORRUGATED
STAINLESS STEEL
HOSE WITH
STAINLESS STEEL
BRAID; MIN. 1" I.D.
TYPICAL FLEXIBLE HEAD SPRINKLER DETAIL
SCALE: NONE
SPRINKLER
DROP
1" NIPPLE
CONCENTRIC REDUCER
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
PIPE OR RISER DOWN
PIPE OR RISER UP
PIPE CAP OR PLUG
SPRINKLER CONTROL VALVE
HEAD LOCATION DETAIL
SCALE: NONE
PIPE SLEEVE SCHEDULE
PIPE SIZE SLEEVE SIZE
1" - 1
" 2" - 2
2" 4"
3" 5"
4" 6"
6" 8"
#1
#1
#1
#2
TOP BEAM CLAMP
ALL THREAD ROD
HANGER RING
LINE PIPE
TOP BEAM CLAMP
ALL THREAD ROD
HANGER RING
TOP BEAM CLAMP
ALL THREAD ROD
HANGER RING
BAR JOIST
PIPE SIZED
PER NFPA 13
ALL THREAD ROD
HANGER RING
BAR JOIST
BAR JOIST
BLDG STEEL
PIPE CLAMP
TOP BEAM CLAMP TRAPEZE / TOP BEAM CLAMP
TOP BEAM CLAMPTOP BEAM CLAMP
TYPICAL PIPE HANGER CLAMP DETAILS
SCALE: NONE
NOTE: ALL HANGERS ARE TYPE #1 UNLESS NOTED OTHERWISE.
6" 6" 6" 6"
6" 6" 6" 6"
ACCEPTABLE SPRINKLER
HEAD LOCATION WITHIN
CEILING TILE (TYP)
1'-0" 1'-0" 1'-0" 1'-0"
1'-0" 1'-0" 1'-0" 1'-0"
2' x 4' CEILING TILE 2' x 2' CEILING TILE
" MIN. DIA. EXPANSION
BOLTS FOR (E) CONCRETE &
INSERTS FOR NEW (TYP)
FOR PIPES UNDER 2" USE
" x 1
" x
" ANGLE,
FOR PIPES LARGER THAN 2"
USE 3" x 3" x
" ANGLE
TURNBUCKLE
" MIN. DIA.
HANGER RODS
(TYP)
CONC. SLAB OR BEAM
STEEL EXPANSION SHIELD ANCHOR IN
(E) CONCRETE & INSERTS FOR NEW;
THIS TYPE SHALL ONLY BE USED IN
SLABS OR BEAMS OF 4" MIN. DEPTH
NUTS & WASHERS
(TYP)
SECURING PIPE HANGER RODS FROM CONCRETE DECK DETAILS
SCALE: NONE
NOTE:
SYMBOL LIST SHOWN IS FOR GENERAL
REFERENCE ONLY. THE PRESENCE OF A
SYMBOL DOES NOT IMPLY ITS USE ON THIS
PROJECT. REFER TO THE DRAWINGS FOR
SPECIFIC SYMBOLS USED.
o n e e i g h t h i n c e f o o t
B
A
C
D
E
F t h r e e i n c h e e f o o t o n e a n d o l f i n c h e o t o n e i n c e f o o t t h r a r t e r s i n o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE
VA MEDICAL
CENTER
ENGINEERING
DEPARTMENT
800 IRVING AVE. SYRACUSE, NY 13210
03/22/2022
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-22-160
ALTER PHARMACY WAITING
ROOM FOR ALTERNATE
COMPOUNDING SUITE
S S
Y R
M
S M
S E n g i n e e r i n g P
R O
J E
C T
S A
C T
I V
E
P
R O
J E
C T
S A
A l t e r
P h a r m a c y f o r
A l t
C o m p o u n d i n g
S u i t e D e s i g n
C o n t r a c t D r a w i n g s C
A D
F i r e
P r o t e c t i o n A
F
I R
E P
R O
T A
L L d w g
NOT IN CONTRACT-REFERENCE ONLY
FX-001
JDAM
FIRE PROTECTION ABBREVIATIONS,
SYMBOLS, NOTES & DETAILS
SPRINKLER RISER
C105
C107
PHARMACY WAITING
B140
PHARMACY
CORRIDOR
SHAFT 9
1"
1"
1"
1"
1" 1"
ZONE 20
ZONE 20
