36C25025Q0535.docx

DOCX document 150 KB Posted

Attached to
H261--Triennial Electrical Inspection Federal contract opportunity
Solicitation number
36C25025Q0535
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This is a Request for Quote (RFQ) for triennial electrical inspection services issued by the Department of Veterans Affairs Network Contracting Office. The solicitation (No. 36C25025Q0535) is specifically set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) and seeks a contractor to perform comprehensive electrical system inspections at the Chillicothe VA Medical Center. The scope of work includes cleaning, inspecting, lubricating, and testing various electrical power distribution system components, including switchgear, transformers, circuit breakers, protective relays, grounding systems, emergency generators, and automatic transfer switches.

Key details include a solicitation issue date of May 9, 2025, with quotes due by May 23, 2025 at 4:00 PM EDT. The contract will require infrared scanning of electrical equipment, system function tests, and detailed reporting within seven calendar days of work completion. The period of performance is no more than 90 days from the Notice to Proceed, with work to be conducted after hours to minimize disruption to medical center operations. The NAICS code is 541350 with a size standard of $19 million, and the contractor must provide all necessary tools, equipment, and personnel with specific certifications from the InterNational Electrical Testing Association (NETA) and OSHA safety training.

View the file

Other files for this federal contract opportunity

Other files attached to H261--Triennial Electrical Inspection, newest first.
File Type Posted
36C25025Q0535 0002.docx DOCX document
single line.zip ZIP file
36C25025Q0535 0001.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

36C25025Q0535

PAGE 1 OF

1. REQUISITION NO.

2. CONTRACT NO.

3. AWARD/EFFECTIVE DATE

4. ORDER NO.

5. SOLICITATION NUMBER

6. SOLICITATION ISSUE DATE

a. NAME

b. TELEPHONE NO. (No Collect Calls)

8. OFFER DUE

DATE/LOCAL

TIME

9. ISSUED BY

CODE

10. THIS ACQUISITION IS

UNRESTRICTED OR

SET ASIDE:

% FOR:

SMALL BUSINESS

HUBZONE SMALL

BUSINESS

SERVICE-DISABLED

VETERAN-OWNED

SMALL BUSINESS

WOMEN-OWNED SMALL BUSINESS

(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED

SMALL BUSINESS PROGRAM

EDWOSB

8(A)

NAICS:

SIZE STANDARD:

11. DELIVERY FOR FOB DESTINA-

TION UNLESS BLOCK IS

MARKED

SEE SCHEDULE

12. DISCOUNT TERMS

13a. THIS CONTRACT IS A

RATED ORDER UNDER

DPAS (15 CFR 700)

13b. RATING

14. METHOD OF SOLICITATION

RFQ

IFB

RFP

15. DELIVER TO

CODE

16. ADMINISTERED BY

CODE

17a. CONTRACTOR/OFFEROR

CODE

FACILITY CODE

18a.

PAYMENT WILL BE MADE BY

CODE

TELEPHONE NO.

UEI:

EFT:

PHONE:

FAX:

17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER 18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED

SEE

ADDENDUM

19.

20.

21.

22.

23.

24.

ITEM NO.

SCHEDULE OF SUPPLIES/SERVICES

QUANTITY

UNIT

UNIT PRICE

AMOUNT

(Use Reverse and/or Attach Additional Sheets as Necessary)

25. ACCOUNTING AND APPROPRIATION DATA

26.

TOTAL AWARD AMOUNT (For Govt. Use Only) 27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA

ARE

ARE NOT ATTACHED.

27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA

ARE

ARE NOT ATTACHED

28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________

29. AWARD OF CONTRACT: REF. ___________________________________ OFFER

COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND

DATED ________________________________. YOUR OFFER ON SOLICITATION

DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY

(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE

ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED

SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:

30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER) 30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED

AUTHORIZED FOR LOCAL REPRODUCTION

(REV. NOV 2021)

PREVIOUS EDITION IS NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.212

7. FOR SOLICITATION

INFORMATION CALL:

STANDARD FORM 1449

SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL

PRODUCTS AND COMMERCIAL SERVICES

OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30

538-25-4-6068-0029 36C25025Q0535 05-09-2025 Mary Jane Crim 937-268-6511 X3065 05-23-2025

4PM

EDT

36C250 Department of Veterans Affairs Network Contracting Office (NCO) 10 3140 Governor’s Place Blvd. Suite 210 Kettering OH 45409-1337 X X 541350 $19 Million N/A X 36C250 Department of Veterans Affairs Chillicothe VA Medical Center 17273 State Route 104 Chillicothe OH 45601-9718 36C250 Department of Veterans Affairs Network Contracting Office (NCO) 10 3140 Governor's Place Blvd. Suite 210 Kettering OH 45409-1337

Department of Veterans Affairs Financial Services Center Invoices To Be Submitted Electronically https://www.ob10.com/us/en/veterans-affairs// Invoice Setup Info Phone 877 353 9791 512 460 5429 See CONTINUATION Page This solicitation is a Request for Quotes (RFQ) for triennial electrical inspection services. The contractor shall provide all personnel, supervision, labor, equipment, materials, and disposal necessary to provide triennial electrical inspections services at the Chillicothe VA Medical Center pursuant to the Statement of Work described herein.

The following Wage Determination applies to this RFQ:

Wage Determination Number: 2015-4771 Revision Number: 28 Date of Revision: 12/23/2024 Available at www.sam.gov.

