5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 1 of 442-21-009 36C259 Department of Veterans Affairs Network Contracting Office
NCO 19
6162 South Willow Drive, Suite 300 Greenwood Village
CO
80111 36C259 Department of Veterans Affairs Network Contracting Office
NCO 19
6162 South Willow Drive, Suite 300 Greenwood Village
CO
80111 To all Offerors/Bidders
36C25921Q0364 04-28-2021
X X X
June 7, 2021 1:00 PM Mountain Time This amendment is created to provide the following:
1. Site visit notes and attendance from Site Visit #2.
2. Questions and answers for RFI #1 to include attachments.
RFI #2
Replace Inaccessible Fire Dampers
1. Refer to the Fire Damper Location Map. Many of the FD/FSD Codes shown on these sheets are illegible.
0. Please provide legible Damper Codes on the Location Map. This is what we have to work with but the COR will lead you to any location as need be.
1. Refer to the Fire Damper Location Map. Table #1 & 2 refer to P-FD-002A, P-FD-003A, P-FD-0016, P-FD-0016A, P-FD-0017, P-FD-0017A, A-FSD-007, & A-FSD-006 that are not shown on the map.
1. Please provide a location for these dampers. P-FD-003A and P-FD-002A are in the return of AHU 5, P-FD-0016 is located inside supply fan 2, P-FD-0016A is located inside supply fan AHU 7, P-FD-0017, P-FD-0017A located inside AHU 2 Supply. A-FSD – 006 located in A attic adjacent to elevator room.
1. Refer to the Fire Damper Location Map, Sheet #3 Shows P-FD-002 & P-FD-003 in the wrong location, not in the Penthouse.
2. Please provide the correct location for P-FD-002 & P-FD-003 on the location map. These are located in A attic adjacent to elevator room. These are labeled as A-FD-002 and AD-FD-003 See reference drawings.
1. Refer to the Solicitation SOW, Item H the contractor is to provide 3rd party testing to confirm the fire dampers pass inspection.
3. Please confirm the only dampers requiring inspection are the ones that failed their initial inspection, A-FSD-006, A-FSD-007, A-FSD-009. This is correct
1. During the Site Walk the group was unable to locate P-FD-002, P-FD-003, A-FSD-006, A-FSD-007, A-FSD-009.
4. Please provide pictures on both sides of the wall/floor for these dampers and indicate their location on the Fire Damper Location Map. Please see added drawings for Fire damper locations, note A-FSD-009 is really 2-FSD-009. No pictures are required.
1. Refer to the Solicitation SOW, Item L indicates duct cleaning is required 15 feet on both sides of the “removal of the inaccessible fire dampers.” As discussed on the Site Walk, the intent of the solicitation is to provide access to the existing dampers, no dampers are to be replaced.
5. Please confirm the intent is to provide access to the existing dampers and repair of the failed actuators on A-FSD-006, A-FSD-007, A-FSD-009, no dampers are required to be replaced. If the dampers are accessible and just need repaired then that meets the scope.
5. Please confirm the AHU’s can be shut down for the required cleaning duration and that the VA will perform an inspection prior to restart of the AHU’s. This will need to be scheduled with the facility but yes for a short period of time.
1. Refer to the Solicitation SOW, Item M specifies “Pictures (.jpg) are required to prove the removal of the inaccessible fire dampers and the installation of new fire dampers.”
6. Please confirm no FD or FSD’s are required to be replaced, the requirement is for new access doors only. If the contractor finds it best to replace the door that is okay, however the FD or the FSD need to be accessible for maintenance.
1. Refer to Table 2 - Inoperable Fire Dampers. The FSD’s listed in this table indicate that they have “Inoperable Actuators”.
7. Please confirm the intent is to repair the inoperable actuators only. Repair unless they are not accessible then they will need to be accessible.
7. Are the actuators powered by pneumatic, high voltage, or low voltage? Low voltage
1. During the 2nd Site Walk on 5/12/21, a new table was distributed, not the table included with the solicitation.
8. Please issue the new/revised table by Amendment. I will send this back, but I believe these lists were identical.
8. Please clarify the intent of the note “access door install not authorized-?” This is an error and access door install is authorized as long as it meets NFPA.
1. Refer to Table 1 - Inaccessible Fire Dampers. 1-FD-015 & 1-FSD-013 indicate “immovable object blocking work area”. No repair design is specified.
9. Please provide desired repair design for accurate pricing. This is on the contractors to come up with the repair as per NFPA.
1. During the Site Walk, the VA representative indicated that this is a “Design-Build’ Project. The Solicitation does not indicate that this is a Design-Build Project, which would require a design team, not included in the VA’s estimate.
10. Please confirm this is not a Design-Build Project.
This is labeled as a design build, but no design is needed. We are looking for a detailed plan on how you will solve the issue and details for where you will located the dampers. We are looking for a detailed plan on how you will solve the problem though. Not a design.
