S02 ATTACHMENT Device Decriptions v2.pdf

PDF 314 KB Posted

Attached to
Z1DA--629-20-113 - Fire Alarm System Replacement Federal contract opportunity
Solicitation number
36C25620R0159
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document includes a federal contract solicitation for fire alarm system replacement services at the Southeast Louisiana Veterans Healthcare System facilities in New Orleans, Louisiana. The solicitation is set aside 100% for Service-Disabled Veteran-Owned Small Businesses and seeks a contractor to design and build a new addressable fire alarm and suppression system across multiple buildings. Interested offerors must be verified as a SDVOSB, registered in the System for Award Management and Vendor Information Pages databases, and have a current VETS-4212 report on file. The anticipated proposal due date is December 3, 2020 with contract award expected within 30 days thereafter. The contractor will be provided a 365 calendar day period of performance once the notice to proceed is issued. The construction cost range is between $500,000 to $1,000,000.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--629-20-113 - Fire Alarm System Replacement, newest first.
File Type Posted
36C25620R0159 0002.docx DOCX document
S02 ATTACHMENT Life Safety Drawings v2.pdf PDF
36C25620R0159 0001.docx DOCX document
P07 Wage Decision LA20210041 (01.01.2021).pdf PDF
S02 EXHIBIT A CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY .docx DOCX document
P09 Updated SOW Final (10.22.2020) 04.pdf PDF
36C25620R0159_1.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE ALARM SYSTEM REPLACEMENT

PROJECT # 629-20-113

SOUTHEAST LOUISIANA VETERANS HEALTH CARE SYSTEM (SLVHCS)

NEW ORLEANS, LA

DEVICE TOTALS

All listed device totals are estimates.

Building: New Orleans VAMC "B,C" Bldg 1 Inpatient Total Device Count: 708

EC 02.03.05 EP 02

Every 6 months, the hospital tests vane-type and pressure-type water flow devices and valve tamper switches on the inventory.

Devices Total

Quantity

Waterflow Switch 21

Tamper Switch 26

EC 02.03.05 EP 03

Every 12 months, the hospital tests duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors on the inventory.

Devices Total

Quantity

Duct Detector 12

Heat Detector 21

Pull Station 54

Smoke Detector 118

EC 02.03.05 EP 04

Every 12 months, the hospital tests visual and audible fire alarms, including speakers and door-releasing devices on the inventory.

Devices Total

Quantity

Releasing Device 21

Speaker 42

Speaker/Strobe 192

Strobe 47

Voice Evacuation 1

EC 02.03.05 EP 05

Every 12 months, the hospital tests fire alarm equipment on the inventory for notifying off-site fire responders. The results and completion dates are documented.

Devices Total

Quantity

Communicator 1

EC 02.03.05 EP 18

The hospital operates fire and smoke dampers one year after installation and then at least every six years to verify that they fully close. The results and completion dates are documented.

Note: For additional guidance on performing tests, see NFPA 90A-

2012: 5.4.8; NFPA 80-2010: 19.4; NFPA 105-2010: 6.5.

Devices Total

Smoke & Fire Dampers 34

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2015

Devices Total

Quantity

Duct Detector 12

Fan Shutdown 6

LS 02.01.30 EP 26

All other Life Safety Code fire and smoke protection requirements related to NFPA 101-2012 18/19.3

Devices Total

Damper Control 3

LS 02.01.34 EP 02 Protected master fire alarm control panel

Total

Control Panel 5

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA

101-2012 18/19.3.4

Devices Total

Quantity

Battery 46

Expander Panel 4

Fan Running 7

Phone Jack 8

Phone Station 1

Power Supply 7

Programmable Relay 12

LS 02.01.50 EP 07 Elevators are fully equipped and protected

Total

Elevator 18

Building: New Orleans VAMC "D,E,F,G" Bldg 2 D & T Total Device Count: 3438 water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Waterflow Switch 39

Tamper Switch 54 manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Duct Detector 53

Heat Detector 26

Pull Station 207

Smoke Detector 339 including speakers and door-releasing devices on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Releasing Device 122

Speaker 135

Speaker/Strobe 848

Strobe 245 inventory for notifying off-site fire responders. The results and completion dates are documented.

Devices Total

Monitor Device 18 installation and then at least every six years to verify that they fully close. The results and completion dates are documented.

