36C25919R0010-005.pdf
PDF 4 MB Posted
- Attached to
- Whole Health Office Construction Federal contract opportunity
- Solicitation number
- 36C25919R0010
About this file
36C25919R0010 660-18-252 Asbestos Report.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25919C0064_1.docx | DOCX document | |
| 36C25919R0010-0002000.docx | DOCX document | |
| 36C25919R0010-0002001.pdf | ||
| 36C25919R0010-0002002.pdf | ||
| 36C25919R0010-0001000.docx | DOCX document | |
| 36C25919R0010-0001002.pdf | ||
| 36C25919R0010-0001001.pdf | ||
| 36C25919R0010-002.docx | DOCX document | |
| 36C25919R0010-007.docx | DOCX document | |
| 36C25919R0010-006.docx | DOCX document | |
| 36C25919R0010-003.pdf | ||
| 36C25919R0010-004.pdf | ||
| 36C25919R0010-001.docx | DOCX document | |
| 36C25919R0010-000.docx | DOCX document |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NESHAP ASBESTOS INSPECTION
ASSOCIATED WITH 660-18-252
FORECAST WHOLE HEALTH
SIX ROOMS IN BUILDINGS 1 AND 14
GEORGE E. WHALEN VA MEDICAL CENTER
500 FOOTHILL DRIVE
SALT LAKE CITY, UTAH 84148
CONTRACT NUMBER 36C25918C0298
SEPTEMBER 20, 2018
NESHAP ASBESTOS INSPECTION
ASSOCIATED WITH 660-18-252
FORECAST WHOLE HEALTH
SIX ROOMS IN BUILDINGS 1 AND 14
GEORGE E. WHALEN VA MEDICAL CENTER
500 FOOTHILL DRIVE
SALT LAKE CITY, UTAH 84148
CONTRACT NUMBER 36C25918C0298
PREPARED BY:
TTL ASSOCIATES, INC.
1915 N 12TH STREET
TOLEDO, OHIO 43614
(419) 324-2222
(419) 241-1808 (FAX)
SEPTEMBER 20 2018
TTL PROJECT NO. 1712701
Teamwork - Trust - Leadership Since 1927
September 20, 2018 TTL Project No. 1732701
Mr. Jeremiah Percy Construction Control Representative George E. Whalen Veterans Medical Center 500 Foothill Blvd Salt Lake City, UT 84148
NESHAP Asbestos Inspection Associated with 660-18-252
Forecast Whole Health Six Rooms in Buildings 1 and 14
George E. Whalen VA Medical Center 500 Foothill Drive
Salt Lake City, Utah 84148 Contract Number 36C25918C0298
Dear Mr. Percy:
Enclosed is the National Emissions Standard for Hazardous Air Pollutants (NESHAP) Asbestos Inspection report for the Forecast Whole Health project in Buildings 1 and 14 the George E.
Whalen VA Medical Center located in Salt Lake City, Utah. TTL Associates, Inc. (TTL) conducted the inspection on September 10, 2018. This project was conducted in accordance with contract number 36C25918C0298.
TTL appreciates the opportunity to perform as consultant for this project. If you should have any questions or need further assistance, please contact Ms. Veronica Allen at 734.582.4992.
Sincerely, TTL Associates, Inc.
Adam G. Mead Veronica Allen, P.E., PMP Utah Asbestos Inspector ASB-6245 Federal Services Director
Attachments
V:\Toledo\VA\Salt Lake City\NESHAP Asbestos Survey Remodeling project (1732701) - 2018\Report\660-18-252 Asbestos Report.docx
660-18-252 Forecast Whole Health TTL Project No. 1732701 George E. Whalen VA Medical Center Page i
TABLE OF CONTENTS
Section Page
1.0 EXECUTIVE SUMMARY
2.0 FACILITY DESCRIPTION
3.0 ASBESTOS INSPECTION METHODOLOGY
4.0 SUSPECT ASBESTOS-CONTAINING MATERIALS
Table 1.0 – Identified Asbestos-Containing Materials
5.0 LIMITATIONS AND CONDITIONS
APPENDICES
Appendix A – Inspector Credentials Appendix B – NESHAP Asbestos Inspection Summary Table Appendix C – Asbestos Sampling Location Drawings Appendix D – Analytical Laboratory Report Appendix E – Photographic Documentation of Sample Locations
George E. Whalen VA Medical Center Page 1
1.0 EXECUTIVE SUMMARY
TTL Associates, Inc. (TTL) conducted a National Emissions Standard for Hazardous Air Pollutants (NESHAP) asbestos inspection for the Forecast Whole Health project in Buildings 1 and 14 at the George E. Whalen VA Medical Center located in Salt Lake City, Utah. The inspection was conducted by Mr. Adam Mead on September 10, 2018. Mr. Mead is certified by the State of Utah Division of Air Quality as an Asbestos Inspector.