See CONTINUATION Page X X X Table of Contents

SECTION A1
A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES1
SECTION B - CONTINUATION OF SF 1449 BLOCKS3
B.1 CONTRACT ADMINISTRATION DATA3
B.2 STATEMENT OF WORK4
B.3 PRICE/COST SCHEDULE45
ITEM INFORMATION45
SECTION C - CONTRACT CLAUSES46
C.1 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)46
C.2 52.217-8 OPTION TO EXTEND SERVICES (NOV 1999)46
C.3 52.217-9 OPTION TO EXTEND THE TERM OF THE CONTRACT (MAR 2000)46
C.4 52.237-2 PROTECTION OF GOVERNMENT BUILDINGS, EQUIPMENT, AND VEGETATION (APR 1984)47
C.5 VAAR 852.203-70 COMMERCIAL ADVERTISING (MAY 2018)47
C.6 VAAR 852.219-73 VA NOTICE OF TOTAL SET-ASIDE FOR CERTIFIED SERVICE-DISABLED VETERAN-OWNED SMALL BUSINESSES (JAN 2023) (DEVIATION)47
C.7 VAAR 852.232-72 ELECTRONIC SUBMISSION OF PAYMENT REQUESTS (NOV 2018)50
C.8 VAAR 852.242-71 ADMINISTRATIVE CONTRACTING OFFICER (OCT 2020)51
C.9 52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT STATUTES OR EXECUTIVE ORDERS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (JAN 2025) (DEVIATION FEB 2025)51
SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS59
SECTION E - SOLICITATION PROVISIONS60
E.1 52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE (FEB 1998)60
E.2 52.237-1 SITE VISIT (APR 1984)60
E.3 52.212-2 EVALUATION—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (NOV 2021)60
E.5 52.212-3 OFFEROR REPRESENTATIONS AND CERTIFICATIONS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (MAY 2024) (DEVIATION FEB 2025)62

SECTION B - CONTINUATION OF SF 1449 BLOCKS

B.1 CONTRACT ADMINISTRATION DATA

1. Contract Administration: All contract administration matters will be handled by the following individuals:

a. CONTRACTOR: TBD

b. GOVERNMENT: Contracting Officer 36C250 Mary Jane Crim

Department of Veterans Affairs Network Contracting Office (NCO) 10 3140 Governor’s Place Blvd. Suite 210 Kettering OH 45409-1337

2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:

[X]
52.232-33, Payment by Electronic Funds Transfer—System For Award Management, or
[X]
52.232-36, Payment by Third Party

3. INVOICES: Invoices shall be submitted in arrears:

a. Quarterly[]
b. Semi-Annually[]
c. Other[X] Upon completion

4. GOVERNMENT INVOICE ADDRESS: All Invoices from the contractor shall be submitted electronically in accordance with VAAR Clause 852.232-72 Electronic Submission of Payment Requests.

ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the Solicitation numbered and dated as follows:

AMENDMENT NO
DATE

B.2 STATEMENT OF WORK

1. Introduction:

A. This Statement of Work (SOW) describes the requirements for the maintenance, inspection, testing, and/or calibration of the Electrical Power Distribution System to include all components at the Chillicothe, OH VA Medical Center. These work items are referenced as “Maintenance and Testing” in this document, hereafter.

B. This SOW describes the requirements for the Qualified Electrical Contract Professionals – known as “Contractors” in this document, hereafter. Contractors who are contracted by VA Medical Center to perform maintenance and testing of the Electrical Power Distribution System, and all its components shall meet all requirements stated in Section 2 of this SOW.

C. This SOW describes the requirements to establish maintenance and testing reports.

2. Qualifications of Contractors:

A. Contractors shall be experienced Electrical Contractors, having properly trained and licensed permanent staff required to perform the proposed work. Electrical Contracting (i.e. the construction, repair, testing and maintenance of industrial and commercial electrical distribution systems) shall be the primary interest/specialty of the Contractor’s business.

B. Contractors shall be certified by the InterNational Electrical Testing Association (NETA) or equivalent certifying organization as Certified Technicians with each having completed the Occupational Safety & Health Administration (OSHA) approved 10-hour construction safety training. Certifications for key workers and specific work crews to be assigned to this contract shall be submitted to the VA Contracting Officer prior to work.

C. Contractors shall have technical training and demonstrable track records of working experience in maintenance, inspection, and testing of the Electrical Power Distribution Systems and related components in healthcare, industrial, educational, and commercial facilities for a minimum of five (5) continuous years. Electrical components on which the Contractors have experience shall include, but not be limited to, switchboards & switchgear (low and medium voltage); low voltage controls; emergency and standby generators; automatic transfer switches, wiring, transformers, meters, and other electrical appurtenances. Work history shall be submitted to the VA Contracting Officer prior to work.

D. Contractors shall have safety trainings – either on-the-job or class-room type - in electrical safety outlined in the OSHA Standard 29 Code of Federal Regulations (CFR) 1910 Subpart S – Electrical, and the NFPA 70E – Standard for Electrical Safety in the Workplace. Training certification shall be provided indicating each technician is a Qualified Person as defined by NFPA 70E. Training certifications shall be submitted to the VA Contracting Officer prior to work.

E. Contractors shall have ready access to the latest versions of the following references:

1) NFPA 70, National Electrical Code.

2) NFPA 70B, Recommended Practice for Electrical Equipment Maintenance.

3) NFPA 70E, Standard for Electrical Safety for the Workplace.

4) NFPA 110, Standard for Emergency and Standby Power System.

5) OSHA Standard 29 CFR 1910, Subparts I & S.

6) InterNational Electrical Testing Association, Inc. (NETA) – Maintenance and Testing Specifications.

7) Operating/Maintenance manuals, and specifications of the electrical equipment to be maintained and tested. These documents may be obtained from the VHA Medical Center, or the equipment manufacturers.

8) VHA Directive 1028, Electrical Power Distribution Systems

F. Contractors shall have and provide all necessary tools, equipment (including power generation equipment if applicable), supervision and personal protective equipment (PPE) to perform the work safely, effectively, and timely. Tools, equipment, and PPE shall comply with the requirements of OSHA Standard 29 CFR 1910, Subpart I, and NFPA 70E. Prior to initiating work, Contractor shall provide documentation that all instruments, test equipment, tools and PPE have current calibration. Dated calibration labels shall be visible on all instruments, test equipment, tools and PPE as appropriate.

3. Summary of Work:

A. The Contractor shall provide a proposed schedule and detailed work plan for all phases and tasks with their bid proposal. The schedule shall be in the form of a progress chart of suitable scale to indicate the work scheduled for completion by any given date during the work period. The proposed schedule shall be reviewed by the VAMC Facilities Management; any requirements for adjusting the schedule (e.g. to minimize disruption to the VAMC) shall be incorporated by the Contractor.

