501-18130-095_Lockwood_RTU_Replacement_Drawing.pdf

PDF 10 MB Posted

Attached to
160761 Lockwood BLDG. Rooftop HVAC Replacement
Solicitation number
IFB-122360
Issued by
Halifax County, Virginia

About this file

This file comprises the working drawings and technical specifications for the VDOT Lockwood Building Rooftop HVAC Replacement project located at 9120 Lockwood Boulevard, Mechanicsville, Virginia 23116 (Project Code: 50-18130-095, IFB #160761). The project scope consists of the in-kind replacement of four rooftop-mounted HVAC units (RTUs 1-4) serving the existing 154,877-square-foot, four-story building. The replacement work includes new Annexair rooftop units with DX cooling coils, supply and return air dampers with variable frequency drives, integrated BACnet MSTP controls systems, 2-inch composite panel construction, economizer louvers with demand-controlled ventilation, direct digital feedback controls for temperature and humidity, new condensate drain systems with indirect roof drain connections, roof curbs with composite panel construction and lifting lugs, new 24-inch by 24-inch by 6-inch junction boxes for wiring extensions, and reconnection of existing electrical power and control wiring to new units. The project requires refrigerant upgrades from R-410A to R-454B with integral leak detection sensors, installation of MERV 13 filters, structural support evaluation, lightning protection system reconnections, and fire alarm interface for new smoke detectors integral to the units.

The working drawings indicate that the project must comply with the 2021 Virginia Existing Building Code and 2021 Virginia Construction Code, utilizing ASHRAE 90.1-2019 standards for direct replacement of existing HVAC equipment. The building is exempt from High Performance Buildings Act compliance as renovation costs do not exceed 50 percent of building value. Electrical work includes disconnection and reconnection of existing power wiring from panels L4A and L4B located on a lower level, with new 20-amp branch circuits provided for unit receptacles utilizing number 12 wiring from spare breakers. The project involves no asbestos or lead-based paint concerns as the building was constructed after January 1, 1985. All demolition debris and scrap materials must be disposed of at approved sites with signed notifications provided to the owner's representative prior to disposal. The drawings were prepared by Architectural Partners (Lynchburg, Virginia), with mechanical and electrical engineering by Master Engineers & Designers and Rockingham Engineering PLLC, and preliminary unit designs provided by Annexair and Hobbs & Associates - Richmond. Contract award and project timeline information are not specified within the technical drawings.

View the file

Other files

File Type Posted
VDOT_Lockwood_RTU_Replacement_-_Project_Manual (2).pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A001

SECTION

NO.

SECTION SHOWN

ON THIS

SHEET

SECTION MARKER

A001

DETAIL

NO.

DETAIL SHOWN

ON THIS

SHEET

DETAIL MARKER

A001

ELEV.

NO.

ELEV. SHOWN

ON THIS

SHEET

ELEVATION MARKER

ELEVATION

NO.

ELEVATION SHOWN

ON THIS

SHEET

INTERIOR ELEVATION

MARKERA001

A001

DETAIL

NO.

DETAIL SHOWN

ON THIS

SHEET

DETAIL/SECTION

MARKER

SYMBOL LEGEND

CODE INFORMATION

PROJECT INFORMATION VDOT LOCKWOOD BUILDING RTU REPLACEMENT

9120 LOCKWOOD BLVD

MECHANICSVILLE, VIRGINIA

APPLICABLE CODES 2021 EDITION VIRGINIA EXISTING BUILDING CODE - VEBC

2021 EDITION VIRGINIA CONSTRUCTION CODE - VCC

CONSTRUCTION CLASS EXIST IIB / NO

CHANGE

USE GROUP EXIST B & A-2 / NO CHANGE

FIRE SUPPRESSION NFPA 13 / NO CHANGE

BUILDING TO BE

EVALUATED USING

REPAIR OF ROOFTOP HVAC EQUIPMENT

BUILDING AREAS

BUILDING AREA IS EXISTING (154,877 SF) WITH NO CHANGE OCCURING.

BUILDING HEIGHT

BUILDING HEIGHT (74 FEET) AND NUMBER OF STORIES (4) ARE EXISTING WITH NO CHANGE.

* NOTE: PROJECT CONSISTS OF REPLACEMENT OF ROOFTOP MOUNTED HVAC UNITS. PER VEBC CHAPTER 2 DEFINITIONS, A REPAIR IS DEFINED AS "THE RECONSTRUCTION, REPLACEMENT OR RENEWAL OF ANY PART OF

AN EXISTING BUILDING FOR THE PURPOSE OF ITS MAINTENANCE OR TO CORRECT DAMAGE".

