63516102-Bid_Documents-Drawings-050418.pdf

PDF 7 MB Posted

Attached to
Increase Electrical Capacity to 9th Floor Server Room Federal contract opportunity
Solicitation number
36C25919R0031
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

36C25919R0031 63516102-Bid Documents-Drawings-050418.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Increase Electrical Capacity to 9th Floor Server Room, newest first.
File Type Posted
36C25919C0088-000.docx DOCX document
36C25919R0031-0004000.docx DOCX document
36C25919R0031-0004001.pdf PDF
36C25919R0031_0003.docx DOCX document
36C25919R0031_0002.docx DOCX document
RFI__1.pdf PDF
36C25919R0031_0001.docx DOCX document
63516102-Bid_Documents-Specifications-050418-3.pdf PDF
S02_Past_Performance_Questionnaire.docx DOCX document
36C25919R0031_2.docx DOCX document
S02_Calculation_of_Self-Performed_and_Subcontracted_Work.docx DOCX document
63516102-Bid_Documents-Specifications-050418-2.pdf PDF
63516102-Bid_Documents-Specifications-050418-1.pdf PDF
36C25919R0031-000.docx DOCX document
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NE 13th STREET

NE 13th STREET

N

K

E L L Y

S

T R

E E

T

E

F

A

C

G

B

D

N

M c M

E C

H A

N

S

T R

E E

T

PROJECT LOCATION:

PROJECT TITLE:

BUILDING NUMBER: A

DRAWING INDEX

DRAWING

NUMBER

PDF PAGE

NUMBER

DRAWING TITLE

GENERAL

G-001 1 COVER SHEET

G-002 2 INFECTION CONTROL NOTES, CONSTRUCTION PHASING NOTES

E-101

E-103

E-104

ELECTRICAL

PARTIAL FIRST FLOOR - ELECTRICAL CONSTRUCTION PLAN

PARTIAL NINTH FLOOR - ELECTRICAL CONSTRUCTION PLAN

TENTH FLOOR - ELECTRICAL CONSTRUCTION PLAN

E-107

E-001 ELECTRICAL GENERAL NOTES, SYMBOLS AND DETAIL

E-102 PARTIAL SECOND FLOOR - ELECTRICAL CONSTRUCTION PLAN

E-105 ELEVENTH FLOOR / PENTHOUSE - ELECTRICAL CONSTRUCTION PLAN

E-106 PARTIAL NINTH FLOOR - ELECTRICAL SERVER ROOM CONSTRUCTION PLAN

ARCHITECTURAL

A-201 3 EXTERIOR ELEVATION

A-501 4 ARCHITECTURAL DETAILS

A-502 5 ARCHITECTURAL DETAILS

E-601 ELECTRICAL RISER DIAGRAM15

TENTH FLOOR REFLECTED CEILING - ELECTRICAL CONSTRUCTION PLAN

A-503 6 ARCHITECTURAL DETAILS

NORTH

X

A-501

A-502

NORTH

GENERAL NOTES

KEY NOTES

1. EXISTING EXIT DOOR AND PASSAGE WAY TO REMAIN CLEAR

AT ALL TIMES. CONTRACTOR WILL PROVIDE TEMPORARY

ENCLOSURE DURING ALL CONSTRUCTION ACTIVITIES.

2. REFER TO DRAWING E-101 FOR EXISTING ELECTRICAL

SWITCHGEAR (ELECTRICAL SUBSTATION - 1G137) AND

RELATED WORK.

3. EXISTING ROOF DECK. REFER TO DRAWING E-102 FOR

CONDUIT PENETRATIONS AND RELATED WORK.

4. EXISTING EXTERIOR BUILDING WALL PROFILE LINE.

5. CONTRACTOR WILL PROTECT ALL EXISTING WINDOW UNITS

ADJACENT TO PROJECT AREA DURING CONSTRUCTION

ACTIVITIES. REFER TO NOTES ON DRAWING A-502 FOR FINAL

CLEANING OF WINDOW SYSTEMS AT PROJECT COMPLETION

PHASE.

6. EXISTING FACE BRICK EXTERIOR WALL.

7. EXISTING ROOF DECK. NO CONSTRUCTION STAGING OR

MATERIAL STORAGE WILL BE ALLOWED AT THIS ROOF AREA.

8. PROVIDE ALUMINUM SCREENWALL SYSTEM AND

ASSOCIATED STEEL SUPPORT/FRAMING SYSTEM. REFER TO

DETAIL SECTIONS AND PLANS FOR REQUIRED WORK.

9. EXISTING THROUGH-WALL SCUPPER IS SCHEDULED TO

REMAIN.

10. EXISTING LIMESTONE COPING IS SCHEDULED TO REMAIN.

11. REFER TO DRAWING E-105 FOR CONDUIT ROUTING AT THIS

ROOF DECK LEVEL.

12. REFER TO DRAWING E-102 FOR CONDUIT ROUTING AT THIS

ROOF DECK LEVEL.

13. INDICATES EXISTING FINISH FLOOR ELEVATION.

CONTRACTOR WILL VERIFY ALL FLOOR-TO-FLOOR

ELEVATION DIMENSIONS PRIOR TO FABRICATION OF STEEL

FRAMING/SUPPORT SYSTEM.

14. BOTTOM ELEVATION OF STEEL FRAMING SYSTEM WILL BE

APPROXIMATELY 3-FEET ABOVE EXISTING ROOF DECK.

15. CONTRACTOR WILL PROVIDE SURVEY DOCUMENTATION OF

EXTERIOR BUILDING FACADE FOR FLOOR-TO-FLOOR

ELEVATIONS AND FOR VERTICAL ALIGNMENT OF EXTERIOR

MASONRY WALL FROM SECOND FLOOR LEVEL ROOF DECK

UP TO ELEVENTH FLOOR LEVEL. SUBMIT FIELD

DOCUMENTATION TO VA AND ARCHITECT FOR REVIEW AND

RECORD.

TYPICAL

1. REFER TO DRAWING G-002 FOR INFECTION CONTROL NOTES

AND CONSTRUCTION PHASING NOTES.