B. Contractors shall report deficiencies that are deemed critical or catastrophic immediately to the Contracting Officer and Chief of Facilities Management, for immediate actions.

C. Work items, definitions, and references shall comply with the latest edition of the NETA – Maintenance Testing Specifications (MTS) and with the VHA Directive, Electrical Power Distribution System. Appendix A (attached) is a list of electrical equipment that shall be maintained and tested.

D. Scope of work to include the cleaning, inspecting, lubricating, and testing (including infrared imaging) of the Chillicothe, Ohio Veteran’s Administration Medical Center (VAMC) electrical power distribution system, testing components of the campus electrical system grounding and lightning protection systems, as well as furnishing reports on all action items.

E. All work performed shall be fully documented by the Contractor. This shall include the recording of all the testing, servicing, any evaluation data, recommendations, inspections, adjustments, and maintenance performed on all the devices listed in the specification. Testing shall be performed in complete compliance with manufacturer’s recommendations.

F. Work for electrical inspection and preventive maintenance shall be conducted after 5pm and before 7am M-F. All power distribution switching will be done by the VA electricians only. Work on electrical infrared inspections shall be conducted 7am to 3:30pm M-F.

G. Equipment to be Inspected, Maintained and Tested Includes:

1. Switchgear and Switchboard Assemblies.

2. Transformers, Dry Type, Air-Cooled, Low-voltage, Small.

3. Transformers, Dry Type, Air-Cooled, Low-voltage, Large.

4. Transformers, Liquid-Filled.

5. Metal–Enclosed Busways.

6. Switches, Air, Low-Voltage.

7. Switches, Air, High and Medium-Voltage, Metal-Enclosed.

8. Switches, Oil, Medium-Voltage.

9. Switches, Vacuum, Medium-Voltage.

10. Switches, SF6, Medium-Voltage.

11. Circuit Breakers, Air, Insulated-Case/ Molded-Case.

12. Circuit Breakers, Air, Low-Voltage Power.

13. Circuit Breakers, Air, Medium-Voltage.

14. Circuit Breakers, Oil, Medium and High-Voltage.

15. Circuit Breakers, Vacuum, Medium-Voltage.

16. Circuit Breakers, SF6.

17. Protective Relays, Mechanical, and Solid State.

18. Protective Relays, Microprocessor Based.

19. Grounding Systems.

20. Ground-fault Protection Systems.

21. Motor Control, Motor Starters, Low-Voltage.

22. Motor Control, Motor Starter, Medium-Voltage.

23. Emergency Systems, Engine Generators.

24. Emergency Systems, Automatic Transfer Switches.

25. Lightning protection Systems

A. Attachments, Government Furnished.

1. Inventory of Electrical Power Distribution System equipment to be maintained, inspected, and tested under this Scope of Work.

2. One-line and other informational drawings of the Electrical Power Distribution System. These drawings are not certified as-built drawings.

B. Infra-Red Scanning/Thermographic Survey shall be performed on electrical equipment.

1. Use an infra-red scanning camera to detect hot spots in the Electrical Power Distribution System. Objective of this work is to detect any loose, broken, or corroded connections in the system. Problem connections shall be replaced with new connectors, and/or tightened with torque wrench to meet the equipment manufacturers’ specifications.

2. Note that since this work item must be done while the Electrical Power Distribution System is energized, appropriate safety precautions must be taken before, during and after scanning the system.

3. Infrared scans will consist of all major electrical primary and secondary distribution system components. This shall include the complete VA owned electrical systems from the commercial electric service point through the distribution system to the wiring load terminal at each protective device, including distribution system apparatus of all generators while under normal load conditions. The Contractor shall provide reports listing the results of the infrared scans.

C. System Function Tests. Provide function test for all equipment listed in this Scope of Work.

D. Test Conditions may be indoor or outdoor in all types of weather conditions.

E. Grounding Systems

1. Locate, inspect, and tighten ground connections on all station generators, main switch gear (B19 and 218), main switch gear for each building, transfer switches, and the first branch panels after the mains/transfer switches. Measure and record resistance for facility grounding system components mentioned above. Include a list of any obvious deficiencies to grounding systems and resistance measurements of each component in final report.

2. Any method of ground resistance testing is considered acceptable if it can verify continuity and quantify impotence to ground to include fall-of-potential, induced frequency, and clamp-on testing. If initial tests indicate a problem or concern (e.g. ground resistance greater than 25 ohms), a more detailed test must be performed using fall -of-potential or 3-point test. Contractor shall submit a ground testing plan prior to commencing testing.

3. In the following locations, where installed, the lightning protection system must be inspected and tested for continuity to ground, ground resistance and certification in accordance with Underwriters Laboratory (UL) standard 96A. Include a list of any obvious deficiencies to lightning protection systems and resistance measurements of each component in final report.

Electrical Sub Station Building 261 (Boiler Plant) Building 19 Building 218 Building 18 Building 24 Building 26 Building 27 Building 30 Building 31 Building 35 Building 210 Building 211

4. Summary of Report Requirements:

A. A complete written report of the work performed shall be provided to the VA within 7 days of completion of the service. Information shown in the report shall be as following:

1) Company’s name, addresses, telephone, & FAX numbers.

2) Name, credentials, and signature of contractors who perform the maintenance and testing.

3) VA Work Contract Number, name and number of VA Contracting Officer.

4) Date and Time of work.

5) Copies of contractors’ valid licenses, professional and training certificates.

6) Descriptions and model number of specialized tools and equipment used, such as torque wrench or infra-red scanning camera.

7) Location, Type, Name, and nameplate information of electrical equipment maintained and tested.

8) Descriptions of work items.

9) Test data.

10) Reference materials such as equipment manufacturer’s specifications, coordination study, etc.

11) Remarks on conditions of electrical equipment. List all deficiencies, if any.

12) A Registered Professional Engineer shall personally review and sign the final report as well as provide the VA with the results, recommendations, future actions, and professional opinions.

