36C24818R0391-240.pdf

PDF 13 MB Posted

Attached to
Renovate A/C Bldg 102 Ph I Federal contract opportunity
Solicitation number
36C24818R0391
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

36C24818R0391 Support Hub FINAL Complete Set - REDACTED.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Renovate A/C Bldg 102 Ph I, newest first.
File Type Posted
36C24818R0391-0001000.docx DOCX document
36C24818R0391-242.pdf PDF
36C24818R0391-236.pdf PDF
36C24818R0391-241.pdf PDF
36C24818R0391-247.pdf PDF
36C24818R0391-239.pdf PDF
36C24818R0391-244.pdf PDF
36C24818R0391-245.pdf PDF
36C24818R0391-233.pdf PDF
36C24818R0391-235.pdf PDF
36C24818R0391-243.pdf PDF
36C24818R0391-234.pdf PDF
36C24818R0391-238.pdf PDF
36C24818R0391-246.pdf PDF
36C24818R0391-237.pdf PDF
36C24818R0391-232.docx DOCX document
36C24818R0391-000.docx DOCX document
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AREA OF WORK

A

B

C D

SUPPORT

BUILDING

E0.1 LEGEND & GENERAL NOTES

E2.1 LIGHTING & SIGNAL PLAN

E3.1 POWER PLAN

E4.1 ELECTRICAL ROOF PLAN

E5.1 EXISTING MODIFIED ELECTRICAL RISER DIAGRAM

E5.2 EXISTING MODIFIED FIRE ALARM SYSTEM RISER

E8.1 DETAILS

FP0.1 LEGEND, GENERAL NOTES & DETAILS

FP1.1 FLOOR PLAN

MH0.1 LEGEND & GENERAL NOTES

MH1.1 FLOOR PLAN

MH1.2 ROOF PLAN

MH2.1 ENLARGED PLANS AND SECTIONS

MH3.1 DETAILS

MH3.2 DETAILS

MH4.1 SCHEDULES

MH4.2 SCHEDULES

MH6.1 CONTROLS DIAGRAMS & SEQUENCES

MH6.2 CONTROL DIAGRAMS, POINTS LIST & SEQUENCES

MH6.3 CONTROLS DIAGRAMS & SEQUENCES

MP1.1 FLOOR PLAN

MP3.1 PIPING DIAGRAMS

MP4.1 SCHEDULES

S0.1 SLAB PLAN, STUCTURAL NOTES, DESIGN WIND LOADS & DETAILS

S1.1 ROOF FRAMING PLAN

S2.1 SECTIONS & DETAILS

A0.1 SITE PLAN

A1.0 BUILDING PHASING PLAN

A1.1 FLOOR PLAN

A3.1 REFLECTED CEILING PLAN

A4.1 ROOF PLAN

A5.1 BUILDING SECTION

DA1.1 DEMOLITION FLOOR PLAN

DA3.1 DEMOLITION REFLECTED CEILING PLAN

DA4.1 DEMOLITION ROOF PLAN

DMH1.1 DEMOLITION FLOOR PLAN

DMP1.1 DEMOLITION FLOOR PLAN

DE2.1 DEMOLITION LIGHTING & SIGNAL PLANS

DE3.1 DEMOLITION POWER PLANS

DE4.1 DEMOLITION ELECTRICAL ROOF PLAN

DE5.1 EXISTING ELECTRICAL RISER DIAGRAM

DE5.2 EXISTING FIRE ALARM SYSTEM RISER

LS1.1 LIFE SAFETY PLAN

G0.1 COVER & INDEX

G0.2 ABBREVIATIONS, SYMBOL LEGEND, & MATERIALS LEGEND

G0.3 PARTITION PENETRATION DETAILS

THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION

WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED

4525 S. Manhattan Ave. Tampa, FL 33611-2305

T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991

w w w . l o n g a n d a s s o c i a t e s . c o m

Checked By:

Seal

ALEXANDER M. LONG, A.I.A.

AR 0015104

987654321

B C

D E

F A

98765431 2

A th re e in c h e s o n e fo o t

B

C

D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t

E o n e h a lf in c h o n e fo o t

F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B A Y

P

IN

E S

M E D

IC

A L C E N

TE

R

Drawn By:Approved Division Chief

DIVISION CHIEF

Drawing Title

Approved Service Director

SERVICE DIRECTOR

Location

Building Number

Dwg. Of.

Date

Project No.

Project Title

DRAWING NO.

To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards

:2

:4

P M

AML

01/23/15

G0.1

REPLACE AIR CONDITIONING

SYSTEMS IN B-102

SUPPORT BUILDING

VAMC BAY PINES, FLORIDA 33744

TGS

COVER & INDEX

516-11-108

LOCAL AERIAL

REGIONAL AERIAL

SITESITE

REPLACE AIR CONDITIONING

SYSTEMS IN B-102

SUPPORT BUILDING

VA MEDICAL CENTER

BAY PINES, FLORIDA 33744

INDEX OF DRAWINGS

FINAL CONSTRUCTION DOCUMENTS

JANUARY 23, 2015

GENERAL

LIFE SAFETY

DEMOLITION

ARCHITECTURAL

MECHANICAL

FIRE PROTECTION

STRUCTURAL

ELECTRICAL

Issue & Revision Schedule

No. Description Date

FINAL CONSTRUCTION DOCUMENTS 01/23/15

NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR

CONFLICTS WHICH ARE ALLEGED.

COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY

BAY PINES VAHCS. NO REPRODUCTIONS, CHANGES OR COPIES IN ANY MANNER SHALL BE MADE

WITHOUT OBTAINING PRIOR WRITTEN CONSENT FROM BAY PINES VAHCS.

A

A

PARTITION TYPE

DOOR NUMBER, SEE SCHEDULE

WINDOW TYPE

EQUIPMENT TAG, SEE SCHEDULE

INTERIOR ELEVATION1A99.9.9

1 ASSEMBLY TYPE

Number

ASI # 88

REVISION TAG

NOTE TAG1

0 COLUMN CENTERLINE

A101

A101

DETAIL

SECTION

A101

EXTERIOR ELEVATION

FINISHED FLOOR ELEVATIONFFE

135' - 5 1/2"

FINISHED FLOOR ELEVATION

AFF

9' - 0"

CMU WALL, THICKNESS VARIES

CMU WALL (RATED)

STUD WALL, THICKNESS VARIES

STUD WALL (RATED)

EXISTING WALL TO REMAIN

BRICK VENEER

RIGID INSULATION

CAVITY INSULATION

INSULATION (BATT, BLANKET, OR FILL)

WOOD (FINISHED)

PLYWOOD (SMALL SECTION)

PLYWOOD (LARGE SECTION)

STEEL (LARGE SECTION)

ROUGH LUMBER (CONTINUOUS)

ROUGH LUMBER (INTERMITTENT)

PRECAST CONC. OR CUT STONE

CONCRETE

COMPACTED FILL OR EARTH

FINISHED GRADE

ALIGN OF NEW PARTITION WITH

TO/FROM THE CENTER LINE OF

ALIGN OF NEW PARTITION TO

TO/FROM COLUMN CENTER LINES

NEW WALL CONSTRUCTION

TO/FROM THE FINISHED FACE OF

NEW WALL CONSTRUCTION

ALIGN NEW PARTITION TO FINISH GWB

OF COLUMN

FLUSH BOTH SIDES OF COLUMN

OF WINDOW MULLION

ALIGN NEW PARTITION TO EXIST (VERIFY EXIST

PARTITION CONSTRUCTION MATCHES NEW

PARTITION CONSTRUCTION)

5/8" TYPE "X" FIRE RATED GYP BD EACH

SIDE ON FOR (1) HR FIRE RATING

SHEETING - TAPE JOINTS TO PROVIDE

DUST BARRIER

STRUCTURE

CONSTRUCTION

SIDE

OCCUPIED

SIDE

TAPE 6 MIL SHEET

CONTINUOUS @

FLOOR & CEILING

EXISTING CLG

2" SOUND ATTENUATION BLANKETS

VE

RI

FY

EL 0'-0"

T/SLAB

NOTE:

A. REMOVE AT COMPLETION OF THE WORK AND RESTORE ALL SURFACES &

FINISHES TO NEW CONDITION. MATCH EXISTING.

B. CONTRACTOR SHALL AT ALL TIMES MAINTAIN NEGATIVE PRESSURE IN WORK ARE

AS RELATIVE TO ADJACENT OPERATIONAL SPACES.

C. TEMPORARILY CLOSE ALL OPEN HVAC CEILING DIFFUSERS & SEAL W/ 6 MIL POLY

SHEET SEAL W/ DUCT TAPE IN ANY AREA PROTECTED.

D. BARRIER MUST PROVIDE CLASS III/ IV BARRIERS TO PROTECT ANY DUST, DIRT OR

CONTAMINATES FROM ENTERING OCCUPIED SPACERS DURING THE

CONSTRUCTION PERIOD.

E. PASS-DOORS TO BE SOLID CORE 1 3/4" THICK W/ LOCKABLE HARDWARE. DOOR

SIZES NOTED ON FLOOR PLANS, DOOR & FRAME TO BE (1) HR. FIRE RATED.

PROVIDE SEALS AND TEMPORARILY SEALED THRESHOLD.

REMOVE PORTION OF EXIST. CEILING

AS REQD. TO INSTALL BARRIER &

REPLACE TO MATCH EXISTING

AFTER REMOVAL OF BARRIER

GYPSUM WALLBOARD APPLIED HORIZONTALLY OR

VERTICALLY. VERTICAL JOINTS CENTERED OVER STUDS AND

STAGGERED ONE STUD CAVITY ON OPPOSITE SIDES OF

STUDS. VERTICAL JOINTS IN ADJACENT LAYERS (MULTILAYER

SYSTEMS) STAGGERED ONE STUD CAVITY. HORIZONTAL EDGE

JOINTS AND HORIZONTAL BUTT JOINTS IN ADJACENT LAYERS

(MULTILAYER SYSTEMS) STAGGERED 12" MIN. THICKNESS AND

NUMBER OF LAYERS SHALL BE COORDINATED PER RATED

CONDITION WITH DETAIL AS REQUIRED.