2. REFER TO DRAWING E-001 FOR ELECTRICAL GENERAL

NOTES, ELECTRICAL SYMBOLS LIST AND BASIS OF DESIGN.

3. REFER TO SPECIFICATIONS APPENDIX SECTION A AND B

FOR PHOTO DOCUMENTATION OF EXISTING CONDITIONS.

4. REFER TO DRAWING E-601 FOR ELECTRICAL RISER

DIAGRAM.

A-502

A-502

A-502

A-502

NORTH

GENERAL NOTES

KEY NOTES

1. EXISTING CONCRETE FLOOR SLAB/DECK.

2. EXISTING CONCRETE ENCASEMENT AT EXISTING STEEL

FRAMING MEMBERS.

3. EXISTING INTERIOR MASONRY WALL CONSTRUCTION.

4. EXISTING EXTERIOR FACE BRICK WALL CONSTRUCTION.

5. EXISTING STEEL ANGLE ATTACHED TO CONCRETE

ENCASEMENT.

6. PROVIDE STEEL SUPPORT BRACKET. REFER TO DETAIL A-502

FOR ADDITIONAL INFORMATION.

7. PROVIDE WEDGE/EXPANSION ANCHORS AT STEEL BRACKET

TOP AND SLEEVE ANCHOR AT STEEL BRACKET BOTTOM.

WEDGE/EXPANSION ANCHORS WILL BE INSTALLED INTO

EXISTING CONCRETE ENCASEMENT. SLEEVE ANCHOR WILL BE

INSTALLED INTO FACE BRICK UNITS. REFER TO SPECIFICATION

APPENDIX A AND B FOR EXISTING CONSTRUCTION DETAILS.

8. PROVIDE HORIZONTAL STEEL ANGLE. REFER TO DETAIL ON

A-502 FOR ADDITIONAL INFORMATION. STEEL ANGLE WILL BE

8x4x1/2.

9. PROVIDE VERTICAL STEEL ANGLE HANGER MEMBERS. REFER

TO DETAIL ON A-502 FOR ADDITIONAL INFORMATION.

10. PROVIDE ALUMINUM SCREENWALL SYSTEM. REFER TO

DETAILS ON DRAWING A-502 FOR ADDITIONAL INFORMATION.

11. REFER TO ELECTRICAL DRAWINGS FOR VERTICAL CONDUITS

AND ASSOCIATED WORK TIMES.

12. PROVIDE HORIZONTAL STEEL ANGLE FRAMING. REFER TO

DRAWINGS A-502 FOR ADDITIONAL INFORMATION.

13. PROVIDE STEEL ANGLE MEMBERS ANCHORED INTO EXISTING

FACE BRICK UNITS WITH SLEEVE TYPE ANCHORS. REFER TO

DRAWING A-502 FOR ADDITIONAL INFORMATION.

1. REFER TO DRAWING G-002 FOR INFECTION CONTROL NOTES

AND CONSTRUCTION PHASING NOTES.

2. REFER TO DRAWING E-001 FOR ELECTRICAL GENERAL

NOTES, ELECTRICAL SYMBOLS LIST AND BASIS OF DESIGN.

3. REFER TO SPECIFICATIONS APPENDIX SECTION A AND B

FOR PHOTO DOCUMENTATION OF EXISTING CONDITIONS.

4. REFER TO DRAWING E-601 FOR ELECTRICAL RISER

A-502

A-502

A-502

NORTH

GENERAL NOTES

KEY NOTES

1. EXISTING EXTERIOR MASONRY WALL CONSTRUCTION.

2. EXISTING WINDOW UNITS. CONTRACTOR WILL PROVIDE

TEMPORARY PROTECTION AT ALL UNITS DURING ALL

CONSTRUCTION ACTIVITIES. AT PROJECT COMPLETION

PHASE OF WORK CONTRACTOR WILL CLEAN ALL WINDOW

UNITS ADJACENT TO WORK AREA.

3. PROVIDE STEEL ANGLE FRAMING SYSTEM. ALL EXPOSED

STEEL FRAMING MEMBERS WILL BE GALVANIZED. REFER TO

MATERIAL SPECIFICATION NOTES ON DRAWING A-503.

4. PROVIDE ALUMINUM SCREENWALL SYSTEM.

5. PROVIDE THREE 5-INCH CONDUITS. REFER TO ELECTRICAL

DRAWINGS FOR FEEDER CABLE SIZES AND QUANTITIES.

6. PROVIDE HORIZONTAL STEEL ANGLE FRAMING MEMBER,

ANCHOR TO STEEL BRACKET. REFER TO ENLARGED DETAIL.

7. PROVIDE STEEL OFFSET BRACKETS AT EACH CONDUIT.

REFER TO ENLARGED DETAIL ON THIS DRAWING FOR

ADDITIONAL INFORMATION.

8. PROVIDE VERTICAL STEEL ANGLE HANGERS. REFER TO

ENLARGED DETAIL FOR ASSOCIATED STEEL CLIP ANGLES.

9. PROVIDE TWO STEEL BRACKETS AT EACH FLOOR LINE

ELEVATION. STEEL BRACKETS WILL BE ANCHORED INTO

EXISTING CONCRETE BEAM. PROVIDE SEALANT SYSTEM AT

ALL WEDGE ANCHORS/HOLES AT EXISTING FACE BRICK

UNITS. REFER TO PARTIAL BUILDING ELEVATION ON

DRAWING A-501 FOR FLOOR-TO-FLOOR DIMENSIONS. REFER

TO ENLARGED DETAIL FOR ANCHORING REQUIREMENTS.

1. REFER TO DRAWING G-OO2 FOR INFECTION CONTROL

NOTES AND CONSTRUCTION PHASING NOTES.

2. REFER TO DRAWING E-001 FOR ELECTRICAL GENERAL

NOTES, ELECTRICAL SYMBOLS LIST AND BASIS OF DESIGN.

3. REFER TO SPECIFICATIONS APPENDIX SECTION A FOR

PHOTO DOCUMENTATION OF EXISTING CONDITIONS.