The table below summarizes the suspected asbestos-containing materials (ACM) identified, approximate quantity, and results of the asbestos sampling. ACM is defined by the United States Environmental Protection Agency (U.S. EPA) as any material containing more than 1% asbestos.
The Occupational Safety and Health Administration (OSHA) regulates all asbestos content.
The scope of work for this project associated with 660-18-252 Forecast Whole Health was conducted in accordance with contract number 36C25918C0298.
Summary of NESHAP Asbestos Inspection Forecast Whole Health
Six Rooms in Buildings 1 and 14 George E. Whalen VA Medical Center
Homogeneous Sample Area Material Description Quantity Results
1 Drywall 3,330 s.f. No Asbestos Identified
2 Fireproofing 1,575 s.f. No Asbestos Identified
3 6” Brown Cove Base and Associated Glue 138 l.f. No Asbestos Identified
4 2' x 4' Pinhole with Small Fissure Ceiling Panel 1,260 s.f. No Asbestos Identified
5 2' x 2' Pinhole with Small Fissure Ceiling Panel 560 s.f. No Asbestos Identified
6 4" Grey Cove Base and Associated Glue 246 l.f. No Asbestos Identified
7 Green Duct Sealant 10 s.f. No Asbestos Identified
8 Black Lab Countertop 52 s.f. Asbestos
9 Cementitious Lab Hood Panels 60 s.f. Asbestos
F03.0 12" Floor Tile and Black Mastic - Light Beige with
Green, Purple, and Brown Specks 24 s.f. No Asbestos Identified
F03.01 12" Floor Tile and Yellow Adhesive - Tan with
Rusty Linear Streaks 352 s.f. Asbestos
F03.02 12" Floor Tile and Yellow Adhesive - Lt. Gray with Gray Inclusions 1,468 s.f. Asbestos
M05.0 Plaster 323 s.f. No Asbestos Identified
George E. Whalen VA Medical Center Page 2
Summary of NESHAP Asbestos Inspection Forecast Whole Health
Six Rooms in Buildings 1 and 14 George E. Whalen VA Medical Center
Homogeneous Sample Area Material Description Quantity Results
M2017.04 Dark Brown Glue 40 s.f. Asbestos
T03.0 Pipe Insulation 24 l.f. Asbestos s.f.: Square Feet l.f.: Linear Feet
George E. Whalen VA Medical Center Page 3
2.0 FACILITY DESCRIPTION
A National Emissions Standard for Hazardous Air Pollutants (NESHAP) asbestos inspection was conducted by TTL Associates, Inc. (TTL) on September 10, 2018, for the Forecast Whole Health project in Buildings 1 and 14 at the George E. Whalen VA Medical Center (VAMC) located in Salt Lake City, Utah.
George E. Whalen VA Medical Center Page 4
3.0 ASBESTOS INSPECTION METHODOLOGY
The inspection was conducted by Mr. Adam Mead on September 10, 2018. Mr. Mead is certified by the State of Utah Division of Air Quality as an Asbestos Inspector. A copy of his certification is included in Appendix A.
The asbestos inspection was performed by identifying suspect Asbestos-Containing Materials (ACM) in accessible areas of the six rooms identified in the project scope of work. The suspect ACM were then grouped into Homogeneous Sampling Areas (HSA). An HSA is a material that exhibits similar physical characteristics and was installed at the same time as observed by the licensed inspector. TTL utilized previous inspection data provided by the VA to assist in the identification of HSAs.
Upon identifying the suspect ACM, representative bulk samples were collected from each HSA following United States Occupational Safety and Health Administration (OSHA) and United States Environmental Protection Agency (U.S. EPA) NESHAP regulations. Sample locations were selected as to be representative of the material sampled based on the licensed inspector’s professional judgement. Each sample collected was given a unique sample number. Sample and material locations were documented on floorplan drawings provided by the VAMC.
At the completion of the field work, the collected bulk samples were logged onto chain-of-custody sheets and transported to TTL’s asbestos laboratory for analysis by Polarized Light Microscopy with Dispersion Staining (PLM/DS). A total of 22 samples (51 material layers) were collected and analyzed. TTL’s asbestos laboratory is accredited by the National Voluntary Laboratory Accreditation Program (NVLAP). The bulk samples were analyzed in accordance with the U.S. EPA “Method for Determination of Asbestos in Bulk Building Materials” 600/R- 93/116. This method requires that multiple and distinct layers be analyzed separately.
