36E77619R0025-005.pdf
PDF 17 MB Posted
- Attached to
- Construct Lab Addition Minor Construction Sioux Falls VAMC Federal contract opportunity
- Solicitation number
- 36E77619R0025
About this file
This pre-solicitation notice announces an upcoming Request for Proposal for the construction of a new laboratory addition at the Sioux Falls VA Medical Center. The project involves building a lab on the roof of an existing building between a recent addition and the coffee shop area, with an estimated value between $10 million and $20 million. The solicitation will be a total SDVOSB set-aside issued on April 23rd, 2019, with a 60-day response window. The project includes structural phases critical in the early stages and coordination in patient care areas. The work is to be design-bid-build and last approximately 450 calendar days from notice to proceed. Questions must be submitted in writing by the specified date.
36E77619R0025 ATTACHMENT 4 _ Final Drawings Volume 2 - 2-1-19.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36E77619C0056-000.docx | DOCX document | |
| 36E77619R0025-0004000.docx | DOCX document | |
| 36E77619R0025-0004001.docx | DOCX document | |
| 36E77619R0025-0003000.docx | DOCX document | |
| 36E77619R0025-0003001.docx | DOCX document | |
| 36E77619R0025-0002000.docx | DOCX document | |
| 36E77619R0025-0002001.docx | DOCX document | |
| 36E77619R0025-0001001.pdf | ||
| 36E77619R0025-0001002.pdf | ||
| 36E77619R0025-0001000.docx | DOCX document | |
| 36E77619R0025-003.pdf | ||
| 36E77619R0025-002.pdf | ||
| 36E77619R0025-004.pdf | ||
| 36E77619R0025-006.pdf | ||
| 36E77619R0025-007.docx | DOCX document | |
| 36E77619R0025-009.pdf | ||
| 36E77619R0025-001.docx | DOCX document | |
| 36E77619R0025-008.docx | DOCX document | |
| 36E77619R0025-000.docx | DOCX document | |
| 36E77619R0025-000.docx | DOCX document |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STORAGE
EE
CE
DE
11E22
2 1/2" CW
1 1/2" HW
3/4" HWC
4" SAN
WHA-1
1" CW UP
WC
1/2" HW UP
LAV
1/2" CW UP
WHA-1
WHA-1
WHA-1
WHA-1
WHA-1
1" CW
3" SAN
FD
1" CW UP
WC
3" SAN
1/2" HW UP
LAV
1/2" CW UP
1" CW UP
WC
1/2" HW UP
LAV
1/2" CW UP
FD
FD
1/2" CW
1/2" CW
1/2" CW
1/2" CW
1/2" CW
WHA-1
FD
WC
1 1/2" SAN
1 1/2" SAN
1 1/2" CW
1" HW
1/2" HWC
3/4" RO
8" STS UP
SV-1
WHA-1
FD
MB
LAV
LAV8" STS
8" STS
2 1/2" CW
1 1/2" HW
3/4" HWC
1 1/2" CW
3/4" CW
3/4" HW
1" CW
3/4" CW
3/4" HW
3/4" CW
1-1/2" V UP
1-1/2" V UP
1/2" HW UP
1/2" CW UP
LAV
1/2" CW UP
1/2" HW UP
3/4" RO
3/4" HWC
1 1/2" HW
2 1/2" CW
1/2" HW UP
1/2" CW UP
3/4" HW
3/4" CW
3/4" HWC
1 1/2" HW
2 1/2" CW
3/4" CW
3/4" HW
3/4" CW UP
3/4" HW UP
4" SAN
3/4" CW
3" SAN
4" SAN
4" SAN
4" SAN
4" SAN
3" SAN
4" SAN
1 1/2" SAN
4" SAN
1 1/2" SAN
3/4" CO2
3/4" CO2 UP
3/4" CW SUPPLY UP TO TP-2
1/2" DISCHARGE FROM TP-2 ABOVE (TYP. 5)
SV-12
2" D
2" D
1 1/2" CW
1 1/2" CW
3/4" HW
3" SAN
4" SAN
1 1/2" CW
CO3/4" CW
3/4" HW
GE
8E7E
FD
1 1/2" V UP
FCO
S A
N
3" SAN
WHA-1
WHA-1
FD
ESE/1 1/2" V UP
1 1/4" TW UP
SK
3/4" CW UP
3/4" HW UP
LAV
1/2" HW UP
1/2" CW UP
FS-2
LAV
1/2" HW UP
1/2" CW UP
FCO
MB
FD
1 1/2" V UP
1 1/2" V UP
3/4" CW SUPPLY UP TO TP-2
1/2" CW DISCHARGE FROM TP-2 ABOVE (TYP. 5)
3/4" HW UP
3/4" CW UP
0.8 GPM
FD
1 1/2" V UP
FCO
WC
1" CW UP
WC
1" CW UP
WC
1" CW UP
WHA-1
WHA-1
FD
WHA-1 1 1/2" V UP
2" SAN
2" SAN
3" SAN
3" SAN 4" SAN 4" SAN 4" SAN
10" ST
1/2" HWC
1" HW
2" CW
/4
C
W
MV-1
/2
C
W
/2
C
W
/2
C
W
10" ST
3/4" CW
3/4" HW
3/4" CW 2" CW
3/4" HW
1/2" HWC
C W
3" SAN 4" SAN
2" S
AN
3" SAN
3" SAN
LAV
1/2" HW UP
1/2" CW UP
1" CW UP
WC
FCO
1 1/2" TW
S A
N
4" SAN
LAV
1/2" CW UP
1/2" HW UP
LAV
1/2" CW UP
1/2" HW UP
BFP-1
UR
UR
3/4" CW
1 1/2" CW
1 1/2" CW
1" CW
/4
C
W
/4
H
W
/4
H
W
1/2" CW
3/4" CW
BY M.C.
BY P.C.
1" D UP
1" D
FE
EE
13E
FD
FD
FD
MV-1
FS-2
WHA-1
WHA-1
1/2" CW
1/2" CW
1 1/2" TW
1 1/4" TW UP
ESE
2" V DN
ROUTE TIGHT TO COLUMN
/4
H
W
/4
C
W
/4
C
W
/4
H
W
3/4" CW
2" V UP
1 1/2" V UP
LAV
1/2" CW UP
1/2" HW UP
1" CW UP
WC
1/2" CW UP
LAV
1/2" HW UP
1 1/2" CW
1" CW
1 1/2" V UP
3" SAN
1 1/2" TW
3/4" CW SUPPLY UP TO TP-1
1/2" CW DISCHARGE FROM TP-1 ABOVE (TYP. 3)
3/4" CW UP
SK
3/4" HW UP
3/4" RO UP
1 1/4" TW UP
ESE
1 1/2" V UP
3/4" HW UP
SK
3/4" CW UP
1 1/2" AW
2" CW
1" HW
1/2" HWC
2" CW
1" HW
1/2" HWC
1" CW 1" CW
1" HW
3/4" HW
1/2" HWC
3/4" HW
1" CW
3/4" CW
1/2" CW
3/4" HW
3" SAN
S A
N
S
A N
3" SAN
4" SAN
4" SAN
2" SAN
3" SAN
S T
S
3" AW
6" STS UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
01/11/2019
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
C R e v it L o c a l F ile s \M
E P
T
.0
V A
S
IO
U X
F A
L L S
L A
B A
D D
IT
IO
N k e it h
.m .p a d g e tt im e g c o rp .c o m
.r v t
/1
/2
:2
:2
A
M
P400
ENLARGED PLANS - PLUMBING CONSTRUCT LABORATORY
ADDITION
SIOUX FALLS, SOUTH DAKOTA
438-440
PETERN DELLLE
15 SUNNEN DR
SUITE 104
SAINT LOUIS, MO
63143
PH: 314.645.1132
FAX: 314.645.1173
www.imegcorp.com
N
O R HT
1/4" = 1'-0"1
1ST FLOOR PLAN - PLUMBING - ENLARGED PLAN
N
O R HT
1/4" = 1'-0"2
1ST FLOOR PLAN - PLUMBING - ENLARGED PLAN 2
N
O R HT
1/4" = 1'-0"3
1ST FLOOR PLAN - PLUMBING - ENLARGED PLAN 3
GENERAL NOTES :
1. REFER TO P000 - PLUMBING COVERSHEET -
FOR PLUMBING SYMBOLS LIST, ABBREVIATION
KEY, AND GENERAL NOTES.
2. EXISTING CONDITIONS ARE SHOWN BASED ON
INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS,
AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEDING.
3. COMPLETE LAYOUT DRAWINGS SHALL BE
REQUIRED BY SPECIFICATION SECTION 22 05
11. CONSTRUCTION WORK SHALL NOT BEGIN
UNTIL SYSTEM LAYOUT DRAWINGS HAVE BEEN
APPROVED BY THE COR.
4. REFER TO P401 FOR PLUMBING ISOMETRIC
DRAWINGS.
5. REFER TO P500 FOR PLUMBING MATERIAL LIST.
6. REFERENCE 8/P300 FOR WATER HAMMER
ARRESTER LOCATION DETAIL.