CONTROL VALVE 175
TEST & DRAIN VALVES 176 / 177
VALVE TAMPER SWITCH 07080139
FLOW SWITCH 07080138
6" RISER #5 LOCATED IN STAIR #5
C107
PHARMACY WAITING
B140
PHARMACY
CORRIDOR
SHAFT 9
1"
1"
1"
C105C
HAZ MIX
65 SF
C105
ENTRY
121 SF
C105B
ANTE ROOM
64 SF
C105D
NON-HAZ MIX
71 SF
C105A
GARB
41 SF
1 1
PA
ZONE 20
EXISTING SPRINKLER HEAD
TO REMAIN (TYP)
MODIFY EXISTING SPRINKLER PIPING AS
REQUIRED TO SUIT NEW LAYOUT AND
COORDINATION WITH OTHER UTILITIES
LOCATED ABOVE THE NEW CEILING
(TYPICAL) - REFER TO FIRE PROTECTION
SPECIFICATIONS AND DRAWINGS
ZONE 20
CONTROL VALVE 175
TEST & DRAIN VALVES 176 / 177
VALVE TAMPER SWITCH 07080139
FLOW SWITCH 07080138
6" RISER #5 LOCATED IN STAIR #5
1. REFER TO DRAWING FX-001 FOR FIRE PROTECTION SYMBOLS, LEGEND, GENERAL
NOTES, SYSTEM DESIGN CRITERIA AND DETAILS.
2. ANY DISCREPANCIES, CONFLICTS OR CHANGES IN CONSTRUCTION DRAWINGS, NOTES
AND SPECIFICATIONS SHALL BE BROUGHT IMMEDIATELY TO THE ATTENTION OF THE
CONTRACTING REPRESENTATIVE (COR) FOR COORDINATION PRIOR TO STARTING
WORK.
3. PROVIDE ALL CUTTING, PATCHING AND FIRE STOPPING REQUIRED TO ACCOMPLISH
WORK SHOWN. PATCH OPENINGS TO MATCH ADJACENT WALLS, FLOORS, AND
CEILINGS. PATCH AND RESEAL IN AN APPROVED MANNER ANY NEW PENETRATIONS
THROUGH FIRE AND/OR SMOKE RATED WALLS AS REQUIRED. REFER TO FX-001
GENERAL NOTES, SPECIFICATIONS AND DETAILS.
4. MAINTAIN THE INTEGRITY OF ALL EXISTING EQUIPMENT AND SYSTEMS LOCATED
OUTSIDE THE WORK AREA AND INTERRUPTED BY INSTALLATION WORK. PROVIDE ALL
ADDITIONAL PIPING, FITTINGS & ACCESSORIES REQUIRED TO EXTEND AND
RECONNECT REMAINING EQUIPMENT AND SYSTEMS. ANY DAMAGE TO EXISTING
SPRINKLERS AND OR EQUIPMENT LOCATED OUTSIDE THE WORK AREA SHALL BE
REPLACED AT NO COST TO OWNER.
5. SCHEDULE ALL SHUTDOWNS WITH THE COR TWO WEEKS IN ADVANCE. SHUTDOWNS
SHALL NOT INTERFERE WITH BUILDING OPERATIONS. PROVIDE TEMPORARY FIRE
PROTECTION DURING CONSTRUCTION AND SHUTDOWNS ACCORDING TO THE
INTERNATIONAL BUILDING AND FIRE CODE, NFPA AND VA MEDICAL CENTER DESIGN
MANUAL. CONTRACTOR SHALL REACTIVATE THE SYSTEM AT THE END OF EACH WORK
DAY.
6. FIRE PROTECTION CONTRACTOR SHALL INSPECT ALL EXISTING FIRE PROTECTION
MAINS TO BE REUSED AND REPLACE ANY THAT ARE DAMAGED, CORRODED OR
OTHERWISE COMPROMISED. COORDINATE ANY FINDINGS WITH THE COR.
7. ALL SINGLE SPRINKLER HEAD BRANCH LINES SHALL BE 1" UNLESS OTHERWISE NOTED.
8. SPRINKLER HEADS SHALL BE INSTALLED AND SPACED TO PREVENT ANY
OBSTRUCTIONS AS REQUIRED BY NFPA 13. PROVIDE SPRINKLER PROTECTION BELOW
ANY OBSTRUCTIONS MORE THAN 4'-0" WIDE.