Devices Total

Smoke & Fire Dampers 1045 handling equipment per NFPA 90A-2017

Devices Total

Quantity

Duct Detector 53

Fan Shutdown 20

Total

Control Panel 9

101-2017 18/19.3.4

Quantity

Battery 136

Expander Panel 29

Phone Jack 21

Power Supply 49

Total

Elevator 43

Building: New Orleans VAMC "H,J" Bldg 3 Outpatient Total Device Count: 985 water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Waterflow Switch 15

Tamper Switch 17 manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Duct Detector 24

Heat Detector 17

Pull Station 41

Smoke Detector 126 including speakers and door-releasing devices on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Horn/Strobe 2

Releasing Device 12

Speaker 37

Speaker/Strobe 223

Strobe 68 installation and then at least every six years to verify that they fully close. The results and completion dates are documented.

Devices installation and then at least every six years to verify that they fully close. The results and completion dates are documented.

Devices Total

Smoke & Fire Dampers 260

Every 12 months, the hospital tests automatic smoke-detection shutdown devices for air-handling equipment. The results and completion dates are documented.

Devices Total

Quantity

Duct Detector 24

Fan Shutdown 7 related to NFPA 101-2017 18/19.3

Devices Total

Damper 2

Total

Control Panel 4

Total

Elevator 18

Building: New Orleans VAMC "K" Bldg 4 Staff Parking Total Device Count: 79 manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA

101-2017 18/19.3.4

Devices Total

Quantity

Battery 60

Expander Panel 18

Fan Running 3

Phone Station 8

Power Supply 8

Programmable Relay 15

Quantity

Heat Detector 14

Pull Station 9

Smoke Detector 29

Total

Control Panel 1

101-2017 18/19.3.4

Devices Total

Quantity

Battery 12

Phone Station 2

Power Supply 5

Total

Elevator 7

Building: New Orleans VAMC "L" Bldg 5 Patient Parking Total Device Count: 98 water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Waterflow Switch 9

Tamper Switch 10 manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Heat Detector 14

Pull Station 9

Smoke Detector 29

Total

101-2017 18/19.3.4

Devices Total

Quantity

Battery 12

Phone Station 2

Power Supply 5

Total

Elevator 7

Building: New Orleans VAMC "M" Bldg 6 Transitional Living Total Device Count: 757

*Transitional Living does not include Shotgun Houses. Additional devices will be added within the scope of this contract.

water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Waterflow Switch 12

Tamper Switch 14 manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Duct Detector 10

Heat Detector 6

Pull Station 33

Smoke Detector 79 including speakers and door-releasing devices on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Horn/Strobe 27

Releasing Device 6

Speaker 8

Speaker/Strobe 257

Strobe 87 installation and then at least every six years to verify that they fully close. The results and completion dates are documented.

Note: For additional guidance on performing tests, see NFPA 90A-

2012: 5.4.8; NFPA 80-2010: 19.4; NFPA 105-2010: 6.5.

Devices Total

Smoke & Fire Dampers 137 handling equipment per NFPA 90A-2015

Devices Total

Quantity

Duct Detector 10

Fan Shutdown 2 related to NFPA 101-2017 18/19.3

Devices Total

Damper 1

Total

Control Panel 2

101-2017 18/19.3.4

Devices Total

Quantity

Battery 30

Expander Panel 6

Fan Running 4

Phone Station 7

Power Supply 7

Programmable Relay 10

Total

Elevator 12

Building: New Orleans VAMC "N" Bldg 7 CEP Total Device Count: 575

EC 02.03.05 EP 01

At least quarterly, the hospital tests supervisory signal devices on the inventory (except valve tamper switches). The results and completion dates are documented.

Devices Total

Quantity

Fire Pump Power 2

Fire Pump Running 2

Fire Pump Trouble 2 water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Waterflow Switch 11

Tamper Switch 17 manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Duct Detector 19

Heat Detector 5

Pull Station 16

Smoke Detector 42 including speakers and door-releasing devices on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Releasing Device 2

Speaker 34

Speaker/Strobe 185

Strobe 17

Voice Evacuation 1 inventory for notifying off-site fire responders. The results and completion dates are documented.

Devices Total

Monitor Device 2 installation and then at least every six years to verify that they fully close. The results and completion dates are documented.

Note: For additional guidance on performing tests, see NFPA 90A-

2012: 5.4.8; NFPA 80-2010: 19.4; NFPA 105-2010: 6.5.