B. Submit hard copy and digital copy of the complete written report to VA Contracting Officer within seven (7) calendar days of completion of work.

C. Submit hard copy and digital copy of the complete written report, in Microsoft Word format to the Chief of Facilities Management within seven (7) calendar days of completion of work. All reference materials shall be included in the electronic version of the report, either through scanning or other means of electronic text import methods.

RECORDS MANAGEMENT OBLIGATIONS

A. Applicability This clause applies to all Contractors whose employees create, work with, or otherwise handle Federal records, as defined in Section B, regardless of the medium in which the record exists.

B. Definitions “Federal record” as defined in 44 U.S.C. § 3301, includes all recorded information, regardless of form or characteristics, made or received by a Federal agency under Federal law or in connection with the transaction of public business and preserved or appropriate for preservation by that agency or its legitimate successor as evidence of the organization, functions, policies, decisions, procedures, operations, or other activities of the United States Government or because of the informational value of data in them.

The term Federal record:

1. Includes Chillicothe VAMC records.

2. Does not include personal materials.

3. Applies to records created, received, or maintained by Contractors pursuant to their Chillicothe VAMC contract.

4. May include deliverables and documentation associated with deliverables.

C. Requirements

1. Contractor shall comply with all applicable records management laws and regulations, as well as National Archives and Records Administration (NARA) records policies, including but not limited to the Federal Records Act (44 U.S.C. chs. 21, 29, 31, 33), NARA regulations at 36 CFR Chapter XII Subchapter B, and those policies associated with the safeguarding of records covered by the Privacy Act of 1974 (5 U.S.C. 552a). These policies include the preservation of all records, regardless of form or characteristics, mode of transmission, or state of completion.

2. In accordance with 36 CFR 1222.32, all data created for Government use and delivered to, or falling under the legal control of, the Government are Federal records subject to the provisions of 44 U.S.C. chapters 21, 29, 31, and 33, the Freedom of Information Act (FOIA) (5 U.S.C. 552), as amended, and the Privacy Act of 1974 (5 U.S.C. 552a), as amended and must be managed and scheduled for disposition only as permitted by statute or regulation.

3. In accordance with 36 CFR 1222.32, Contractor shall maintain all records created for Government use or created in the course of performing the contract and/or delivered to, or under the legal control of the Government and must be managed in accordance with Federal law. Electronic records and associated metadata must be accompanied by sufficient technical documentation to permit understanding and use of the records and data.

4. Chillicothe VAMC and its contractors are responsible for preventing the alienation or unauthorized destruction of records, including all forms of mutilation. Records may not be removed from the legal custody of Chillicothe VAMC or destroyed except for in accordance with the provisions of the agency records schedules and with the written concurrence of the Head of the Contracting Activity. Willful and unlawful destruction, damage or alienation of Federal records is subject to the fines and penalties imposed by 18 U.S.C. 2701. In the event of any unlawful or accidental removal, defacing, alteration, or destruction of records, Contractor must report to Chillicothe VAMC. The agency must report promptly to NARA in accordance with 36 CFR 1230.

5. The Contractor shall immediately notify the appropriate Contracting Officer upon discovery of any inadvertent or unauthorized disclosures of information, data, documentary materials, records or equipment. Disclosure of non-public information is limited to authorized personnel with a need-to-know as described in the contract. The Contractor shall ensure that the appropriate personnel, administrative, technical, and physical safeguards are established to ensure the security and confidentiality of this information, data, documentary material, records and/or equipment is properly protected. The Contractor shall not remove material from Government facilities or systems, or facilities or systems operated or maintained on the Government’s behalf, without the express written permission of the Head of the Contracting Activity. When information, data, documentary material, records and/or equipment is no longer required, it shall be returned to Chillicothe VAMC control or the Contractor must hold it until otherwise directed. Items returned to the Government shall be hand carried, mailed, emailed, or securely electronically transmitted to the Contracting Officer or address prescribed in the [contract vehicle]. Destruction of records is EXPRESSLY PROHIBITED unless in accordance with Paragraph (4).

6. The Contractor is required to obtain the Contracting Officer's approval prior to engaging in any contractual relationship (sub-contractor) in support of this contract requiring the disclosure of information, documentary material and/or records generated under, or relating to, contracts. The Contractor (and any sub-contractor) is required to abide by Government and Chillicothe VAMC guidance for protecting sensitive, proprietary information, classified, and controlled unclassified information.

7. The Contractor shall only use Government IT equipment for purposes specifically tied to or authorized by the contract and in accordance with Chillicothe VAMC policy.

8. The Contractor shall not create or maintain any records containing any non-public Chillicothe VAMC information that are not specifically tied to or authorized by the contract.

9. The Contractor shall not retain, use, sell, or disseminate copies of any deliverable that contains information covered by the Privacy Act of 1974 or that which is generally protected from public disclosure by an exemption to the Freedom of Information Act.

10. The Chillicothe VAMC owns the rights to all data and records produced as part of this contract. All deliverables under the contract are the property of the U.S. Government for which Chillicothe VAMC shall have unlimited rights to use, dispose of, or disclose such data contained therein as it determines to be in the public interest. Any Contractor rights in the data or deliverables must be identified as required by FAR 52.227-11 through FAR 52.227-20.

11. Training. All Contractor employees assigned to this contract who create, work with, or otherwise handle records are required to take Chillicothe VAMC-provided records management training. The Contractor is responsible for confirming training has been completed according to agency policies, including initial training and any annual or refresher training.

[Note: To the extent an agency requires contractors to complete records management training, the agency must provide the training to the contractor.] D. Flowdown of requirements to subcontractors

1. The Contractor shall incorporate the substance of this clause, its terms and requirements including this paragraph, in all subcontracts under this [contract vehicle], and require written subcontractor acknowledgment of same.

2. Violation by a subcontractor of any provision set forth in this clause will be attributed to the Contractor.

5. Enterprise Management Controls.

All work will be coordinated a minimum of 14 working days in advance with the VAMC COR and Chief, Engineering. All contractor personnel will report to Building 21, Engineering to sign into the facility and receive contractor identification as well as any special instructions at the beginning of each workday. Contractor must report to B21, Engineering to sign out and report out at the end of each workday.