FRICTION FIT BATT INSULATION WITHIN CAVITY AS REQUIRED.

SEE FLOOR PLANS FOR SMOKE BARRIER & FIRE RATED WALL

LOCATIONS AND COORDINATE WITH THE REQUIREMENTS OF

THIS DETAIL FOR EACH CONDITION.

NO. 25 MSG GALVANIZED STL STUDS W/ DEPTH AS

REQUIRED PER THE REQUIREMENTS OF THIS DETAIL

SPACED @ 24" O.C. MAX

NOTE:

USE THIS DETAIL FOR THE PATCHING OF ABANDONED OPENINGS EQUAL TO OR

GREATER THAN 12" X 12" IN SMOKE BARRIER & FIRE RATED WALLS. OPENINGS

SMALLER THAN 12" X 12" SHALL BE CUT TO MINIMUM 12" X 12" SIZE AND THEN

PATCHED ACCORDING TO THIS DETAIL.

THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION

WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED

4525 S. Manhattan Ave. Tampa, FL 33611-2305

T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991

w w w . l o n g a n d a s s o c i a t e s . c o m

Checked By:

Seal

ALEXANDER M. LONG, A.I.A.

AR 0015104

987654321

B C

D E

F A

98765431 2

A th re e in c h e s o n e fo o t

B

C

D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t

E o n e h a lf in c h o n e fo o t

F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B A Y

P

IN

E S

M E D

IC

A L C E N

TE

R

Drawn By:Approved Division Chief

DIVISION CHIEF

Drawing Title

Approved Service Director

SERVICE DIRECTOR

Location

Building Number

Dwg. Of.

Date

Project No.

Project Title

DRAWING NO.