KEYNOTES:
1. MV-1 PROVIDED FOR EMERGENCY
SHOWER/EYEWASH ON FLOOR ABOVE. MOUNT
MIXING VALVE CABINET SECURELY TO
STRUCTURAL COLUMN OR FABRICATED ANGLE
IRON RACK. REFERENCE 1/P300 FOR
EMERGENCY SHOWER & EYEWASH DETAIL.
2. NORMALLY OPEN SOLENOID VALVES
PROVIDED FOR FIXTURES SERVING DRUG
TESTING RESTROOM ABOVE. VALVES SHALL
POWER CLOSED UPON ACTIVATION OF A
SINGLE SWITCH OUTSIDE OF RESTROOM ON
FLOOR ABOVE. REFERENCE P121 FOR
LOCATION OF SWITCH. PC SHALL PROVIDE
AND INSTALL SOLENOID VALVES; COORDINATE
ELECTRICAL REQUIREMENTS AND SWITCH
WITH EC.
3. OFFSET CONDENSATE DRAIN DOWN BELOW
STAIRS INTO PIT. ROUTE ALONG WALL TO
FLOOR SINK AT WEST END OF PIT.
4. ROUTE 1" DRAIN ALONG FLOOR TO FLOOR
SINK AND DISCHARGE INTO FLOOR SINK
THROUGH 45° ELBOW. REDUCE TRIPPING
HAZARD OF PIPE ON FLOOR AS MUCH AS
POSSIBLE BY ROUTING TIGHT TO PUMP
EQUIPMENT PADS.
Revisions: Date:
2 1/2" CW
1 1/2" HW
3/4" HWC
3" CW
2" HW
1" HWC
3/4" HWC
1 1/2" HW
2 1/2" CW
1 1/2" CW
1" HW
1/2" HWC
3/4" RO
2" CW
1" HW
1/2" HWC
BFP-1
WC-1
WC-1
WC-2
WC-3
L-1
L-1
L-1
L-1
MB-1
L-2
L-2
ESE-1
L-2
TP-1
WC-2
L-1
SK-3
SK-1
SK-3
MV-1 MV-1
L-2
ESE-1
SK-1
L-2
L-2
SK-3
SK-4
L-2
T-1
RO-1
ESE-1
TP-2
TP-1
SK-2
MB-1
WC-2
WC-1
WC-1
L-1
L-1
UR-2
UR-1
L-1
L-1
L-2
WC-2
BFP-4
1 1/2" TW
1 1/2" TW
FS-2
FD-2
SK-3
FS-2
FS-2
FD-1
FS-2
RD-1
RD-2
RD-2
RD-1
RD-1
RD-2
AGF-1
FCO-2
FCO-1
FCO-2
FD-1
RD-1
RD-2
SK-3
SK-3
SK-3
FCO-1
FCO-2
FCO-2
FCO-1
FD-1FCO-1
FCO-1
FD-1
WC-2
WC-1
WC-1
L-1
L-1
ESE-1
L-2
WC-2
UR-1
UR-2
L-1
L-1
MB-1
SK-2
NT-1
L-2
L-2
SK-4
FS-1
L-2
FD-1
FCO-1
ESE-1
L-2
L-2
WC-3
L-1 L-1
L-1
L-1WC-2
WC-1
WC-1
WC-2
L-1
L-2
ESE-1
6" ST
6" STS
FCO-1
UB-2
3" SAN
6" ST
2" V
2" V
L-2
3" SAN
8" STS
4" SAN
MB-1
4" AVTR
10" STS
4" AVTR
4" SAN
2" V
2" V
S A
N
4" S
AN
6" S T
6" ST
8" ST
6" ST
4" S
AN 4" SAN
V
1 1/2" V
8" STS
S T
S
2" V
/2
A V
6" ST
6" STS
10" ST
4" SAN
3" S
AN
A V
3" A W
2" AW
1 1/2" A V
3" AW
/2
A V
S A
N 4" SAN
1 1/2" S
AN
4" AVTR
4" VTR
1 1/2" V
1 1/2" V
2" SAN
/2
V
V
3" SAN
1 1/2" V
/2
V
1 1/2" V
V
V
V
V
2" V
3" SAN
V
3" SAN
4" S
AN
3" AW
1 1/2" AV
4" S
AN
3" AV CAPPED FOR
FUTURE EXTENSION
4" AVTR
4" VTR
4" VTR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
01/11/2019
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
C R e v it L o c a l F ile s \M
E P
T
.0
V A
S
IO
U X
F A
L L S
L A
B A
D D
IT
IO
N k e it h
.m .p a d g e tt im e g c o rp .c o m
.r v t
/1
/2
:2
:4
A
M
P401
PLUMBING ISOMETRIC VIEWS CONSTRUCT LABORATORY
ADDITION
SIOUX FALLS, SOUTH DAKOTA
438-440
PETERN DELLLE
15 SUNNEN DR
SUITE 104
SAINT LOUIS, MO
63143
PH: 314.645.1132
FAX: 314.645.1173
www.imegcorp.com
NO SCALE1
PLUMBING ISOMETRIC - PRESSURE SYSTEMS
GENERAL NOTES :
1. REFER TO P000 - PLUMBING COVERSHEET -
FOR PLUMBING SYMBOLS LIST, ABBREVIATION
KEY, AND GENERAL NOTES.
2. EXISTING CONDITIONS ARE SHOWN BASED ON
INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS,
AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEDING.
NO SCALE2
PLUMBING ISOMETRIC - GRAVITY SYSTEMS
KEYNOTES:
1. CW SUPPLY TO FLOOR DRAIN OR FLOOR SINK.
SEE FLOOR PLANS FOR ADDITIONAL
INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
01/11/2019
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
C R e v it L o c a l F ile s \M
E P
T
.0
V A
S
IO
U X
F A
L L S
L A
B A
D D
IT
IO
N k e it h
.m .p a d g e tt im e g c o rp .c o m
.r v t
/1
/2
:2
:4
A
M
P500
PLUMBING SCHEDULES CONSTRUCT LABORATORY
ADDITION
SIOUX FALLS, SOUTH DAKOTA
438-440
PETERN DELLLE
PLUMBING FIXTURE SCHEDULE
TAG NAME DESCRIPTION MANF. & MODEL
VB-1 VALVE BOX - EXTRUDED ALUMINUM WITH PLASTER FRAME, TEMPORARY PLASTER
GUARD, IDENTIFICATION COVER AND SHIELD. THE FINISH FRAME SHALL MOUNT TO
BOX WITH CONCEALED MOUNTING SCREWS.
PLACEMENT OF VALVE HANDLE WITHIN THE BOX SHALL BE SUCH THAT THE
EMERGENCY PLASTIC PULL-OUT WINDOW CANNOT BE REPLACED WITH THE VALVE
HANDLE IN THE "OFF" POSITION.
FACTORY INSTALLED TUBING SHALL EXTEND AT LEAST 3" BEYOND THE BOX, AND THE
VALVE BODY SHALL BE SWUNG OUT OF LINE OF HEAT TRANSFER, PERMITTING JOINT
TO BE BRAZED WITHOUT OBSTRUCTION OR HEAT DAMAGE TO VALVE. OPEN ENDS OF
TUBING SHALL BE CAPPED TO AVOID PREINSTALLATION CONTAMINATION.
A 1-1/2" DIAMETER LINE PRESSURE GAUGE SHALL BE SUPPLIED AND INSTALLED
DOWNSTREAM OF SHUTOFF VALVE.
VALVE SHALL BE PREPARED FOR OXYGEN SERVICE AND SHALL CONFORM TO NFPA
#99. ALL VALVES SHALL BE OF BALL-TYPE, WITH DOUBLE O-RING STEM SEAL AND
TEFLON BALL SEATING, MINIMUM WORKING PRESSURE OF 400 PSIG, ACTUATED FROM
FULL "ON" TO FULL "OFF" BY 90 DEGREE TURN OF VALVE HANDLE. IDENTIFY SERVICE
ON EACH VALVE HANDLE.
VALVE SHALL BE THE SAME SIZE AS THE PIPING ENTERING THE VALVE.
VALVE BOX SHALL CONTAIN CARBON DIOXIDE.
MANUFACTURER & CATALOG NO.:
BEACON/MEDAES, ALLIED
HEALTHCARE/CHEMETRON,
SQUIRE-COGSWELL/AEROS,
AMICO
WC-1 (VA FIXTURE P-103) WATER CLOSET - WALL MOUNTED, FLUSH VALVE TYPE, WHITE
VITREOUS CHINA, SIPHON JET, WATER SAVING, ELONGATED BOWL, 1-1/2" TOP SPUD.
FLUSH VALVE - EXPOSED, MANUAL OPERATION, 1.6 GALLONS PER FLUSH, 11-1/2"
ROUGH-IN, CHROME PLATED, 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH
VANDAL RESISTANT CAP, HIGH BACK PRESSURE VACUUM BREAKER, NON-HOLD-OPEN
HANDLE, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH
SET SCREW, CHLORAMINE RESISTANT MATERIALS, ADA COMPLIANT, 3 YEAR
WARRANTY.