4. REFER TO DRAWING E-610 FOR ELECTRICAL RISER

MATERIAL SPECIFICATIONS

1. ALUMINUM SCREENWALL SYSTEM WILL BE AS MANUFACTURED

BY CONSTRUCTION SPECIALTIES INC. OR VA APPROVED

EQUAL. PROVIDE VERT-A-CADE 1100 SCREEN SYSTEM

INCLUDING SUPPORTS, ANCHORAGE AND ACCESSORIES

REQUIRED FOR COMPLETE ASSEMBLY. BLADES TO BE

FABRICATED FROM EXTRUDED ALUMINUM SECTIONS IN

6063-T5 ALLOY, MINIMUM 0.081-INCH THICK AND SPACED

APPROXIMATELY 5-1 / 4 INCH ON CENTER. BLADES TO BE

NOMINAL 2-5/16 INCH DEEP. ALL FASTENERS WILL BE

STAINLESS STEEL. REFER TO PROJECT SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS.

2. MEDIUM WELDED STEEL BRACKET WILL BE AS

MANUFACTURED BY ANVIL OR VA APPROVED EQUAL. BRACKET

NUMBER 1. WEIGHT 51.8, 18-INCH WIDE BY 24-INCH HIGH.

MATERIAL WILL BE CARBON STEEL, FINISH HOT-DIP

GALVANIZED. COMPLY WITH FEDERAL SPECIFICATION

A-A-1192A. MAXIMUM LOAD 1,500 POUNDS.

3. STAINLESS STEEL OFFSET PIPE CLAMP WILL BE AS

MANUFACTURED BY FM STAINLESS STEEL, LLC OR VA

APPROVED EQUAL. ITEM # 63-5, MATERIAL WILL BE 304

STAINLESS STEEL, CONDUIT SIZE IS 5-INCH I.D. PROVIDE ALL

ACCESSORIES FOR ATTACHMENT. ITEM # HHB - 1/2, STAINLESS

STEEL HEAVY HEX BOLTS WITH UNC THREADS 1 / 2 -INCH

DIAMETER BOLT BY LENGTH REQUIRED, ITEM # HHN - 1/2

STAINLESS STEEL HEAVY HEX NUTS.

4. WEDGE ANCHORS WILL BE AS MANUFACTURED BY FM

STAINLESS STEEL, LLC OR VA APPROVED EQUAL. SIZE OF

ANCHOR 3/4-INCH DIAMETER. ANCHOR MATERIAL

COMPOSITION BODY 304 STAINLESS STEEL, CLIP 304

STAINLESS STEEL, NUT 18-8, WASHER 18-8, PLATING TYPE 4,

CLASS 1 PASSIVATED. LENGTH OF BODY 8-INCH FOR 3-INCH

EMBEDMENT.

5. SLEEVE ANCHORS WILL BE AS MANUFACTURED BY FM

STAINLESS STEEL, LLC OR VA APPROVED EQUAL. SIZE OF

ANCHOR 5/8-INCH DIAMETER. ANCHOR MATERIAL

COMPOSITION BODY 304 STAINLESS STEEL, CLIP 304

STAINLESS STEEL, NUT 18-8, WASHER 18-8, PLATING TYPE 4,

CLASS 1 PASSIVATED. LENGTH OF BODY +/- 5-INCH FOR 2-INCH

MINIMUM EMBEDMENT.

STRUCTURAL NOTES

1. ALL STRUCTURAL STEEL WORK WILL CONFORM TO THE

MOST CURRENT PUBLISHED EDITIONS OF AISC:

A. “SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS”

B. “SPECIFICATIONS FOR STRUCTURAL JOINTS USING

ASTM A325 BOLTS”

2. CONTRACTOR WILL PROVIDE STRUCTURAL STEEL ERECTION

AND SHOP DRAWINGS IN ACCORDANCE WITH THE

GUIDELINES AND GOOD PRACTICES NOTED IN THE AISC

“DETAILING FOR STEEL CONSTRUCTION”.

3. ALL STEEL FRAMING CONNECTIONS WILL BE BOLTED. NO

FIELD WELDING WILL BE ALLOWED.

4. STEEL SHOP DRAWINGS WILL BE SUBMITTED FOR REVIEW

AND COMMENT FOR ALL STEEL FRAMING SYSTEMS AND

DETAILS SPECIFIED ON DRAWINGS.

5. CONTRACTOR WILL BE REQUIRED TO FIELD MEASURE

EXISTING BUILDING COMPONENTS AS IT RELATES TO

DIMENSIONS OF STEEL FRAMING SYSTEMS.

6. ALL STEEL MEMBERS WILL BE GALVANIZED MATERIAL

CONFORMING TO ASTM A123.

7. ALL WEDGE AND SLEEVE ANCHOR LOCATIONS WILL BE

INSPECTED. PROVIDE SPECIAL INSPECTION UNDER THE IBC

IN ACCORDANCE WITH SECTION 1704 AND 1705 OF THE IBC.

ADDITIONAL REQUIREMENTS AS SET FORTH IN SECTIONS

1705 AND 1706 MUST BE OBSERVED, WHERE APPLICABLE.

PROVIDE WRITTEN REPORT FROM INDEPENDENT

INSPECTION AGENCY THAT INCLUDES THE FOLLOWING

DETAILS :

A. ANCHOR DESCRIPTION, INCLUDING THE ANCHOR

PRODUCT NAME, NOMINAL ANCHOR AND BOLT

DIAMETERS, AND ANCHOR LENGTH.

B. HOLE DESCRIPTION, INCLUDING VERIFICATION OF

DRILL BIT COMPLIANCE WITH ANSI B212.15-1994.

C. INSTALLATION DESCRIPTION, INCLUDING VERIFICATION

OF MASONRY COMPRESSIVE STRENGTH AND

VERIFICATION OF ANCHOR INSTALLATION AND

LOCATION (SPACING AND EDGE DISTANCE).