VEBC CHAPTER 5 REPAIRS

SECTION 501 GENERAL

501.1 SCOPE. REPAIRS, INCLUDING REPLACEMENT OF DAMAGED EQUIPMENT SHALL COMPLY WITH THE

REQUIREMENTS OF THIS CHAPTER

501.2 CONFORMANCE. THE WORK SHALL NOT MAKE THE BUILDING LESS CONFORMING THAN IT WAS BEFORE THE REPAIR WAS UNDERTAKEN. REPAIRS SHALL BE DONE IN A MANNER THAT MAINTAINES THE

FOLLOWING:

1. LEVEL OF FIRE PROTECTION THAT IS EXISTING.

2. LEVEL OF PROTECTION THAT IS EXISTING FOR THE MEANS OF EGRESS.

3. LEVEL OF ACCESSIBILITY THAT IS EXISTING.

SECTION 505 MECHANICAL

505.1 GENERAL. EXISTING MECHANICAL SYSTEMS UNDERGOING REPAIR SHALL NOT MAKE THE BUILDING

LESS CONFORMING THAN IT WAS BEFORE THE REPAIR WAS UNDERTAKEN.

M1.0

E1.0

DATE:

DESIGNED:

DRAWN:

CHECKED:

REVISIONS:

WRITTEN DIMENSIONS ON THESE DRAWINGS

SHALL TAKE PRECEDENCE OVER SCALED

DIMENSIONS. CONTRACTORS SHALL VERIFY

AND BE RESPONSIBLE FOR ALL

DIMENSIONS AND CONDITIONS ON THE JOB

AND THIS OFFICE MUST BE NOTIFIED OF

ANY VARIATION FROM THE DIMENSIONS AND

CONDITIONS SHOWN BY THESE DRAWINGS

IF

B

: 1

3/

/2

2:

:3

PM

2026-02-03

AAA

AAA

AAA

WORKING DRAWINGS

T0.1

COVER

SHEET

P R

O

JE

C T

N O

V D

O T

LO

C

K W

O O

D B

U

IL

D

IN

G

HV

AC

R

EP

LA

CE

M

EN

T

L

O C

K W

O O

D B

LV

D

, M

EC

H A

N

IC

SV

IL

LE

, V

A

P R

O

JE

C T

C O

D E

:5 0-

0-

DRAWING LIST

LOCATION MAP VICINITY MAP

IFB#: 160761

HVAC REPLACEMENT

VDOT LOCKWOOD BUILDING

9120 LOCKWOOD BLVD, MECHANICSVILLE, VA 23116

PROJECT NO.: 25144

PROJECT CODE:50-18130-095

T0.1 COVER SHEET

MECHANICAL

M0.1 GNRL NOTES, ABBR, SCHED. & DETAILS

M1.0 HVAC NEW WORK PLAN

M2.0 ROOFTOP UNITS 1 & 4 DRAWINGS

M2.1 ROOFTOP UNITS 2 & 3 DRAWINGS

M3.0 HVAC ROOFTOP UNIT CONTROLS

ELECTRICAL

E1.0 ELECTRICAL NEW WORK PLAN

E1.1 PANEL SCHEDULE

ARCHITECT

Architectural Partners 10 9th Street Lynchburg, Virginia 24504 434-846-8456 Gary E. Harvey, RA gary@architecturalpartners.com

OWNER/AGENCY

Virginia Department of Transportation 1401 E. Broad Street Richmond, Virginia, 23219 804-786-2775 Jeffrey Godfrey, VCCO Jeffrey.Godfrey@VDOT.Virginia.gov

THE DRAWINGS WITHIN THIS PACKAGE ARE INTENDED

TO BE PRINTED IN .

THESE DRAWINGS UTILIZE COLOR FOR MAXIMUM CLARITY

OF THE INFORMATION CONVEYED. SOME INFORMATION

MAY BE LOST IF PRINTED IN GRAYSCALE.