To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards

:2

:5

P M

AML

01/23/15

G0.2

REPLACE AIR CONDITIONING

SYSTEMS IN B-102

SUPPORT BUILDING

VAMC BAY PINES, FLORIDA 33744

TGS

ABBREVIATIONS, SYMBOL LEGEND, &

MATERIALS LEGEND

516-11-108

ABBREVIATIONS MATERIALS LEGENDSYMBOL LEGEND

D

A

C

B

E

AREA

ANCHOR BOLT

AIR CONDITIONING

ALTERNATING CURRENT

A

AB

A/C

AC

ACCESS FLOOR

AMERICAN CONCRETE INSTITUTE

ACOUSTICAL

ACOUSTICAL CEILING TILE

AMERICANS WITH DISABILITIES ACT

ADDITIONAL

ADJUSTABLE

ADJACENT

ABOVE FINISHED COUNTER

ABOVE FINISHED FLOOR

AIR HANDLING UNIT

AMERICAN INSTITUTE OF

AMERICAN INSTITUTE OF

ACOUSTICAL LINING

ALTERNATE

ALUMINUM

AMPERE

ANCHOR

ANODIZED

ACOUSTICAL PANEL

APARTMENT

APPROXIMATE

ACID RESISTANT

ARCHITECTURAL / ARCHITECT

ASBESTOS

AMERICAN SOCIETY OF

& AIR-CONDITIONING ENGINEERS

AMERICAN SOCIETY OF

ASPHALT

ASSOCIATION

AMERICAN SOCIETY FOR

AUTOMATIC

AUXILIARY

AVENUE

ACFL

ACI

ACOUS

ACT

ADA

ADDNL

ADJ

ADJT

AFC

AFF

AHU

AIA

AISC

AL

ALT

ALUM

AMP

ANC

ANOD

AP

APT

APP

AR

ARCH

ASB

ASHRAE

ASME

ASPH

ASSOC

ASTM

AUTO

AUX

AVE

AWI

BULLETIN BOARD

BOARD

BOTTOM FACE

BITUMINOUS

BLOCK

BLOCKING

BUILDING

BACK

BENCH MARK

BEAM

BOTTOM

BASE PLATE

BEARING

BRITISH THERMAL UNIT

BRITISH THERMAL UNIT PER HOUR

BETWEEN

BASEMENT

BUILT UP ROOFING

BOTH WAYS

BB

BD

BF

BIT

BLDG

BLK

BLKG

BK

B/M

BM

BOT

BP

BRG

BSMT

BTU

BTUH

BTWN

BUR

BW

CABINET

CENTER TO CENTER

CEMENT

CUBIC FEET PER SECOND

CHANNEL

CONTROL JOINT

CENTER LINE

CEILING

CLEAR

CONSTRUCTION MANAGER

CONCRETE MASONRY UNIT

CLEAN OUT

COLUMN

CONNECTION

CONSTRUCTION

CONTINUOUS

CONTRACTOR

COUPLING

CARPET

CARBON STEEL

CERAMIC TILE

CONDENSER UNIT

CUBIC YARD

CENTER

CERAMIC

CUBIC FEET

CUBIC FEET PER MINUTE

COMPUTER

COMPUTER PROCESSING UNIT

CONDUIT

CONCRETE

CORRIDOR

CAB

C/C

CEM

CER

CF

CFM

CFS

CH

CJ

CL

CLG

CLR

CM

CMU

CO

COL

COMP

CND

CONC

CONN

CONST

CONT

CONTR

CORR

CPLG

CPT

CPU

CS

CT

CTR

CU

CY

DEMOLITION

DENSITY

DETAIL

DIAMETER

DIAGONAL

DIFFUSER

DIMENSION

DISCONNECT

DOWN

DOOR

DOWNSPOUT

DRINKING FOUNTAIN

DITTO

DOUBLE

DEAD LOAD

DRAWING

STEEL CONSTRUCTION

ARCHITECTS

HEATING. REFRIGERATION

MECHANICAL ENGINEERS

TESTING & MATERIALS

DBL

DEM

DEN

DET

DF

DIA

DIAG

DIFF

DIM

DISC

DL

DO

DN

DR

DS

DWG

EACH

EXPANSION BOLT

EXHAUST FAN

EFFICIENCY

EXTRA HAZARD

ELEVATION

ELECTRIC / ELECTRICAL

EMERGENCY

ENERGY MANAGEMENT

ENCLOSURE

EXPLOSION PROOF

EQUAL

EQUIPMENT

ESTIMATE / ESTIMATED

EXISTING TO REMAIN

EVAPORATIVE / EVAPORATOR

EACH WAY

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

EXFILTRATION

EXHAUST

EXPANSION JOINT

EXPANSION

EXISTING RELOCATED

EXISTING

EXTERIOR

& CONTROL SYSTEM

MODULUS OF ELASTICITY

ENGINEER

ENGINEERING

E

EA

EB

EF

EFF

EH

EL

ELEC

EMERG

EMCS

ELEVATOR

ENCL

ENGR

ENGRG

EP

EQ

EQPT

EST

ETR

EVAP

EVTR

EW

EWC

EWH

EXF

EXH

EJ

EXP

EXR

EXST

EXT

AMOUNTAMT

Q

P

O

N

W

V

U

L

K

J

I

T

S

X

Y

F

G

H

M

R

FA

FACP

FBRK

FC

FD

FDC

FDN

FDPR

FE

FEC

FF

FFE

FFF

FG

FH

FHMS

FHS

FHWS

FIN

FJT

FL

FLG

FLSHG

FLR

FP

FPG

FPM

FPS

FO

FOC

FOF

FOM

FR

FRMG

FRTL

FS

FT

FTG

FURR

FV

FIRE ALARM

FIRE ALARM CONTROL PANEL

FIRE BRICK

FLEXIBLE CONNECTION

FLOOR DRAIN

FIRE DEPARTMENT CONNECTION

FOUNDATION

FIRE DAMPER

FIRE EXTINGUISHER

FIRE EXTINGUISHER CABINET

FINISHED FLOOR

FINISHED FLOOR ELEVATION

FROM FINISHED FLOOR

FLANGED CONNECTION

FIRE HYDRANT

FLAT HEAD MACHINE SCREW

FIRE HOSE STATION

FLAT HEAD WOOD SCREW

FINISH / FINISHED

FLUSH JOINT

FLOOR

FLANGE

FLASHING

FLUORESCENT

FIRE PROTECTION

FIREPROOFING

FEET PER MINUTE

FEET PER SECOND

FLAT OVAL

FACE OF CONCRETE

FACE OF FINISH

FACE OF MASONRY

FRAME

FRAMING

FIRE RETARDANT TREATED LUMBER

FULL SIZE

FEET

FOOTING

FURRED / FURRING

FLUSH VALVE

FOS FACE OF STUD

FZR FREEZER

GA

GAL

GALV

GB

GC

GI

GL

GLBK

GP

GPM

GR

GRD

GRND

GS

GST

GWB

GYP

GAGE / GAUGE

GALLON

GALVANIZED

GRAB BAR

GENERAL CONTRACTOR

GALVANIZED IRON

GLASS / GLAZING

GLASS BLOCK

GENERAL PURPOSE

GALLONS PER MINUTE

GROOVED CONNECTION

GRADE

GROUND

GALVANIZED STEEL

GLAZED STRUCTURAL TILE

GYPSUM WALL BOARD

GYPSUM

HB

HC

HCP

HD

HDNR

HDW

HGR

HM

HORIZ

HP

HR

HRS

HSS

HT

HVAC

HZ

HOSE BIBB

HOLLOW CORE

HANDICAPPED

HARD

HARDENER

HARDWARE

HANGER

HOLLOW METAL

HORIZONTAL

HORSEPOWER

HOUR

HOURS

HOLLOW STRUCTURAL STEEL

HEIGHT

HEATING, VENTILATION,

HERTZ / CYCLES PER SECOND

I

IC

ID

IF

IN

INCL

INF

INFO

INSUL

INT

INV

MOMENT OF INERTIA

INTERCOM

INSIDE DIAMETER

INSIDE FACE

INCHES

INCLUDED

INFILTRATION

INFORMATION

INSULATION

INTERIOR

INVERT

IRON PIPEIP

AIR-CONDITIONING

LTWT LIGHTWEIGHT

MASONRY OPENING

NOISE REDUCTION

NOT IN CONTRACT

OUTSIDE DIAMETER

PLASTIC LAMINATE

POLYVINYL CHLORIDE

POUNDS PER SQUARE INCH

POUNDS PER SQUARE FOOT

POUNDS PER LINEAR FOOT

POUNDS PER CUBIC FOOT

PRESSURE TREATED

POST INDICATOR VALVE

QTY

QT

PA

QUARRY TILE

PUBLIC ADDRESS

QUANTITY

PLAM

PVC

PSF

PLF

PCF

PREFAB

PROJ

PRES

PVMT

PLYWD

PSI

PT

PIV

PREFABRICATED

PROJECTION

PRESSURE

PAVEMENT

PLYWOOD

OHD

OPP HD

PTD

PNLB

PNL

PLAS

PART

PR

OD

OH

PAINTED

PAIR

PANEL

PANELBOARD

PLASTER

PARTITION

OVERHEAD

OVERHEAD DOOR

OPPOSITE HAND

NAT

NRC

NTP

N/A

NEG

OPNG

NO

OC

NIC

NUMBER

OPENING

ON CENTER

NATURAL

NOTICE TO PROCEED

NOT APPLICABLE

NEGATIVE

MAXIMUMMAX

MULL

MOD

MOV

MISC

MIRR

MTL

MED

MECH

MM

MIL

MISCELLANEOUS

MULLION

MODEL

MOVABLE

MILLIMETER(S)

MILITARY

MIRROR

METAL

MEDIUM

MECHANICAL

MAT

MAS

MFR

MFD

MH

MO

MK

LL

LF

MANHOLE

MARK

MATERIAL

MASONRY

MANUFACTURER

MANUFACTURED

LIVE LOAD

LINEAR FOOT

VINYL TILEVT

VOLTS

VOLUME

VINYL WALL COVERING

WALL HUNG

WALL TO WALL

WALL CLEANOUT

WEATHER PROTECTED

WELDED WIRE FABRIC

WINDOW

WIDE FLANGE

WOOD

WITHOUT

WITH

WEIGHT

WATER CLOSET

WAINSCOT

WD

WWF

WIN

W/O

WF

W/

WT

WTW

WCO

WAINS

WH

WP

WC

VOL

VWC

V

UNLESS OTHERWISE NOTED

UTILITY

URINAL

UNDERCUT

UNDERGROUND

UNDERWRITER'S

VELOCITY

VARIABLE AIR VOLUME

VAPOR RETARDER

VERTICAL

VINYL COMPOSITION TILE

VINYL

VENT THRU ROOF

VACUUM

TRANSFER

TYPICAL

TRANSFORMER

TACK BOARD

URL

VPR

VAV

VEL

VERT

VCT

VTR

VIN

UTY

VAC

UON

UL

UG

UC

XFR

TYP

XFMR

TB

KILOVOLT AMPERE

KILOVOLTKV

KVA

LAM

LAB

LVG

LTG

LAV

KO

KIT

KW

LABORATORY

LIGHTING

LAVATORY

LEAVING

LAMINATE(D)

KNOCKOUT

KITCHEN

KILOWATT(S)

JT

JB

JST

JOINT

JUNCTION BOX

JOIST

SA SUPPLY AIR

SWITCH

SYMBOL

SYMMETRICAL

SYSTEM

SUSPEND(ED)

TELEVISION

TELEPHONE

THERMOSTAT

THICK(NESS)

TOILET

TONGUE AND GROOVE

TOP

THRESHOLD

TEMPERATURE

TOP OF MASONRY

TOP OF FOOTING

TOP OF CURB

TOP OF BEAM

TOP OF STEEL

TOP OF SLAB

TOP OF

TOP AND BOTTOM

TOP FACE

THK

T/

T/C

T/FTG

T/BM

T/MAS

T/STL

T/SLAB

TLT

T&G

TSHD

T&B

T/F

T

TEL

TSTAT

TEMP

TV

SYMB

SYM

SYS

SUSP

SW

SHEET

SOLID CORE

SPEAKER

SOUNDPROOF

STANDARD

SQUARE

SPRINKLER

STAINLESS STEEL

SQUARE FEET

STRUCTURAL CLAY TILE

SUPPLY

STEAM

STEEL JOIST

STORAGE

STEEL

STATION

SPECIFICATION(S)

SMOKE DETECTOR

SIMILAR

SAWCUT JOINT

SECONDARY

SECTION

SCHEDULE

SPKR

STA

SCT

SUP

STL JST

STM

STL

STOR

STD

SST

SPRK

SQ FT

SPEC

SQ

SHT

SNDP

SIM

SECT

SC

SD

SCH

SEC

SJ

JAN JANITOR

KNOCKDOWNKD

KILOGRAMKG

LBS

LVR

LS

POUNDS

LUMP SUM

LOUVER

LIN LINEAR

LH LEFT HAND

M BENDING MOMENT

MBF 1OOO BOARD FEET

MFG MANUFACTURING

MB MARKER BOARD

MEZZ MEZZANINE

MW MICROWAVE

MR MOISTURE RESISTANT

NEC NATIONAL ELECTRIC CODE

NOA NOTICE OF ACCEPTANCE

OPP OPPOSITE

OZ OUNCE

OF OUTSIDE FACE

OA OUTDOOR AIR

PCS PIECES

PLATEPL

PP POWER POLE

SMALLSM

SQUARE INCHSQ IN

SQUARE YARDSQ YD

STRUCTURALSTRUC

TOLERANCETOL

VINYL BASEVB

WIDE(WIDTH)W

YARDYD

COEFFICIENT

LABORATORY

W/

SOUND TRANSMISSION CLASSSTC

J JUNCTION

KIP / 1000 LBK

L LENGTH

LG LARGE

LO

LOC LOCATION

LOCKOUT

LT/GA LIGHT GAGE

LTH LIGHT HAZARD

LT LIGHT

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

MC MEDICINE CABINET

MD MOTORIZED DAMPER

MIN MINIMUM

MTD MOUNTED

MT METAL THRESHOLD

MP MIDPOINT

ML METAL LATH

MS MOP SINK

MTR METER

NFA NET FREE AREA

NTS NOT TO SCALE

O ROUND

OAI OUTDOOR AIR INTAKE

ORDINARY HAZARDODH

OJ OPEN WEB JOIST

PC PHOTOCELL

PRECAST CONCRETEPCC

PHASEPH

PREFORMED JOINT FILLERPJF

PFD PREFORMED

POS POSITIVE

PRESTRESSED CONCRETEPSC

POST TENSIONED CONCRETEPTC

PWR POWER

PER UNITPU

PNT POINT

RIGHT

ROUGH OPENING

ROOF VENT

ROOFING

ROOM

RADIUS

RECIRCULATING

RECIPROCATING

REINFORCE(D),

REQUIRED

REVISION

RIGHT OF WAY

RETURN GRILLE

REVOLUTIONS PER MINUTE

RETURN

RETURN AIR

RELATIVE HUMIDITY

REGULAR

RECEIVER

RECEPTACLE

RT

RFG

ROW

RO

RV

RM

REQD

RPM

REV

RET

RG

RA

RH

RECIP

RECIRC

REINF

REG

RECPT

REC

RAD

REFRIGERATORREFG

REFERENCEREF

REINFORCING

RISER

REQUIREMENTREQT

REFLECTED CEILING PLANRCP

REDUCERED

ROOF DRAINRD

ROOF TOP UNITRTU

RAIN PROOFRP

RAIN WATER COLLECTORRWC

RAIN WATER LEADERRWL

S SANITARY

SQUARE FEETSF

SHEATHINGSHTG

STORM DRAINSDN

SQUARE YARDSY

SERVICESERV

TOP OF PIPET/P

TOP OF WALLT/W

TOP OF PLATET/PL

TOWEL RODTR

TRANSOMTRAN

TOILET PARTITIONTPTN

TREADTRD

THREADEDTHRD

TIME CLOCKTC

UNDER COUNTERUCR

VOLTSVA

VERIFY IN FIELDVIF

VINYL FABRICVF

WORK POINTWPT

EXTRA HEAVY

EXTRA STRONG

XHVY

XSTG

DOUBLE EXTRA STRONGXXSTG

DIMENSIONING CONVENTIONS

GENERAL NOTES

SCALE: 1/2" = 1'-0"1

TEMPORARY PARTITION

DETAIL

ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE GENERAL

CONDITIONS OF THE CONTRACT AND THE PROJECT SPECIFICATIONS, INCLUDING THE

REQUIREMENTS OF DIVISION ONE.

ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF

THE INTERNATIONAL BUILDING CODE (IBC 2012), NFPA 101 (2012 EDITION) AND VA HVAC

DESIGN MANUAL.

IN SOME CASES, THE REQUIREMENTS SET FORTH IN THE CONSTRUCTION DRAWINGS

AND SPECIFICATIONS EXCEED THE MINIMUM REQUIREMENTS OF THE CODE.

GENERAL CONTRACTOR SHALL COORDINATE THE SEQUENCING AND EXECUTION OF ALL

TRADES IN STRICT CONFORMANCE WITH THE REQUIREMENTS OF ALL CONSTRUCTION

DRAWINGS AND CONTRACT DOCUMENTS.

GENERAL CONTRACTOR SHALL MAINTAIN & PROTECT FROM DAMAGE ALL PORTIONS OF

THE EXISTING FACILITY SCHEDULED TO REMAIN OR NOT INDICATED FOR DEMOLITION.

ALL DAMAGED AREAS & ELEMENTS SHALL BE REPLACED TO MATCH EXISTING ADJACENT

CONSTRUCTION IN ALL RESPECTS.

GENERAL CONTRACTOR SHALL PROTECT THE PUBLIC FROM CONSTRUCTION ACTIVITIES

AND PROVIDE FOR A SECURE CONSTRUCTION SITE.