SEAT - WHITE, EXTRA HEAVY, OPEN FRONT, INJECTION MOLDED SOLID ANTI-MICROBIAL
PLASTIC, SELF-SUSTAINING HINGE, STAINLESS STEEL OR PLATED STEEL POSTS AND
NUTS.
CONTRACTOR OPTION: COMBINATION WATER CLOSET/FLUSH VALVE PACKAGED
SYSTEM BY AMERICAN STANDARD, KOHLER, SLOAN, OR ZURN
ACCESSORIES - WATER CLOSET SUPPORT CARRIER RATED FOR 500 LBS.
MOUNT WATER CLOSET WITH CARRIER BOLTED SECURELY TO FLOOR. TOP OF SEAT
SHALL BE AT 16"-17" ABOVE FINISHED FLOOR (VERIFY EXACT MOUNTING HEIGHT WITH
MANUFACTURER). VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS.
WATER CLOSET -
AMERICAN STANDARD (2257.101),
GERBER, KOHLER, SLOAN, TOTO,
ZURN
FLUSH VALVE -
AMERICAN STANDARD (6047.161),
ZURN, SLOAN, KOHLER, TOTO,
DELANY
SEAT -
BEMIS (3155SSCT), CHURCH
(3155C), BENEKE (533PC),
OLSONITE (95), SAME AS WATER
CLOSET MANUFACTURER
WC-2 (VA FIXTURE P-103) WATER CLOSET - ACCESSIBLE, WALL MOUNTED, FLUSH VALVE
TYPE, WHITE VITREOUS CHINA, SIPHON JET, WATER SAVING, ELONGATED BOWL, 1-1/2"
TOP SPUD.
FLUSH VALVE - EXPOSED, MANUAL OPERATION, 1.6 GALLONS PER FLUSH, 11-1/2"
ROUGH-IN, CHROME PLATED, 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH
VANDAL RESISTANT CAP, HIGH BACK PRESSURE VACUUM BREAKER, NON-HOLD-OPEN
HANDLE, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH
SET SCREW, CHLORAMINE RESISTANT MATERIALS, ADA COMPLIANT, 3 YEAR
WARRANTY.
SEAT - WHITE, EXTRA HEAVY, OPEN FRONT, INJECTION MOLDED SOLID ANTI-MICROBIAL
PLASTIC, SELF-SUSTAINING HINGE, STAINLESS STEEL OR PLATED STEEL POSTS AND
NUTS.
CONTRACTOR OPTION: COMBINATION WATER CLOSET/FLUSH VALVE PACKAGED
SYSTEM BY AMERICAN STANDARD, KOHLER, SLOAN, OR ZURN
ACCESSORIES - WATER CLOSET SUPPORT CARRIER RATED FOR 500 LBS.
MOUNT WATER CLOSET WITH CARRIER BOLTED SECURELY TO FLOOR. TOP OF SEAT
SHALL BE AT 17"-19" ABOVE FINISHED FLOOR (VERIFY EXACT MOUNTING HEIGHT WITH
MANUFACTURER). VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS.
WATER CLOSET -
AMERICAN STANDARD (2257.101),
GERBER, KOHLER, SLOAN, TOTO,
ZURN
FLUSH VALVE -
AMERICAN STANDARD (6047.161),
ZURN, SLOAN, KOHLER, TOTO,
DELANY
SEAT -
BEMIS (3155SSCT), CHURCH
(3155C), BENEKE (533PC),
OLSONITE (95), SAME AS WATER
CLOSET MANUFACTURER
WC-3 (VA FIXTURE P-114) WATER CLOSET - FLOOR MOUNTED, ACCESSIBLE BARIATRIC,
FLUSH VALVE TYPE, WHITE VITREOUS CHINA, SIPHON JET, HIGH EFFICIENCY, EXTRA
WIDE ELONGATED BOWL, 1-1/2" TOP SPUD, BOLT CAPS, 2,000 LBS. LOAD RATING,
PLASTIC OPEN-FRONT SEAT.
FLUSH VALVE - EXPOSED, MANUAL OPERATION, 1.6 GALLONS PER FLUSH, 11-1/2"
ROUGH-IN, CHROME PLATED, 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH
VANDAL RESISTANT CAP, HIGH BACK PRESSURE VACUUM BREAKER, NON-HOLD-OPEN
HANDLE, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH
SET SCREW, CHLORAMINE RESISTANT MATERIALS, ADA COMPLIANT, 3 YEAR
WARRANTY.
TOP OF SEAT SHALL BE AT 17"-19" ABOVE FINISHED FLOOR. VERIFY EQUIPMENT
REQUIREMENTS AND ROUGH-IN LOCATIONS.
WATER CLOSET -
AMERICAN STANDARD (3641.001)
FLUSH VALVE -
AMERICAN STANDARD (6047.161),
ZURN, SLOAN, KOHLER, TOTO,
DELANY
WCO-1 WALL CLEANOUT - TEE, CAST IRON ACCESS BODY, GAS AND WATERTIGHT THREADED
PLUG, ROUND STAINLESS STEEL ACCESS COVER, EXTENDED MACHINE SCREW.
ZURN (Z-1446), SMITH, WADE,
JOSAM, WATTS
WHA-1 WATER HAMMER ARRESTER - BELLOWS TYPE, PRE-CHARGED, ALL LEAD FREE
STAINLESS STEEL CONSTRUCTION, ASSE 1010 APPROVED, PDI CERTIFIED.
REFERENCE 8/P300 FOR CAPACITY REQUIREMENTS.
ZURN (Z1700), JR SMITH, WADE,
JOSAM, WATTS, MIFAB
PLUMBING FIXTURE SCHEDULE
TAG NAME DESCRIPTION MANF. & MODEL
SK-1 (VA FIXTURE P-524) SINK - SELF-RIMMING SINGLE COMPARTMENT WITH FAUCET DECK,
18 GAUGE TYPE 316 STAINLESS STEEL, 27" (SIDE-TO-SIDE) x 22" (FRONT-TO-BACK) OVERALL SIZE, 24" x 16" x 8" DEEP BOWL, COMPLETELY UNDERCOATED, 3-3/8"
DIAMETER DRAIN OUTLET LOCATION CENTERED IN BOWL, PERFORATED TYPE 316
STAINLESS STEEL GRID STRAINER.
SINK TRIM - TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION, INTEGRAL CAST
BODY, CHROME-PLATED FINISH, GOOSENECK SWING SPOUT, NOMINAL 8" REACH,
LAMINAR FLOW OUTLET, 6" WRISTBLADE HANDLES AT 4" CENTERS, 1/4-TURN
OPERATION CERAMIC DISC CARTRIDGE.
MAXIMUM FLOW TO BE 1.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005
AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT
S.3874. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON PLATE AS REQUIRED.
ACCESSORIES - 1-1/2" POLYPROPYLENE TAILPIECE AND P-TRAP, QUARTER-TURN BALL
VALVE TYPE 3/8" CHROME-PLATED BRASS ANGLE SUPPLIES WITH LOOSE KEY STOPS,
CHROME-PLATED SOFT COPPER SUPPLY LINES.
SINK -
ELKAY (LSR/LK18B), JUST, FRANKE
SINK TRIM -
CHICAGO FAUCET (895),
SPEAKMAN, ZURN
SK-2 (VA FIXTURE P-524) SINK - SELF-RIMMING DOUBLE COMPARTMENT WITH FAUCET DECK,
18 GAUGE TYPE 304 STAINLESS STEEL, COMPLETELY UNDERCOATED, 33"
(SIDE-TO-SIDE) x 21-1/4" (FRONT-TO-BACK) OVERALL SIZE, EACH COMPARTMENT 13-1/2" x 16" x 7-3/4" DEEP, 3-1/2" DIAMETER DRAIN OUTLET LOCATION CENTERED IN EACH
BOWL, REMOVABLE TYPE 304 STAINLESS STEEL BASKET STRAINERS WITH NEOPRENE
STOPPERS.
SINK TRIM - SINGLE HANDLE MIXING FAUCET, BRASS CONSTRUCTION, CHROME-PLATED
FINISH, CONVENTIONAL SWING SPOUT, NOMINAL 8" REACH, LAMINAR FLOW OUTLET,
LEVER HANDLE, SINGLE HOLE SUPPLIES, SPRAY HOSE WITH LEVER CONTROL.
MAXIMUM FLOW TO BE 2.2 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005
AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT
S.3874. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON PLATE AS REQUIRED.
ACCESSORIES - 1-1/2" 17 GAUGE CHROME-PLATED BRASS TAILPIECE AND P-TRAP,
QUARTER-TURN BALL VALVE TYPE 3/8" CHROME-PLATED BRASS ANGLE SUPPLIES WITH
LOOSE KEY STOPS, CHROME-PLATED SOFT COPPER SUPPLY LINES.