Devices Total

Smoke & Fire Dampers 116 shutdown devices for air-handling equipment. The results and completion dates are documented.

Note: For additional guidance on performing tests, see NFPA 90A-

2012: 6.4.1.

Devices Total

Quantity

Duct Detector 19

Fan Shutdown 14

Total

LS 02.01.34 EP 04 Approved location for remote annunciator panel

Total

Annunciator 1

101-2015 18/19.3.4

Devices Total

Quantity

Battery 32

Expander Panel 9

Fan Running 12

Generator Running 2

Generator Trouble 1

Phone Jack 6

Phone Station 1

Power Supply 6

Printer 1

Programmable Relay 10

Total

Elevator 6

Building: New Orleans VAMC "P" Bldg 8 Research Total Device Count: 435 water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Waterflow Switch 13

Tamper Switch 15 manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Duct Detector 10

Heat Detector 6

Pull Station 19

Smoke Detector 25 including speakers and door-releasing devices on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Releasing Device 2

Speaker 4

Speaker/Strobe 179

Strobe 31 installation and then at least every six years to verify that they fully close. The results and completion dates are documented.

Note: For additional guidance on performing tests, see NFPA 90A-

2012: 5.4.8; NFPA 80-2010: 19.4; NFPA 105-2010: 6.5.

Devices Total

Smoke & Fire Dampers 105 handling equipment per NFPA 90A-2015

Devices Total

Duct Detector 10

101-2017 18/19.3.4

Devices Total Quantity

Battery Needs to be accessed

Expander Panel Needs to be accessed

Fan Running Needs to be accessed

Phone Station Needs to be accessed

Power Supply Needs to be accessed

Programmable Relay Needs to be accessed

Total

Elevator 15

Building: New Orleans Pan AM Bldg 9 Total Device Count: 188 the inventory (except valve tamper switches). The results and completion dates are documented.

Devices Total

Quantity

Fire Pump Power 2

Fire Pump Running 1

Fire Pump Trouble 1 water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Waterflow Switch 7

Tamper Switch 15 manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Duct Detector 12

Heat Detector 15

Pull Station 29

Smoke Detector 54 including speakers and door-releasing devices on the inventory. The results and completion dates are documented.

Devices Total

Releasing Device 9 installation and then at least every six years to verify that they fully close. The results and completion dates are documented.

Note: For additional guidance on performing tests, see NFPA 90A-

2012: 5.4.8; NFPA 80-2010: 19.4; NFPA 105-2010: 6.5.

Devices Total Quantity

Smoke & Fire Dampers Needs to be assessed shutdown devices for air-handling equipment. The results and completion dates are documented.

Devices Total

Quantity

Duct Detector 12

Fan Shutdown 4 related to NFPA 101-2015 18/19.3

Devices Total

Damper Control 2

101-2015 18/19.3.4

Devices Total

Quantity

Phone Jack 14

Power Supply 12

Programmable Relay 5

Total

Elevator 6

Building: New Orleans Fisher House Total Device Count: 80 the inventory (except valve tamper switches). The results and completion dates are documented.

Quantity

Fire Pump Power 1

Fire Pump Running 1

Fire Pump Trouble 1 water flow devices and valve tamper switches on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Waterflow Switch 1

Tamper Switch 1 manual fire alarm boxes, and smoke detectors on the inventory. The results and completion dates are documented.

Devices Total

Quantity

Duct Detector 3

Heat Detector 13

Pull Station 10

Smoke Detector 40 including speakers and door-releasing devices on the inventory. The results and completion dates are documented.

Devices Total Quantity

Releasing Device Needs to be assessed installation and then at least every six years to verify that they fully close. The results and completion dates are documented.

Note: For additional guidance on performing tests, see NFPA 90A-

2012: 5.4.8; NFPA 80-2010: 19.4; NFPA 105-2010: 6.5.

Devices Total

Smoke & Fire Dampers 1 shutdown devices for air-handling equipment. The results and completion dates are documented.

Devices Total

Duct Detector 3 related to NFPA 101-2015 18/19.3

Devices related to NFPA 101-2015 18/19.3

Devices Total

Damper Control

101-2015 18/19.3.4

Devices Total Quantity

Phone Jack 0

Power Supply 4

Programmable Relay Needs to be assessed

Total

Elevator 1

File details come from the government source that posted it. Updated .