6. Security Requirements Contractor will not require access to VA sensitive information to fulfill the terms of the contract. Contractor will require access to the building and the related building service equipment during normal business hours.

7. Risk Control Work to be conducted in non-patient care area. No PCRA/ICRA required for this work.

8. Place of Performance The place of performance is Chillicothe VAMC 17273 State Route 104 Chillicothe, Ohio 45601

9. Period of Performance The period of performance shall be no more than 90 days from the issuance of the Notice to Proceed by the Contracting Officer.

Appendix A

Inventory of Electrical Gear for Testing and Preventive Maintenance

MAIN SUBSTATION

ITEM #1. ONE (1) GENERAL ELECTRIC 15KV 1200A THREE PHASE DRAW-OUT VACUUM CIRCUIT BREAKER.

Clean, inspect, lubricate, and test as per appropriate appendix.

ITEM #2. THREE (3) BASLER ELECTRIC TYPE BE1-50/51 SINGLE PHASE TIME OVER CURRENT RELAYS.

Clean, inspect, lubricate, and test as per appropriate appendix.

ITEM #3. TWO (2) PACIFIC CREST ELECTRIC 7500KVA 12470V-4160/2400V THREE PHASE OIL FILLED POWER TRANSFORMERS.

Clean, inspect, and test as per appropriate appendix.

ITEM #4. Test grounding systems and lightning protection systems on main substation equipment as per appendix #12

BACK-UP GENERATOR (OUTDOOR)

ITEM #5. TWO (2) SQUARE D ELECTRIC 5KV 1200A TYPE VR THREE PHASE DRAW-OUT VACUUM CIRCUIT BREAKERS.

Clean, inspect, lubricate, and test as per appropriate appendix.

ITEM #6. ONE (1) GENERAL ELECTRIC TYPE MULTILIN SR-750 THREE PHASE TIME OVER CURRENT SYSTEM PROTECTION RELAY.

Clean, inspect, lubricate, and test as per appropriate appendix.

ITEM #7. ONE (1) GENERAL ELECTRIC TYPE 489 THREE PHASE MULTI-FUNCTION GENERATOR PROTECTION RELAY.

Clean, inspect, lubricate, and test as per appropriate appendix.

ITEM #8. Test all grounding systems on backup generators.

5KV CIRCUIT BREAKERS

ITEM #9. EIGHT (8) WESTINGHOUSE ELECTRIC 5KV 1200A TYPE 50-DHP-250 THREE PHASE DRAW-OUT AIR MAGNETIC CIRCUIT BREAKERS.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #10. THIRTY-TWO (32) WESTINGHOUSE ELECTRIC TYPE CO-8 50/51 SINGLE PHASE TIME OVERCURRENT RELAYS.

Clean, inspect, and test as per appropriate appendix.

ITEM #11. Test all grounding systems on 5 KV circuit breakers as per appropriate appendix

PARALLELING SWITCHGEAR (INDOOR)

ITEM #12. FIVE (5) SQUARE D ELECTRIC 5KV 1200A TYPE VR THREE PHASE DRAW-OUT VACUUM CIRCUIT BREAKERS.

Clean, inspect, lubricate, and test as per appropriate appendix.

ITEM #13. TWO (2) BASLER ELECTRIC TYPE BE1-851 THREE PHASE TIME OVER CURRENT SYSTEM PROTECTION RELAYS.

Clean, inspect, lubricate, and test as per appropriate appendix.

ITEM #14. Test grounding systems and lightning protection systems on parallelling switchgear as per appropriate appendix.

BUILDING #7

ITEM #15. ONE (1) COOPER ELECTRIC 750KVA 4160V-480/277V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #16. ONE (1) WESTINGHOUSE ELECTRIC 480V 1600A TYPE DS-416 THREE PHASE DRAW-OUT AIR FRAME CIRCUIT BREAKER.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #17. EIGHT (8) WESTINGHOUSE ELECTRIC 480V 800A TYPE DS-206 THREE PHASE DRAW-OUT AIR FRAME CIRCUIT BREAKERS.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #18. ONE (1) WESTINGHOUSE ELECTRIC 480V 1600A THREE PHASE METAL ENCLOSED SWITCHGEAR STRUCTURE.

Clean, inspect, and test as per appropriate appendix.

ITEM #19. Test all grounding systems on above equipment at Building 7 as well as building grounding systems as per appropriate appendix.

CHAPEL BUILDING #252

ITEM #20. ONE (1) COOPER ELECTRIC 150KVA 4160V-480/277V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #21. Test all grounding systems on above equipment at Building 252 as well as building grounding systems as per appropriate appendix.

BUILDING #24

ITEM #22. ONE (1) PAUWELS ELECTRIC 750KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #23. ONE (1) WESTINGHOUSE ELECTRIC 208V 1600A TYPE DS-416 THREE PHASE DRAW-OUT AIR FRAME CIRCUIT BREAKER.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #24. ONE (1) WESTINGHOUSE ELECTRIC 208V 1600A THREE PHASE METAL ENCLOSED SWITCHGEAR STRUCTURE.

Clean, inspect, and test as per appropriate appendix.

ITEM #25. Test all grounding systems on above equipment at Building 24 as well as building grounding and lightning protection systems as per appropriate appendix.

BUILDING #24 (CHILLER)

ITEM #26. ONE (1) T&R ELECTRIC 300KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #27. Test all grounding systems on above equipment as per appropriate appendix.

BUILDING #26

ITEM #28. ONE (1) COOPER ELECTRIC 500KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #29. ONE (1) WESTINGHOUSE ELECTRIC 208V 1600A TYPE DS-416 THREE PHASE DRAW-OUT AIR FRAME CIRCUIT BREAKER.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #30. ELEVEN (11) WESTINGHOUSE ELECTRIC 208V 800A TYPE DS-206 THREE PHASE DRAW-OUT AIR FRAME CIRCUIT BREAKERS.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #31. ONE (1) WESTINGHOUSE ELECTRIC 208V 1600A THREE PHASE METAL ENCLOSED SWITCHGEAR STRUCTURE.

