36C24818R0391-240.pdf
PDF 13 MB Posted
- Attached to
- Renovate A/C Bldg 102 Ph I Federal contract opportunity
- Solicitation number
- 36C24818R0391
About this file
36C24818R0391 Support Hub FINAL Complete Set - REDACTED.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24818R0391-0001000.docx | DOCX document | |
| 36C24818R0391-242.pdf | ||
| 36C24818R0391-236.pdf | ||
| 36C24818R0391-241.pdf | ||
| 36C24818R0391-247.pdf | ||
| 36C24818R0391-239.pdf | ||
| 36C24818R0391-244.pdf | ||
| 36C24818R0391-245.pdf | ||
| 36C24818R0391-233.pdf | ||
| 36C24818R0391-235.pdf | ||
| 36C24818R0391-243.pdf | ||
| 36C24818R0391-234.pdf | ||
| 36C24818R0391-238.pdf | ||
| 36C24818R0391-246.pdf | ||
| 36C24818R0391-237.pdf | ||
| 36C24818R0391-232.docx | DOCX document | |
| 36C24818R0391-000.docx | DOCX document |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AREA OF WORK
A
B
C D
SUPPORT
BUILDING
E0.1 LEGEND & GENERAL NOTES
E2.1 LIGHTING & SIGNAL PLAN
E3.1 POWER PLAN
E4.1 ELECTRICAL ROOF PLAN
E5.1 EXISTING MODIFIED ELECTRICAL RISER DIAGRAM
E5.2 EXISTING MODIFIED FIRE ALARM SYSTEM RISER
E8.1 DETAILS
FP0.1 LEGEND, GENERAL NOTES & DETAILS
FP1.1 FLOOR PLAN
MH0.1 LEGEND & GENERAL NOTES
MH1.1 FLOOR PLAN
MH1.2 ROOF PLAN
MH2.1 ENLARGED PLANS AND SECTIONS
MH3.1 DETAILS
MH3.2 DETAILS
MH4.1 SCHEDULES
MH4.2 SCHEDULES
MH6.1 CONTROLS DIAGRAMS & SEQUENCES
MH6.2 CONTROL DIAGRAMS, POINTS LIST & SEQUENCES
MH6.3 CONTROLS DIAGRAMS & SEQUENCES
MP1.1 FLOOR PLAN
MP3.1 PIPING DIAGRAMS
MP4.1 SCHEDULES
S0.1 SLAB PLAN, STUCTURAL NOTES, DESIGN WIND LOADS & DETAILS
S1.1 ROOF FRAMING PLAN
S2.1 SECTIONS & DETAILS
A0.1 SITE PLAN
A1.0 BUILDING PHASING PLAN
A1.1 FLOOR PLAN
A3.1 REFLECTED CEILING PLAN
A4.1 ROOF PLAN
A5.1 BUILDING SECTION
DA1.1 DEMOLITION FLOOR PLAN
DA3.1 DEMOLITION REFLECTED CEILING PLAN
DA4.1 DEMOLITION ROOF PLAN
DMH1.1 DEMOLITION FLOOR PLAN
DMP1.1 DEMOLITION FLOOR PLAN
DE2.1 DEMOLITION LIGHTING & SIGNAL PLANS
DE3.1 DEMOLITION POWER PLANS
DE4.1 DEMOLITION ELECTRICAL ROOF PLAN
DE5.1 EXISTING ELECTRICAL RISER DIAGRAM
DE5.2 EXISTING FIRE ALARM SYSTEM RISER
LS1.1 LIFE SAFETY PLAN
G0.1 COVER & INDEX
G0.2 ABBREVIATIONS, SYMBOL LEGEND, & MATERIALS LEGEND
G0.3 PARTITION PENETRATION DETAILS
THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION
WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED
4525 S. Manhattan Ave. Tampa, FL 33611-2305
T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991
w w w . l o n g a n d a s s o c i a t e s . c o m
Checked By:
Seal
ALEXANDER M. LONG, A.I.A.