GENERAL CONTRACTOR SHALL PROVIDE FOR CUTTING, PATCHING & PAINTING OF ALL

EXTERIOR AND INTERIOR FINISHED SURFACES TO MATCH EXISTING CONDITIONS AS

REQUIRED TO FACILITATE SCOPE OF WORK.

GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CEILING CONDITIONS, TYPES

AND HEIGHT PRIOR TO DEMOLITION. ALL NEW CEILINGS ARE TO BE INSTALLED TO

MATCH EXISTING CONDITIONS UNLESS OTHERWISE NOTED.

PROTECT AND MAINTAIN THE INTERIOR FLOOR FINISHES AND CASEWORK DURING

CONSTRUCTION AND DEMOLITION. DAMAGED FINISHES OR MATERIALS AS A RESULT OF

NEW WORK SHALL BE REPLACED AND/OR REPAIRED AT THE CONTRACTOR'S EXPENSE.

PRIOR TO ANY DEMOLITION, GENERAL CONTRACTOR AND OWNER SHALL WALK THROUGH

THE PROJECT AND ESTABLISH A PUNCHLIST OF EXISTING CONDITIONS. ITEMS NOT

IDENTIFIED AND LATER DAMAGED DUE TO CONSTRUCTION SHALL BE THE CONTRACTOR'S

RESPONSIBILITY.

FIELD VERIFY ALL DIMENSIONS PRIOR TO DEMOLITION WORK. COORDINATE AS

REQUIRED FOR NEW WORK.

ISOLATION BARRIERS SHALL BE HARD WALL TYPE CLOSURES. ZIP-WALL CONSTRUCTION

FOR DUST AND INFECTION CONTROL BARRIERS SHALL NOT BE PERMITTED.

IN LIMITED INSTANCES THE RELOCATION OF A SPRINKLER HEAD MAY BE NECESSARY TO

ACCOMMODATE NEW CONSTRUCTION AND SHALL BE INCLUDED IN THE WORK AS

NECESSARY.

GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CEILING CONDITIONS, TYPES

AND HEIGHT PRIOR TO DEMOLITION. ALL NEW CEILINGS ARE TO BE INSTALLED TO

MATCH EXISTING CONDITIONS UNLESS OTHERWISE NOTED

ALL EXISTING WALLS TO REMAIN & SHALL BE PROTECTED FROM DAMAGE. PATCH AND

PAINT WALLS TO MATCH EXISTING AS REQUIRED TO MATCH EXISTING FINISHES.

COORDINATE WITH ALL TRADES.

ALL PENETRATIONS THROUGH WALLS SHALL BE PATCHED TO MATCH WALL FINISH AFTER

REMOVAL OF DUCTWORK, PIPING, CONDUIT, ETC.

ALL ABANDONED WALL PENETRATIONS ABOVE THE CEILING AT EXISTING FIRE RATED OR

SMOKE BARRIER WALLS SHALL BE SEALED WITH UL DETAIL U419 1, 2, 3 OR 4 HOUR

NONBEARING WALL SYSTEM AFTER DEMOLITION OF DUCTWORK, PIPING & CONDUIT.

REFERENCE DETAIL THIS SHEET.

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

Q.

PROJECT NAME: BAY PINES VA - REPLACE AIR CONDITIONING SYSTEM IN B-102

VA PROJECT #: 516-11-108

L/A PROJECT #: 201140

SCOPE OF WORK:

REPLACE AIR CONDITIONING SYSTEMS THROUGHOUT SUPPORT BUILDING.

PHASING:

PHASE I: BUILDINGS C & D (NIC)

BUILDINGS C & D HVAC REPLACEMENT PROJECT WILL COMMENCE ONCE OCCUPANTS MOVE INTO THE

MENTAL HEALTH BUILDING.

START DATE: TO BE DETERMINED; BASED ON THE ACTIVATION OF THE MENTAL HEALTH BUILDING

PHASE II. BUILDING A (NIC)

BUILDING A WILL MOVE INTO BUILDING D ONCE WORK IS COMPLETED PER ABOVE PHASE 1, AND INTERIOR IS

RENOVATED PER ITEM 3 BELOW.

START DATE: TO BE DETERMINED

PHASE III. BUILDING B (NIC)

BUILDING A WILL MOVE INTO BUILDING 1 ONCE BUILDING 1 IS RENOVATED UNDER THE MENTAL HEALTH

ADDITION PROJECT.

START DATE: TO BE DETERMINED, AND WILL BE BASED ON THE RENOVATION AND ACTIVATION OF BUILDING 1

UNDER THE MENTAL HEALTH ADDITION PROJECT

PHASE IV. SUPPORT BUILDING "SB"

WORK IN THIS AREA WILL BE PHASED TO MAINTAIN FACILITY OPERATIONS.

PROJECT DESCRIPTION

NONBEARING WALL

RATINGS - 1, 2, 3 OR 4 HOUR

PARTITION PENETRATION NOTES

1. REFER TO UL UNDERWRITERS LABORATORIES INC. DIRECTORY LATEST EDITION FOR SPECIFIC REQUIREMENTS FOR EACH U.L. DESIGN INDICATED. CONTRACTOR SHALL PREPARE & SUBMIT ALL NECESSARY & SPECIFIC UL LISTED SYSTEMS FOR PENETRATIONS OF THE UTILITIES THROUGH FIRE

RATED & SMOKE BARRIER WALLS DURING THE SHOP DRAWING PROCESS FROM A SINGLE

MANUFACTURER.

2. ALL PENETRATIONS THROUGH SMOKE BARRIER WALLS SHALL BE SEALED AIRTIGHT ALL AROUND, NO EXCEPTIONS. VERIFY ALL EXISTING SMOKE BARRIER WALLS ARE SEALED TO DECK AS REQUIRED.

NOTE:

THE TERM "TYPICAL" SHALL BE DEFINED IN THESE DRAWINGS AS:

IN EACH SIMILAR CASE WHETHER INDIVIDUALLY IDENTIFIED BY NOTATION OR NOT, AND IN OCCURRENCES WHERE THE TYPICAL KEYNOTED ITEM IS SHOWN MAY NOT IDENTIFY ALL OCCURRENCES. ALL OCCURRENCES ARE TO BE FIELD VERIFIED. THE KEYNOTED ITEM IS SHOWN FOR REFERENCE AND APPLIES TO ALL OTHER

SIMILAR OCCURRENCES.

SCALE: 1 1/2" = 1'-0"2 UL DETAIL U419

Issue & Revision Schedule

No. Description Date

FINAL CONSTRUCTION DOCUMENTS 01/23/15

NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR

CONFLICTS WHICH ARE ALLEGED.

COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

UL DESIGN # W-L-2029

1 & 2 HR FRAMING, 2" PVC PIPE

UL DESIGN # W-L-1089

1 & 2 HR FRAMING, METALLIC PIPE

PARTITION PENETRATION NOTES

REFER TO UL UNDERWRITERS LABORATORIES

INC. DIRECTORY LATEST EDITION FOR SPECIFIC

REQUIREMENTS FOR EACH U.L. DESIGN

INDICATED. CONTRACTOR SHALL PREPARE &

SUBMIT ALL NECESSARY & SPECIFIC UL LISTED

SYSTEMS FOR PENETRATIONS OF THE UTILITIES

THROUGH FIRE RATED & SMOKE STOP WALLS

DURING THE SHOP DRAWING PROCESS FROM A

SINGLE MANUFACTURER

ALL PENETRATIONS THROUGH A SMOKE-STOP

PARTITION SHALL BE SEALED AIRTIGHT ALL

AROUND, NO EXCEPTIONS. VERIFY ALL EXISTING

SMOKE-STOP WALLS ARE SEALED TO DECK AS

REQUIRED

ELEV

UL DESIGN # W-L-1093

1 & 2 HR FRAMING, MULTI-METALLIC

UL DESIGN # W-L-5001

1 & 2 HR FRAMING, INSUL METALLIC

ELEV

UL DESIGN # W-L-7008

1 & 2 HR FRAMING, METALLIC DUCT

ELEV

UL DESIGN # W-J-7002

2 HR BLK, METALLIC DUCT

UL DESIGN # W-J-5007

1 & 2 HR BLK, INSUL METALLIC

UL DESIGN # W-J-2019

1 & 2 HR BLK, NON METALLIC

UL DESIGN # W-J-1028

1 & 2 HR D-2 BLK, METALLIC

ELEV

UL DESIGN # W-J-1033

1 & 2 HR BLK, MULTI-METALLIC

UL DESIGN # W-L-2003

1 & 2 HR FRAMING, 2" PVC PIPE

FIRE CAULK SEALANT

1 HR RATED WALL 5/8" TYPE

"X" GYP BD W/ 3 5/8" MTL

STUDS @16" O.C. (2) LAYERS

FOR (2) HR WALL EA. SIDE

4" PVC PIPE OR SMALLER

FIRESTOP DEVICE GALV

STEEL COLLAR W/

FASTENERS

1 HR RATED WALL 5/8" TYPE

"X" GYP BD W/ 3 5/8" MTL

STUDS 16" O.C. (2) LAYERS

FOR (2) HR WALL EA.SIDE

6" COPPER PIPE , 4"

CONDUIT, 24"

STEEL PIPE OR SMALLER

MINERAL WOOL PACKING

FIRE CAULK SEALANT

2 LAYERS OF 5/8"

TYPE "X" GYP

BD BUILD-UP

2" STEEL PIPE 2

IRON PIPE

2" CONDUIT OR

SMALLER

FIRE CAULK SEALANT

6" COPPER PIPE, 12" STEEL PIPE OR

SMALLER W/ GLASS INSULATION

FIRE CAULK SEALANT

1 HR RATED WALL 5/8" TYPE "X" GYP

BD W/ 3 5/8" MTL STUDS @ 16" O.C. (2)

LAYERS FOR (2) HR WALL EA. SIDE

STEEL VENT

DUCT

FIRE CAULK

SEALANT

ALONG

PERIMETER

STEEL RETAINING

ANGLE

NOTE

PROVIDE TOP AND

BOTTOM TRACK

LIGHT GAGE

FRAMING AROUND

PERIMETER OF

DUCTWORK TO

SECURE GYP BD

8" CONC.