Clean, inspect, and test as per appropriate appendix.

ITEM #32. Test all grounding systems on above equipment at Building 26 as well as building grounding and lightning protection systems as per appropriate appendix.

BUILDING #26 (CHILLER)

ITEM #33. Reserved

ITEM #34. Test all grounding systems on above equipment as per appropriate appendix.

BUILDING #27

ITEM #35. ONE (1) COOPER ELECTRIC 500KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #36. ONE (1) WESTINGHOUSE ELECTRIC 208V 1600A TYPE DS-416 THREE PHASE DRAW-OUT AIR FRAME CIRCUIT BREAKER.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #37. ELEVEN (11) WESTINGHOUSE ELECTRIC 208V 800A TYPE DS-206 THREE PHASE DRAW-OUT AIR FRAME CIRCUIT BREAKERS.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #38. ONE (1) WESTINGHOUSE ELECTRIC 208V 1600A THREE PHASE METAL ENCLOSED SWITCHGEAR STRUCTURE.

Clean, inspect, and test as per appropriate appendix.

ITEM #39. Test all grounding systems on above equipment at Building 26 as well as building grounding and lightning protection systems as per appropriate appendix.

ITEM #41 Test all grounding systems on above equipment as per appendix #12

BUILDING #30

ITEM #42. ONE (1) WESTINGHOUSE ELECTRIC 300KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #43. ONE (1) WESTINGHOUSE ELECTRIC 208V 1600A TYPE DS-416 THREE PHASE DRAW-OUT AIR FRAME CIRCUIT BREAKER.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #44. TWELVE (12) WESTINGHOUSE ELECTRIC 208V 800A TYPE DS-206 THREE PHASE DRAW-OUT AIR FRAME CIRCUIT BREAKERS.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #45. ONE (1) WESTINGHOUSE ELECTRIC 208V 1600A THREE PHASE METAL ENCLOSED SWITCHGEAR STRUCTURE.

Clean, inspect, and test as per appropriate appendix.

ITEM #46. Test all grounding systems on above equipment at Building 30 as well as building grounding and lightning protection systems as per appropriate appendix.

BUILDING #30 (CHILLER)

ITEM #47. ONE (1) SQUARE D ELECTRIC 300KVA 4160V-480/277V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #48. Test all grounding systems on above equipment as per appropriate appendix.

BUILDING #35

ITEM #49. ONE (1) COOPER ELECTRIC 500KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #50. ONE (1) WESTINGHOUSE ELECTRIC 208V 2000A TYPE DS-420 THREE PHASE DRAW-OUT AIR FRAME CIRCUIT BREAKER.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #51. ONE (1) WESTINGHOUSE ELECTRIC 208V 2000A THREE PHASE METAL ENCLOSED SWITCHGEAR STRUCTURE.

Clean, inspect, and test as per appropriate appendix.

ITEM #52. Test all grounding systems on above equipment at Building 35 as well as building grounding and lightning protection systems as per appendix #12

BUILDING #35 (CHILLER)

ITEM #53. Reserved

ITEM #54. Test all grounding systems on above equipment as per appendix #12

BUILDING #210

ITEM #55. ONE (1) GE PROLEC 750KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #56. ONE (1) CUTLER HAMMER ELECTRIC 208V 2000A TYPE 310 + TRIP UNIT THREE PHASE STATIONARY MOUNTED CIRCUIT BREAKER.

Clean, inspect, lubricate and megger, and contact resistance test.

ITEM #57. ONE (1) GENERAL ELECTRIC 208V 2000A TYPE HPC THREE PHASE FUSED BOLTED PRESSURE SWITCH.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #58. ONE (1) GENERAL ELECTRIC 208V 2000A THREE PHASE METAL ENCLOSED SWITCHGEAR STRUCTURE.

Clean, inspect, and test as per appropriate appendix.

ITEM #59. Test all grounding systems on above equipment at Building 210 as well as building grounding and lightning protection systems as per appropriate appendix.

BUILDING #210 (CHILLER)

ITEM #60. ONE (1) GE PROLEC 500KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #61. Test all grounding systems on above equipment as per appropriate appendix.

BUILDING #211

ITEM #62. ONE (1) SQUARE D ELECTRIC 1000KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #63. ONE (1) SQUARE D ELECTRIC 208V 3000A TYPE BP THREE PHASE FUSED BOLTED PRESSURE SWITCH.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #64. ONE (1) SQUARE D ELECTRIC 208V 3000A THREE PHASE METAL ENCLOSED SWITCHGEAR STRUCTURE.

Clean, inspect, and test as per appropriate appendix.

ITEM #65. Test all grounding systems on above equipment at Building 210 as well as building grounding and lightning protection systems as per appropriate appendix.

BUILDING #211 (CHILLER)

ITEM #66. ONE (1) CG POWER 750KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #67. Test all grounding systems on above equipment as per appropriate appendix.

BOILER PLANT #261

ITEM #68. ONE (1) COOPER ELECTRIC 750KVA 4160V-480/277V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #69. ONE (1) CUTLER HAMMER ELECTRIC 480V 2000A TYPE MAGNUM DS THREE PHASE STATIONARY MOUNTED INSULATED CASE CIRCUIT BREAKER.

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #70. ONE (1) CUTLER HAMMER ELECTRIC 480V 2000A TYPE MAGNUM DS THREE PHASE STATIONARY MOUNTED INSULATED CASE CIRCUIT BREAKER.

Clean, inspect, lubricate, and contact resistance test.

ITEM #71. Test all grounding systems on above equipment at Building 210 as well as building grounding and lightning protection systems as per appropriate appendix.

ITEM #72. Test all grounding systems on above equipment at Building 261 as well as building grounding and lightning protection systems as per appropriate appendix.

BUILDING #1

ITEM #73. ONE (1) COOPER ELECTRIC 300KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #74. Test all grounding systems on above equipment at Building 1 as well as building grounding as per appropriate appendix.

