36C25919R0031-0004001.pdf

PDF 64 KB Posted

Attached to
Increase Electrical Capacity to 9th Floor Server Room Federal contract opportunity
Solicitation number
36C25919R0031
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

36C25919R0031 0004 RFI #2.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Increase Electrical Capacity to 9th Floor Server Room, newest first.
File Type Posted
36C25919C0088-000.docx DOCX document
36C25919R0031-0004000.docx DOCX document
36C25919R0031_0003.docx DOCX document
36C25919R0031_0002.docx DOCX document
RFI__1.pdf PDF
36C25919R0031_0001.docx DOCX document
63516102-Bid_Documents-Specifications-050418-2.pdf PDF
63516102-Bid_Documents-Drawings-050418.pdf PDF
63516102-Bid_Documents-Specifications-050418-1.pdf PDF
63516102-Bid_Documents-Specifications-050418-3.pdf PDF
S02_Past_Performance_Questionnaire.docx DOCX document
36C25919R0031_2.docx DOCX document
S02_Calculation_of_Self-Performed_and_Subcontracted_Work.docx DOCX document
36C25919R0031-000.docx DOCX document
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFI #2 36C25919R0031

1. Are permanent roof walk pads required and if so please provide information on where they are to be placed?

a. No, permanent walk pads are not required

2. Is there an interior service elevator that can be used for access to upper floors/roofs?

a. There are two service elevators available that go from Basement to 9th floor. Access to 10th and 11th floors will require use of stairwells.

3. Is there a service elevator that can be used to load materials and if so does it need to be off-hours?

a. There are two service elevators available that go from Basement to 9th floor. Access to

10th and 11th floors will require use of stairwells. For large equipment there is a 4’ x 9’ access panel to the from the 9th floor.

4. Can the roles and responsibilities of the Superintendent, QC, and SSHO be covered by the same person?

a. Yes, they can be the same person.