9. IN THE EVENT OF ANY LOW POINTS, THE CONTRACTOR SHALL PROVIDE AN AUXILIARY
DRAIN, IDENTIFICATION AND ACCESS.
10. ALL NEW OR EXISTING PIPING LEFT EXPOSED SHALL BE IDENTIFIED AND PAINTED FIRE
HYDRANT RED. PAINT TO MATCH EXPOSED PIPING IN ADJACENT FINISHED AREAS.
NEW WORK GENERAL NOTES:
o n e e i g h t h i n c e f o o t
B
A
C
D
E
F t h r c h e e f o o t o d o n e h a l f i n c h e e f o o t o o t t h r e e q u a r t e r s i n c e f o o t o n e h a l f i n c e f o o t t h r e e e i g h t h s i n c e f o o t o n e q u a r t e r i n c e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
DRAWING NUMBER
BUILDING NUMBER
PROJECT NUMBER
REVISION DATE
SYRACUSE
VA MEDICAL
CENTER
ENGINEERING
DEPARTMENT
800 IRVING AVE. SYRACUSE, NY 13210
03/22/2022
GENERAL PROJECT INFORMATION
100% SPRINKLERED
DWG.
U.S. Department of Veterans Affairs
B
A
C
D
E
F
528A7-22-160
ALTER PHARMACY WAITING
ROOM FOR ALTERNATE
COMPOUNDING SUITE
S S
Y R
M
S M
S E n g i n e e r i n g P
R O
J E
C T
S A
C T
I V
E
P
R O
J E
C T
S A
A l t e r
P h a r m a c y f o r
A l t
C o m p o u n d i n g
S u i t e D e s i g n
C o n t r a c t D r a w i n g s C
A D
F i r e
P r o t e c t i o n A
F
I R
E P
R O
T A
L L d w g
NOT IN CONTRACT-REFERENCE ONLY
FX-001
JDAM
FIRE PROTECTION FLOOR PLANS
FIRE PROTECTION DEMOLITION FLOOR PLAN
SCALE: 1/4" = 1'-0"
N
FIRE PROTECTION NEW WORK FLOOR PLAN
SCALE: 1/4" = 1'-0"
N
DEMOLITION GENERAL NOTES:
1. REFER TO DRAWING FX-001 FOR FIRE PROTECTION SYMBOLS LEGEND, GENERAL
NOTES, SYSTEM DESIGN CRITERIA AND DETAILS.
2. ANY DISCREPANCIES, CONFLICTS OR CHANGES IN CONSTRUCTION DRAWINGS, NOTES
AND SPECIFICATIONS SHALL BE BROUGHT IMMEDIATELY TO THE ATTENTION OF THE
COR FOR COORDINATION PRIOR TO STARTING WORK.
3. REMOVE SPRINKLER HEADS (UPRIGHT AND PENDANT) AND ASSOCIATED BRANCH
PIPING AS SHOWN BACK TO SYSTEM MAINS TO BE REUSED. TEMPORARILY OR
PERMANENTLY CAP AT MAINS AS REQUIRED.
4. PROVIDE ALL CUTTING, PATCHING AND FIRE STOPPING REQUIRED TO ACCOMPLISH
WORK SHOWN. PATCH OPENINGS TO MATCH ADJACENT WALLS, FLOORS, AND
CEILINGS. PATCH AND RESEAL IN AN APPROVED MANNER ANY OPEN PENETRATIONS
THROUGH FIRE AND/OR SMOKE RATED BARRIERS AS REQUIRED AFTER PIPING
REMOVALS USING UL LISTED MATERIALS. REFER TO GENERAL NOTES AND
SPECIFICATIONS.
5. MAINTAIN THE INTEGRITY OF ALL EXISTING EQUIPMENT AND SYSTEMS LOCATED
OUTSIDE THE WORK AREA AND INTERRUPTED BY THE REMOVALS WORK. PROVIDE ALL
ADDITIONAL PIPING, FITTINGS & ACCESSORIES REQUIRED TO EXTEND AND
RECONNECT REMAINING EQUIPMENT AND SYSTEMS. ANY DAMAGE TO EXISTING
SPRINKLERS AND OR EQUIPMENT LOCATED OUTSIDE THE WORK AREA SHALL BE
REPLACED AT NO COST TO OWNER.