BUILDING #3

ITEM #75. ONE (1) COOPER ELECTRIC 150KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #76. Test all grounding systems on above equipment at Building 3 as well as building grounding systems as per appropriate appendix.

BUILDING #8

ITEM #77. ONE (1) COOPER ELECTRIC 75KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #78. Test all grounding systems on above equipment at Building 8 as well as building grounding systems as per appropriate appendix.

BUILDING #9

ITEM #79. ONE (1) COOPER ELECTRIC 150KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #80. Test all grounding systems on above equipment at Building 9 as well as building grounding systems as per appropriate appendix.

BUILDING #25

ITEM #81. ONE (1) COOPER ELECTRIC 500KVA 4160V-480/277V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appendix #8 ITEM #65. Test all grounding systems on above equipment at Building 25 as well as building grounding as per appropriate appendix.

BUILDING #28

ITEM #82. ONE (1) COOPER ELECTRIC 300KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #83. Test all grounding systems on above equipment at Building 28 as well as building grounding systems as per appropriate appendix.

BUILDING #36

ITEM #84. ONE (1) COOPER ELECTRIC 225KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #85. Test all grounding systems on above equipment at Building 36 as well as building grounding as per appropriate appendix.

ITEM #86. ONE (1) COOPER ELECTRIC 75KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #87. Test all grounding systems on above equipment at Building 53 as well as building grounding and lightning protection systems as per appropriate appendix.

BUILDING #212

ITEM #88. ONE (1) COOPER ELECTRIC 300KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #89. Test all grounding systems on above equipment at Building 212 as well as building grounding systems as per appropriate appendix.

BUILDING #247

ITEM #90. ONE (1) COOPER ELECTRIC 300KVA 4160V-208/120V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #91. Test all grounding systems on above equipment at Building 247 as well as building grounding systems as per appropriate appendix.

BUILDING #256

ITEM #92. ONE (1) COOPER ELECTRIC 112.5KVA 4160V-480/277V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #93. Test all grounding systems on above equipment at Building 256 as well as building grounding systems as per appropriate appendix.

BUILDING #31

ITEM #94. ONE (1) SQUARE D 2000KVA 4160V-480/277V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #95. ONE (1) SQUARE D 1500KVA 4160V-480/277V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #96. ONE (1) SQUARE D 750KVA 4160V-480/277V THREE PHASE OIL FILLED POWER TRANSFORMER.

Clean, inspect, and test as per appropriate appendix.

ITEM #97. TWO (2) SQUARE D ELECTRIC (INDOOR) 480V 3000A THREE PHASE METAL ENCLOSED SWITCHGEAR STRUCTURE.

Clean, inspect, and test as per appropriate appendix.

ITEM #98. ONE (1) SQUARE D ELECTRIC (OUTDOOR) 480V 3000A THREE PHASE METAL ENCLOSED SWITCHGEAR STRUCTURE.

Clean, inspect, and test as per appropriate appendix.

ITEM #99. TWO (2) SQUARE D ELECTRIC 480V 3000A, NW 30 H CIRCUIT BREAKER, NEMA AB1/NMX-J-266-ANCE Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #100. ELEVEN (11) SQUARE D ELECTRIC 480V 400A, LG400 CIRCUIT BREAKER

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #101. FIVE (5) SQUARE D ELECTRIC 480V 600A, LG600 CIRCUIT BREAKER,

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #102. FIVE (5) SQUARE D ELECTRIC 480V 800A, PG800 CIRCUIT BREAKER,

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #103. THREE (3) SQUARE D ELECTRIC 480V 150A, HG600 CIRCUIT BREAKER,

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #104. ONE (1) SQUARE D ELECTRIC 480V 1600A, RG1600 CIRCUIT BREAKER,

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #105. ONE (1) SQUARE D ELECTRIC 480V 250A, JG250 CIRCUIT BREAKER,

Clean, inspect, lubricate and test as per appropriate appendix.

ITEM #106. Test all grounding systems on above equipment at Building 31 as well as building grounding and lightning protection systems as per appropriate appendix.

Appendix B

Inventory of Electrical Gear for Infrared Inspection Below is a list of electrical distribution equipment that shall be inspected with infrared equipment testing with appendixes of detailed work for each equipment type.

Main Substation:

One 15KV 1200A draw out vacuum breaker Two 5000KVA Transformers Overhead connection points

Backup Generator:

Two 5KV 1200A breakers Seven 5KV 1200A breakers

5KV Circuit Breakers:

Eight 5KV 1200A breakers

Building 7 Load Center:

One 750KVA Transformer One 1600A breaker Eight 800A breakers One Switchgear Structure

Building 18 Load Center:

Two 150KVA transformers

Building 24 Load Center:

One 750KVA transformer One 1600A breaker One Switchgear Structure

Building 24 Chiller:

One 300KVA transformer

Building 26 Load Center:

One 500KVA transformer One 1600A breaker Eleven 800A breakers One Switchgear Structure

Building 27 Load Center:

One 500KVA transformer One 1600A breaker Eleven 800A breakers One Switchgear Structure

Building 30 Load Center:

One 300KVA transformer One 1600A breaker Twelve 800A breakers One Switchgear Structure

Building 30 Chiller:

One 300KVA transformer

Building 31 Load Center:

One 1500KVA transformer One 2000KVA transformer One 750KVA transformer One 1600A breaker One 3000A breaker Two Switchgear Structure

Building 35 Load Center:

One 500KVA transformer One 2000A breaker One Switchgear Structure

Building 210 Load Center:

One 750KVA transformer One 2000A breaker One Switchgear Structure

Building 210 Chiller:

One 500KVA transformer

Building 211 Load Center:

One 750KVA transformer One 2000A breaker One Switchgear Structure

Building 211 Chiller:

One 500KVA transformer

Building 261 Load Center:

One 750KVA transformer One 2000A breaker

Government-Furnished Equipment (GFE)/Government-Furnished Information (GFI).

No GFE will be supplied by the VA.

Inspection and acceptance will be certified by the COR and the Electrical Supervisor.

Risk Control All distribution switching will be done by VAMC electricians.

Period of Performance Inspections to be completed in calendar year 2025.