ABBREVIATION DESCRIPTIONSYMBOL

ELEVATOR

P-1

ELEVATOR

P-2

ELEVATOR

P-3

ELEVATOR

P-4

ELEVATOR

P-5

ELEVATOR

P-6

TOILET

MALE

1B117

ELECTRICAL

SUBSTATION

1G137

STAFF

WORK AREA

OFFICE

INTERN/

EXECUTIVE

ASSISTANT

1A105F

OFFICE

PRIVACY

OFFICER

1A105G

OFFICE

DEPUTY

DIRECTOR

1A105E

OFFICE

PUBLIC

AFFAIRS

1A105D

STORAGE

1A101

ELEC

1A102

ELEC

1A100

ELECTRICAL

1A103

STAIR 1

TOILET

FEMALE

1B116

DN UP

MEDS

1G134

EXAM 6

1G124

EXAM 4

1G122

EXAM 2

1G120

OPEN TO DECK

NORTH

GENERAL NOTES

1. REFER TO DRAWING G-002 FOR INFECTION CONTROL NOTES

AND CONSTRUCTION PHASING NOTES.

2. REFER TO DRAWING E-001 FOR ELECTRICAL GENERAL

NOTES, ELECTRICAL SYMBOLS LIST AND BASIS OF DESIGN.

3. REFER TO SPECIFICATIONS APPENDIX SECTION A AND B

FOR PHOTO DOCUMENTATION OF EXISTING CONDITIONS.

4. REFER TO DRAWING E-601 FOR ELECTRICAL RISER

DIAGRAM.

KEY NOTES

NORTH

1. EXISTING FEEDER CIRCUIT BREAKER 600AF/200AT, 3P TO BE

REUSED. INCREASE THE TAP SETTING TO 400 AMPHERES.

2. PROVIDE FEEDER CONDUIT FOR NEW UPS "10AUPS-SR" WITH

TWO (2) SETS 4 #300 KCMIL & ONE (1) #2 GRD IN 5" CONDUIT.

3. PROVIDE FEEDER CONDUIT FOR EXISTING "PANELBOARD

10AC1-2-SR" WITH 4 #500 KCMIL & 1 #3 GRD IN 5" CONDUIT.

4. PROVIDE ONE (1) 5" CONDUIT SPARE.

5. CONTRACTOR WILL PROVIDE WRITTEN NOTIFICATION TO

VA/COR PRIOR TO DE-ENERGIZING EXISTING EMERGENCY

SWITCHGEAR. REFER TO SPECIFICATION SECTIONS 01 00 00

GENERAL REQUIREMENTS 1.6 OPERATIONS AND STORAGE

AREAS, 01 35 26 SAFETY REQUIREMENTS 1.15 ELECTRICAL

AND 26 05 11 REQUIREMENTS FOR ELECTRICAL

INSTALLATIONS 1.9 WORK PERFORMANCE.

6. ROUTE THREE (3) 5-INCH CONDUITS UP THROUGH METAL

ROOF DECK. EXISTING ROOF STRUCTURE IS A CONCRETE

AND METAL DECK ASSEMBLY. THE UNDERSIDE/EXPOSED

METAL ROOF DECK HAS A SPRAYED ON FIRE PROOFING

SYSTEM. AFTER ROOF DECK PENETRATIONS ARE

COMPLETED FOR CONDUIT INSTALLATION PROVIDE ALL

WATER STOPPING SYSTEMS AT DECK OPENINGS. PROVIDE

SPRAYED ON FIRE PROOFING FOR A 2 HOUR U.L. RATED

ASSEMBLY AT CONDUIT PENETRATIONS.

7. REFER TO DRAWING E-102, E-103, E-104 AND E-105 FOR

CONTINUATION.

8. ROOF SYSTEMS ARE UNDER A ROOFING SYSTEM

WARRANTY. CONTRACTOR WILL UTILIZE A CERTIFIED

ROOFING CONTRACTOR APPROVED BY ROOF MEMBRANE

MANUFACTURER FOR ALL ROOF SYSTEM RENOVATIONS AND

MODIFICATIONS. VA/COR WILL PROVIDE COPY OF WARRANTY

INFORMATION TO CONTRACTOR AWARDED THE PROJECT.

ELEVATOR

P-2

ELEVATOR

P-3

ELEVATOR

P-4

ELEVATOR

P-5

ELEVATOR

P-6

ELECTRICAL

SUBSTATION

1G137

[BELOW]

STORAGE

TELE/

DATA

2A101

ELEC

2A100

ELECTRICAL

2A102

STAIR 1

DN UP

RD RDODOD

TOILET

SHOWER

2A104A

PATIENT

ROOM

2A104

TOILET

SHOWER

2A103A

PATIENT

ROOM

2A103

MECHANICAL

ROOM

2G100

TOILET

2B129

OFFICE

2B128

ROOF

ROOF

NORTH

GENERAL NOTES

1. REFER TO DRAWING G-002 FOR INFECTION CONTROL NOTES

AND CONSTRUCTION PHASING NOTES.

2. REFER TO DRAWING E-001 FOR ELECTRICAL GENERAL

NOTES, ELECTRICAL SYMBOLS LIST AND BASIS OF DESIGN.

3. REFER TO SPECIFICATIONS APPENDIX SECTION A AND B FOR

PHOTO DOCUMENTATION OF EXISTING CONDITIONS.

4. REFER TO DRAWING E-601 FOR ELECTRICAL RISER DIAGRAM.

KEY NOTES

1. EXISTING ROOF MOUNTED EXHAUST FAN SCHEDULED TO

REMAIN.

2. EXISTING OVER FLOW ROOF DRAIN SCHEDULED TO

REMAIN.

3. EXISTING ROOF DRAIN SCHEDULED TO REMAIN.

4. EXISTING LOW ROOF AREA OVER ENTRY EXIT VESTIBULE.

5. EXISTING STEEL PIPING SCHEDULED TO REMAIN.

6. EXISTING ROOF MOUNT FRESH AIR INTAKE SCHEDULED TO

REMAIN.

7. EXISTING WINDOW UNITS SCHEDULED TO REMAIN.

8. INDICATES LOCATION OF CONDUITS ROUTED THROUGH

EXISTING ROOF DECK FROM EXISTING ELECTRICAL

SWITCHGEAR ROOM BELOW. ROUTE CONDUITS ALONG

EXISTING MASONRY WALL CONSTRUCTION TO POINT

INDICATED.

9. INDICATES LOCATION OF CONDUITS ROUTED VERTICALLY

UP TO ELEVENTH FLOOR LEVEL/ROOF DECK. CONDUIT

STEEL SUPPORT SYSTEM WILL BE CENTERED BETWEEN

THE TWO EXISTING WINDOW UNITS.