Two materials (HSA 8 – Black lab countertops and HSA 9 - Cementitious lab hood panels) were assumed to be ACM because sampling would compromise the integrity of the system.
George E. Whalen VA Medical Center Page 5
4.0 SUSPECT ASBESTOS-CONTAINING MATERIALS
Table 1.0 below summarizes the ACM identified during this inspection. Refer to Appendix B for the NESHAP Asbestos Inspection Summary Table for a listing of all suspect ACM, locations, approximate quantities, and results of sample analysis. Floorplan drawings detailing the bulk sampling locations are included in Appendix C. Appendix D contains the laboratory analytical report for the bulk sampling analysis. Photographic documentation of each sample location is included in Appendix E.
Table 1.0 Identified Asbestos-Containing Materials
Forecast Whole Health Six Rooms in Buildings 1 and 14
George E. Whalen VA Medical Center
Homogeneous Sample Area Material Description Quantity Material Location
8 Black Lab Countertop 52 s.f. 1C03-14, 1C05-14
9 Cementitious Lab Hood Panels 60 s.f. 1C05-14
F03.01 12" Floor Tile and Yellow Adhesive - Tan with
Rusty Linear Streaks 352 s.f. BB03D-14
F03.02 12" Floor Tile and Yellow Adhesive - Lt. Gray with
Gray Inclusions 1,468 s.f.
BA11-14, 1C01-14,
1C03-14, 1C05-14
M2017.04 Dark Brown Glue 40 s.f. 1B47-1
T03.0 Pipe Insulation 24 l.f. 1B47-1
George E. Whalen VA Medical Center Page 6
5.0 LIMITATIONS AND CONDITIONS
The information contained within this report was prepared for the exclusive use and reliance of the VAMC and TTL. This information is based on the specific parameters of the scope of work and the regulations in force at the time of this project.
TTL has made reasonable efforts to identify and quantify suspect ACM based upon the standard of care in the environmental industry existing at the time of the survey. This survey only summarizes the potential presence and estimated quantities of visually observed ACM.
Additional material disturbed during renovation and demolition activities should be evaluated on a case-by-case basis, especially materials that were previously hidden, obscured, or inaccessible, to determine if the material is included in this survey. If a given material is not described in this survey or cannot be identified as a non-suspect material, the material should be assumed to contain asbestos and renovation and demolition activities should be halted until sampling and analysis can be accomplished. Parties conducting renovation and demolition activities should follow all applicable federal, state, and local regulations in handling identified and suspect ACM.
TTL accepts no responsibility for the use, interpretation, or reliance by other parties on the information contained herein, nor does this report represent an instrument of regulatory compliance or an asbestos abatement specification.
APPENDIX A
INSPECTOR CREDENTIALS
APPENDIX B
NESHAP ASBESTOS INSPECTION SUMMARY TABLE
NESHAP Asbestos Inspection Summary Table
George E. Whalen VA Medical Center
Forecast Whole Health
500 Foothill Drive
Salt Lake City, Utah 84148
HSA HSA Description Friability Functional Area Quantity Unit Results
1 Drywall NF-II BB03D-14 684 s.f. NEGATIVE
1 Drywall NF-II BA11-14 432 s.f. NEGATIVE
1 Drywall NF-II 1C01-14 738 s.f. NEGATIVE
1 Drywall NF-II 1C03-14 558 s.f. NEGATIVE
1 Drywall NF-II 1C05-14 918 s.f. NEGATIVE
Total 3,330 s.f.
2 Fireproofing F BB03D-14 200 s.f. NEGATIVE
2 Fireproofing F 1C01-14 400 s.f. NEGATIVE
2 Fireproofing F 1C03-14 225 s.f. NEGATIVE
2 Fireproofing F 1C05-14 750 s.f. NEGATIVE
Total 1,575 s.f.
3 6" Brown Cove Base and Associated Glue NF-II BB03D-14 76 l.f. NEGATIVE
3 6" Brown Cove Base and Associated Glue NF-II BA11-14 62 l.f. NEGATIVE
Total 138 l.f.
4 2' x 4' Pinhole with Small Fissure Ceiling Panel F 1C01-14 420 s.f. NEGATIVE
4 2' x 4' Pinhole with Small Fissure Ceiling Panel F 1C03-14 220 s.f. NEGATIVE
4 2' x 4' Pinhole with Small Fissure Ceiling Panel F 1C05-14 620 s.f. NEGATIVE
Total 1,260 s.f.