SINK -
ELKAY (LR/LK99), JUST, FRANKE
SINK TRIM -
AMERICAN STANDARD (4175.501),
DELTA, CHICAGO FAUCET, ELKAY,
KOHLER, MOEN, SYMMONS
SK-3 (VA FIXTURE P-528) SINK - SELF-RIMMING SINGLE COMPARTMENT WITH FAUCET DECK,
18 GAUGE TYPE 316 STAINLESS STEEL, 19-1/2" (SIDE-TO-SIDE) x 19" (FRONT-TO-BACK) OVERALL SIZE, 16" x 13-1/2" x 10" DEEP BOWL, COMPLETELY UNDERCOATED, 3-1/2"
DIAMETER DRAIN OUTLET LOCATION CENTERED IN BOWL, PERFORATED TYPE 316
STAINLESS STEEL GRID STRAINER.
SINK TRIM - TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION, CHROME-PLATED
FINISH, GOOSENECK RIGID SPOUT, NOMINAL 5-1/4" REACH, LAMINAR FLOW OUTLET, 4"
WRISTBLADE HANDLES AT 4" CENTERS, 1/4-TURN OPERATION CERAMIC DISC
CARTRIDGE.
MAXIMUM FLOW TO BE 2.2 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005
AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT
S.3874. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON PLATE AS REQUIRED.
ACCESSORIES - 1-1/2" POLYPROPYLENE TAILPIECE AND P-TRAP, QUARTER-TURN BALL
VALVE TYPE 3/8" CHROME-PLATED BRASS ANGLE SUPPLIES WITH LOOSE KEY STOPS,
CHROME-PLATED SOFT COPPER SUPPLY LINES.
SINK -
ELKAY (LR/LK18B), JUST, FRANKE
SINK TRIM -
CHICAGO FAUCET (895),
AMERICAN STANDARD,
SPEAKMAN, ZURN
SK-4 (VA FIXTURE P-528) SINK - SELF-RIMMING SINGLE COMPARTMENT WITH FAUCET DECK,
18 GAUGE TYPE 304 STAINLESS STEEL, 22" (SIDE-TO-SIDE) x 19-1/2" (FRONT-TO-BACK) OVERALL SIZE, 18" x 14" x 6-3/8" DEEP BOWL, COMPLETELY UNDERCOATED, 3-1/2"
DIAMETER DRAIN OUTLET LOCATION OFF-CENTERED LEFT IN BOWL, REMOVABLE TYPE
304 STAINLESS STEEL BASKET STRAINER AND NEOPRENE STOPPER.
SINK TRIM - TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION, CHROME-PLATED
FINISH, GOOSENECK RIGID SPOUT, NOMINAL 5-1/4" REACH, LAMINAR FLOW OUTLET, 4"
WRISTBLADE HANDLES AT 4" CENTERS, 1/4-TURN OPERATION CERAMIC DISC
CARTRIDGE.
MAXIMUM FLOW TO BE 2.2 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005
AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT
S.3874. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON PLATE AS REQUIRED.
REVERSE OSMOSIS SINK TRIM - DECK MOUNTED POLYPROPYLENE PURE WATER
FAUCET, CHROME PLATED BRASS DECK FLANGE, SHANK, RISER AND COUPLING OUTER
SHELL, NOMINAL 6" REACH, POLYPROPYLENE VALVE WITH "RO" INDEX BUTTON ON
HANDLE.
ACCESSORIES - 1-1/2" 17 GAUGE CHROME-PLATED BRASS TAILPIECE AND P-TRAP,
QUARTER-TURN BALL VALVE TYPE 3/8" CHROME-PLATED BRASS ANGLE SUPPLIES WITH
LOOSE KEY STOPS, CHROME-PLATED SOFT COPPER SUPPLY LINES.
SINK -
ELKAY (LRAD/LKPD), JUST,
FRANKE
SINK TRIM -
CHICAGO FAUCET (895),
AMERICAN STANDARD,
SPEAKMAN, ZURN
REVERSE OSMOSIS SINK TRIM -
CHICAGO FAUCET (828-ACP),
AMERICAN STANDARD,
SPEAKMAN, ZURN
SV-1 SOLENOID VALVE (WATER) - NORMALLY OPEN GENERAL SERVICE, BRASS BODY
CONSTRUCTION, LINE SIZE NPT PIPE CONNECTIONS, SLOW CLOSING, TWO WAY PILOT
OPERATED, METAL SOLENOID ENCLOSURE, CONTINUOUS DUTY MOLDED CLASS F COIL,
SUITABLE FOR USE WITH WATER. PROVIDE STRAINER UPSTREAM OF SOLENOID
VALVE.
MINIMUM OPERATING PRESSURE DIFFERENTIAL OF 5 PSI
ELECTRICAL REQUIREMENTS - 120 VAC, HARD-WIRED, 16.1 WATTS.
ASCO (8221)
SV-2 SOLENOID VALVE (WATER) - NORMALLY CLOSED GENERAL SERVICE, BRASS BODY
CONSTRUCTION, LINE SIZE NPT PIPE CONNECTIONS, SLOW CLOSING, TWO WAY PILOT
OPERATED, METAL SOLENOID ENCLOSURE, CONTINUOUS DUTY MOLDED CLASS F COIL,
SUITABLE FOR USE WITH WATER. PROVIDE STRAINER UPSTREAM OF SOLENOID
VALVE.
MINIMUM OPERATING PRESSURE DIFFERENTIAL OF 5 PSI
ELECTRICAL REQUIREMENTS - 120 VAC, HARD-WIRED, 16.1 WATTS.
ASCO (8221)
T-1 RO WATER STORAGE TANK - VERTICAL, NATURAL COLOR HDLPE CONSTRUCTION, 1"
INLET/OUTLET.
65 GALLON CAPACITY, 23" DIAMETER x 45-3/4" HIGH
150 PSIG WORKING PRESSURE, ASME STAMPED, 25-YEAR WARRANTY.
SNYDER INDUSTRIES INC
(VERTICAL TANK SERIES)
TP-1 TRAP PRIMER - ELECTRONIC SOLENOID ACTIVATED, FLUSH MOUNTED CABINET, FULLY
ENCLOSED WITH KEYED ACCESS DOOR, MANUAL OVERRIDE, 3/4" FNPT INLET AND 1/2"
COMPRESSION OUTLET, BUILT-IN VACUUM BREAKER, CAPABLE OF SERVING 4 TRAPS.
ELECTRICAL REQUIREMENTS - 120VAC, 3-WIRE CONNECTION
PRECISION PLUMBING PRODUCTS
(PT), SIOUX CHIEF
TP-2 TRAP PRIMER - ELECTRONIC SOLENOID ACTIVATED, FLUSH MOUNTED CABINET, FULLY
ENCLOSED WITH KEYED ACCESS DOOR, MANUAL OVERRIDE, 3/4" FNPT INLET AND 1/2"
COMPRESSION OUTLET, BUILT-IN VACUUM BREAKER, CAPABLE OF SERVING 6 TRAPS.
ELECTRICAL REQUIREMENTS - 120VAC, 3-WIRE CONNECTION
PRECISION PLUMBING PRODUCTS
(PT), SIOUX CHIEF
UB-1 UTILITY BOX - GALVANIZED STEEL ENCLOSURE, ANGLE VALVE WITH 1/4"
COMPRESSION OUTLET, INTREGAL WATER HAMMER ARRESTOR.
GUY GRAY (BIM875AB), OATEY
(39140)
UB-2 UTILITY BOX - POLYSTYRENE PLASTIC CONSTRUCTION, SNAP ON FACE PLATE,
MINIMUM 6" HIGH BY 10" WIDE BOX, WIDE MOUTH RIGHT HAND 2" DRAIN.
WATER-TITE (87405), OATEY
(38640)
UR-1 (VA FIXTURE P-203) URINAL - WALL MOUNTED, WHITE VITREOUS CHINA, FLUSH VALVE
TYPE, WASHOUT ACTION, ELONGATED RIM, EXTENDED SIDE SHIELDS, 3/4" TOP SPUD, 2"
OUTLET.
FLUSH VALVE - EXPOSED, MANUAL OPERATION, 1.0 GALLONS PER FLUSH, 11-1/2"
ROUGH-IN, CHROME-PLATED, 3/4" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH
VANDAL RESISTANT CAP, HIGH BACK PRESSURE VACUUM BREAKER, NON-HOLD-OPEN
HANDLE, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH
SET SCREW, CHLORAMINE RESISTANT MATERIALS, 3-YEAR WARRANTY.
CONTRACTOR OPTION: COMBINATION URINAL/FLUSH VALVE PACKAGED SYSTEM BY
AMERICAN STANDARD, KOHLER, SLOAN, OR ZURN
ACCESSORIES - SUPPORT CARRIER WITH TOP AND BOTTOM BEARING PLATES.
MOUNT WITH CARRIER BOLTED SECURELY TO FLOOR. TOP OF BOWL RIM SHALL BE AT
22" ABOVE FLOOR. VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS.
URINAL -
AMERICAN STANDARD (6590.001),
KOHLER, SLOAN, GERBER, TOTO,
ZURN
FLUSH VALVE -
AMERICAN STANDARD (6045.101),
ZURN, SLOAN, KOHLER, DELANY,
TOTO
UR-2 (VA FIXTURE P-204) URINAL - ACCESSIBLE, WALL MOUNTED, WHITE VITREOUS CHINA,
FLUSH VALVE TYPE, WASHOUT ACTION, ELONGATED RIM, EXTENDED SIDE SHIELDS,
3/4" TOP SPUD, 2" OUTLET.