6. SCHEDULE ALL SHUTDOWNS WITH COR TWO WEEKS IN ADVANCE. SHUTDOWNS SHALL
NOT INTERFERE WITH BUILDING OPERATIONS. PROVIDE TEMPORARY FIRE PROTECTION
DURING CONSTRUCTION AND SHUTDOWNS ACCORDING TO THE INTERNATIONAL
BUILDING AND FIRE CODE, NFPA AND VA MEDICAL CENTER DESIGN MANUAL.
CONTRACTOR SHALL REACTIVATE THE SYSTEM AT THE END OF EACH WORK DAY.
DEMOLITION KEYED NOTES:
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
NEW SYSTEM KEYED NOTES:
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
RATED BARRIER LEGEND
SMOKE BARRIER
1 HR. FIRE RATED BARRIER
2 HR. FIRE RATED BARRIER
PATCH AND RESEAL IN AN APPROVED MANNER ANY OPEN PENETRATIONS
PLUMBING ABBREVIATIONS
A/E ARCHITECT / ENGINEER
AD AREA DRAIN/ACCESS DOOR
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AG AIR GAP
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER
ASD ADJUSTABLE SPEED DRIVES
ASD AUTOMATIC SPRINKLER DRAIN
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION, AIR
CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
AV ACID VENT
AW ACID WASTE
BFP REDUCED PRESSURE BACKFLOW PREVENTER
BHP BREAK HORSEPOWER
BSP BLACK STEEL PIPE
BT BATHTUB
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CELSIUS
CA COMPRESSED AIR
CGA COMPRESSED GAS ASSOCIATION
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CO CLEANOUT
COR CONTRACTING OFFICER'S REPRESENTATIVE
CS CLINICAL SINK
CV CONTROL VALVE
DCW DOMESTIC COLD WATER
DFU DRAINAGE FIXTURE UNITS
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DI DEIONIZED WATER
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
EL or ELEV ELEVATION
EMCS ENERGY MONOSERRAT AND CENTRAL SYSTEM
EPA ENVIROMENTAL PROTECTION AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
EWS EYE WASH STATION
EWS/SH EYE WASH/DRENCH SHOWER
EX EXISTING
F FAHRENHEIT
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FS FLOW SWITCH
FU FIXTURE UNITS
GAL GALLON
GCO GRADE CLEANOUTS
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GT GREASE TRAP
GVTR GAS VENT THROUGH ROOF
GWH GAS FIRED WATER HEATER
H&CW HOT AND COLD WATER
HB HOSE BIBB
HD HUB DRAIN
HEX HEAT EXCHANGER
HP HORSEPOWER
HS HAND SINK
HST HOT WATER STORAGE TANK (DOMESTIC)
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HYD HYDRANT
ID INSIDE DIAMETER
IE INVERT ELEVATION
ICW INDUSTRIAL COLD WATER
IHW INDUSTRIAL HOT WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
KW KILOWATT
KWH KILOWATT-HOUR
L/S LITER PER SECOND
LA LABORATORY AIR
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LCW LABORATORY COLD WATER
LHW LABORATORY HOT WATER
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LV LABORATORY VACUUM
LW LOW WATER
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH 1000 BTUH
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MH MANHOLE
MOU MEMORANDUM OF UNDERSTANDING
MSB MOP SERVICE BASIN
MV MEDICAL VACUUM
N2 NITROGEN
N20 NITROUS OXIDE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM. NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
O2 OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OR OPERATING ROOM
OVFL OVERFLOW
PA PASCAL
PD PRESSURE DROP OR DIFFERENCE
ΔP DIFFERENTIAL PRESSURE
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAGE
PP PLUMBING PUMP
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ATMOSPHERE
PSIG POUNDS PER SQUARE INCH GAGE
PTRV PRESSURE TEMPERATURE RELIEF VALVE
PW POTABLE WATER
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RP RECIRCULATION PUMP
RO REVERSE OSMOSIS WATER
RWL RAIN WATER LEADER
SAN SANITARY SEWER
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
SCFM STANDARD CUBIC FOOT/MINUTE
SCW SOFTENED COLD WATER
SDMH STORM DRAIN MANHOLE
SMH SANITARY MANHOLE
SP SUMP PUMP
SPR SPRINKLER LINE
SQFT/SF SQUARE FEET
SS STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
TCV TEMPERATURE CONTROL VALVE
TD TEMPERATURE DIFFERENCE
ΔT DIFFERENTIAL TEMPERATURE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TWR…