1. During the Site Walk, inspection of the access doors for P-FD-002A & P-FD-003A indicated they were not located at the horizontal rated assembly, no fire damper was visible.
11. Please provide access to the rated assemble and fire damper for inspection. We can provide access. Answered Already
1. Refer to the Fire Damper Location Map. Many of the FD/FSD Codes shown on these sheets are illegible.
12. Please provide legible Damper Codes on the Location Map. Answered Already
1. Refer to the Fire Damper Location Map. Table #1 & 2 refer to P-FD-002A, P-FD-003A, P-FD-0016, P-FD-0016A, P-FD-0017, P-FD-0017A, A-FSD-007, & A-FSD-006 that are not shown on the map.
13. Please provide a location for these dampers. Answered already
1. Refer to the Fire Damper Location Map, Sheet #3 Shows P-FD-002 & P-FD-003 in the wrong location, not in the Penthouse.
14. Please provide the correct location for P-FD-002 & P-FD-003 on the location map. Answered already
1. Refer to the Solicitation SOW, Item H the contractor is to provide 3rd party testing to confirm the fire dampers pass inspection.
15. Please confirm the only dampers requiring inspection are the ones that failed their initial inspection, A-FSD-006, A-FSD-007, A-FSD-009. This is correct
1. During the Site Walk the group was unable to locate P-FD-002, P-FD-003, A-FSD-006, A-FSD-007, A-FSD-009.
16. Please provide pictures on both sides of the wall/floor for these dampers and indicate their location on the Fire Damper Location Map. Please see added drawings for Fire damper locations, note A-FSD-009 is really 2-FSD-009. No pictures are required.
1. Refer to the Solicitation SOW, Item L indicates duct cleaning is required 15 feet on both sides of the “removal of the inaccessible fire dampers.” As discussed on the Site Walk, the intent of the solicitation is to provide access to the existing dampers, no dampers are to be replaced.
17. Please confirm the intent is to provide access to the existing dampers and repair of the failed actuators on A-FSD-006, A-FSD-007, A-FSD-009. If the dampers are accessible and just need repaired then that meets the scope.
17. Please confirm the AHU’s can be shut down for the required cleaning duration and that the VA will perform an inspection prior to restart of the AHU’s. This will need to be scheduled with the facility but yes for a short period of time.
1. Refer to the Solicitation SOW, Item M specifies “Pictures (.jpg) are required to prove the removal of the inaccessible fire dampers and the installation of new fire dampers.”
18. Please confirm no FD or FSD’s are required to be replaced, the requirement is for new access doors only. If the contractor finds it best to replace the door that is okay, however the FD or the FSD need to be accessible for maintenance.
1. Refer to Table 2 - Inoperable Fire Dampers. The FSD’s listed in this table indicate that they have “Inoperable Actuators”.
19. Please confirm the intent is to repair the inoperable actuators only. They are intended to be repaired unless inaccessible which then they will need to be made accessible.
19. Are the actuators powered by pneumatic, high voltage, or low voltage? Low voltage
1. During the 2nd Site Walk on 5/12/21, a new table was distributed, not the table included with the solicitation.
20. Please issue the new/revised table by Amendment. I will send this back, but I believe these lists were identical.
20. Please clarify the intent of the note “access door install not authorized-?” This in incorrect, access door installs are authorized.
1. Refer to Table 1 - Inaccessible Fire Dampers. 1-FD-015 & 1-FSD-013 indicate “immovable object blocking work area”. No repair design is specified.
21. Please provide desired repair design for accurate pricing.
Contractor needs to come up with a plan on how to repair or replace.
1. During the Site Walk, the VA representative indicated that this is a “Design-Build’ Project. The Solicitation does not indicate that this is a Design-Build Project, which would require a design team, not included in the VA’s estimate.
22. Please confirm this is not a Design-Build Project.
This is labeled as a design build, but no design is needed. We are looking for a detailed plan on how you will solve the problem though. Not a design.
1. During the Site Walk, inspection of the access doors for P-FD-002A & P-FD-003A indicated they were not located at the horizontal rated assembly, no fire damper was visible.
23. Please provide access to the rated assemble and fire damper for inspection. Answered Already
1. The SOW wording refers to Repair and Install/Replace. May repairable dampers be repaired or does the VA expect all dampers to be replaced, even if repair is possible? Repair is possible as long as it is accessible determined by the COR.
1. For dampers that require the installation of access panels followed by inspection, does the VA expect those dampers inspected for the first time and subsequently requiring repair, to be repaired or replaced free of charge or will these repairs be quoted separately as needed? I don’t understand this question, may be out of scope
1. For dampers blocked by pipe, structural steel, concrete, electrical, etc. does the VA expect the contractor to relocated pipe and other immovable objects as part of the base bid? If so, please provide applicable system drawings for applicable systems surrounding the dampers involved. The least invasive approach will be the acceptable one. I do not for see any moving of structural steel, pipe, or electrical.
CONTINUATION PAGE
See attached document: fire damper floor 2.
See attached document: FD Attic.