FLUSH VALVE - EXPOSED, MANUAL OPERATION, 1.0 GALLONS PER FLUSH, 11-1/2"
ROUGH-IN, CHROME-PLATED, 3/4" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH
VANDAL RESISTANT CAP, HIGH BACK PRESSURE VACUUM BREAKER, NON-HOLD-OPEN
HANDLE, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH
SET SCREW, CHLORAMINE RESISTANT MATERIALS, 3-YEAR WARRANTY.
CONTRACTOR OPTION: COMBINATION URINAL/FLUSH VALVE PACKAGED SYSTEM BY
AMERICAN STANDARD, KOHLER, SLOAN, OR ZURN
ACCESSORIES - SUPPORT CARRIER WITH TOP AND BOTTOM BEARING PLATES.
MOUNT WITH CARRIER BOLTED SECURELY TO FLOOR. TOP OF BOWL RIM SHALL BE AT
17" (MAXIMUM) ABOVE FLOOR IN COMPLIANCE WITH LATEST ADA STANDARDS. FLUSH
HANDLE SHALL BE AT 44" (MAXIMUM) ABOVE FLOOR AND OPERATE WITH NO GREATER
THAN 5 LB FORCE IN COMPLIANCE WITH LATEST ADA STANDARDS. VERIFY EQUIPMENT
REQUIREMENTS AND ROUGH-IN LOCATIONS.
URINAL -
AMERICAN STANDARD (6590.001),
KOHLER, SLOAN, GERBER, TOTO,
ZURN
FLUSH VALVE -
AMERICAN STANDARD (6045.101),
ZURN, SLOAN, KOHLER, DELANY,
TOTO
PLUMBING FIXTURE SCHEDULE
TAG NAME DESCRIPTION MANF. & MODEL
L-1 (VA FIXTURE P-401) LAVATORY - ACCESSIBLE, WALL MOUNTED, WHITE VITREOUS
CHINA, 20"x18", 4" HIGH CONTOURED BACKSPLASH, FAUCET HOLES ON 4" CENTERS, WALL MOUNTING BRACKETS.
LAVATORY TRIM - SINGLE HANDLE MIXING FAUCET, BRASS CONSTRUCTION,
CHROME-PLATED FINISH, CONVENTIONAL SPOUT WITH LAMINAR FLOW OUTLET,
WASHERLESS PUSH-PULL LEVER HANDLE WITH SUPPLIES AT 4" CENTERS, CERAMIC
DISC CARTRIDGE, PERFORATED GRID STRAINER WITH 1-1/4" 17 GAUGE TAILPIECE.
MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005
AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT
S.3874. PROVIDE RESTRICTIVE DEVICE AS REQUIRED.
MIXING VALVE - POINT-OF-USE ANTI-SCALD THERMOSTATIC MIXING VALVE FOR
TEMPERED WATER CONTROL, ALL BRONZE/BRASS CONSTRUCTION, ROUGH FINISH,
THREADED INLETS, TAMPER RESISTANT SETPOINT, 3/8" COMPRESSION INLETS AND
OUTLETS, COLD WATER BYPASS IF USED WITH MIXING FAUCET.
0.5 GPM OUTPUT. UNIT TO MIX 120 DEGREE F HOT WATER SUPPLY AND 40 DEGREE F
COLD WATER SUPPLY FOR 110 DEGREE F OUTLET.
UNIT SHALL BE ASSE 1070 LISTED AND APPROVED. VALVE SHALL COMPLY WITH
FEDERAL ACT S.3874.
INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES AND SUPPLY LINES.
ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLY
LOOSE KEY STOPS, CHROME PLATED SOFT COPPER SUPPLY LINES, DRAIN AND
TAILPIECE, 1-1/4" 17 GAUGE CAST BRASS P-TRAP, SUPPORT CARRIER.
TOP OF RIM SHALL BE AT 34" ABOVE FLOOR IN COMPLIANCE WITH LATEST ADA
STANDARD. PROVIDE 29" MINIMUM CLEARANCE FROM FLOOR TO BOTTOM OF APRON
IN COMPLIANCE WITH LATEST ANSI A117.1 AND ADA STANDARDS. ARMAFLEX WITH
TAPE IS NOT ACCEPTABLE IN LIEU OF INSULATION KIT.
LAVATORY -
AMERICAN STANDARD (0355.012),
KOHLER, SLOAN, TOTO, ZURN
LAVATORY TRIM-
AMERICAN STANDARD (7385),
DELTA, CHICAGO FAUCET,
KOHLER, MOEN, SPEAKMAN,
SYMMONS, ZURN
MIXING VALVE-
WATTS (LFUSG-B), LAWLER,
ACORN CONTROLS, APOLLO,
LEONARD, POWERS, SLOAN,
SYMMONS, WILKINS
INSULATION KIT - TRUEBRO
(LAV-GUARD), BROCAR
PRODUCTS, MCGUIRE,
PLUMBEREX
L-2 (VA FIXTURE P-408) LAVATORY - ACCESSIBLE, WALL MOUNTED, WHITE VITREOUS
CHINA, 20"x18", 4" HIGH CONTOURED BACKSPLASH, FAUCET HOLES ON 8" CENTERS, WALL MOUNTING BRACKETS.
LAVATORY TRIM - TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION,
CHROME-PLATED FINISH, RIGID GOOSENECK SPOUT WITH NOMINAL 6" REACH AND
LAMINAR FLOW OUTLET, 4" WRIST BLADE HANDLES AT 8" CENTERS, CERAMIC DISC
CARTRIDGE, PERFORATED GRID STRAINER WITH 1-1/4" 17 GAUGE TAILPIECE.
MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005
AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT
S.3874. PROVIDE RESTRICTIVE DEVICE AS REQUIRED.
MIXING VALVE - POINT-OF-USE ANTI-SCALD THERMOSTATIC MIXING VALVE FOR
TEMPERED WATER CONTROL, ALL BRONZE/BRASS CONSTRUCTION, ROUGH FINISH,
THREADED INLETS, TAMPER RESISTANT SETPOINT, 3/8" COMPRESSION INLETS AND
OUTLETS, COLD WATER BYPASS IF USED WITH MIXING FAUCET.
CABINET - SEMI-RECESSED MOUNTED 18 GUAGE STAINLESS STEEL CABINET WITH 16
GUAGE LOCKING DOOR TO ENCLOSE VALVE, INLET STOPS, OUTLET THERMOMETER,
AND OUTLET VALVES.
0.5 GPM OUTPUT. UNIT TO MIX 120 DEGREE F HOT WATER SUPPLY AND 40 DEGREE F
COLD WATER SUPPLY FOR 110 DEGREE F OUTLET.
UNIT SHALL BE ASSE 1070 LISTED AND APPROVED. VALVE SHALL COMPLY WITH
FEDERAL ACT S.3874.
INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES AND SUPPLY LINES.
ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLY
LOOSE KEY STOPS, CHROME PLATED SOFT COPPER SUPPLY LINES, DRAIN AND
TAILPIECE, 1-1/4" 17 GAUGE CAST BRASS P-TRAP, SUPPORT CARRIER.
TOP OF RIM SHALL BE AT 34" ABOVE FLOOR IN COMPLIANCE WITH LATEST ADA
STANDARD. PROVIDE 29" MINIMUM CLEARANCE FROM FLOOR TO BOTTOM OF APRON
IN COMPLIANCE WITH LATEST ANSI A117.1 AND ADA STANDARDS. ARMAFLEX WITH
TAPE IS NOT ACCEPTABLE IN LIEU OF INSULATION KIT.
LAVATORY -
AMERICAN STANDARD (0356.015),
KOHLER, SLOAN, TOTO, ZURN
LAVATORY TRIM-
AMERICAN STANDARD (6540.170),
DELTA, CHICAGO FAUCET,
KOHLER, MOEN, SYMMONS, T&S
BRASS, ZURN
MIXING VALVE-
WATTS (LFUSG-B), LAWLER,
ACORN CONTROLS, APOLLO,
LEONARD, POWERS, SLOAN,
SYMMONS, WILKINS
INSULATION KIT - TRUEBRO
(LAV-GUARD), BROCAR
PRODUCTS, MCGUIRE,
PLUMBEREX
LGO-1 MEDICAL GAS SERVICE OUTLET - RECESSED DISS TYPE WALL OUTLET. ROUGHING IN
ASSEMBLY AND FINISH ASSEMBLY,
MOUNTING FLANGES, PLASTER STRIKE, SECONDARY CHECK, 3/8" O.D. TYPE
K COPPER INLET TUBE, LABEL IDENTIFYING SPECIFIC GAS BY NAME AND
COLOR, BRUSHED STAINLESS STEEL FINISHING PLATE. SYMBOLS FOR
OUTLETS ARE AS FOLLOWS:
CO2 CARBON DIOXIDE
BEACON/MEDAES DIAMOND III
ALLIED
HEALTHCARE/CHEMETRON
SQUIRE-COGSWELL/AEROS
AMICO
MB-1 (VA FIXTURE P-501) MOP BASIN - PRECAST TERRAZZO, 36"x24"x12", STAINLESS STEEL
INTEGRAL DRAIN WITH REMOVABLE STRAINER, 3" OUTLET, CONTINUOUS STAINLESS
STEEL CAP ON ALL EDGES.
