4 - Drawing.pdf

PDF 9 MB Posted

Attached to
Fire Alarm System Field Device Upgrade at FDC SeaTac Federal contract opportunity
Solicitation number
15B61120B00000002
Issued by
Department of Justice Bureau of Prisons Field Acquisition Office

About this file

This document package includes drawings and specifications for a fire alarm system field device upgrade project, as well as a related federal contract opportunity notice. The project consists of upgrading fire alarm system field devices at the Federal Detention Center in SeaTac, Washington, and includes furnishing all necessary labor, equipment, and materials. The performance period is 240 calendar days from notice to proceed. The solicitation will be awarded as a firm-fixed-price construction contract with an estimated value between $250,000 and $500,000 by the Federal Bureau of Prisons. Interested vendors must register in beta.SAM.gov as a small business to qualify for this 100% small business set-aside. The NAICS code for the project is 238210 with a $16.5 million size standard. The solicitation will be distributed solely through beta.SAM.gov and all future information will also be posted there.

View the file

Other files for this federal contract opportunity

Other files attached to Fire Alarm System Field Device Upgrade at FDC SeaTac, newest first.
File Type Posted
Bid Abstract.pdf PDF
AMEND 0001 SET.pdf PDF
Site Visit Pre Bid Meeting Minutes.pdf PDF
Questions and Answer.pdf PDF
6 - Construction Wage Rate 11062020.pdf PDF
6 - SF24 Bid Bond.pdf PDF
5 - Construction Wage Rate.pdf PDF
7 - Criminal History Check Form.pdf PDF
1 - Instructions to Bidders.pdf PDF
3 - Statement of Work.pdf PDF
2 - Solicitation.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LLC and shall be handled as proprietary and confidential information and must be returned upon request. This document cannot be reproduced by any means without the written authorization of

Convergint Technologies LLC.

450 Shattuck Avenue South, Renton, Washington 98057

Phone: 425-272-2250 Fax: 425-251-0949

R

DATE:SCALE:

DRAWING:

APPROVED

DRAWN BY:

JOB NUMBER:

PROJECT MANAGER:

PROJECT ENGINEER:

REV DESCRIPTION DATE

FA-0-1

GSFDC

SEATAC, WA 98199

TITLE, INDEX, LEGEND

SHEET

FIRE ALARM SYSTEM

1) ALL WIRE AND CONDUIT MUST BE INSTALLED IN ACCORDANCE WITH PLANS AND SPECIFICATIONS, AND MUST MEET ALL APPLICABLE CODES.

2) ALL WIRE AND CABLE MUST BE RATED FOR FIRE ALARM USE PER THE LATEST REVISIONS OF THE NATIONAL ELECTRICAL CODE SECTION 760. THIS IS A POWER LIMITED FIRE ALARM SYSTEM, ALL CABLE

MUST BE MARKED FPL, FPLR, CI OR FPLP .

3) ALL CONDUCTORS MUST TEST FREE OF GROUND BEFORE MAKING CONNECTION TO THE FIRE ALARM

CONTROL PANEL.

4) TO RETAIN WARRANTY, THE FIRE ALARM EQUIPMENT MUST BE POWERED UP UNDER THE DIRECTION

OF A QUALIFIED MANUFACTURERS TECHNICIAN.

5) THE LIFE SAFETY SYSTEM IS A COMPLETELY SUPERVISED SYSTEM.

6) INSTALLING ELECTRICAL CONTRACTOR SHALL COORDINATE ALL FIELD CHANGES WITH THE FIRE ALARM CONTRACTOR INCLUDING CHANGES IN DEVICES, WIRE, CONDUIT RUNS AND OPERATION IN THE

SYSTEM. FIRE ALARM CONTRACTOR SHALL NOT BE HELD RESPONSIBLE FOR UNDOCUMENTED

CHANGES, OR THE RESULTS CAUSED BY THOSE CHANGES.

7) LIFE SAFETY AUDIBLE SHALL BE AUDIBLE THROUGHOUT THE SPACE AND SHALL HAVE A SOUND PRESSURE LEVEL NOT LESS THAN 15db ABOVE AMBIENT NOISE LEVEL MEASURED AT 4'0" ABOVE

FINISHED FLOOR.

8) MAIN BUILDING FIRE ALARM & SUPPRESSION SYSTEMS SHALL BE CLASS "B" IN CONFIGURATION.

PRE-ACTION & DELUGE ALARM SYSTEMS SHALL BE CLASS "A" IN CONFIGURATION. CLASS "A"

APPLICATIONS SHALL MAINTAIN A MINIMUM SEPARATION OF 4 FEET BETWEEN FEED AND RETURN

CIRCUITS.

9) LOCATE ALL PULL STATIONS AND HORN/STROBE UNITS AT SPECIFIED HEIGHTS PER NFPA 72 AND ADA

SEE DETAIL SHEET.

10) SMOKE DETECTOR LOCATIONS ARE FOR REFERENCE ONLY AND SHALL BE INSTALLED PER NFPA 72.