10. PROVIDE TEMPORARY ROOF PROTECTION DURING ALL

CONSTRUCTION ACTIVITIES. CLEAN ROOF AREA AT THE

COMPLETION OF EACH WORK DAY.

11. PROVIDE NEMA TYPE 3R PULL BOX AS REQUIRED.

12. PROVIDE 3-5" CONDUITS AND SPECIFIED POWER

WIRING/CABLES, REFER TO DRAWING E-601.

13. ROOF SYSTEMS ARE UNDER A ROOFING SYSTEM

WARRANTY. CONTRACTOR WILL UTILIZE A CERTIFIED

ROOFING CONTRACTOR APPROVED BY ROOF MEMBRANE

MANUFACTURER FOR ALL ROOF SYSTEM RENOVATIONS

AND MODIFICATIONS. VA/COR WILL PROVIDE COPY OF

WARRANTY INFORMATION TO CONTRACTOR AWARDED THE

PROJECT.

ELEVATOR

P-2

ELEVATOR

P-3

ELEVATOR

P-4

ELEVATOR

P-5

ELEVATOR

P-6

ELEC

CLOSET

9A100

TELE/

DATA

9A101

ELECTRICAL

CLOSET

9A102

STAIR 1

OFFICE

INTERIOR

DESIGN

OFFICE

CHIEF

ENGINEER

IRM

CLASSROOM

9A103

H.A.C.

9A125

H.A.C.

9A126

DN UP

SERVER

ROOM

9A123a

OFFICE

TECHNICIAN

9A123

TOILET

FEMALE

9A122

TOILET

MALE

9A121

OFFICE

TECHNICIAN

9A120

OFFICE

TECHNICIAN

9A120A

TELE /

DATA

9A118

OFFICE

COMPUTER

LAB

9A123M

OFFICE

9A124A

OFFICE

IT SERVICE DESK

9A124

OFFICE

INDUSTRIAL

HYGIENIST

9B100A

SAFETY

MANAGER

9B100B

LAB

9B100C

STORAGE

9B100D

OFFICE

SECRETARY

ENGINEERING

RECEPTION/PURCHASING

9B100

NORTH

NORTH

GENERAL NOTES

1. REFER TO DRAWING G-OO2 FOR INFECTION CONTROL

NOTES AND CONSTRUCTION PHASING NOTES.

2. REFER TO DRAWING E-001 FOR ELECTRICAL GENERAL

NOTES, ELECTRICAL SYMBOLS LIST AND BASIS OF DESIGN.

3. REFER TO SPECIFICATIONS APPENDIX SECTION A FOR

PHOTO DOCUMENTATION OF EXISTING CONDITIONS.

4. REFER TO DRAWING E-610 FOR ELECTRICAL RISER

DIAGRAM.

KEY NOTES

1. REMOVE SECTIONS OF EXISTING SUSPENDED CEILING

SYSTEM AS REQUIRED TO PERFORM SPECIFIED WORK.

2. PROVIDE CONDUITS UP THROUGH CONCRETE ROOF DECK.

3. INDICATES EXISTING SPRINKLER HEAD AT SUSPENDED

CEILING SYSTEM.

4. INDICATES EXISTING VENT STACK SCHEDULED TO REMAIN.

5. ROUTE CONDUITS VERTICALLY UP TO ELEVENTH FLOOR

LEVEL/ROOF DECK.

6. LOCATE STEEL SUPPORT SYSTEM AT CENTER POINT

BETWEEN THE TWO EXISTING WINDOW OPENINGS.

7. PROVIDE STEEL CONDUIT SUPPORT SYSTEM MOUNTING

BRACKETS AT EACH EXISTING FLOOR LEVEL/ELEVATION.

STEEL SUPPORT BRACKETS ARE LOCATED

APPROXIMATELY AT EVERY 11'-6" VERTICALLY.

8. PROVIDE ALUMINUM SCREENWALL SYSTEM.

9. REFER TO TYPICAL STEEL CONDUIT SUPPORT BRACKET

DETAIL ON DRAWINGS A-501, A-502 AND A-503 FOR

ADDITIONAL INFORMATION.

ELEVATOR

P-2

ELEVATOR

P-3

ELEVATOR

P-4

ELEVATOR

P-5

ELEVATOR

P-6

STAIR 1

10A103

DN

ROOF LEVEL

[ABOVE NINTH FLOOR]

A-503

TELEPHONE

ROOM

10A100

MECHANICAL

ROOM

10A102

10A101

A-503

NORTH

NORTH

GENERAL NOTES

1. REFER TO DRAWING G-002 FOR INFECTION CONTROL NOTES

AND CONSTRUCTION PHASING NOTES.

2. REFER TO DRAWING E-001 FOR ELECTRICAL GENERAL NOTES,

ELECTRICAL SYMBOL LIST AND BASIS OF DEIGN.

3. REFER TO SPECIFICATIONS APPENDIX SECTION A AND B FOR

PHOTO DOCUMENTATION OF EXISTING CONDITIONS.

4. REFER TO DRAWING E-601 FOR ELECTRICAL RISER DIAGRAM.

KEY NOTES

1. PROVIDE THREE (3) CONDUITS ON STEEL SUPPORT

SYSTEM. CONDUITS EXTEND UP TO ELEVENTH FLOOR

LEVEL/ROOF DECK. REFER TO DRAWING E-105. PROVIDE

STEEL SUPPORT SYSTEM AND ALUMINUM SCREENWALL

SYSTEM. REFER TO ARCHITECTURAL DRAWINGS A-201

AND A-501, A-502 AND A-503 FOR ADDITIONAL INFORMATION

AND REQUIREMENTS.

2. PROVIDE UPS SYSTEM. REFER TO DRAWING E-601 AND

SPECIFICATIONS, SECTION 26 33 53 STATIC

UNINTERRUPTIBLE POWER SUPPLY FOR PRODUCT

DESCRIPTION AND REQUIREMENTS.

3. PROVIDE ELECTRIC PANELBOARD - 10AC1-2-SR, SURFACE

MOUNTED.