TRIM - EXPOSED TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION,
CHROME-PLATED FINISH, SINGLE WING HANDLES, 1/4 TURN CERAMIC DISC
CARTRIDGE, 3/4" HOSE THREAD SPOUT WITH INTEGRAL VACUUM BREAKER, WALL
BRACE, PAIL HOOK, CHECK STOPS OR INLINE CHECK VALVES TO PREVENT THERMAL
CROSSOVER. FAUCET SHALL COMPLY WITH FEDERAL ACT S.3874.
ACCESSORIES - MOP HANGER, HOSE AND HOSE BRACKET, DEEP SEAL TRAP
MOP BASIN -
FIAT (TSB), ACORN, CREATIVE
INDUSTRIES, WILLIAMS
TRIM -
AMERICAN STANDARD (8344.012),
DELTA, CHICAGO FAUCETS,
MOEN, SPEAKMAN, SYMMONS,
ZURN
VACUUM BREAKER -
WATTS (8A), OR APPROVED
EQUAL
MV-1 MIXING VALVE - THERMOSTATIC MIXING VALVE FOR EMERGENCY SHOWER OR
COMBINATION SHOWER/EYEWASH FIXTURE, BRONZE BODY CONSTRUCTION, COLD
WATER BYPASS, INLET AND OUTLET THERMOMETERS, COMBINATION CHECK STOPS
OR SEPARATE SUPPLY CHECK VALVES AND SHUT OFF VALVES, OUTLET ISOLATION
VALVE, MOUNTING BRACKET. SUPPLY SHUT OFF VALVES SHALL BE LOCKED OPEN OR
CONTRACTOR SHALL PROVIDE A LOCKING CABINET TO PREVENT UNAUTHORIZED
CLOSURE. CABINET SHALL BE SURFACE MOUNTED 18 GAUGE STAINLESS STEEL WITH
16 GAUGE LOCKING DOOR TO ENCLOSE VALVE, INLET CHECK STOPS, OUTLET
THERMOMETER, AND OUTLET VALVE. DUAL THERMOSTATIC MIXING AND PRESSURE
REGULATING VALVE TO DELIVER 25 GPM OF TEMPERED WATER (60-100 DEGREE F)
WITH 10 PSI PRESSURE DIFFERENTIAL. UNIT SHALL BE ASSE 1071 LISTED AND
APPROVED. VALVE SHALL COMPLY WITH FEDERAL ACT S.3874.
LEONARD (TM-LF), ACORN
CONTROLS, ARMSTRONG,
BRADLEY, HAWS, LAWLER,
POWERS, OR PRE-PACKAGED
WITH EMERGENCY SHOWER
FROM SAME MANUFACTURER.
NT-1 NEUTRALIZATION TANK - 27"x21"x15" RECTANGULAR WITH 22 GALLON CAPACITY, HIGH
DENSITY POLYETHYLENE, ROTATIONALLY MOLDED WITH FLANGED TOP AND BOLTED
COVER, HOLD-DOWN FLANGES, 3" INLET, 3" OUTLET, AND 2" VENT CONNECTIONS.
PROVIDE GAS-TIGHT FRAME AND COVER.
TANK SHALL BE SUPPLIED AND INSTALLED WITH MANUFACTURER APPROVED
NEUTRALIZING AGENT SUCH AS LIMESTONE OR MARBLE CHIPS (TWO TO THREE
INCHES IN SIZE WITH A CALCIUM CARBONATE CONTENT OF GREATER THAN 90%) TO A
LEVEL JUST BELOW TANK OUTLET. ADD WATER AFTER PLACEMENT OF
NEUTRALIZATION AGENT.
STRIEM (LB-25), ORION
RD-1 ROOF DRAIN - CAST IRON BODY, SECURED CAST IRON DOME, 15" ROUND, BOTTOM
OUTLET, FLASHING CLAMP, GRAVEL STOP, UNDERDECK CLAMP, BEARING PAN,
ADJUSTABLE EXTENSION TO MATCH INSULATION THICKNESS, OUTLET SIZE AS LISTED
ON DRAWINGS.
ZURN (Z-100), SMITH, WADE,
JOSAM, WATTS, MIFAB, SUN,
FROET
RD-2 ROOF DRAIN - CAST IRON BODY, SECURED CAST IRON DOME, 15" ROUND, BOTTOM
OUTLET, FLASHING CLAMP, GRAVEL STOP, UNDERDECK CLAMP, BEARING PAN,
EXTENSION TO MATCH INSULATION THICKNESS, 2" TALL EXTERNAL WATER DAM,
OUTLET SIZE AS LISTED ON DRAWINGS.
ZURN (Z-100), SMITH, WADE,
WATTS, MIFAB, SUN
RDO-1 ROOF DRAIN OUTLET - LAMBS TONGUE DOWNSPOUT NOZZLE, BRONZE BODY,
INTEGRAL ANCHORING FLANGE, OUTLET SIZE AS LISTED ON DRAWINGS.
ZURN (Z-199), SMITH, WADE,
JOSAM, WATTS, MIFAB, SUN
RG-1 GENERAL PURPOSE INLINE MEDICAL GAS LOW PRESSURE REGULATOR WITH 1/4” NPTF
GAUGE PORT. PROVIDE WITH SEPARATE 2” DIAMETER ZONE VALVE BOX STYLE GAUGE
WITH 1/8” NPTM CONNECTION. PROVIDE BUSHING AS NECESSARY TO CONNECT THE
GAUGE TO REGULATOR PORT.
AMICO ALERT-1 SERIES
R-X-REF-W-LP
RO-1 REVERSE OSMOSIS SYSTEM - WALL MOUNTED INDUSTRIAL TYPE WATER TREATMENT
SYSTEM CAPABLE OF PRODUCING 300 GALLONS PER DAY OF REVERSE OSMOSIS
WATER. DESIGNED FOR CONTINUOUS AUTOMATIC OPERATION. SYSTEM SHALL
INCLUDE PRE-FILTER, PRODUCT STORAGE TANK, AND ALL DEVICES NECESSARY FOR
FULLY OPERATIONAL SYSTEM. SYSTEM SHALL BE CONTROLLED BY WATER LEVEL IN
STORAGE TANK, T-1.
US WATER SYSTEMS
(220-USCRO-300FR-NT),
APPROVED EQUAL
PLUMBING FIXTURE SCHEDULE
TAG NAME DESCRIPTION MANF. & MODEL
AGF-1 AIR GAP FITTING - CAST IRON CONSTRUCTION, SET SCREW OR THREADED INLET,
SELECT SIZE TO MATCH INDIRECT WASTE LINE INLET AND STANDPIPE OUTLET.
ZURN (Z1025), JOSAM, SMITH,
WADE
AP-1 COMBINATION MASTER/AREA ALARM PANEL - MODULAR IN DESIGN, DIGITAL TYPE,
USED WITH REMOTE OR LOCAL SENSORS AND PRESSURE SWITCHES TO MONITOR THE
FOLLOWING:
CARBON DIOXIDE CHANGEOVER/RESERVE IN USE
CARBON DIOXIDE LINE PRESSURE HIGH
CARBON DIOXIDE LINE PRESSURE LOW
CARBON DIOXIDE LINE PRESSURE
ABNORMAL PRESSURE SHALL BE INDICATED IF THE PRESSURE AT ANY OF THE
MEDICAL GAS SERVICES IS 20% ABOVE OR 20% BELOW THEIR NORMAL PRESSURE.
EACH OF THE ITEMS MONITORED AS INDICATED ABOVE SHALL HAVE A GREEN LIGHT TO
INDICATE ALL SYSTEMS ARE NORMAL. AN AUDIBLE WARNING DEVICE WILL SOUND AND
THE “ABNORMAL” RED LIGHT SHALL COME ON TO INDICATE AN ALARM. A SWITCH SHALL
BE PROVIDED TO SILENCE WARNING DEVICE. “ABNORMAL” RED LIGHT WILL REMAIN LIT
UNTIL CONDITION HAS BEEN CORRECTED. A TEST SWITCH SHALL BE SUPPLIED TO
TEST INTERNAL CIRCUITS, LIGHTS AND WARNING DEVICES. A BUILT-IN LCD WILL
CONTINUOUSLY DISPLAY THE PRESSURE AT ALL TIMES.
PROVIDE RELAY BOARD DRY CONTACTS FOR EACH ALARM POINT FOR CONNECTION TO
THE BUILDING AUTOMATION SYSTEM.
A 115 VOLT POWER SUPPLY TO THE ALARM PANEL TO BE WIRED BY THE ELECTRICAL
CONTRACTOR. ALL POWER WIRING SERVING THE EQUIPMENT SHALL BE BY THE
ELECTRICAL CONTRACTOR.