RATED BLK.

STEEL VENT

DUCT

FIRE CAULK

SEALANT

ALONG

PERIMETER

STEEL RETAINING

ANGLE

4" COPPER PIPE, 4" STEEL

PIPE, OR SMALLER W/

GLASS INSULATION

8" CONC. BLK

FIRE CAULK SEALANT

2" PVC OR CPVC PIPE

OR SMALLER

RATED CMU

FIRE CAULK SEALANT

10" STEEL PIPE OR

SMALLER & 4" METALLIC

PIPE OR SMALLER

RATED CMU

FIRE CAULK SEALANT

2 LAYERS OF

5/8" TYPE

"X" GYP BD

BUILD-UP

FIRE CAULK SEALANT

RATED CMU

2" STEEL PIPE 2" IRON

PIPE 2" CONDUIT OR

SMALLER

1 HR RATED WALL 5/8" TYPE

"X" GYP BD W/ 3 5/8" MTL

STUDS @ 16" O.C. (2) LAYERS

FOR (2) HR WALL EA. SIDE

FIRE CAULK SEALANT &

WRAP STRIP

2" PVC TUBE OR SMALLER

1 HR RATED WALL 5/8"

TYPE "X" GYP BD W/ 3

5/8" MTL STUDS @ 16"

O.C. (2) LAYERS FOR

(2) HR WALL EA. SIDE

1 HR RATED WALL 5/8"

TYPE "X" GYP BD W/ 3

5/8" MTL STUDS @ 16"

O.C. (2) LAYERS FOR (2)

HR WALL EA. SIDE

PIPE PENETRATION

SCALE: 3" = 1' - 0"

PIPE PENETRATION

SCALE: 3" = 1' - 0"

UL DESIGN # W-J-1226

3 HR BLK, METALLIC

UL DESIGN #W-J-2190

3 HR BLK, NON METALLIC

2" PVC TUBING OR

SMALLER

RATED CMU

FIRE CAULK SEALANT

4" OR SMALLER METALLIC

PIPE OR CONDUIT

RATED CMU

FIRE CAULK SEALANT

1.

2.

THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION

WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED

4525 S. Manhattan Ave. Tampa, FL 33611-2305

T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991

w w w . l o n g a n d a s s o c i a t e s . c o m

Checked By:

Seal

ALEXANDER M. LONG, A.I.A.

AR 0015104

987654321

B C

D E

F A

98765431 2

A th re e in c h e s o n e fo o t

B

C

D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t

E o n e h a lf in c h o n e fo o t

F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B A Y

P

IN

E S

M E D

IC

A L C E N

TE

R

Drawn By:Approved Division Chief

DIVISION CHIEF

Drawing Title

Approved Service Director

SERVICE DIRECTOR

Location

Building Number

Dwg. Of.

Date

Project No.

Project Title

DRAWING NO.

To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards

:2

:5

P M

AML

01/23/15

G0.3

REPLACE AIR CONDITIONING

SYSTEMS IN B-102

SUPPORT BUILDING

VAMC BAY PINES, FLORIDA 33744

TGS

PARTITION PENETRATION DETAILS

516-11-108

Issue & Revision Schedule

No. Description Date

FINAL CONSTRUCTION DOCUMENTS 01/23/15

NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR

CONFLICTS WHICH ARE ALLEGED.

COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY

FOR CONTINUATION OF CORRIDOR,

SEE DRAWING 5/LS1.1

FOR CONTINUATION OF CORRIDOR,

SEE DRAWING 3/LS1.1

FOR CONTINUATION OF CORRIDOR,

SEE DRAWING 2/LS1.1

FOR CONTINUATION

OF CORRIDOR, SEE

DRAWING 4/LS1.1

158 SF

OFFICE

114 SF

OFFICE

143 SF

OFFICE

151 SF

OFFICE

39 SF

TOILET

39 SF

TOILET

103 SF

RECEPTION

101A

217 SF

OFFICE & MAIL

10 SF

CLOSET

105A

9 SF

CLOSET

132A

7 SF

CLOSET

943 SF

CONF ROOM

306 SF

CONF ROOM

111 SF

CLINIC

146 SF

LOCKER ROOM

133 SF

STORAGE

408 SF

REC THERAPY OFFICES

227 SF

CLINIC

27 SF

TEL

117 SF

OFFICE

102 SF

WALK-IN

422 SF

CORRIDOR

CE-3

196 SF

OFFICE

197 SF

BREAK ROOM

301 SF

DISHWASHING

429 SF

BLDG MGMT STORAGE

121 SF

JANITOR

1126 SF

MECHANICAL

405 SF

ELECTRICAL

228 SF

EMER GEN

425 SF

DIETARY SERVICE

3884 SF

DINING AREA

677 SF

GROUP ROOM

63 SF

TOILET

72 SF

TOILET

119 SF

OFFICE

109A

1298 SF

REC ROOM

829 SF

REC ROOM

107A

388 SF

GROUP ROOM

107B

17 SF

CLOSET

106A

17 SF

CLOSET

106B

24 SF

CLOSET

106C

16 SF

CLOSET

107C

16 SF

CLOSET

107D

16 SF

CLOSET

107E

16 SF

CLOSET

107F

43 SF

HAC

292 SF

CORRIDOR

CE-2

1051 SF

CORRIDOR

CE-1

1151 SF

CORRIDOR

CE-4

380 SF

CORRIDOR C

CE-C

762 SF

CORRIDOR D

CE-D

380 SF

CORRIDOR A

CE-A

719 SF

CORRIDOR B

CE-B

93 SF

OFFICE

109B

225 SF

SERVING LINE

113A

236 SF

LOBBY

49 SF

STORAGE

127A

LS005

LS006LS006

LS005

LS004LS004

LS002

LS002

LS010

LS002

50 SF

HAC

114A

TRAVEL DISTANCE: 129'-0"

LS007LS007

LS099LS099

TRAVEL DISTANCE: 154'-0"

LS010

LS010

LS010

LS002

CODE COMPLIANCE

ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE REQUIREMENTS

OF THE FOLLOWING CODES:

INTERNATIONAL BUILDING CODE, 2012 EDITION

NFPA 101 LIFE SAFETY CODE, 2012 EDITION

CONSTRUCTION TYPE (IBC TABLE 601): TYPE II-B UNPROTECTED

(SPRINKLED)

OCCUPANCY CLASSIFICATION (NFPA 6.1.11): BUSINESS

EXISTING RENOVATION AREA: 7,742 S.F.

OCCUPANT LOAD (NFPA TABLE 7.3.1.2): 7,742/100 GROSS = 77 PERSONS

OCCUPANCY CLASSIFICATION (NFPA 6.1.2): ASSEMBLY

EXISTING RENOVATION AREA: 9,020 S.F.

OCCUPANT LOAD (NFPA TABLE 7.3.1.2): 9,020/15 NET = 600 PERSONS

TOTAL OCCUPANT LOAD: 77 + 600 = 677 PERSONS

TRAVEL DISTANCE (NFPA 19.2.5.7.2.3(B)(2)): 200'-0" MAX

COMMON PATH OF TRAVEL (NFPA 39.2.5.3.1): 100'-0" MAX

DEAD END CORRIDOR (NFPA 19.2.5.2): 30'-0" MAX

REQUIRED EGRESS WIDTH (NFPA 19.2.3.4): 48" MIN

FIRE RESISTANCE RATING (IBC TABLE 601):

PARTITIONS 0 HOUR

BEARING WALLS: 0 HOUR

FLOOR SEPARATION: 0 HOUR

ROOF CONSTRUCTION: 0 HOUR

STRUCTURAL FRAME: 0 HOUR

CORRIDORS (NFPA 19.3.6.2.4):

EXISTING HEALTH CARE OCCUPANCY WITH AN AUTOMATIC SPRINKLER SYSTEM -

SMOKE COMPARTMENT SEPARATION NOT REQUIRED TO BE FIRE RATED, BUT WALLS

MUST BE CONSTRUCTED TO RESIST THE PASSAGE OF SMOKE

GENERAL LIFE SAFETY NOTES

A. PORTIONS OF THE BUILDING SHALL MAINTAIN OPERATION THROUGHOUT

DEMOLITION & NEW WORK AS REQUIRED. THE WORK SHALL BE PHASED IN

ORDER TO MAINTAIN OPERATION AS REQUIRED, SEE PHASING PLAN.

COORDINATE ALL PHASING WITH OWNER

B. THIS PROJECT WAS REVIEWED BASED ON THE ABOVE CODE INFORMATION.

A FULL CORRECTION OF THIS BUILDING TO THE 2010 FBC IS IS BEYOND THE

SCOPE OF WORK AND IS NOT INCLUDED SUPPORT BLDG

WORK AREA

B

A

D

C

CORRIDOR A

CE-A

LS003 LS002

LS009LS009

LS010

CORRIDOR C

CE-C

LS002 LS003

LS010

LS009LS009

CORRIDOR B

CE-B

LS003

LS002

LS009LS009

LS010

CORRIDOR D

CE-D

LS003

LS002

LS009LS009

LS010

EXISTING TWO HOUR FIRE-RATED PARTITION

LIFE SAFETY LEGEND

EXISTING SMOKE STOP PARTITION

PRIMARY EXIT WAY

SECONDARY EXIT WAY

EXISTING THREE HOUR FIRE-RATED PARTITION

EXISTING PARTITION

EGRESS TRAVEL DISTANCE

EXISTING ONE HOUR FIRE-RATED PARTITION

NOT AN EXIT

2' - 0"

5'

- 0

8" NOT AN EXIT

TEMPORARY SIGN W/

3" GRAPHIC LETTERING

CENTERED ON EACH

DOOR LEAF

SCALE: 1/8" = 1'-0"1

SUPPORT BUILDING

LIFE SAFETY PLAN

THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION

WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED

4525 S. Manhattan Ave. Tampa, FL 33611-2305

T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991

w w w . l o n g a n d a s s o c i a t e s . c o m

Checked By:

Seal

ALEXANDER M. LONG, A.I.A.