4. ROUTE OF CONDUITS UP TO ELEVENTH FLOOR

LEVEL/ROOF DECK.

5. PROVIDE HORIZONTAL CONDUIT ROUTING ON EXISTING

EXTERIOR MASONRY WALL. LOCATE CONDUITS

APPROXIMATELY 2'-0" ABOVE EXISTING DOOR OPENING.

6. EXTEND CONDUITS DOWN EXISTING MASONRY WALL AND

CONTINUE OVER EXISTING ROOF AREA TO POINT OF

PENETRATION TO NINTH FLOOR LEVEL SERVER ROOM.

7. PROVIDE INSULATED EQUIPMENT CURB FOR CONDUIT

INSTALLATION. CORE DRILL EXISTING CONCRETE ROOF

DECK FOR CONDUIT INSTALLATION. REFER TO TYPICAL

DETAIL ON DRAWING A-503.

8. EXISTING VENT STACK SCHEDULED TO REMAIN.

9. DISCONNECT AND REMOVE EXISTING DISCONNECT

SWITCH, POWER WIRING AND RELATED CONDUIT

SYSTEMS. REMOVE POWER WIRING BACK TO RESPECTIVE

PANELBOARD AT NINTH FLOOR SERVER ROOM. PROVIDE

DISCONNECT SWITCH AT ROOF MOUNTED EXISTING AC-1

AND AC-2 UNITS. PROVIDE CONDUITS AND POWER WIRING

BACK TO PANELBOARD 10AC1-2-SR. ROUTE CONDUITS ON

ROOF DECK, REFER TO PIPE MOUNTING PEDESTAL DETAIL

ON DRAWING A-503. REFER TO APPENDIX A FOR PHOTO

VIEWS AT EXISTING CONDENSING UNITS.

10. REMOVE EXISTING WALL MOUNTED FURNITURE SYSTEM.

RETURN TO VA AND MOVE/TANSPORT TO STORAGE ROOM

AS DIRECTED BY VA/COR. REMOVE WALL MOUNTED

DUPLEX OUTLET, POWER WIRING AND VOICE DATA

OUTLET. REMOVE POWER WIRING BACK TO RESPECTIVE

ELECTRIC PANELBOARD. REMOVE VOICE/DATA CABLING

BACK TO RESPECTIVE DATA COMPONENT.

11. EXISTING STEEL VERTICAL CABLE RACK TO REMAIN.

12. EXISTING BATTERY RACK TO REMAIN.

13. EXISTING FLOOR MOUNTED AC UNIT TO REMAIN.

14. EXISTING FLOOR MOUNTED EQUIPMENT STORAGE UNITS

TO REMAIN.

15. ROOF SYSTEMS ARE UNDER A ROOFING SYSTEM

WARRANTY. CONTRACTOR WILL UTILIZE A CERTIFIED

ROOFING CONTRACTOR APPROVED BY ROOF MEMBRANE

MANUFACTURER FOR ALL ROOF SYSTEM RENOVATIONS

AND MODIFICATIONS. VA/COR WILL PROVIDE COPY OF

WARRANTY INFORMATION TO CONTRACTOR AWARDED

THE PROJECT.

ROOF LEVEL

[ABOVE TENTH

FLOOR]

ROOF LEVEL

[ABOVE TENTH FLOOR]

DN

DN

ELEVATOR

PENTHOUSE

NORTH

NORTH

GENERAL NOTES

1. REFER TO DRAWING G-002 FOR INFECTION CONTROL NOTES

AND CONSTRUCTION PHASING NOTES.

2. REFER TO DRAWING E-001 FOR ELECTRICAL GENERAL

NOTES, ELECTRICAL SYMBOLS LIST AND BASIS OF DESIGN.

3. REFER TO SPECIFICATIONS APPENDIX SECTION A AND B FOR

PHOTO DOCUMENTATION OF EXISTING CONDITIONS.

4. REFER TO DRAWING E-601 FOR ELECTRICAL RISER DIAGRAM.

KEY NOTES

1. EXTEND CONDUITS OVER EXISTING PARAPET WALL AND

ROUTE ALONG EXISTING STEEL ANGLE FRAMING SYSTEM.

2. EXISTING PARAPET COPING AT ELEVENTH FLOOR LEVEL.

3. INDICATES EXISTING STEEL BRACING SYSTEM AT PARAPET

WALL SYSTEM.

4. PROVIDE CONDUIT SUPPORT SYSTEM ON ROOF DECK FOR

HORIZONTAL LENGTH INDICATED. REFER TO DETAIL ON

DRAWING A-503.

5. PROVIDE INSULATED EQUIPMENT CURB FOR CONDUIT

PENETRATIONS DOWN THROUGH ROOF SYSTEM AND

CONCRETE DECK. REFER TO DETAIL ON A-503 FOR

EQUIPMENT CURB AND ROOF MEMBRANE FLASHING

REQUIREMENTS.

6. LOCATION OF CONDUITS AND FEEDER CABLES/WIRES

FROM TENTH FLOOR UPS UNIT AND PANELBOARD

10AC1-2-SR. ROUTE CONDUIT SYSTEM TO SOUTH POINT OF

THIS ROOF DECK LEVEL.

7. EXTEND CONDUITS OVER EXISTING PARAPET WALL AND

DOWN EXISTING EXTERIOR MASONRY WALL.

8. PROVIDE CONDUIT DOWN TO ROOF LEVEL AT TENTH FLOOR

LEVEL/ROOF DECK.

10. PROVIDE THREE (3) 5" CONDUITS.

11. PROVIDE TWO (2) 4" CONDUITS AND FOUR (4) 2" CONDUITS

RIGID GALVANIZED STEEL (RGS), PVC COATED.

12. PROVIDE NEMA TYPE 3R PULL BOX.

13. ROOF SYSTEMS ARE UNDER A ROOFING SYSTEM

WARRANTY. CONTRACTOR WILL UTILIZE A CERTIFIED

ROOFING CONTRACTOR APPROVED BY ROOF MEMBRANE

MANUFACTURER FOR ALL ROOF SYSTEM RENOVATIONS

AND MODIFICATIONS. VA/COR WILL PROVIDE COPY OF

WARRANTY INFORMATION TO CONTRACTOR AWARDED THE

PROJECT.