AR 0015104
987654321
B C
D E
F A
98765431 2
A th re e in c h e s o n e fo o t
B
C
D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t
E o n e h a lf in c h o n e fo o t
F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B A Y
P
IN
E S
M E D
IC
A L C E N
TE
R
Drawn By:Approved Division Chief
DIVISION CHIEF
Drawing Title
Approved Service Director
SERVICE DIRECTOR
Location
Building Number
Dwg. Of.
Date
Project No.
Project Title
DRAWING NO.
To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards
:2
:4
P M
AML
01/23/15
G0.1
REPLACE AIR CONDITIONING
SYSTEMS IN B-102
SUPPORT BUILDING
VAMC BAY PINES, FLORIDA 33744
TGS
COVER & INDEX
516-11-108
LOCAL AERIAL
REGIONAL AERIAL
SITESITE
REPLACE AIR CONDITIONING
SYSTEMS IN B-102
SUPPORT BUILDING
VA MEDICAL CENTER
BAY PINES, FLORIDA 33744
INDEX OF DRAWINGS
FINAL CONSTRUCTION DOCUMENTS
JANUARY 23, 2015
GENERAL
LIFE SAFETY
DEMOLITION
ARCHITECTURAL
MECHANICAL
FIRE PROTECTION
STRUCTURAL
ELECTRICAL
Issue & Revision Schedule
No. Description Date
FINAL CONSTRUCTION DOCUMENTS 01/23/15
NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR
CONFLICTS WHICH ARE ALLEGED.
COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY
BAY PINES VAHCS. NO REPRODUCTIONS, CHANGES OR COPIES IN ANY MANNER SHALL BE MADE
WITHOUT OBTAINING PRIOR WRITTEN CONSENT FROM BAY PINES VAHCS.
A
A
PARTITION TYPE
DOOR NUMBER, SEE SCHEDULE
WINDOW TYPE
EQUIPMENT TAG, SEE SCHEDULE
INTERIOR ELEVATION1A99.9.9
1 ASSEMBLY TYPE
Number
ASI # 88
REVISION TAG
NOTE TAG1
0 COLUMN CENTERLINE
A101
A101
DETAIL
SECTION
A101
EXTERIOR ELEVATION
FINISHED FLOOR ELEVATIONFFE
135' - 5 1/2"
FINISHED FLOOR ELEVATION
AFF
9' - 0"
CMU WALL, THICKNESS VARIES
CMU WALL (RATED)
STUD WALL, THICKNESS VARIES
STUD WALL (RATED)
EXISTING WALL TO REMAIN
BRICK VENEER
RIGID INSULATION
CAVITY INSULATION
INSULATION (BATT, BLANKET, OR FILL)
WOOD (FINISHED)
PLYWOOD (SMALL SECTION)
PLYWOOD (LARGE SECTION)
STEEL (LARGE SECTION)
ROUGH LUMBER (CONTINUOUS)
ROUGH LUMBER (INTERMITTENT)
PRECAST CONC. OR CUT STONE
CONCRETE
COMPACTED FILL OR EARTH
FINISHED GRADE
ALIGN OF NEW PARTITION WITH
TO/FROM THE CENTER LINE OF
ALIGN OF NEW PARTITION TO
TO/FROM COLUMN CENTER LINES
NEW WALL CONSTRUCTION
TO/FROM THE FINISHED FACE OF
NEW WALL CONSTRUCTION
ALIGN NEW PARTITION TO FINISH GWB
OF COLUMN
FLUSH BOTH SIDES OF COLUMN
OF WINDOW MULLION
ALIGN NEW PARTITION TO EXIST (VERIFY EXIST
PARTITION CONSTRUCTION MATCHES NEW
PARTITION CONSTRUCTION)
5/8" TYPE "X" FIRE RATED GYP BD EACH
SIDE ON FOR (1) HR FIRE RATING
SHEETING - TAPE JOINTS TO PROVIDE
DUST BARRIER
STRUCTURE
CONSTRUCTION
SIDE
OCCUPIED
SIDE
TAPE 6 MIL SHEET
CONTINUOUS @
FLOOR & CEILING
EXISTING CLG
2" SOUND ATTENUATION BLANKETS
VE
RI
FY
EL 0'-0"
T/SLAB
NOTE:
A. REMOVE AT COMPLETION OF THE WORK AND RESTORE ALL SURFACES &
FINISHES TO NEW CONDITION. MATCH EXISTING.