AR 0015104

987654321

B C

D E

F A

98765431 2

A th re e in c h e s o n e fo o t

B

C

D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t

E o n e h a lf in c h o n e fo o t

F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B A Y

P

IN

E S

M E D

IC

A L C E N

TE

R

Drawn By:Approved Division Chief

DIVISION CHIEF

Drawing Title

Approved Service Director

SERVICE DIRECTOR

Location

Building Number

Dwg. Of.

Date

Project No.

Project Title

DRAWING NO.

To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards

:2

:0

P M

AML

01/23/15

LS1.1

REPLACE AIR CONDITIONING

SYSTEMS IN B-102

SUPPORT BUILDING

VAMC BAY PINES, FLORIDA 33744

TGS

LIFE SAFETY PLAN

516-11-108

KEYNOTE LEGEND

NO. DESCRIPTION

LS002 EXISTING SMOKESTOP PARTITION. PROVIDE CONSTRUCTION

LOCKSET AT EXISTING DOORS AND AIR BARRIER FOR

DURATION OF DEMOLITION AND NEW WORK. SEE DETAIL 1 ON

SHEET G0.2

LS003 PROVIDE AIR BARRIER FOR DURATION OF DEMOLITION AND

NEW WORK. SEE DETAIL 1 ON SHEET G0.2

LS004 EXISTING 1-HR FIRE RATED PARTITION TO PROTECT &

MAINTAIN

LS005 EXISTING 2-HR FIRE RATED PARTITION TO PROTECT &

MAINTAIN

LS006 EXISTING 3-HR FIRE RATED PARTITION TO PROTECT &

MAINTAIN

LS007 PROVIDE & CONFIRM THIS PORTION OF WALL IS 1 HOUR FIRE

RATED EQUAL TO UL#U465 OR MADE AS SUCH FOR THE

REQUIRED FIRE RATING

LS009 PROVIDE DOOR AT AIR BARRIER WITH TEMPORARY SIGN FOR

THE DURATION OF DEMOLITION AND NEW WORK. TEMPORARY

SIGN SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE

BUILDING SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR

SIDE.

LS010 PROVIDE TEMPORARY SIGN AT EXISTING DOORS FOR THE

DURATION OF DEMOLITION AND NEW WORK. TEMPORARY SIGN

SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE BUILDING

SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR SIDE.

LS099 SEE GENERAL NOTES ON SHEET G0.2 FOR ADDITIONAL NOTES

N

0' 4' 8' 16'

SCALE: NTS

B-102 KEY PLAN

SCALE: 1/8" = 1'-0"2

CORRIDOR A

LIFE SAFETY PLAN

SCALE: 1/8" = 1'-0"3

CORRIDOR C

LIFE SAFETY PLAN

SCALE: 1/8" = 1'-0"4

CORRIDOR B

LIFE SAFETY PLAN

SCALE: 1/8" = 1'-0"5

CORRIDOR D

LIFE SAFETY PLAN

SCALE: 1/2" = 1'-0"

TEMPORARY SIGN DETAIL

NOTE:

THE TERM "TYPICAL" SHALL BE DEFINED IN THESE DRAWINGS AS:

IN EACH SIMILAR CASE WHETHER INDIVIDUALLY IDENTIFIED BY NOTATION OR

NOT, AND IN OCCURRENCES WHERE THE TYPICAL KEYNOTED ITEM IS SHOWN

MAY NOT IDENTIFY ALL OCCURRENCES. ALL OCCURRENCES ARE TO BE FIELD

VERIFIED. THE KEYNOTED ITEM IS SHOWN FOR REFERENCE AND APPLIES TO

ALL OTHER SIMILAR OCCURRENCES.

Issue & Revision Schedule

No. Description Date

FINAL CONSTRUCTION DOCUMENTS 01/23/15

NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR

CONFLICTS WHICH ARE ALLEGED.

COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY

SUPPORT BLDG

WORK AREA

B

A

D

C

158 SF

OFFICE

114 SF

OFFICE

143 SF

OFFICE

151 SF

OFFICE

39 SF

TOILET

39 SF

TOILET

103 SF

RECEPTION

101A

217 SF

OFFICE & MAIL

10 SF

CLOSET

105A

9 SF

CLOSET

132A

7 SF

CLOSET

943 SF

CONF ROOM

306 SF

CONF ROOM

111 SF

CLINIC

38 SF

STORAGE

146 SF

LOCKER ROOM

133 SF

STORAGE

408 SF

REC THERAPY OFFICES

227 SF

CLINIC

27 SF

TEL

117 SF

OFFICE

102 SF

WALK-IN

422 SF

CORRIDOR

CE-3

196 SF

OFFICE

197 SF

BREAK ROOM

301 SF

DISHWASHING

50 SF

HAC

114A

429 SF

BLDG MGMT STORAGE

121 SF

JANITOR

1126 SF

MECHANICAL

405 SF

ELECTRICAL

228 SF

EMER GEN

425 SF

DIETARY SERVICE

3884 SF

DINING AREA

677 SF

GROUP ROOM

63 SF

TOILET

72 SF

TOILET

31 SF

OFFICE

109B

119 SF

OFFICE

109A

1298 SF

REC ROOM

829 SF

REC ROOM

107A

388 SF

GROUP ROOM

107B

17 SF

CLOSET

106A

17 SF

CLOSET

106B

24 SF

CLOSET

106C

16 SF

CLOSET

107C

16 SF

CLOSET

107D

16 SF

CLOSET

107E

16 SF

CLOSET

107F

43 SF

HAC

292 SF

CORRIDOR

CE-2

1051 SF

CORRIDOR

CE-1

1151 SF

CORRIDOR

CE-4

380 SF

CORRIDOR C

CE-C

762 SF

CORRIDOR D

CE-D

380 SF

CORRIDOR A

CE-A

719 SF

CORRIDOR

CE-B

225 SF

SERVING LINE

113A

236 SF

LOBBY

49 SF

STORAGE

127A

FOR CONTINUATION OF CORRIDOR,

SEE DRAWING 5/DA1.1

FOR CONTINUATION OF CORRIDOR,

SEE DRAWING 3/DA1.1

FOR CONTINUATION OF CORRIDOR,

SEE DRAWING 2/DA1.1

FOR CONTINUATION

OF CORRIDOR, SEE

DRAWING 4/DA1.1

DA136

DA102

DA136

DA136

DA132 DA133

DA199DA199

DA102

DA136

DA102

DA102

CORRIDOR A

CE-A

DA103 DA136DA135DA103 /

DA102

CORRIDOR C

CE-C

DA102 DA103DA103DA135 /

DA136

CORRIDOR

CE-B

DA103

DA102

DA103DA135 /

DA136

CORRIDOR D

CE-D

DA103

DA102

DA135

DA136

EXISTING TWO HOUR FIRE-RATED PARTITION

WALL LEGEND

EXISTING SMOKE STOP PARTITION

EXISTING THREE HOUR FIRE-RATED PARTITION

EXISTING PARTITION

EXISTING ONE HOUR FIRE-RATED PARTITION

THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION

WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED

4525 S. Manhattan Ave. Tampa, FL 33611-2305

T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991

w w w . l o n g a n d a s s o c i a t e s . c o m

Checked By:

Seal

ALEXANDER M. LONG, A.I.A.

AR 0015104

987654321

B C

D E

F A

98765431 2

A th re e in c h e s o n e fo o t

B

C

D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t

E o n e h a lf in c h o n e fo o t

F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B A Y

P

IN

E S

M E D

IC

A L C E N

TE

R

Drawn By:Approved Division Chief

DIVISION CHIEF

Drawing Title

Approved Service Director

SERVICE DIRECTOR

Location

Building Number

Dwg. Of.

Date

Project No.

Project Title

DRAWING NO.

To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards

:0

:3

P

M

AML

01/23/15

DA1.1

REPLACE AIR CONDITIONING

SYSTEMS IN B-102

SUPPORT BUILDING

VAMC BAY PINES, FLORIDA 33744

TGS

DEMOLITION FLOOR PLAN

516-11-108

DEMOLITION NOTES

NO. DESCRIPTION

DA102 EXISTING SMOKESTOP PARTITION. PROVIDE CONSTRUCTION

LOCKSET AT EXISTING DOORS AND AIR BARRIER FOR DURATION

OF DEMOLITION AND NEW WORK. SEE DETAIL 1 ON SHEET G0.2

DA103 PROVIDE AIR BARRIER FOR DURATION OF DEMOLITION AND NEW

WORK. SEE DETAIL 1 ON SHEET G0.2

DA132 EXISTING FLOOR FINISHES ARE TO BE PROTECTED DURING

DEMOLITION & CONSTRUCTION WITH LAYER OF 1/8" MASONITE

TAPED TO EXISTING FLOOR CONTINUOUS THROUGHOUT AREA OF

WORK MIN, TYPICAL

DA133 ALL INTERIOR FINISHES, WALLS, SURFACES, DOORS & ITEMS TO

REMAIN SHALL BE PROTECTED & MAINTAINED. WALLS DAMAGED

DURING CONSTRUCTION SHALL BE PATCHED & PAINTED TO

MATCH EXISTING UPON COMPLETION OF NEW WORK, TYPICAL

FOR ENTIRE AREA.

DA135 PROVIDE DOOR AT AIR BARRIER WITH TEMPORARY SIGN FOR THE

DURATION OF DEMOLITION AND NEW WORK. TEMPORARY SIGN

SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE BUILDING

SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR SIDE.

DA136 PROVIDE TEMPORARY SIGN AT EXISTING DOORS FOR THE

DURATION OF DEMOLITION AND NEW WORK. TEMPORARY SIGN

SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE BUILDING

SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR SIDE.