Delivery Schedule Reports to be delivered within 60 days of completed inspections.

APPENDIX C

SF6 CIRCUIT SWITCHER

A) VISUAL AND MECHANICAL INSPECTION

B) ELECTRICAL TESTS

APPENDIX D

MEDIUM AND HIGH VOLTAGE SURGE PROTECTION DEVICES

APPENDIX E

TRANSFORMERS - LIQUID FILLED

a) Dielectric breakdown voltage, Acid neutralization number, Specific gravity

b) Interfacial tension, Color, Visual condition, PPM water

c) Perform dissolved gas analysis (DGA)

APPENDIX F

CIRCUIT BREAKER - MEDIUM VOLTAGE - VACUUM

in excess of the breaker manufacturer's recommended maximum.

APPENDIX G

PROTECTIVE RELAYS

a) Pickup parameters on each operating element.

b) Timing test shall be performed at two (2) points on time dial curve.

c) Pickup targets and seal in units.

d) Special tests as required to check operation of restraint, direction, and other elements per manufacturer's instructions.

APPENDIX H

AIR SWITCHES - MEDIUM VOLTAGE - METAL ENCLOSED

APPENDIX I

TRANSFORMERS - LIQUID FILLED

APPENDIX J

CIRCUIT BREAKERS - LOW VOLTAGE - POWER

APPENDIX K

TRANSFORMERS - LIQUID FILLED – SINGLE PHASE

APPENDIX L

CIRCUIT BREAKERS - LOW VOLTAGE - POWER

APPENDIX M

PAD-MOUNT SWITCHES

APPENDIX N

Grounding Systems

B.3 PRICE/COST SCHEDULE

ITEM INFORMATION

ITEM NUMBER
DESCRIPTION OF SUPPLIES/SERVICES
QUANTITY
UNIT
UNIT PRICE
AMOUNT
1.00
JB
__________________
__________________

Triennial Electrical Inspection

GRAND TOTAL
__________________

Page 1 of Page 1 of

SECTION C - CONTRACT CLAUSES

ADDENDUM to FAR 52.212-4 CONTRACT TERMS AND CONDITIONS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES Clauses that are incorporated by reference (by Citation Number, Title, and Date), have the same force and effect as if they were given in full text. Upon request, the Contracting Officer will make their full text available.

The following clauses are incorporated into 52.212-4 as an addendum to this contract:

C.1 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)

This contract incorporates one or more clauses by reference, with the same force and effect as if they were given in full text. Upon request, the Contracting Officer will make their full text available. Also, the full text of a clause may be accessed electronically at this/these address(es):

https://www.acquisition.gov/browse/index/far https://www.va.gov/oal/library/vaar/

(End of Clause)

FAR Number
Title
Date
52.203-17
CONTRACTOR EMPLOYEE WHISTLEBLOWER RIGHTS
NOV 2023
52.204-13
SYSTEM FOR AWARD MANAGEMENT MAINTENANCE
OCT 2018
52.204-18
COMMERCIAL AND GOVERNMENT ENTITY CODE MAINTENANCE
AUG 2020

C.2 52.217-8 OPTION TO EXTEND SERVICES (NOV 1999)

The Government may require continued performance of any services within the limits and at the rates specified in the contract. These rates may be adjusted only as a result of revisions to prevailing labor rates provided by the Secretary of Labor. The option provision may be exercised more than once, but the total extension of performance hereunder shall not exceed 6 months. The Contracting Officer may exercise the option by written notice to the Contractor within 30 days.

(End of Clause)

C.3 52.217-9 OPTION TO EXTEND THE TERM OF THE CONTRACT (MAR 2000)

(a) The Government may extend the term of this contract by written notice to the Contractor within 30 days; provided that the Government gives the Contractor a preliminary written notice of its intent to extend at least 60 days before the contract expires. The preliminary notice does not commit the Government to an extension.

(b) If the Government exercises this option, the extended contract shall be considered to include this option clause.

(c) The total duration of this contract, including the exercise of any options under this clause, shall not exceed five (5) years.

(End of Clause) C.4 52.237-2 PROTECTION OF GOVERNMENT BUILDINGS, EQUIPMENT, AND VEGETATION (APR 1984) The Contractor shall use reasonable care to avoid damaging existing buildings, equipment, and vegetation on the Government installation. If the Contractor's failure to use reasonable care causes damage to any of this property, the Contractor shall replace or repair the damage at no expense to the Government as the Contracting Officer directs. If the Contractor fails or refuses to make such repair or replacement, the Contractor shall be liable for the cost, which may be deducted from the contract price.

(End of Clause)

C.5 VAAR 852.203-70 COMMERCIAL ADVERTISING (MAY 2018)

The Contractor shall not make reference in its commercial advertising to Department of Veterans Affairs contracts in a manner that states or implies the Department of Veterans Affairs approves or endorses the Contractor’s products or services or considers the Contractor’s products or services superior to other products or services.

(End of Clause) C.6 VAAR 852.219-73 VA NOTICE OF TOTAL SET-ASIDE FOR CERTIFIED SERVICE-DISABLED VETERAN-OWNED SMALL BUSINESSES (JAN 2023) (DEVIATION)

(a) Definition. for the Department of Veterans Affairs, ‘‘Service-disabled Veteran-owned small business concern or SDVOSB’’:

(1) Means a small business concern—

(i) Not less than 51 percent of which is owned by one or more service-disabled Veterans or, in the case of any publicly owned business, not less than 51 percent of the stock of which is owned by one or more service-disabled Veterans or eligible surviving spouses (see VAAR 802.201, Surviving Spouse definition);

(ii) The management and daily business operations of which are controlled by one or more service-disabled Veterans (or eligible surviving spouses) or, in the case of a service-disabled Veteran with permanent and severe disability, the spouse or permanent caregiver of such Veteran;

(iii) The business meets Federal small business size standards for the applicable North American Industry Classification System (NAICS) code identified in the solicitation document;

(iv) The business has been certified for ownership and control pursuant to 38 U.S.C. 8127, 13 CFR 128, and is listed as certified in the SBA certification database at…