LL COFU LOR-

MECHANICAL & ELECTRICAL

Master Engineers & Designers 904 Lakeside Drive Lynchburg, Virginia 24501 434-846-1350 Grant Beasley, PE gbeasley@masterengineersinc.com

Rockingham Engineering PLLC 14 Whistle Lane Weyers Cave, VA 24486 540-453-4262 Winston Rhodes, PE winston@rockinghasmeng.com

1" = 40'-0"T0.1

1 SITE PLAN

0 40' 80' 120' 160'

1" = 40'

TN

ADDRESS:

9120 LOCKWOOD BLVD,

MECHANICSVILLE, VA 23116

HPBA COMPLIANCE STATEMENT

ASBESTOS DISCLOSURE STATEMENT

LEAD PAINT DISCLOSURE STATEMENT

DISPOSAL NOTE

A/E DISCLAIMER

THE BUILDING INDICATED IN THIS ROOFTOP HVAC REPLACEMENT WAS

NOT DESIGNED BY ARCHITECTURAL PARTNERS OR ANY OF THE

CONSULTANTS INVOLVED IN THIS CURRENT PROJECT. VALUES

PERTAINING TO HEIGHT, NUMBER OF STORIES, AREA, BUILDING

CONSTRUCTION TYPE OR OCCUPANCY CLASSIFICATION WERE

OBTAINED FROM EXAMINATION OF THE EXISTING CONSTRUCTION

DRAWINGS PROVIDED BY THE VIRGINIA DEPARTMENT OF

TRANSPORTATION. THESE VALUES ARE PRESENTED FOR INFORMATION

ONLY AND HAVE NOT BEEN VERIFIED BY ON-SITE OBSERVATION.

IN ACCORD WITH THE HIGH PERFORMANCE BUILDINGS ACT, THE BUILDING IS EXEMPT FROM

COMPLIANCE BECAUSE THE COST OF RENOVATIONS DOES NOT EXCEED 50% OF THE VALUE OF THE

BUILDING.

IN ACCORD WITH THE VIRGINIA ENERGY CONSERVATION CODE (VECC), THE BUILDING SHALL COMPLY WITH ASHRAE 90.1 -2019, 6.1.1.3.1 FOR DIRECT REPLACEMENT OF EXISTING HVAC EQUIPMENT.

STRUCTURAL LOADING

ROOF LIVE LOAD:

ROOF SNOW LOAD:

WIND DESIGN DATA:

WIND EXPOSURE CATEGORY:

RISK CATEGORY:

20 PSF UNREDUCED

GROUND SNOW LOAD 20 PSF

BASIC WIND SPEED 90 MPH

B

VALUE DESIGNATED AS IMPORTANCE FACTOR (IBC 2000). PER STRUCTURAL

DRAWINGS, BUILDING IS CATEGORY I (TRANSLATES TO RISK FACTOR II IN

VCC 2021)

ALL STRUCTURAL VALUES ARE PER THE EXISTING STRUCTURAL DRAWINGS DATED 10/27/04

ALL DEBRIS FROM DEMOLITION AND SCRAP BUILDING MATERIAL FROM NEW CONSTRUCTION SHALL BE DISPOSED OF AT AN APPROVED DISPOSAL SITE. THE CONTRACTOR MUST PROVIDE THE OWNER'S REPRESENTATIVE WITH A SIGNED APPROVAL NOTIFICATION FROM THE DISPOSAL SITE PRIOR TO DISPOSAL OF ANY MATERIALS. THE NOTIFICATION MUST INDICATE THAT THE MATERIALS FROM THE SITE WILL BE

ACCEPTED AND DISPOSAL IS IN ACCORDANCE WITH APPLICABLE REGULATIONS.

AN ASBESTOS INSPECTION WAS NOT PERFORMED BECAUSE ALL PORTIONS OF THE EXISTING BUILDING THAT MAY BE AFFECTED BY THE WORK WERE ORIGINALLY CONSTRUCTED AFTER JANUARY 1, 1985

AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS NOT BEEN CONDUCTED BECAUSE THE BUILDING WAS CONSTRUCTED AFTER JANUARY 1, 1985 AND THE OWNER HAS NO KNOWLEDGE OF LEAD CONTAINING OR COATED BUILDING COMPONENTS IN THE BUILDING. IT IS THE CONTRACTOR’S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED

BUILDING COMPONENTS SHALL BE RECYCLED TO THE EXTENT POSSIBLE

ARCHITECTURAL PARTNERS, P.C. ASSUMES NO RESPONSIBILITY FOR THE ADEQUACY OR ACCURACY OF THE ASBESTOS AND LEAD BASED PAINT INFORMATION PROVIDED BY THE OWNER. THE CONTRACTOR SHALL

ADDRESS ANY RELATED QUESTIONS TO THE OWNER'S PROJECT MANAGER.