DA199 SEE GENERAL NOTES ON SHEET G0.2 FOR ADDITIONAL NOTES

SCALE: NTS

B-102 KEY PLAN

SCALE: 1/8" = 1'-0"1

SUPPORT BUILDING

DEMOLITION FLOOR PLAN

N

0' 4' 8' 16'

SCALE: 1/8" = 1'-0"2

CORRIDOR A

DEMOLITION FLOOR PLAN

SCALE: 1/8" = 1'-0"3

CORRIDOR C

DEMOLITION FLOOR PLAN

SCALE: 1/8" = 1'-0"4

CORRIDOR B

DEMOLITION FLOOR PLAN

SCALE: 1/8" = 1'-0"5

CORRIDOR D

DEMOLITION FLOOR PLAN

NOTE:

THE TERM "TYPICAL" SHALL BE DEFINED IN THESE DRAWINGS AS:

IN EACH SIMILAR CASE WHETHER INDIVIDUALLY IDENTIFIED BY NOTATION OR NOT,

AND IN OCCURRENCES WHERE THE TYPICAL KEYNOTED ITEM IS SHOWN MAY NOT

IDENTIFY ALL OCCURRENCES. ALL OCCURRENCES ARE TO BE FIELD VERIFIED. THE

KEYNOTED ITEM IS SHOWN FOR REFERENCE AND APPLIES TO ALL OTHER SIMILAR

OCCURRENCES.

Issue & Revision Schedule

No. Description Date

FINAL CONSTRUCTION DOCUMENTS 01/23/15

NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR

CONFLICTS WHICH ARE ALLEGED.

COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY

SEE DRAWING 5/DA3.1

FOR CONTINUATION OF CORRIDOR,

SEE DRAWING 3/DA3.1

FOR CONTINUATION OF CORRIDOR,

SEE DRAWING 2/DA3.1

FOR

CONTINUATION

OF CORRIDOR,

SEE DRAWING

4/DA3.1DA108DA108

DA110

DA110

DA110

DA110

DA110DA110DA110DA110

DA110

DA128DA128 DA128

DA128

DA128

DA128

DA128

DA129

DA129

DA129

DA129

DA109DA109

DA109

DA109

DA132DA199 DA133/

DA134

GYP BD CEILING OR

AND ACOUSTICAL PANEL

2'x2' SUSPENDED CEILING GRID

STRIP LIGHT FIXTURE

FLUORESCENT INDUSTRIAL OR

DOWN LIGHT FIXTURE

SURFACE OR RECESSED

WALL MOUNTED

LIGHT FIXTURE

EXIT SIGN

EMERGENCY

SUPPLY AIR DIFFUSER

RETURN EXHAUST GRILLE

SMOKE DETECTORS

SURFACE FLUORESCENT

1'x4' LIGHT FIXTURE

OPEN-PAINTED FINISH

CURTAIN TRACK

PENDENT SPRINKLER HEAD

CANOPY METAL INSULATED

UPRIGHT SPRINKLER HEAD

SOFFIT DROP

ROOF DECK SYSTEM

SURFACE FLUORESCENT

2'X 4' LIGHT FIXTURE

EMERGENCY

FIRE ALARM SPEAKER

CEILING MOUNTED

SF

STRIP LIGHT FIXTURE

RECESSED FLUORESCENT

FLUORESCENT INDUSTRIAL OR

SURFACE FLUORESCENT

RECESSED FLUORESCENT

2'x4' LIGHT FIXTURE

2'x4' LIGHT FIXTURE

2'X 4' LIGHT FIXTURE

EMERGENCY

EXHAUST FAN

PENDANT FIXTURES

EMERGENCY PENDANT FIXTURES

RECESSED DOWN LIGHT FIXTURE

EMERGENCY SURFACE OR

PENDENT CONCEALED

SPRINKLER HEAD

POWER POLE

ACCESS PANEL

REFLECTED CEILING PLAN LEGEND

SUPPORT BLDG

WORK AREA

B

A

D

C

DA103DA103 DA135 DA102 DA136

DA103DA103DA135 /DA102

DA136

DA103DA103

DA102

DA136

DA135

DA135 /

DA103DA103DA135 /

DA102 DA136

THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION

WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED

4525 S. Manhattan Ave. Tampa, FL 33611-2305

T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991

w w w . l o n g a n d a s s o c i a t e s . c o m

Checked By:

Seal

ALEXANDER M. LONG, A.I.A.

AR 0015104

987654321

B C

D E

F A

98765431 2

A th re e in c h e s o n e fo o t

B

C

D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t

E o n e h a lf in c h o n e fo o t

F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B A Y

P

IN

E S

M E D

IC

A L C E N

TE

R

Drawn By:Approved Division Chief

DIVISION CHIEF

Drawing Title

Approved Service Director

SERVICE DIRECTOR

Location

Building Number

Dwg. Of.

Date

Project No.

Project Title

DRAWING NO.

To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards

:0

:4

P

M

AML

01/23/15

DA3.1

REPLACE AIR CONDITIONING

SYSTEMS IN B-102

SUPPORT BUILDING

VAMC BAY PINES, FLORIDA 33744

TGS

DEMOLITION REFLECTED CEILING

PLAN

516-11-108

SCALE: 1/8" = 1'-0"1

SUPPORT BUILDING

DEMOLITION

REFLECTED CEILING PLAN

SCALE: NTS

B-102 KEY PLAN

DEMOLITION NOTES

NO. DESCRIPTION

DA102 EXISTING SMOKESTOP PARTITION. PROVIDE CONSTRUCTION

LOCKSET AT EXISTING DOORS AND AIR BARRIER FOR DURATION

OF DEMOLITION AND NEW WORK. SEE DETAIL 1 ON SHEET G0.2

DA103 PROVIDE AIR BARRIER FOR DURATION OF DEMOLITION AND NEW

WORK. SEE DETAIL 1 ON SHEET G0.2

DA108 REMOVE EXISTING 2 X 4 ACOUSTIC CEILING IN ITS ENTIRETY,

TYP. SEE ELECTRICAL & MECHANICAL DEMOLITION DRAWINGS

FOR REMOVAL OF LIGHTS, FANS AND MECHANICAL DIFFUSERS.

THIS APPLIES TO ALL AREAS ON THE DRAWINGS.

DA109 REMOVE EXISTING FIRE PROTECTION SPRINKLER HEADS, TYP.

SEE FIRE PROTECTION DRAWINGS FOR DEDUCTIVE ALTERNATE.

COORDINATE ALL WORK WITH FIRE PROTECTION DRAWINGS.

BUILDING SHALL REMAIN FIRE PROTECTED DURING

CONSTRUCTION. COORDINATE AS REQUIRED.

DA110 ALL EXISTING GYPSUM BOARD CEILINGS & SOFFITS SHALL BE

PROTECTED & MAINTAINED. ANY DISTURBED SHALL BE PATCHED

AND FINISHED TO MATCH EXISTING CONSTRUCTION, TYPICAL.

DA128 CAREFULLY REMOVE EXISTING CONVEX MIRROR AND STORE

FOR REINSTALLATION IN SAME LOCATION AS PART OF NEW

WORK, TYPICAL

DA129 CAREFULLY REMOVE EXISTING CEILING MOUNTED SIGNAGE.

STORE FOR REINSTALLATION IN SAME LOCATION AS PART OF

NEW WORK, TYPICAL

DA132 EXISTING FLOOR FINISHES ARE TO BE PROTECTED DURING

DEMOLITION & CONSTRUCTION WITH LAYER OF 1/8" MASONITE

TAPED TO EXISTING FLOOR CONTINUOUS THROUGHOUT AREA

OF WORK MIN, TYPICAL

DA133 ALL INTERIOR FINISHES, WALLS, SURFACES, DOORS & ITEMS TO

REMAIN SHALL BE PROTECTED & MAINTAINED. WALLS DAMAGED

DURING CONSTRUCTION SHALL BE PATCHED & PAINTED TO

MATCH EXISTING UPON COMPLETION OF NEW WORK, TYPICAL

FOR ENTIRE AREA.

DA134 EXISTING EXHAUST HOOD TO REMAIN

DA135 PROVIDE DOOR AT AIR BARRIER WITH TEMPORARY SIGN FOR

THE DURATION OF DEMOLITION AND NEW WORK. TEMPORARY

SIGN SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE

BUILDING SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR

SIDE.

DA136 PROVIDE TEMPORARY SIGN AT EXISTING DOORS FOR THE

DURATION OF DEMOLITION AND NEW WORK. TEMPORARY SIGN

SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE BUILDING

SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR SIDE.

DA199 SEE GENERAL NOTES ON SHEET G0.2 FOR ADDITIONAL NOTES

N

0' 4' 8' 16'

SCALE: 1/8" = 1'-0"2

CORRIDOR A DEMOLITION

REFLECTED CEILING PLAN

SCALE: 1/8" = 1'-0"3

CORRIDOR C DEMOLITION

REFLECTED CEILING PLAN

SCALE: 1/8" = 1'-0"4

CORRIDOR B DEMOLITION

REFLECTED CEILING PLAN

SCALE: 1/8" = 1'-0"5

CORRIDOR D DEMOLITION

REFLECTED CEILING PLAN

NOTE:

THE TERM "TYPICAL" SHALL BE DEFINED IN THESE DRAWINGS AS:

IN EACH SIMILAR CASE WHETHER INDIVIDUALLY IDENTIFIED BY NOTATION OR NOT,

AND IN OCCURRENCES WHERE THE TYPICAL KEYNOTED ITEM IS SHOWN MAY NOT

IDENTIFY ALL OCCURRENCES. ALL OCCURRENCES ARE TO BE FIELD VERIFIED. THE

KEYNOTED ITEM IS SHOWN FOR REFERENCE AND APPLIES TO ALL OTHER SIMILAR

OCCURRENCES.

Issue & Revision Schedule

No. Description Date

FINAL CONSTRUCTION DOCUMENTS 01/23/15

NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR

CONFLICTS WHICH ARE ALLEGED.

COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY

SEE DRAWING 5/DA4.1

FOR CONTINUATION OF CORRIDOR,

SEE DRAWING 3/DA4.1

FOR CONTINUATION OF CORRIDOR,

SEE DRAWING 2/DA4.1

FOR

CONTINUATION

OF CORRIDOR,

SEE DRAWING

4/DA4.1

DA006

DA006

DA006

DA006

DA006

DA006

DA006

DA006DA006

DA006

DA006

DA006

DA007

DA007

DA007

DA007

DA006

DA199DA199

DA018

DA017

DA016

DA016

DA019

DA007

DA020

DA020

PROVIDE ALL NECESSARY TEMPORARY

SERVICES AND SYSTEM ISOLATIONS TO

ACCOMODATE PROJECT PHASING. REFER

TO ARCHITECTURE PHASING PLAN.

SUPPORT BLDG

WORK AREA

B

A

D

C

NO NEW

WORK

DA017

NO NEW

WORK

NO NEW

WORK

NO NEW

WORK

ROOF NOTE

EXISTING ROOF IS TO BE PROTECTED AND IS UNDER AN EXISTING WARRANTY TO

REMAIN IN EFFECT. ALL NEW WORK MUST MAINTAIN EXISTING ROOF WARRANTY.

OBTAIN COPY OF WARRANTY FROM VA PRIOR TO STARTING WORK, TYPICAL.

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K

L.

M.

PERFORM DEMOLITION WORK AS NOTED TO PROVIDE COMPLETE DEMOLITION

AND PREPARATION FOR NEW WORK. THIS INCLUDES DEMOLITION OF WORK

WHICH IS A PART OF SYSTEMS TO BE REMOVED WHETHER IDENTIFIED TO BE

REMOVED ON THIS DRAWING OR NOT.

ALL BUILDING SYSTEMS SERVING OCCUPIED AREAS OF THE EXISTING FACILITY

SHALL REMAIN FULLY OPERATIONAL. THE CONTRACTOR SHALL PROTECT AND

MAINTAIN THESE SYSTEMS PASSING THROUGH AND ADJACENT TO THE AREAS

REQUIRING DEMOLITION WORK. WORK THAT REQUIRES DISRUPTION OF THE

OPERATION OF THE OCCUPIED SPACES SHALL BE PERFORMED DURING HOURS,

INCLUDING EVENINGS AND WEEKENDS, WHICH MINIMIZE INTERRUPTION TO THE

OCCUPANTS OF THE BUILDING. THE TIMES AND DURATION OF THIS WORK MUST

BE CAREFULLY COORDINATED WITH THE OWNER. WHERE NECESSARY,

CONTRACTOR SHALL REROUTE EXISTING UTILITIES TO TEMPORARILY SERVE

OTHER AREAS OCCUPIED DURING DEMOLITION AND CONSTRUCTION.

WHERE EXISTING CONDITIONS ARE SHOWN, THEY HAVE BEEN DERIVED FROM

AVAILABLE DRAWINGS AND FIELD INVESTIGATION. THEY REPRESENT THE

ENGINEER'S BEST ESTIMATE OF ACTUAL FIELD CONDITIONS. CONTRACTOR

SHALL VISIT THE JOB SITE AND BECOME FAMILIAR WITH THE SITE CONDITIONS

AND THE EXISTING SYSTEMS BEFORE SUBMITTING A BID.

WHERE DUCTWORK MUST BE REMOVED, IT SHALL MEAN THE COMPLETE

REMOVAL OF DUCTWORK, INCLUDING, BUT NOT LIMITED TO, DUCT FITTINGS,

INSULATION, SUPPORTS, HANGERS, STRAPS, BASES, GUYS, BRACKETS,

BRACES, ANCHORS, DAMPERS, DEVICES AND INCIDENTAL ITEMS FASTENED,

CONNECTED AND SUPPORTED FROM THE DUCTWORK, UNLESS SPECIFICALLY

INDICATED OTHERWISE.

WHERE PIPING MUST BE REMOVED, IT SHALL MEAN THE COMPLETE REMOVAL

OF PIPING, INCLUDING, BUT NOT LIMITED TO, PIPE FITTINGS, VALVES,

STRAINERS, FLANGES, INSULATION, SUPPORTS, HANGERS, STRAPS, BASES,

GUYS, BRACKETS, BRACES, ANCHORS, DEVICES AND INCIDENTAL ITEMS

FASTENED, CONNECTED AND SUPPORTED FROM THE PIPING, UNLESS

SPECIFICALLY INDICATED OTHERWISE.

WHERE EQUIPMENT MUST BE REMOVED, IT SHALL MEAN THE COMPLETE

REMOVAL OF EQUIPMENT, INCLUDING, BUT NOT LIMITED TO, SUPPORTS,

HANGERS, STRAPS, BRACKETS, BRACES, ANCHORS, DUCTWORK, PIPING AND

INCIDENTAL ITEMS FASTENED, CONNECTED AND SUPPORTED FROM THE

EQUIPMENT, UNLESS SPECIFICALLY INDICATED OTHERWISE.

WHERE CONTROLS MUST BE REMOVED, IT SHALL MEAN THE COMPLETE

REMOVAL OF CONTROLS, INCLUDING, BUT NOT LIMITED TO, THERMOSTATS,

SENSORS, CONTROLLERS, PANELS AND ENCLOSURES, RELAYS, SWITCHES,

TRANSFORMERS, AND OTHER CONTROL DEVICES, CONTROL TUBING, WIRING,

CONDUITS, SUPPORTS, HANGERS, STRAPS, BASES, GUYS, BRACKETS,

BRACES, ANCHORS, AND DEVICES FASTENED, CONNECTED AND SUPPORTED

FROM THE CONTROL SYSTEM, UNLESS SPECIFICALLY INDICATED OTHERWISE.

UNLESS OTHERWISE INDICATED, PATCH ALL OPENINGS AND HOLES IN WALLS

AND FLOORS LEFT FROM THE REMOVAL OF DUCTWORK, PIPING AND EQUIPMENT

WITH SAME MATERIALS AND FINISH TO MATCH EXISTING SURFACE. REFER TO

ARCHITECTURAL DRAWINGS FOR SPECIFIC PATCHING DETAILS AND NOTES.

REFER TO STRUCTURAL DRAWINGS FOR PATCHING OF ROOF OPENINGS

CREATED BY REMOVAL OF ROOFTOP MECHANICAL EQUIPMENT AND DEVICES.

SEE DETAIL 8/S2.1.

WHERE EXISTING EQUIPMENT, DUCTWORK, PIPING AND CONTROLS ARE

INDICATED TO REMAIN, PROTECT FROM DAMAGE AND MAINTAIN IN SERVICE.

COORDINATE SHUTDOWN OF ALL UTILITIES AND EQUIPMENT WITH THE VA.

THE VA RESERVES THE RIGHT OF REFUSAL FOR ALL MECHANICAL EQUIPMENT

AND CONTROLS. NOTIFY THE OWNER TO DETERMINE DISPOSITION OF

EQUIPMENT AND CONTROL PRIOR TO DEMOLITION WORK. WHERE THE OWNER

ELECTS TO MAINTAIN OWNERSHIP OF EQUIPMENT AND CONTROLS, TURN OVER

AND TRANSPORT EQUIPMENT AND CONTROLS TO A LOCATION WITHIN 3 MILES

OF PROJECT SITE AS DIRECTED BY THE OWNER. WHERE THE OWNER

REFUSES TO MAINTAIN OWNERSHIP OF EQUIPMENT AND CONTROL ,

OWNERSHIP SHALL CONVEY TO THE CONTRACTOR AND CONTRACTOR SHALL

DISPOSE OF SUCH ITEMS OFF SITE.

NO OPEN BURNING SHALL BE PERMITTED.

GENERAL DEMOLITION NOTES

THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION

WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED

4525 S. Manhattan Ave. Tampa, FL 33611-2305

T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991

w w w . l o n g a n d a s s o c i a t e s . c o m

Checked By:

Seal

ALEXANDER M. LONG, A.I.A.

AR 0015104

987654321

B C

D E

F A

98765431 2

A th re e in c h e s o n e fo o t

B

C

D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t

E o n e h a lf in c h o n e fo o t

F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B A Y

P

IN

E S

M E D

IC

A L C E N

TE

R

Drawn By:Approved Division Chief

DIVISION CHIEF

Drawing Title

Approved Service Director

SERVICE DIRECTOR

Location

Building Number

Dwg. Of.

Date

Project No.

Project Title

DRAWING NO.

To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards

:0

:4

P

M

AML

01/23/15

DA4.1

REPLACE AIR CONDITIONING

SYSTEMS IN B-102

SUPPORT BUILDING

VAMC BAY PINES, FLORIDA 33744

TGS

DEMOLITION ROOF PLAN

516-11-108

SCALE: 1/8" = 1'-0"1

SUPPORT BUILDING

DEMOLITION ROOF PLAN

N

0' 4' 8' 16'

DEMOLITION NOTES

NO. DESCRIPTION

DA006 DEMOLISH AND REMOVE ROOFTOP MECHANICAL EQUIPMENT &

CURBS TO DECK. REMOVE ALL RELATED UTILITIES AND

SERVICES BACK TO SOURCE, CAP AND TERMINATE AS REQ'D.

REMOVE CONDENSATE DRAIN LINES & SUPPORTS. SEE ELEC &

MECH DWG'S. SEE NEW WORK. ROOF SHALL BE PATCHED BY

ROOF SYSTEM MANUFACTURER'S CERTIFIED REPRESENTATIVE

TO RETAIN ROOF WARRANTY. ROOF PENETRATIONS SHALL BE

RESTORED TO MATCH EXISTING ROOF STRUCTURE, INCLUDING

THE INSTALLATION OF ROOF SLAB STRUCTURAL ELEMENTS.

COORDINATE ROOF RESTORATION WITH NEW SYSTEMS

INSTALLATIONS.

DA007 EXISTING ROOFTOP MECHANICAL EQUIPMENT TO REMAIN. SEE

ELE…