ALL ALARM WIRING SERVING CENTRAL EQUIPMENT AND ALARM PANELS SHALL BE THE
RESPONSIBILITY OF THE PLUMBING CONTRACTOR. ALL ALARM WIRING SERVING
PRESSURE SWITCHES, ACTUATORS, SENSORS, AND ANY OTHER EQUIPMENT
REQUIRED FOR COMPLETE MEDICAL GAS AND MEDICAL GAS ALARM SYSTEMS SHALL
BE THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR.
WIRING TO COMPLY WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE.
THE PLUMBING CONTRACTOR SHALL PROVIDE WIRING DIAGRAMS TO THE ELECTRICAL
CONTRACTOR.
REFER TO 11/P300 FOR MEDICAL GAS SCHEMATIC WIRING DIAGRAM.
BEACON/MEDAES
ALLIED
HEALTHCARE/CHEMETRON
SQUIRE-COGSWELL/AEROS
AMICO
BFP-1 BACK FLOW PREVENTER - DOUBLE CHECK, LEAD FREE BRONZE CONSTRUCTION,
SAME SIZE AS PIPE, NON-CORROSIVE INTERNAL PARTS, STAINLESS STEEL SPRINGS,
SPRING-LOADED CHECK VALVES, BALL STYLE SHUT-OFF VALVES ON INLET AND OUTLET
OF UNIT, TEST PORTS WITH SHUT-OFF VALVES, FACTORY TESTED, RATED FOR 175 PSI
AT 33°F TO 140°F, 8 PSI (MAXIMUM) PRESSURE DROP AT 10 FPS, ALL PARTS TO BE
SERVICEABLE WITHOUT REMOVING UNIT FROM LINE, APPROVED BY USC FCCC & HR,
AWWA C510-92, ASSE 1015, IAPMO AND SBCCI LISTED.
MOUNT WITHIN 60" OF FINISHED FLOOR. PROVIDE AND INSTALL BRONZE OR EPOXY
COATED STRAINER UPSTREAM OF EACH UNIT AND ADDITIONAL VALVE UPSTREAM OF
EACH STRAINER. FLOW PRESSURE DROP CURVES SHALL BE SUBMITTED.
APOLLO (4ALF-100), WATTS
(LF719), WILKINS (950XLT2)
BFP-2 BACK FLOW PREVENTER - REDUCED PRESSURE ZONE, ENTIRELY LEAD FREE
STAINLESS STEEL CONSTRUCTION, SIZE SAME AS PIPE 3/4", STAINLESS STEEL
INTERNAL PARTS, STAINLESS STEEL SPRINGS, DIFFERENTIAL PRESSURE RELIEF VALVE
BETWEEN SPRING-LOADED CHECK VALVES, FULL PORT BALL SHUT-OFF VALVES ON
INLET AND OUTLET OF UNIT, AIR GAP DRAIN FITTING, TEST PORTS WITH SHUT-OFF
VALVES, RATED FOR 175 PSI AT 33°F TO 140°F, 15 PSI (MAXIMUM) PRESSURE DROP AT
10 FPS, FACTORY TESTED, ALL PARTS TO BE SERVICEABLE WITHOUT REMOVING UNIT
FROM LINE, APPROVED BY USC FCCC & HR, AWWA C511-92, ASSE 1013, IAPMO AND
SBCCI LISTED.
MOUNT WITHIN 60" OF FINISHED FLOOR. FLOW PRESSURE DROP CURVES SHALL BE
SUBMITTED.
WATTS (SS009), WILKINS, APOLL
BFP-3 BACK FLOW PREVENTER - REDUCED PRESSURE ZONE, LEAD FREE BRONZE
CONSTRUCTION, SIZE SAME AS PIPE, NON-CORROSIVE INTERNAL PARTS, STAINLESS
STEEL SPRINGS, DIFFERENTIAL PRESSURE RELIEF VALVE BETWEEN SPRING-LOADED
CHECK VALVES, BALL STYLE SHUT-OFF VALVES ON INLET AND OUTLET OF UNIT, AIR
GAP DRAIN FITTING, TEST PORTS WITH SHUT-OFF VALVES, RATED FOR 175 PSI AT 33°F
TO 140°F, 15 PSI (MAXIMUM) PRESSURE DROP AT 10 FPS, FACTORY TESTED, ALL PARTS
TO BE SERVICEABLE WITHOUT REMOVING UNIT FROM LINE, APPROVED BY USC FCCC &
HR, AWWA C511-92, ASSE 1013, IAPMO AND SBCCI LISTED.
MOUNT WITHIN 60" OF FINISHED FLOOR. ROUTE DRAIN PIPE FROM AIR GAP FITTING TO
FLOOR DRAIN. PROVIDE AND INSTALL BRONZE OR EPOXY COATED STRAINER
UPSTREAM OF EACH UNIT AND ADDITIONAL VALVE UPSTREAM OF EACH STRAINER.
FLOW PRESSURE DROP CURVES SHALL BE SUBMITTED.
WATTS (LF919), APOLLO, WILKINS
BFP-4 BACK FLOW PREVENTER - DUAL CHECK, LEAD FREE STAINLESS STEEL BODY, HEAVY
DUTY FDA APPROVED RUBBER DIAPHRAGMS, 3/8" SIZE, RATED FOR 150 PSI AT 33°F TO
110°F, APPROVED BY ASSE 1032.
WATTS (SD-2)
ESE-1 (VA FIXTURE P-707) EMERGENCY SHOWER & EYE/FACE WASH - COMBINATION UNIT,
FREESTANDING, FLOOR MOUNTED WITH BACK INLET, POLISHED CHROME SHOWER
HEAD, BRASS/BRONZE STAY OPEN BALL VALVE, STAINLESS STEEL/ALUMINUM PULL
ROD, STAINLESS STEEL BOWL, PLASTIC SPRAY HEADS WITH CAPS AND RETAINING
CHAINS/STRAPS, BRASS SUPPLY ARMS, BRASS/BRONZE STAY OPEN BALL VALVE,
METAL FLAG, INTEGRAL FLOW CONTROL FITTINGS, STAINLESS STEEL SUPPLY PIPING
AND FITTINGS, UNIVERSAL IDENTIFICATION SIGN, ANSI Z358.1-2004 COMPLIANT.
PROVIDE ELECTRIC ALARM UNIT INCLUDING VISUAL AND AUDIBLE ALARM. SHALL BE
ACTIVATED BY EITHER FLOW TO EYEWASH OR SHOWER.
ELECTRICAL REQUIREMENTS - 120 VOLT, 0.11 AMP
MINIMUM FLOW RATE OF SHOWER SHALL BE 20 GPM AT 30 PSI. MINIMUM FLOW RATE
OF EYE/FACE WASH SHALL BE 3.0 GPM AT 30 PSI. ACTIVATION TIME SHALL BE 1
SECOND OR LESS. BRASS/BRONZE PIPING, FITTINGS, AND VALVES SHALL BE
CHROME-PLATED OR CHEMICAL-RESISTANT POWDER COATED.
MOUNT SHOWER HEAD BETWEEN 84" AND PULL ROD AT MAXIMUM 60" ABOVE FINISH
FLOOR. EYE/FACE WASH OUTLET HEADS SHALL BE 42" ABOVE FINISH FLOOR.
GUARDIAN (G1900 SERIES),
BRADLEY, ACORN SAFETY, HAWS,
SPEAKMAN, ENCON
F-1 WATER FILTER - CAST BRASS OR STAINLESS STEEL HEAD, STAINLESS STEEL SUMP, 5
MICRON FILTER CARTRIDGE, FDA APPROVED MATERIALS.
MINIMUM 1.6 GPM FLOW RATE
EVERPURE (i2000), AQUA-PURE, CAMPBELL
FCO-1 FLOOR CLEANOUT - ADJUSTABLE, CAST IRON HOUSING, ANCHOR FLANGE, TAPERED
THREAD PLUG, SECURED NICKEL BRONZE TOP. TOP STYLE SHALL MATCH FLOOR
FINISH AS FOLLOWS:
UNFINISHED FLOOR - ROUND SOLID SCORIATED TOP
TILE OR TERRAZZO - ROUND RECESSED TOP
ZURN (Z1400), JOSAM, MIFAB,
SMITH, WADE, WATTS
FCO-2 FLOOR CLEANOUT - POLYPROPYLENE THREADED ADJUSTABLE BODY, GAS AND
WATER TIGHT TAPERED PLUG AND ROUND SECURED STAINLESS STEEL TOP.
ZURN (Z9A-CO1), ORION, IPEX
ENFIELD
FD-1 FLOOR DRAIN - CAST IRON BODY, NICKEL BRONZE ADJUSTABLE TOP, 6" ROUND, 3"
BOTTOM OUTLET, FLASHING COLLAR, DEEP SEAL TRAP.
FLOOR DRAIN - ZURN (Z-415),
SMITH, WADE, JOSAM, WATTS,
MIFAB, SUN
FD-2 FLOOR DRAIN - ACID RESISTANT, POLYPROPYLENE BODY, POLYPROPYLENE GRATE, 8"
ROUND, 3" BOTTOM OUTLET, FLASHING CLAMP, DEEP SEAL TRAP.
