36C25018B0197-00002001.pdf
PDF 943 KB Posted
- Attached to
- Install PA Systems in Trailers 539-18-201 Federal contract opportunity
- Solicitation number
- 36C25018B0197
About this file
36C25018B0197 00002 RESPONSE to RFI.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25018B0197-00002000.docx | DOCX document | |
| 36C25018B0197-00001002.pdf | ||
| 36C25018B0197-00001000.docx | DOCX document | |
| 36C25018B0197-00001001.pdf | ||
| 36C25018B0197-008.pdf | ||
| 36C25018B0197-001.docx | DOCX document | |
| 36C25018B0197-004.pdf | ||
| 36C25018B0197-007.docx | DOCX document | |
| 36C25018B0197-006.docx | DOCX document | |
| 36C25018B0197-002.doc | DOC document | |
| 36C25018B0197-005.docx | DOCX document | |
| 36C25018B0197-003.pdf | ||
| 36C25018B0197-000.docx | DOCX document |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
QUESTIONS AND ANSWERS TO RFI’s
1. Q: Conduit and boxes need to be installed above the ceiling in the IH&S trailer, but the ceiling is drywall.
Will the contractor be required to demo the ceiling and repair as needed?
A: Yes, Refer to E001/Notes D/E.
2. Q: Please verify if J-Hooks are acceptable for the armored fiber cable. Specs state that all cable shall be in conduit?
A: J-Hooks are acceptable for armored fiber.
3. Q: Are there any ductbanks from the manhole to the trailers? Please see attached sketch-A. If there is not an existing ductbank in place from the manhole to the trailers will the 1-1/4” conduit from the manhole need to be encased in a trench and then rise up below the platform between the trailers. Please confirm trench details if required.
A: Provide 2-2” PVC conduit concrete encase 30” below grade from trailer to manhole near street.
4. Q: Can you provide us the current service provider for the existing Honeywell fire alarm system?
A: Courtney Shoemaker, Honeywell, (614) 800-9450, Courtney.shoemaker@honeywell.com.
mailto:Courtney.shoemaker@honeywell.com
RFI #1: SKETCH A
| A: Yes, Refer to E001/Notes D/E. |
| A: J-Hooks are acceptable for armored fiber. |
| A: Provide 2-2” PVC conduit concrete encase 30” below grade from trailer to manhole near street. |