CONDENSATE TRAP DETAIL (ROOFTOP UNITS)

INDIRECT DRAIN TO ROOF DRAIN DETAILFLAT ROOF CURB DETAIL

DATE:

DESIGNED:

DRAWN:

CHECKED:

REVISIONS:

WORKNG DRAWINGS

P R

O

JE

C T

N O

V D

O T

LO

C

K W

O O

D B

U

IL

D

IN

G

HV

AC

RE

PL

AC

EM

EN

T

L O

C K

W O

O D

B

LV

D , M

EC

H

A N

IC

SV

IL

LE

, V A

P

R O

JE

C

T C

O D

E :5

0-

0-

IF

B

: 1

4-

6-

F ax

: 4

-8

-1

La ke sid e Dr ive , L yn ch bu rg

, V A

3-

12-18-2025

ETO/WR

ETO

WR

M0.1

GNRL NOTES,

ABBR., SCHED.

& DETAILS

HVAC NEW WORK PARTIAL ROOF PLAN

NORTH

PLAN NOTES

DATE:

DESIGNED:

DRAWN:

CHECKED:

REVISIONS:

WORKNG DRAWINGS

P R

O

JE

C T

N O

V D

O T

LO

C

K W

O O

D B

U

IL

D

IN

G

HV

AC

RE

PL

AC

EM

EN

T

L O

C K

W O

O D

B

LV

D , M

EC

H

A N

IC

SV

IL

LE

, V A

P

R O

JE

C

T C

O D

E :5

0-

0-

IF

B

: 1

4-

6-

F ax

: 4

-8

-1

La ke sid e Dr ive , L yn ch bu rg

, V A

3-

12-18-2025

ETO/WR

ETO

WR

M1.0

HVAC NEW

WORK PLAN

GENERAL NOTES

DATE:

DESIGNED:

DRAWN:

CHECKED:

REVISIONS:

WORKNG DRAWINGS

P R

O

JE

C T

N O

V D

O T

LO

C

K W

O O

D B

U

IL

D

IN

G

HV

AC

RE

PL

AC

EM

EN

T

L O

C K

W O

O D

B

LV

D , M

EC

H

A N

IC

SV

IL

LE

, V A

P

R O

JE

C

T C

O D

E :5

0-

0-

IF

B

: 1

4-

6-

F ax

: 4

-8

-1

La ke sid e Dr ive , L yn ch bu rg

, V A

3-

12-18-2025

ETO/WR

ETO

WR

M2.0

ROOFTOP

UNITS 1 & 4

DRAWINGS

module A

1 - 2" D/W CASING

2 - OA HOOD W/ 4" LOUVER W/ AFMS W/ DAMPER

3 - 4" ECONOMIZER LOUVER W/ DAMPER

4 - MIXING / RECIRCULATION DAMPER

5 - 2"+12" OA FILTERS

CE: CONTROLS ENTRANCE

POWER ENTRANCE

THIS DRAWING IS FOR PRELIMINARY PURPOSE ONLY, ANNEXAIR RESERVED THE RIGHT TO CHANGE DESIGN AND COMPONENTS WITHOUT NOTICE. ONLY AT THE SUBMITTAL STAGE DIMENSIONS & WEIGHT WILL BE CONFIRMED

REP. :

REV.:

TAG :

MODEL :

BY :

DATE :

DWG. :

App.:

RTU-4

S-31454 12-12-2025

AHUE-40-DX-AZC140.3-CA-4-M-T

Hobbs & Associates - Richmond

DH

LG

TL

CONCRETE PAD

(BY OTHERS) FLOOR CROSS BEAM

LIFTING LUGS

UNIT BASE FLOOR

UNIT WALLS & DOORS

2" COMPOSITE PANEL WALL

UNIT FLOOR

2" COMPOSITE PANEL

158.5 47 208 63

EA

EA

ECONO

Min. OA

SA RA

CE Ø2

PE 8X10

PWR

Annexair

CTRL

Annexair

6 - DX COIL (QTY 2) 60H X 94L

7 - SA DDF (QTY 6) 500 W/ 9.6 kW EACH

8 - RA DDF (QTY 6) 500 W/ 4.6 kW EACH

9 - 2" EA LOUVER W/ DAMPER

10 - ACU AZC140.3

108 MC

to remove

PLAN VIEW components

ELEVATION VIEW

module B

PLAN VIEWS

THIS DRAWING IS FOR PRELIMINARY PURPOSE ONLY, ANNEXAIR RESERVED THE RIGHT TO CHANGE DESIGN AND COMPONENTS WITHOUT NOTICE. ONLY AT THE SUBMITTAL STAGE DIMENSIONS & WEIGHT WILL BE CONFIRMED

REP. :

REV.:

TAG :

MODEL :

BY :

DATE :

DWG. :

App.:

O A

: O U

TD

O

O R

A

IR

SA

SU

PP

LY

A

IR

R

A : R

ET

U

R N

A

IR

EA

EX

H

AU

ST

A

IR

M C

M

IN

IM

U M

C

LE

AR

AN

C E

SW

IT

C H

: S G

FI

: O

PRELIMINARY / VDOT Lockwood

RTU-1 & 4

S-31454 12-12-2025

AHUE-40-DX-AZC140.3-CA-4-M-T

Hobbs & Associates - Richmond

DH

LG

TL

RTU-4

EA

ECONO

Min. OA

PLAN VIEW

EA 115

ECONO

Min. OA

PRELIMINARY / VDOT Lockwood

O A

: O U

TD

O

O R

A

IR

SA

SU

PP

LY

A

IR

R

A : R

ET

U

R N

A

IR

EA

EX

H

AU

ST

A

IR

M C

M

IN

IM

U M

C

LE

AR

AN

C E

SW

IT

C H

: S G

FI

: O

THIS DRAWING IS FOR PRELIMINARY PURPOSE ONLY, ANNEXAIR RESERVED THE RIGHT TO CHANGE DESIGN AND COMPONENTS WITHOUT NOTICE. ONLY AT THE SUBMITTAL STAGE DIMENSIONS & WEIGHT WILL BE CONFIRMED

1 - 2" D/W CASING

2 - OA HOOD W/ 4" LOUVER W/ AFMS W/ DAMPER

3 - 4" ECONOMIZER LOUVER W/ DAMPER

4 - MIXING / RECIRCULATION DAMPER

5 - 2"+12" OA FILTERS

CE: CONTROLS ENTRANCE

POWER ENTRANCE

REP. :

REV.:

TAG :

MODEL :

BY :

DATE :

DWG. :

App.:

O A

: O U

TD

O

O R

A

IR

SA

SU

PP

LY

A

IR

R

A : R

ET

U

R N

A

IR

EA

EX

H

AU

ST

A

IR

M C

M

IN

IM

U M

C

LE

AR

AN

C E

SW

IT

C H

: S G

FI

: O

PRELIMINARY / VDOT Lockwood

RTU-1

S-31454 12-12-2025

AHUE-40-DX-AZC128.3-CA-4-M-T

Hobbs & Associates - Richmond

DH

LG

TL

6 - DX COIL (QTY 2) 60H X 94L

7 - SA DDF (QTY 6) 500 W/ 9.6 kW EACH

8 - RA DDF (QTY 6) 500 W/ 4.6 kW EACH

9 - 2" EA LOUVER W/ DAMPER

10 - ACU AZC128.3

module A

CONCRETE PAD

(BY OTHERS) FLOOR CROSS BEAM

LIFTING LUGS

UNIT BASE FLOOR

UNIT WALLS & DOORS

2" COMPOSITE PANEL WALL

UNIT FLOOR

2" COMPOSITE PANEL

1581 472 208 63

EA

EA

ECONO

Min. OA

SA RA

CE Ø2

PE 8X10

PWR

Annexair

CTRL

Annexair

108 MC

to remove components

PLAN VIEW

ELEVATION VIEW

module B

DRAWN:

CHECKED:

REVISIONS:

WORKNG DRAWINGS

P R

O

JE

C T

N O

V D

O T

LO

C

K W

O O

D B

U

IL

D

IN

G

HV

AC

RE

PL

AC

EM

EN

T

L O

C K

W O

O D

B

LV

D , M

EC

H

A N

IC

SV

IL

LE

, V A

P

R O

JE

C

T C

O D

E :5

0-

0-

IF

B

: 1

4-

6-

F ax

: 4

-8

-1

La ke sid e Dr ive , L yn ch bu rg

, V A

3-

12-18-2025

ETO/WR

ETO

WR

M2.1

ROOFTOP

UNITS 2 & 3

DRAWINGS

1 - 2" D/W CASING

2 - OA HOOD W/ 4" LOUVER W/ AFMS W/ DAMPER

3 - 4" ECONOMIZER LOUVER W/ DAMPER

4 - MIXING / RECIRCULATION DAMPER

5 - 2"+12" OA FILTERS

CE: CONTROLS ENTRANCE

POWER ENTRANCE

THIS DRAWING IS FOR PRELIMINARY PURPOSE ONLY, ANNEXAIR RESERVED THE RIGHT TO CHANGE DESIGN AND COMPONENTS WITHOUT NOTICE. ONLY AT THE SUBMITTAL STAGE DIMENSIONS & WEIGHT WILL BE CONFIRMED

REP. :

REV.:

TAG :

MODEL :

BY :

DATE :

DWG. :

App.:

O A

: O U

TD

O

O R

A

IR

SA

SU

PP

LY

A

IR

R

A : R

ET

U

R N

A

IR

EA

EX

H

AU

ST

A

IR

M C

M

IN

IM

U M

C

LE

AR

AN

C E

SW

IT

C H

: S G

FI

: O

PRELIMINARY / VDOT Lockwood

RTU-3

S-31454 12-12-2025

AHUE-30-DX-AZC92.2-CA-4-M-T

Hobbs & Associates - Richmond

DH

LG

TL

CONCRETE PAD

(BY OTHERS) FLOOR CROSS BEAM

LIFTING LUGS

UNIT BASE FLOOR

UNIT WALLS & DOORS

2" COMPOSITE PANEL WALL

UNIT FLOOR

2" COMPOSITE PANEL

47 117163 208 2

EA

EA

ECONO

Min. OA

RA SA

PWR CE Ø2Annexair

CTRL

Annexair

6 - DX COIL 90H X 92L

7 - SA DDF (QTY 4) 560 W/ 9.6 kW EACH

8 - RA DDF (QTY 6) 500 W/ 4.6 kW EACH

9 - 2" EA LOUVER W/ DAMPER

10 - ACU AZC92.2

97 MC

to remove components PLAN VIEW

ELEVATION VIEW

PE Ø314

PLAN VIEWS

THIS DRAWING IS FOR PRELIMINARY PURPOSE ONLY, ANNEXAIR RESERVED THE RIGHT TO CHANGE DESIGN AND COMPONENTS WITHOUT NOTICE. ONLY AT THE SUBMITTAL STAGE DIMENSIONS & WEIGHT WILL BE CONFIRMED

RTU-2

EA

ECONO

Min. OA

REP. :

REV.:

TAG :

MODEL :

BY :

DATE :

DWG. :

App.:

O A

: O U

TD

O

O R

A

IR

SA

SU

PP

LY

A

IR

R

A : R

ET

U

R N

A

IR

EA

EX

H

AU

ST

A

IR

M C

M

IN

IM

U M

C

LE

AR

AN

C E

SW

IT

C H

: S G

FI

: O

PRELIMINARY / VDOT Lockwood

RTU-2 & 3

S-31454 12-12-2025

AHUE-30-DX-AZC92.2-CA-4-M-T

Hobbs & Associates - Richmond

DH

LG

TL

RTU-3

EA

ECONO

Min. OA

PLAN VIEW

THIS DRAWING IS FOR PRELIMINARY PURPOSE ONLY, ANNEXAIR RESERVED THE RIGHT TO CHANGE DESIGN AND COMPONENTS WITHOUT NOTICE. ONLY AT THE SUBMITTAL STAGE DIMENSIONS & WEIGHT WILL BE CONFIRMED

CONCRETE PAD

(BY OTHERS) FLOOR CROSS BEAM

LIFTING LUGS

UNIT BASE FLOOR

UNIT WALLS & DOORS

2" COMPOSITE PANEL WALL

UNIT FLOOR

2" COMPOSITE PANEL

PLAN VIEW

ELEVATION VIEW

86 EA

ECONO

Min. OA

CE Ø2

PWR

Annexair

CTRL

Annexair

98 MC

to remove components

PE Ø314

62 168 37 120

EA

RA SA

1 - 2" D/W CASING

2 - OA HOOD W/ 4" LOUVER W/ AFMS W/ DAMPER

3 - 4" ECONOMIZER LOUVER W/ DAMPER

4 - MIXING / RECIRCULATION DAMPER

5 - 2"+12" OA FILTERS

CE: CONTROLS ENTRANCE

POWER ENTRANCE

6 - DX COIL 90H X 92L

7 - SA DDF (QTY 4) 560 W/ 9.6 kW EACH

8 - RA DDF (QTY 4) 500 W/ 4.6 kW EACH

9 - 2" EA LOUVER W/ DAMPER

10 - ACU AZC108.2

REP. :

REV.:

TAG :

MODEL :

BY :

DATE :

DWG. :

App.:

O A

: O U

TD

O

O R

A

IR

SA

SU

PP

LY

A

IR

R

A : R

ET

U

R N

A

IR

EA

EX

H

AU

ST

A

IR

M C

M

IN

IM

U M

C

LE

AR

AN

C E

SW

IT

C H

: S G

FI

: O

PRELIMINARY / VDOT Lockwood

RTU-2

S-31454 12-12-2025

AHUE-30-DX-AZC108.2-CA-4-M-T

Hobbs & Associates - Richmond

DH

LG

TL

ROOFTOP UNIT CONTROLS

DESIGNED:

DRAWN:

CHECKED:

REVISIONS:

WORKNG DRAWINGS

P R

O

JE

C T

N O

V D

O T

LO

C

K W

O O

D B

U

IL

D

IN

G

HV

AC

RE

PL

AC

EM

EN

T

L O

C K

W O

O D

B

LV

D , M

EC

H

A N

IC

SV

IL

LE

, V A

P

R O

JE

C

T C

O D

E :5

0-

0-

IF

B

: 1

4-

6-

F ax

: 4

-8

-1

La ke sid e Dr ive , L yn ch bu rg

, V A

3-

12-18-2025

ETO/WR

ETO

WR

M3.0

HVAC

ROOFTOP UNIT

CONTROLS

SP CO2 (NET)

CND OVRFL (BI)

SAF (AO)

SA SD (HDW)

OAT (AI)

RTN (BI) RAD (AO)

OAH (AI) CMP2 (BO)

RAT (AI)

SAF (BO)

R PPM (AI)

CMP5 (BO)

OAD (AO)

RTN (AO)

FROSTAT (BI)OA FLW (AI)

CMP3 (BO)

SAF (BI)

CMP4 (BO)

RAH (AI)

FIL (BI) DAT (AI)

RTN (BO)

DA SP (AI)

CMP1 (AO)

RA SD (HDW)

CCT (AI)

RLF

OA

D - 3

HDW - 19HDW - 18

D - 18

D - 6

HDW - 14 HDW - 15

HDW - 30

CO2 - 6

HDW - 3

DA

RA

S - 1 VFD - 3

SD - 2

T - 23

ACT - 2

DPS - 8

ACT - 6

H - 4

R - 7

T - 21

R - 12

RM - 1

R - 10

ACT - 4

VFD - 1

LLT - 1AFS - 1

R - 8

DPS - 4

R - 9

H - 3

DPS - 14

T - 32

R - 18

DPT - 7

SIG - 1

SD - 1

T-41 AFS - 1

AFS - 1

SEQUENCE OF OPERATION (TYP FOR ALL ROOFTOP UNITS)

SP P (AI)

POINTS LIST

DPT - 1 HDW - 2

HDW - 2

NORTH

NEW WORK NOTES

ELECTRICAL DEMOLITION PARTIAL ROOF PLAN

DATE:

DESIGNED:

DRAWN:

CHECKED:

REVISIONS:

WORKNG DRAWINGS

P R

O

JE

C T

N O

V D

O T

LO

C

K W

O O

D B

U

IL

D

IN

G

HV

AC

RE

PL

AC

EM

EN

T

L O

C K

W O

O D

B

LV

D , M

EC

H

A N

IC

SV

IL

LE

, V A

P

R O

JE

C

T C

O D

E :5

0-

0-

IF

B

: 1

4-

6-

F ax

: 4

-8

-1

La ke sid e Dr ive , L yn ch bu rg

, V A

3-

12-19-2025

MGB

NAV

MGB

E1.0

ELECTRICAL NEW WORK PARTIAL ROOF PLAN

NORTH

DEMOLITION NOTES

ELECTRICAL

DEMO & NEW

WORK PLAN

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

RTU-1

AutoCAD SHX Text

RTU-2

AutoCAD SHX Text

RTU-3

AutoCAD SHX Text

RTU-4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

RTU-1

AutoCAD SHX Text

RTU-2

AutoCAD SHX Text

RTU-3

AutoCAD SHX Text

RTU-4

AutoCAD SHX Text

PANEL L4A

AutoCAD SHX Text

PANEL L4B

AutoCAD SHX Text

ON LEVEL BELOW (SECTION 2)