11) ELECTRICAL CONTRACTOR SHALL COORDINATE ALL ROUGH-IN INSTALLATION WITH THE FIRE ALARM

CONTRACTOR.

12) SMOKE DETECTORS ON CEILINGS MUST BE NO MORE THAN 15' FROM A WALL AND/OR NO MORE THAN 30' FROM EACH OTHER. REDUCED SPACING MAY ALSO BE REQUIRED. SEE PLAN DRAWINGS FOR

PROJECT-SPECIFIC LOCATIONS.

13) ALL FIRE ALARM DEVICES SHALL BE RIGIDLY AND SECURELY FASTENED TO WALLS OR CEILINGS.

14) NO SMOKE DETECTOR SHALL BE LOCATED CLOSER THAN 36" TO ANY AIR REGISTER OR DIFFUSER.

15) NO HEAT DETECTOR SHALL BE LOCATED CLOSER THAN 24" TO ANY AIR REGISTER OR DIFFUSER.

16) NO HEAT DETECTOR SHALL BE LOCATED CLOSER THAN 36" TO ANY PART OF ANY HEAT GENERATING

DEVICE (FUSES, BOILERS, WATER HEATERS, ETC.) IN MECHANICAL ROOMS.

17) NO HEAT DETECTOR SHALL BE LOCATED CLOSER THAN 18" TO ANY PART OF ANY LIGHT FIXTURE.

18) INITIATING AND SIGNALING CIRCUITS ARE SEPARATE YET MAY BE RUN IN SAME CONDUIT.

19) ALL CONDUCTORS SHALL BE LABELED BY ZONE AND ALL COLOR CODES SHALL MATCH.

20) DEVICES THAT ARE UNABLE TO BE INSTALLED PERMANENTLY DURING DEVICE TRIM SHALL BE SPLICED THROUGH TO ALLOW DEVICES AND CIRCUIT DOWNSTREAM TO BE PRE-TESTED. THIS INCLUDES ALL CIRCUITS (SPEAKER CIRCUITS, STROBE CIRCUITS, ADDRESSABLE LOOP CIRCUITS, 24VDC CIRCUITS, FIREFIGHTERS TELEPHONE CIRCUITS, ETC.)

21) THESE DRAWINGS DO NOT SUPERSEDE THE CONTRACT DRAWINGS AND SPECIFICATIONS, THEY ARE

INTENDED AS A SUPPLEMENT ONLY AND MUST BE USED IN CONJUNCTION WITH THE CONTRACT

DOCUMENTS. THEY DO NOT MODIFY THE CONTRACTORS OBLIGATIONS TO CONFORM TO THE

PROJECTS ORIGINAL DESIGN CRITERIA.

FIRE

HS

RECORD DRAWINGS

shall be handled as proprietary and confidential information and must be returned upon request. This document cannot be reproduced by any means without the written authorization of

Convergint Technologies LLC.

450 Shattuck Avenue South, Renton, Washington 98057

Phone: 425-272-2250 Fax: 425-251-0949

R

DATE:SCALE:

DRAWING:

APPROVED

DRAWN BY:

JOB NUMBER:

PROJECT MANAGER:

FA-2-1

RISER DRAWING

shall be handled as proprietary and confidential information and must be returned upon request. This document cannot be reproduced by any means without the written authorization of

Convergint Technologies LLC.

450 Shattuck Avenue South, Renton, Washington 98057

Phone: 425-272-2250 Fax: 425-251-0949

R

DATE:SCALE:

DRAWING:

APPROVED

DRAWN BY:

JOB NUMBER:

PROJECT MANAGER:

FA-3-1

DETAILS

shall be handled as proprietary and confidential information and must be returned upon request. This document cannot be reproduced by any means without the written authorization of

Convergint Technologies LLC.

450 Shattuck Avenue South, Renton, Washington 98057

Phone: 425-272-2250 Fax: 425-251-0949

R

DATE:SCALE:

DRAWING:

APPROVED

DRAWN BY:

JOB NUMBER:

PROJECT MANAGER:

FA-7-1

CALCULATIONS

NOTE: PANEL SUPPORTED BY

WITH GENERATOR BACK-UP.

DEDICATED 120VAC CIRCUIT

NOTE: PANEL SUPPORTED BY

WITH GENERATOR BACK-UP.

DEDICATED 120VAC CIRCUIT

NOTE: PANEL SUPPORTED BY

WITH GENERATOR BACK-UP.

DEDICATED 120VAC CIRCUIT

NOTE: PANEL SUPPORTED BY

WITH GENERATOR BACK-UP.

DEDICATED 120VAC CIRCUIT

NOTE: PANEL SUPPORTED BY

WITH GENERATOR BACK-UP.

DEDICATED 120VAC CIRCUIT

NOTE: PANEL SUPPORTED BY

WITH GENERATOR BACK-UP.

DEDICATED 120VAC CIRCUIT

WRO Drawing Approval Project 6C3V November 15, 2018
FDC SeaTac Request for Drawing and SOW Review
Drawings (As-built) pg 8-47