This pre-solicitation announcement and related federal contract opportunity describe a planned invitation for bid for repair work at a Department of Veterans Affairs medical center parking structure. The solicitation will seek bids for repairs to parking structures at the VA Ann Arbor Healthcare System in Ann Arbor, Michigan, including repairing concrete surfaces, installing fall protection systems, replacing lighting and signage, tuckpointing bricks, replacing expansion joints, and roof repairs. The project value is estimated between $1 million and $5 million. The awarded firm fixed price contract will have a performance period of 380 days. The solicitation is expected to be posted on June 10, 2020 on beta.SAM.gov. Questions must be submitted by email by the date specified in the solicitation. Bids will be due on the date provided in the solicitation to be issued.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEVEL AA
89' - 0"
INSTALL NEW SWEEP
ALUMINUM THRESHOLD, SET IN
FULL BED OF SEALANT
VERIFY DOOR, AND REPAIR/
REPLACE CONDITIONS, SEE DOOR
SCHEDULE
BACKER ROD WITH SEALANT
EXISTING CONCRETE SLAB
EXISTING PARKING STRUCTURE
DIAMOND PLATE JOINT COVER, WITH
RECESSED FASTNER AT 6" O.C.
AS500
TYP, EA. SD.
**NOTE:
SIM. CONDITION EXP. JT,
VARIES IN SIZE
INSTALL NEW WEATHERSTRIPPING
BACKER ROD
EXISTING DOOR AND
FRAME TO REMAIN,
REPAIR/REPLACE AS
REQUIRED SEE DOOR
SCHEDULE
CONTINUOUS BACKER ROD
AND SEALANT EA. SD.,
EXISTING WALL
EXISTING BRICK TO REMAIN
EXISTING MORTAR TO REMAIN
TUCKPOINT AREAS OF
LOOSE/DELAPIDATED
MORTAR JOINT, BOTH
HORIZONTAL AND VERTICAL.
TYPICAL, MATCH ADJACENT
EXISTING MORTAR COLOR
AND POINT STYLE
1"
SILICONE FACED
COMPRESSIBLE EXPANSION
JOINT FILLER, CONT. TYP.
UP TO 10"
VARIES
EXISTING STAIR
EXISTING
PARKING
GARAGE
EXISTING CAST
STONE VENEER
TO REMAIN
DOUBLE LINE OF BACKER
ROD AND SEALANT
FILL CHIPPED/ SPALLED PORTIONS
OF CAST STONE (TYP) VERIFY
COLOR MATCH WITH ARCHITECT
PRIOR TO COMMENCING WORK
AS500
INSTALL NEW DOOR SWEEP
ALUMINUM THRESHOLD, SET IN
FULL BED OF SEALANT
SILICONE SEALANT OVER 2" COMPRESSIBLE
FILLER
EXISTING CONCRETE SLAB
EXISTING PARKING STRUCTURE
DIAMOND PLATE JOINT COVER, WITH
RECESSED FASTNER AT 6" O.C.
TYP, EA. SD.
**NOTE:
SIM. CONDITION EXP. JT,
VARIES IN SIZE
TRENCH DRAIN,
COORDINATE W/
PLUMBING
VERIFY DOOR, AND REPAIR/
REPLACE CONDITIONS, SEE DOOR
SCHEDULE
LOW-PROFILE TRENCH
DRAIN (BEYOND),
COORDINATE W/ PLUMBING
INSTALL NEW WEATHERSTRIPPING
BACKER ROD
0' - 7"
0'
/4
E
CAST STONE PARAPET CAP, PROFILE
AND COLOR TO MATCH EXISTING
CAST STONE PANEL, PROFILE
AND COLOR TO MATCH EXISTING
PANEL ANCHOR CLIP, AND WEDGE ANCHOR
BOND BEAM, FULLY GROUTED WITH
REINFORCING BAR, MATCH EXISTING
SIZE, DOWEL INTO ADJACENT
REMAINING BLOCK 1 FULL BLOCK @
EA. END
GROUT, MATCH EXISTING COLOR
AND POINT STYLE, (TYP)
EXISTING CAST STONE
PANEL, SEE 5/AS500
EXISTING PARKING DECK
EXISTING BRICK VENEER
EXISTING SEAT ANGLE, RE ANCHOR AS REQUIRED
FLASHING OVER BOND BEAM.
EXISTING CMU (TYP)
8" CELLULAR VENT, GARAGE SIDE
OF CMU @ 4'-0" O.C., PROVIDE AT
GARAGE LANDING AT TOP
(UNDERSIDE OF DECK) AND
BOTTOM OF WALL (ABOVE DECK)
AT STAIR TOWER (TYP) COLOR TO
MATCH EXISTING MORTAR
Level C 122' - 0"
INSTALL BENTONITE
SHEET WATERPROOFING,
TO T.O.F. SUBGRADE
ALONG WALL FACE
ALUM. THROUGH WALL PAN FLASHING,
CONT., SET IN FULL BED OF SEALANT
RE INSTALL EXISTING CURTIAN WALL ASSEMBLY
CONT. BACKER ROD AND SEALANT
DOUBLE LINE OF
BACKER ROD AND
SEALANT, CONT.