AutoCAD SHX Text

ON LEVEL BELOW (SECTION 2)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text RECONNECT POWER AND CONTROL WIRING TO NEW UNIT. APPROXIMATE LOCATION OF EXISTING POINT OF WIRING TERMINATION IS SHOWN. INSTALL 24" X 24" X 6" JUNCTION BOX IN ACCESSIBLE LOCATION TO EXTEND WIRING TO NEW UNIT POINT OF POWER AND CONTROL WIRING TERMINATION. TERMINATE IN FUSED DISCONNECT SWITCH PROVIDED WITH THE UNIT. UTILIZE THE SAME WIRE SIZE AS THE EXISTING UNITS FOR EXTENSION TO THE NEW UNIT. SIZE OF EXISTING POWER WIRING AND CONDUIT IS SHOWN ON THE SCHEDULE IN THIS SHEET. PROVIDE NEW BRANCH CIRCUIT TO RECEPTACLE, INTEGRAL TO NEW UNIT. PROVIDE FROM SPARE 20-AMP BREAKER IN PANEL “L4A (SECTION 2)” AND UTILIZE #12 WIRING. L4A (SECTION 2)” AND UTILIZE #12 WIRING. AND UTILIZE #12 WIRING. PROVIDE NEW BRANCH CIRCUIT TO RECEPTACLE, INTEGRAL TO NEW UNIT. PROVIDE FROM SPARE 20-AMP BREAKER IN PANEL “L4B (SECTION 2)” AND UTILIZE #12 WIRING. L4B (SECTION 2)” AND UTILIZE #12 WIRING. AND UTILIZE #12 WIRING. PROVIDE WIRING TO SUPPLY AND RETURN SMOKE DETECTORS, PROVIDED WITH NEW UNIT. INTERFACE TO EXISTING FIRE ALARM SYSTEM. DISCONNECT EXISTING LIGHTNING PROTECTION CONDUCTOR FROM EXISTING UNIT. RECONNECT TO NEW UNIT.

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text 3/32"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

WRITTEN DIMENSIONS ON THESE DRAWINGS

AutoCAD SHX Text

SHALL TAKE PRECEDENCE OVER SCALED

AutoCAD SHX Text

DIMENSIONS. CONTRACTORS SHALL VERIFY

AutoCAD SHX Text

AND BE RESPONSIBLE FOR ALL

AutoCAD SHX Text

DIMENSIONS AND CONDITIONS ON THE JOB

AutoCAD SHX Text

AND THIS OFFICE MUST BE NOTIFIED OF

AutoCAD SHX Text

ANY VARIATION FROM THE DIMENSIONS AND

AutoCAD SHX Text

CONDITIONS SHOWN BY THESE DRAWINGS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MICHAEL G. BEASLEY JR.

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text Lic. No. 057808

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text F

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text W

AutoCAD SHX Text E

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text 3/32"=1'-0"

AutoCAD SHX Text

GRAPHIC SCALE

AutoCAD SHX Text 8'

AutoCAD SHX Text 3/32" = 1'-0"

AutoCAD SHX Text 16'

AutoCAD SHX Text 24'

AutoCAD SHX Text 32'

AutoCAD SHX Text 0'

AutoCAD SHX Text 8'

AutoCAD SHX Text

AutoCAD SHX Text DISCONNECT POWER AND CONTROL WIRING FROM EXISTING UNIT. APPROXIMATE LOCATION OF EXISTING POINT OF WIRING TERMINATION IS SHOWN.

DRAWN:

CHECKED:

REVISIONS:

WORKNG DRAWINGS

P R

O

JE

C T

N O

V D

O T

LO

C

K W

O O

D B

U

IL

D

IN

G

HV

AC

RE

PL

AC

EM

EN

T

L O

C K

W O

O D

B

LV

D , M

EC

H

A N

IC

SV

IL

LE

, V A

P

R O

JE

C

T C

O D

E :5

0-

0-

IF

B

: 1

4-

6-

F ax

: 4

-8

-1

La ke sid e Dr ive , L yn ch bu rg

, V A

3-

12-19-2025

MGB

NAV

MGB

E1.1

PANEL

SCHEDULES

AutoCAD SHX Text

WRITTEN DIMENSIONS ON THESE DRAWINGS

AutoCAD SHX Text

SHALL TAKE PRECEDENCE OVER SCALED

AutoCAD SHX Text

DIMENSIONS. CONTRACTORS SHALL VERIFY

AutoCAD SHX Text

AND BE RESPONSIBLE FOR ALL

AutoCAD SHX Text

DIMENSIONS AND CONDITIONS ON THE JOB

AutoCAD SHX Text

AND THIS OFFICE MUST BE NOTIFIED OF

AutoCAD SHX Text

ANY VARIATION FROM THE DIMENSIONS AND

AutoCAD SHX Text

CONDITIONS SHOWN BY THESE DRAWINGS

AutoCAD SHX Text

MICHAEL G. BEASLEY JR.

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text Lic. No. 057808

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text F

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text W

AutoCAD SHX Text E

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text I

AutoCAD SHX Text N

423-335 HVAC Working.pdf
Sheets and Views
423-335 HVAC-M0.1
423-335 HVAC-M1.0
423-335 HVAC-M2.0
423-335 HVAC-M2.1
423-335 HVAC-M3.0
Untitled Extract Pages.pdf
423-335 Electrical Working Drawings.pdf
Sheets and Views
423-335 E1.0-E1.0
423-335 E1.0-E1.1