ELEVATOR

P-2

ELEVATOR

P-3

ELEVATOR

P-4

ELEVATOR

P-5

ELEVATOR

P-6

OFFICE

COMPUTER

LAB

OFFICE

COMPUTER

LAB

OFFICE

TECHNICIAN

OFFICE

TECHNICIAN

OFFICE

TECHNICIAN

OFFICE

TECHNICIAN

TOILET

FEMALE

OFFICE

OFFICE

IT

SERVICE DESK

NORTH

GENERAL NOTES

KEY NOTES

0 2' 4' 8'

NORTH

1. REFER TO DRAWING G-002 FOR INFECTION CONTROL NOTES

AND CONSTRUCTION PHASING NOTES.

2. REFER TO DRAWING E-001 FOR ELECTRICAL GENERAL NOTES,

ELECTRICAL SYMBOLS LIST AND BASIS OF DESIGN.

3. REFER TO SPECIFICATIONS APPENDIX SECTION A AND B FOR

PHOTO DOCUMENTATION OF EXISTING CONDITIONS.

4. REFER TO DRAWING E-601 FOR ELECTRICAL RISER DIAGRAM.

5. SERVER ROOM AND TELEPHONE ROOM ARE BOTH

CONTROLLED ACCESS ROOMS THAT REQUIRE A FULLTIME

ESCORT FOR THE DURATION OF ALL ACTIVITIES WITHIN

THESE SPACES.

1. PROVIDE COMPUTER PANELBOARD "9AC4". 400A MCB WITH

4-50A/3P: 2-50A/3P SPARES

2. EXISTING AIR COOLED UNITS (ACU'S) TO BE RECONNECTED

FROM NORMAL TO EMERGENCY POWER. DISCONNECT AND

REMOVE EXISTING POWER WIRING AND TERMINATE AT

EXISTING ELECTRIC PANELBOARD. REMOVE EXISTING

CONDUIT BACK TO RESPECTIVE ELECTRIC PANELBOARD.

REMOVE ALL ASSOCIATED HANGER SYSTEMS. PROVIDE A

NEW PANELBOARD DESCRIPTION CARD AT RESPECTIVE

PANEL.

3. EXISTING AIR COOLED UNITS (ACU & AHU) NOT IN

CONTRACT (NIC).

4. REFER TO DRAWING E-104 FOR CONDUIT ROUTING AT

ROOF DECK LEVEL.

5. PROVIDE CONDUIT AND POWER WIRING FOR AIR COOLING

UNITS TO BE ROUTED ABOVE EXISTING SUSPENDED

CEILING SYSTEM.

6. PROVIDE DISCONNECT SWITCHES FOR ACU-1 AND ACU-2.

7. PROVIDE 3 #14 IN 3/4" CONDUIT, ROUTE ABOVE EXISTING

SUSPENDED CEILING SYSTEM.

ELEVATOR

P-2

ELEVATOR

P-3

ELEVATOR

P-4

ELEVATOR

P-5

ELEVATOR

P-6

STAIR 1

ROOF LEVEL

[ABOVE 9TH

FLOOR]

10A103

TELEPHONE

ROOM

10A100

ROOF LEVEL

[ABOVE 9TH

FLOOR]

DN

SD

SD

F1 F1 F1

F1F1

F1 F1

F1

10A101

PANELBOARD

ID: 10AC1-2-SR

MECHANICAL

ROOM

10A102

NORTH

NORTH

GENERAL NOTES

1. REFER TO DRAWING G-002 FOR INFECTION CONTROL NOTES

AND CONSTRUCTION PHASING NOTES.

2. REFER TO DRAWING E-001 FOR ELECTRICAL GENERAL NOTES,

ELECTRICAL SYMBOL LIST AND BASIS OF DEIGN.

3. REFER TO DRAWING E-601 FOR ELECTRICAL RISER DIAGRAM.

4. SERVER ROOM 9A123a AND TELEPHONE ROOM 10A100 ARE

BOTH CONTROLLED ACCESS ROOMS THAT REQUIRE A

FULLTIME ESCORT FOR THE DURATION OF ALL ACTIVITIES

WITHIN THESE SPACES.

KEY NOTES

1. CONTRACTOR WILL PROVIDE ALL TEMPORARY BARRIERS

DURING ALL CONSTRUCTION ACTIVITIES.

2. REMOVE AND TEMPORALLY RELOCATE LAY-IN LIGHT

FIXTURES AND ASSOCIATED CONDUIT AND WIRES AS

REQUIRED TO INSTALL PULLBOXES AND RELATED

CONDUITS AND WIRES.

3. CONTRACTOR WILL REMOVE SECTIONS OF EXISTING

SUSPENDED CEILING SYSTEM AS REQUIRED TO INSTALL

ABOVE CEILING COMPONENTS. SALVAGE CEILING TILES

AND SUSPENSION SYSTEM FOR REINSTALLATION.

4. EXISTING SUPPLY AIR DIFFUSERS ARE SCHEDULED TO

REMAIN. CONTRACTOR WILL VERIFY EXISTING SUPPLY

DUCT WHICH SERVICE THESE DIFFUSERS.

5. INDICATES EXISTING FIRE PROTECTION SPRINKLER HEADS

SCHEDULED TO REMAIN.

6. CEILING FINISH WITHIN ROOM 10A 102 IS EXPOSED

CONSTRUCTION.

7. INDICATES PROPOSED LOCATIONS FOR METAL PULLBOXES.

CONTRACTOR WILL DETERMINE FINAL LOCATION IN FIELD

AFTER COMPLETING A SITE SURVEY OF ABOVE CEILING

COMPONENTS.

8. INDICATES CEILING MOUNTED SMOKE DETECTORS.

CONTRACTOR WILL PROVIDE TEMPORARY COVERS DURING

CONSTRUCTION ACTIVITIES.

9. REFER TO DRAWING E-105 FOR LOCATION OF CONDUITS

AND ROUTING REQUIREMENTS.

10. REFER TO DRAWING E-104 FOR UPS UNIT.

11. REFER TO DRAWING E-104 FOR PANELBOARD.

12. PROPOSED ROUTING OF CONDUIT FROM METAL PULLBOX

TO UPS UNIT.