CONT. SEALANT @ FACE
OF WALL AND HEMMED
PAN FLASHING (TYP)
EXISTING CMU (TYP)
CELLULAR VENT, GARAGE SIDE OF BRICK @ 4'-0" O.C.,
PROVIDE AT GARAGE LANDING AT TOP (UNDERSIDE OF
DECK) AND BOTTOM OF WALL (ABOVE DECK) AT STAIR
TOWER (TYP) COLOR TO MATCH EXISTING MORTAR
EXISTING BRICK (TYP)
BACKER ROD WITH SEALANT
EXISTING PARKING STRUCTURE
**NOTE:
SIM. CONDITION EXP. JT,
VARIES IN SIZE
WALL BEYOND
EXISTING CURTAIN WALL
CONT. BACKER ROD AND SEALANT
.080 PREFINISHED BRAKE METAL COVER
OVER EXISTING JAMB.
MATCH CURTAIN WALL FINISH (WHITE)
FASTEN TO MASONRY 2' O.C. MAX. - SEE PROFILE
0' - 3"
0'
/4
0' - 6 3/4"
FLASHING PROFILE
EXISTING CMU WALL,
ROOFING MEMBRANE
EXISTING STONE CAP
NOTE:
PROVIDE LAP SEALANT AROUND ALL
FLASHING PERIMETER
EXISTING ROOF DECK
EXISTING PROTECTION BOARD
EXISTING RIGID INSULATION
CANT STRIP
ROOFING MEMBRANE
TERMINATION BAR WITH FASTENER
EVERY 24" O.C. MIN
BEAD OF SEALANT
(4)- 3/4" EPOXY ANCHORS 3" MIN. EMBED.
3/8"x8"x8" BASE PLATE
GALVANIZED.
EXISTING DOUBLE TEE
6" DIA. STEEL BOLLARD SCHED
40 PIPE, GALVANIZED AND
FILLED WITH CONCRETE.
1/8" THICK HIGH DENSITY
POLYETHYLENE (HDPE) BOLLARD
COVER WITH REFLECTIVE STRIP,
COLOR TO BE SELECTED FROM
MANUFACTURERS FULL RANGE
A F
F M
IN
IM
U M
1/4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
65% DESIGN
95% DESIGN
BID DOCUMENTS
03/06/2019
08/16/2019
05/29/2020
DAVE MARCHIONNA, CHIEF ENGINEERING, DESIGN AND
CONSTRUCTION
AMENDMENT 0005 08/04/2020
C U s e rs \a o g rz e w a lla
\D o c u m e n ts
\1 .1
.0
R e n o v
A ro g rz e w a lla
.r v t
/4
/2
:5
:3
P M
AS500
REPAIR DETAILS
GUIDON DESIGN, INC.
1221 N PENNSYLVANIA ST
INDIANAPOLIS, IN 46204
317-441-3000
GHAFARI ASSOCIATES, LLC
17101 MICHIGAN AVENUE
DEARBORN, MI 48126
313-441-3000
REPAIR PARKING STRUCTURES
VA ANN ARBOR HEALTHCARE SYSTEM, MI
506-19-103
N/A
05/29/2020 JG KN
BID DOCUMENTS
SCALE: 3" = 1'-0"AS500
1 THRESHOLD SECTION
CONTINUOUS BEAD OF SEALANT (BEYOND)
SCALE: 3" = 1'-0"AS500
2 JAMB DETAIL AT STAIR TOWER
SCALE: 6" = 1'-0"AS500
3 TYPICAL TUCK POINT
SCALE: 3" = 1'-0"AS500
4 EXPANSION JOINT JAMB
SCALE: 3" = 1'-0"AS500
5 STONE AND JOINT CORNER REPAIR
SCALE: 3" = 1'-0"AS500
6 STAIR THRESHOLD DRAIN SECTION
SCALE: 1 1/2" = 1'-0"AS500
7 CAST STONE REPAIR AT PARAPET CAP
SCALE: 6" = 1'-0"AS500
8 TYPICAL CELLULAR VENT INSERT
SCALE: 1 1/2" = 1'-0"AS500
9 SECTION DETAIL AT CURTIANWALL SILL AT ENTRYWAY
SCALE: 6" = 1'-0"AS500
10 BRICK CELLULAR VENT
SCALE: 3" = 1'-0"AS500
11 EXPANSION JOINT 2
SCALE: 1 1/2" = 1'-0"AS500
12 JAMB COVER
SCALE: 1 1/2" = 1'-0"AS500
13 ROOF MEMBRANE REPAIR DETAIL
Revisions: Date:
SCALE: 1 1/2" = 1'-0"AS500
14 BOLLARD DETAIL
| Sheets |
| AS500 - REPAIR DETAILS |