36C25018B0197-00002001.pdf

PDF 943 KB Posted

Attached to
Install PA Systems in Trailers 539-18-201 Federal contract opportunity
Solicitation number
36C25018B0197
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25018B0197 00002 RESPONSE to RFI.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Install PA Systems in Trailers 539-18-201, newest first.
File Type Posted
36C25018B0197-00002000.docx DOCX document
36C25018B0197-00001002.pdf PDF
36C25018B0197-00001000.docx DOCX document
36C25018B0197-00001001.pdf PDF
36C25018B0197-008.pdf PDF
36C25018B0197-001.docx DOCX document
36C25018B0197-004.pdf PDF
36C25018B0197-007.docx DOCX document
36C25018B0197-006.docx DOCX document
36C25018B0197-002.doc DOC document
36C25018B0197-005.docx DOCX document
36C25018B0197-003.pdf PDF
36C25018B0197-000.docx DOCX document
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

QUESTIONS AND ANSWERS TO RFI’s

1. Q: Conduit and boxes need to be installed above the ceiling in the IH&S trailer, but the ceiling is drywall.

Will the contractor be required to demo the ceiling and repair as needed?

A: Yes, Refer to E001/Notes D/E.

2. Q: Please verify if J-Hooks are acceptable for the armored fiber cable. Specs state that all cable shall be in conduit?

A: J-Hooks are acceptable for armored fiber.

3. Q: Are there any ductbanks from the manhole to the trailers? Please see attached sketch-A. If there is not an existing ductbank in place from the manhole to the trailers will the 1-1/4” conduit from the manhole need to be encased in a trench and then rise up below the platform between the trailers. Please confirm trench details if required.

A: Provide 2-2” PVC conduit concrete encase 30” below grade from trailer to manhole near street.

4. Q: Can you provide us the current service provider for the existing Honeywell fire alarm system?

A: Courtney Shoemaker, Honeywell, (614) 800-9450, Courtney.shoemaker@honeywell.com.

mailto:Courtney.shoemaker@honeywell.com

RFI #1: SKETCH A

A: Yes, Refer to E001/Notes D/E.
A: J-Hooks are acceptable for armored fiber.
A: Provide 2-2” PVC conduit concrete encase 30” below grade from trailer to manhole near street.
A: Courtney Shoemaker, Honeywell, (614) 800-9450, Courtney.shoemaker@honeywell.com.