ZURN (Z9A-FD), ORION, WATTS,
IPEX
FS-1 FLOOR SINK - CAST IRON BODY, NICKEL BRONZE RIM AND GRATE, 8" ROUND, 3"
BOTTOM OUTLET, MEDIUM RECEPTOR WITH ALUMINUM DOME STRAINER, ACID
RESISTANT COATED INTERIOR, SEEPAGE FLANGE WITH CLAMP, DEEP SEAL TRAP.
ZURN (Z1960), SIOUX CHIEF,
SMITH, WADE, JOSAM, WATTS,
SUN
FS-2 FLOOR SINK - CAST IRON BODY, NICKEL BRONZE RIM AND GRATE, 12" SQUARE, 4"
BOTTOM OUTLET, 6" DEEP RECEPTOR WITH ALUMINUM DOME STRAINER, ACID
RESISTANT COATED INTERIOR, SEEPAGE FLANGE WITH CLAMP, DEEP SEAL TRAP.
ZURN (Z1901), SMITH, WADE,
JOSAM, WATTS, SIOUX CHIEF,
SUN
HST-29 PURE WATER SYSTEM - WALL OR COUNTER MOUNTED SYSTEM CAPABLE OF
PRODUCING 0.3 GPM ULTRAPURE WATER. SYSTEM SHALL INCLUDE PRESSURE
REGULATOR, PRESSURE SENSOR(S), PUMP, PUMP BYPASS, POLISHING CARTRIDGE(S),
RESISTIVITY CELL(S), UV LAMP, AUTOMATIC CIRCULATION VALVES AND FLOW METER.
PROVIDE UNIT WITH SEPERATE DISPENSING UNIT AND ALL TUBING REQUIRED TO
CIRCULATE WATER TO AND FROM THE PURIFICATION SYSTEM. DISPENSING UNIT SHALL
BE CAPABLE OF CONTROLABLE FLOWRATES AND APPLICATION SPECIFIC FINAL
FILTRATION AS OWNER'S REQUESTS.
MILLIPORE (MILLI-Q IQ 7000),
APPROVED EQUAL
15 SUNNEN DR
SUITE 104
SAINT LOUIS, MO
63143
PH: 314.645.1132
FAX: 314.645.1173
www.imegcorp.com
NOTES: 1) SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINUMUM OF 2". 2) 1/2" CW AND HW APPLIES ONLY TO THE FINAL VERTICAL RISE-DROP TO EACH FIXTURE, BRANCH PIPING TO VERTICAL RISE-DROP SHALL BE A MINIMUM OF 3/4" UNLESS NOTED OTHERWISE. 3) SIZES SHOWN ARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE SIZES LISTED IN THE
SCHEDULE SHALL DICTATE THE ROUGH-IN SIZE.
PLUMBING FIXTURE ROUGH-IN SCHEDULE
FIXTURE
DESCRIPTION
DOMESTIC
CW
(NOTE 3)
DOMESTIC
HW
(NOTE 3)
SANITARY
(NOTE 3)
VENT
(NOTE 3) REMARKS
FLOOR
DRAIN/FLOOR SINK
- - 3" 1 1/2" -
FLOOR
DRAIN/FLOOR SINK
- - 4" 2" -
LAVATORY 1/2" 1/2" 1 1/4" 1 1/4" NOTE 1 & 2
MEDICAL GAS
OUTLET
NOTES 1 & 2.
MOP BASIN 3/4" 3/4" 3" 1 1/2" -
SINK 1/2" 1/2" 1 1/2" 1 1/2" NOTES 1 & 2
URINAL 3/4" - 2" 1 1/2" -
UTILITY BOX - COLD
WATER
3/4" - - - -
UTILITY BOX - DRAIN - - 2" 1 1/4" -
WATER CLOSET 1" - 4" 2" -
H
C
T
PIPING SYMBOL LIST
SYMBOL: DESCRIPTION:
STEAM TRAP (REFER TO SCHEDULE)
T-*
TEAM TRAP (REFER TO SCHEDULE)
ALIGNMENT GUIDE
PIPE ANCHOR
EXPANSION JOINT
NOT ALL SYMBOLS MAY APPLY.
### TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
HUMIDIFIERH
METERM
OCCUPANCY SENSORO
HUMIDISTAT SENSOR
CARBON DIOXIDE SENSOR
H HUMIDISTAT / SENSOR
FLOW METER
FM
FLOW SWITCH
F
T
THERMOSTAT
TEMPERATURE SENSOR
TEMPERATURE SENSOR WITH WELL
T
THERMOMETER WITH WELL (DIAL TYPE)T
THERMOMETER WITH WELL (FILLED TYPE)
CONTROL VALVE (TWO-WAY)
PIPING SYMBOL LIST
SYMBOL: DESCRIPTION:
PITCH PIPE IN DIRECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
NEW CONNECTION
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
CONTROL VALVE (THREE-WAY)
SOLENOID VALVE
CHECK VALVE
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE (LIQUID/GAS)
PRESSURE REDUCING VALVE (STEAM)
TRIPLE DUTY VALVE (IN-LINE TYPE)
VACUUM BREAKER
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
SUCTION DIFFUSER WITH SUPPORT FOOT
AUTOMATIC AIR VENT
MANUAL AIR VENT
DRAIN VALVE WITH HOSE CONNECTION AND CAP
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
GLYCOL WATER RETURNGWR
GLYCOL WATER SUPPLYGWS
HIGH PRESSURE CONDENSATEHPC
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
REFRIGERANT LIQUIDLIQ
LOW PRESSURE CONDENSATELPC
PUMPED CONDENSATEPC
REFRIGERANT SUCTIONSUC
SAFETY RELIEF VENTSV
DRAINDPP
NOT ALL SYMBOLS MAY APPLY.
PUMP
STATIC SWITCH
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
SP
ROUTE TO DRAIN
STEAM - NO. INDICATES PRESSURE IN PSIG.S15
T-*
PIPING ABBREVIATION KEY
ABBR: DESCRIPTION:
DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")
DIFFERENTIAL PRESSURE SWITCHDPS
PRESSURE SWITCHPS
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
CO CLEANOUT
NC NEW CONNECTION
N.C. NORMALLY CLOSED
NOT IN CONTRACTNIC
NORMALLY OPENN.O.
TYPICAL TYP
UNLESS NOTED OTHERWISEUNO
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
EXHAUST/RELIEF AIREA
C COMMON
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
T101
SIM
DETAIL REFERRED TO BY ELEVATION
SHEET DETAIL IS LOCATED ON
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
SIM
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE
PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR
(DARK LONG DASHED LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN
(LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR
(DARK SHORT DASHED LINE)
LINE TYPE KEY:
BUILDING CODE: IBC 2015 EDITION
FIRE CODE: IFC 2015 EDITION
PLUMBING CODE: UPC 2015
MECHANICAL CODE: IMC 2015 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2017 EDITION
LIFE SAFETY CODE: NFPA 101 2012 EDITION
ENERGY CONSERVATION CODE: IECC 2009
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
NURSE CALL CONTRACTORN.C.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
MEDICAL EQUIPMENT CONTRACTORM.E.C.
CONTRACTING OFFICER'S REPRESENTATIVEC.O.R.
CONTACT PERSONS:
PROJECT MANAGER
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
TECHNOLOGY ENGINEER
JAMES LESSARD, P.E.
ERIC HENDERSON, P.E.
JAMES LESSARD, P.E.
DAVE LARSON, RCDD
DESCRIPTION: PERSON:
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE
GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE
PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS
PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING,
AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE
SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER
FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE
TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS
WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.
15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.
16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.
17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE
CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE
FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD
CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS WORK AND
SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF
ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL
EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT
DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL
SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
MECHANICAL PHASING NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO
ARCHITECT'S INSTRUCTIONS FOR MORE DETAILS, PHASING SCHEDULES AND FOR
CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT
THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY
DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF
THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE
ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF
PROJECT.
4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP
ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
1. THE SIZE OF BRANCH PIPING TO TERMINAL HEATING DEVICES AND COILS SHALL BE 3/4"
UNLESS NOTED OTHERWISE.
2. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN.
3. INSTALL ALL REFRIGERANT LIQUID AND SUCTION PIPING SIZED PER EQUIPMENT
MANUFACTURER RECOMMENDATIONS.
PIPING GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
01/11/2019
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
C R e v it L o c a l F ile s \M
E P
T
.0
V A
S
IO
U X
F A
L L S
L A
B A
D D
IT
IO
N k e it h
.m .p a d g e tt im e g c o rp .c o m
.r v t
/1
/2
:2
:3
A
M
MP000
PIPING COVER SHEET CONSTRUCT LABORATORY
ADDITION
SIOUX FALLS, SOUTH DAKOTA
438-440
JWK EJH
15 SUNNEN DR
SUITE 104
SAINT LOUIS, MO
63143
PH: 314.645.1132
FAX: 314.645.1173
www.imegcorp.com
SHEET INDEX - PIPING
SHEET
NO. SHEET TITLE S
D I S
S U
E
D
I S
S
I S
S
MP000 PIPING COVER SHEET █ █
MP101 GROUND FLOOR PLAN - MECHANICAL - PIPING █ █
MP111 1ST FLOOR PLAN - MECHANICAL -…