13. PROPOSED ROUTING OF CONDUITS AT SURFACE MOUNTED

PANELBOARD.

14. INDICATES CONDUITS UP TO ELEVENTH FLOOR/ROOF DECK

ELEVATION. REFER TO DRAWING E-105 FOR CONTINUATION.

15. INDICATES CONDUITS MOUNTED AT EXTERIOR MASONRY

WALL.

16. INDICATES CONDUITS ROUTED ALONG ROOF DECK. REFER

TO DRAWING E-104 FOR CONTINUATION OF ROOF PLAN AND

RELATED WORK.

17. REFER TO DRAWINGS A-501, A-502 AND A-503 FOR STEEL

SUPPORT SYSTEM AND RELATED ALUMINUM SCREENWALL

SYSTEM.

1. PROVIDE UPS UNIT "10UPS-SR" 90KW/100KVA, 90% POWER

FACTOR. 208V-208Y/120V, 3 PHASE, 4W, 60HZ, WITH 20

MINUTES BATTERY CAPACITY AT FULL LOAD.

2. PROVIDE POWER PANEL "10AC1-2".

3. PROVIDE COMPUTER PANEL "9AC4", 400A MCB WITH 4-50A/3P;

2-50A/3P SPARE.

4. PROVIDE SERVER RACK 50A, 208 VOLTS, 3 PHASE, 4 WIRES, 60

HZ. SHALL BE PROVIDED BY VA IT COMMUNICATION

DEPARTMENT.

5. EXISTING AIR-COOL UNITS TO BE RECONNECTED FROM

NORMAL POWER TO EMERGENCY POWER.

6. EXISTING CONDENSER UNITS TO BE RECONNECTED FROM

NORMAL POWER TO EMERGENCY POWER.

7. EXISTING FEEDER CIRCUIT BREAKER 600AF/200AT, 3P TO BE

REUSED AND INCREASE THE TAP SETTING TO 450 AMPERES.

8. EXISTING FEEDER CIRCUIT BREAKER 600AF / 200AT, 3 PHASE

TO BE REUSED AND INCREASE THE TAP SETTING TO 400

AMPHERES.

9. PROVIDE FEEDER CONDUIT FOR NEW UPS "10AUPS-SR" WITH

2 SETS 4 #300 KCMIL & 1 #2 GRD IN 5" CONDUIT.

10. PROVIDE FEEDER CONDUIT FOR NEW "PANEL 10AC1-2-SR"

WITH 4# 600 KCML & 1 #3 GRD IN 5" CONDUIT.

11. PROVIDE FEEDER CONDUIT FOR COMPUTER PANEL "9AC4" 5

#500 KCM & 1-4" SPARE CONDUIT. PROVIDE CONTROL WIRES

3 #14 FROM "10UPS-SR" TO EPO (EMERGENCY POWER OFF)

SWITCH IN COMPUTER ROOM AS SHOWN ON DRAWING E-106.

PROVIDE ONE (1) 5" CONDUIT SPARE.

12. PROVIDE ONE (1) 5" CONDUIT SPARE.

13. CONTRACTOR WILL PROVIDE INSULATED ROOF CURB FOR

CONDUIT PENETRATIONS. PROVIDE ALL ROOF MEMBRANE

FLASHING. LOCATE ROOF CURB A MINIMUM OF 12-INCHES

AWAY FROM ADJACENT MASONRY WALL FACE.

14. CONTRACTOR WILL PROVIDE WRITTEN NOTIFICATION TO

VA/COR PRIOR TO DE-ENERGIZING EXISTING EMERGENCY

SWITCHGEAR. REFER TO SPECIFICATION SECTIONS 01 00 00

GENERAL REQUIREMENTS 1.6 OPERATIONS AND STORAGE

AREAS, 01 35 26 SAFETY REQUIREMENTS 1.15 ELECTRICAL

AND 26 05 11 REQUIREMENTS FOR ELECTRICAL

INSTALLATIONS 1.9 WORK PERFORMANCE.

ELECTRICAL KEY NOTES

NOTES:

1. FURNISH AND INSTALL IN ACCORDANCE WITH NATIONAL

AND LOCAL ELECTRICAL CODES.

2. INPUT AND BYPASS MUST SHARE THE SAME SINGLE

SOURCE.

3. PROVIDE A NEUTRAL FROM THE SYSTEM AC INPUT

SOURCE. PROVIDE A FULL CAPACITY NEUTRAL

CONDUCTOR. PROVIDE GROUNDING CONDUCTORS.

4. PROVIDE UPS SYSTEM INPUT AND OUTPUT CABLES

ROUTED IN SEPARATE CONDUITS.

5. PROVIDE CONTROL WIRING ROUTED IN SEPARATE

CONDUITS.

6. PROVIDE INTERNAL BATTERY BREAKER ON UPS WITH

INTERNAL BATTERIES; BATTERY BREAKER IS

FACTORY-SUPPLIED WITH EXTERNAL LIEBERT BATTERY

CABINETS.

SEE NOTE 6

BATTERY

UPS CABINET

STATIC BYPASS

* SYSTEM

AC INPUT

4 WIRE+GRD

BIB MIB

BYPASS DISTRIBUTION CABINET

MBB

OUTPUT

BUSBAR

AC OUTPUT

208V

4 WIRE+GRD

BIB-BYPASS ISOLATION BREAKER

MBB-MAINTENANCE BYPASS

BREAKER

MIB-MAINTENANCE ISOLATION

BREAKER

*EXTERNAL OVERCURRENT

PROTECTION BY OTHERS

FIELD SUPPLIED WIRING

01 G001.pdf (p.1)
02 G002.pdf (p.2)
03 A201.pdf (p.3)
04 A501.pdf (p.4)
05 A502.pdf (p.5)
06 A503.pdf (p.6)
07 E001.pdf (p.7)
08 E101.pdf (p.8)
09 E102.pdf (p.9)
10 E103.pdf (p.10)
11 E104.pdf (p.11)
12 E105.pdf (p.12)
13 E106.pdf (p.13)
14 E107.pdf (p.14)
15 E601.pdf (p.15)

File details come from the government source that posted it.