5 2' x 2' Pinhole with Small Fissure Ceiling Panel F BB03D-14 352 s.f. NEGATIVE
5 2' x 2' Pinhole with Small Fissure Ceiling Panel F BA11-14 208 s.f. NEGATIVE
Total 560 s.f.
6 4" Grey Cove Base and Associated Glue NF-II 1C01-14 82 l.f. NEGATIVE
6 4" Grey Cove Base and Associated Glue NF-II 1C03-14 62 l.f. NEGATIVE
6 4" Grey Cove Base and Associated Glue NF-II 1C05-14 102 l.f. NEGATIVE
Total 246 l.f.
7 Green Duct Sealant NF-II BA11-14 10 s.f. NEGATIVE
Total 10 s.f.
8 Black Lab Countertop NF-II 1C03-14 40 s.f. ASSUMED
8 Black Lab Countertop NF-II 1C05-14 12 s.f. ASSUMED
Total 52 s.f.
TTL Project No. 1732701 Page 1 of 2
NESHAP Asbestos Inspection Summary Table
George E. Whalen VA Medical Center
Forecast Whole Health
500 Foothill Drive
Salt Lake City, Utah 84148
HSA HSA Description Friability Functional Area Quantity Unit Results
9 Cementitious Lab Hood Panels NF-II 1C05-14 60 s.f. ASSUMED
Total 60 s.f.
F03.0 12" Floor Tile and Black Mastic - Light Beige with Green, Purple, and Brown Specks NF-I 1B47-1 (Under Carpet) 24 s.f. NEGATIVE*
Total 24 s.f.
F03.01 12" Floor Tile and Yellow Adhesive - Tan with Rusty Linear Streaks NF-I BB03D-14 (Under Carpet - Mastic Only) 352 s.f. POSITIVE*
Total 352 s.f.
F03.02 12" Floor Tile and Yellow Adhesive - Lt. Gray with Gray Inclusions NF-I BA11-14 (Under Carpet) 208 s.f. POSITIVE*
F03.02 12" Floor Tile and Yellow Adhesive - Lt. Gray with Gray Inclusions NF-I 1C01-14 420 s.f. POSITIVE*
F03.02 12" Floor Tile and Yellow Adhesive - Lt. Gray with Gray Inclusions NF-I 1C03-14 220 s.f. POSITIVE*
F03.02 12" Floor Tile and Yellow Adhesive - Lt. Gray with Gray Inclusions NF-I 1C05-14 620 s.f. POSITIVE*
Total 1,468 s.f.
M05.0 Plaster NF-II 1B47-1 323 s.f. NEGATIVE*
Total 323 s.f.
M2017.04 Dark Brown Glue NF-II 1B47-1 (Above Ceiling) 40 s.f. POSITIVE*
Total 40 s.f.
T03.0 Pipe Insulation F 1B47-1 (In East Wall) 24 l.f. POSITIVE*
Total 24 l.f.
* Previously identified s.f. - square feet l.f. - linear feet
TTL Project No. 1732701 Page 2 of 2
APPENDIX C
ASBESTOS SAMPLING LOCATION DRAWINGS
APPENDIX D
ANALYTICAL LABORATORY REPORT
APPENDIX E
PHOTOGRAPHIC DOCUMENTATION OF SAMPLE LOCATIONS
Not Pictured: Samples 01A, 01B, 01C – Drywall
Sample 01D – Drywall
Sample 01E – Drywall
Sample 01F – Drywall
Sample 01G – Drywall
Not Pictured: Sample 02A – Fireproofing
Sample 02B – Fireproofing
Sample 02C – Fireproofing
Sample 02D – Fireproofing
Sample 02E – Fireproofing
Not Pictured: Samples 03A, 03B – 6” Brown Cove Base and Associated Glue
Sample 04A – 2’ x 4’ Pinhole with Small Fissure Ceiling Panel
Sample 04B – 2’ x 4’ Pinhole with Small Fissure Ceiling Panel
Not Pictured: Samples 05A, 05B – 2’ x 2’ Pinhole with Small Fissure Ceiling Panel
Sample 06A – 4” Grey Cove Base and Associated Glue
Sample 06B – 4” Grey Cove Base and Associated Glue
Not Pictured: Samples 07A, 07B – Green Duct Sealant
HSA 08 – Black Lab Countertop
HSA 09 – Cementitious Lab Hood Panels