B. CONTRACTOR SHALL AT ALL TIMES MAINTAIN NEGATIVE PRESSURE IN WORK ARE
AS RELATIVE TO ADJACENT OPERATIONAL SPACES.
C. TEMPORARILY CLOSE ALL OPEN HVAC CEILING DIFFUSERS & SEAL W/ 6 MIL POLY
SHEET SEAL W/ DUCT TAPE IN ANY AREA PROTECTED.
D. BARRIER MUST PROVIDE CLASS III/ IV BARRIERS TO PROTECT ANY DUST, DIRT OR
CONTAMINATES FROM ENTERING OCCUPIED SPACERS DURING THE
CONSTRUCTION PERIOD.
E. PASS-DOORS TO BE SOLID CORE 1 3/4" THICK W/ LOCKABLE HARDWARE. DOOR
SIZES NOTED ON FLOOR PLANS, DOOR & FRAME TO BE (1) HR. FIRE RATED.
PROVIDE SEALS AND TEMPORARILY SEALED THRESHOLD.
REMOVE PORTION OF EXIST. CEILING
AS REQD. TO INSTALL BARRIER &
REPLACE TO MATCH EXISTING
AFTER REMOVAL OF BARRIER
GYPSUM WALLBOARD APPLIED HORIZONTALLY OR
VERTICALLY. VERTICAL JOINTS CENTERED OVER STUDS AND
STAGGERED ONE STUD CAVITY ON OPPOSITE SIDES OF
STUDS. VERTICAL JOINTS IN ADJACENT LAYERS (MULTILAYER
SYSTEMS) STAGGERED ONE STUD CAVITY. HORIZONTAL EDGE
JOINTS AND HORIZONTAL BUTT JOINTS IN ADJACENT LAYERS
(MULTILAYER SYSTEMS) STAGGERED 12" MIN. THICKNESS AND
NUMBER OF LAYERS SHALL BE COORDINATED PER RATED
CONDITION WITH DETAIL AS REQUIRED.
FRICTION FIT BATT INSULATION WITHIN CAVITY AS REQUIRED.
SEE FLOOR PLANS FOR SMOKE BARRIER & FIRE RATED WALL
LOCATIONS AND COORDINATE WITH THE REQUIREMENTS OF
THIS DETAIL FOR EACH CONDITION.
NO. 25 MSG GALVANIZED STL STUDS W/ DEPTH AS
REQUIRED PER THE REQUIREMENTS OF THIS DETAIL
SPACED @ 24" O.C. MAX
NOTE:
USE THIS DETAIL FOR THE PATCHING OF ABANDONED OPENINGS EQUAL TO OR
GREATER THAN 12" X 12" IN SMOKE BARRIER & FIRE RATED WALLS. OPENINGS
SMALLER THAN 12" X 12" SHALL BE CUT TO MINIMUM 12" X 12" SIZE AND THEN
PATCHED ACCORDING TO THIS DETAIL.
THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION
WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED
4525 S. Manhattan Ave. Tampa, FL 33611-2305
T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991
w w w . l o n g a n d a s s o c i a t e s . c o m
Checked By:
Seal
ALEXANDER M. LONG, A.I.A.
AR 0015104
987654321
B C
D E
F A
98765431 2
A th re e in c h e s o n e fo o t
B
C
D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t
E o n e h a lf in c h o n e fo o t
F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B A Y
P
IN
E S
M E D
IC
A L C E N
TE
R
Drawn By:Approved Division Chief
DIVISION CHIEF
Drawing Title
Approved Service Director
SERVICE DIRECTOR
Location
Building Number
Dwg. Of.
Date
Project No.
Project Title
DRAWING NO.
To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards
:2
:5
P M
AML
01/23/15
G0.2
REPLACE AIR CONDITIONING
SYSTEMS IN B-102
SUPPORT BUILDING
VAMC BAY PINES, FLORIDA 33744
TGS
ABBREVIATIONS, SYMBOL LEGEND, &
MATERIALS LEGEND
516-11-108
ABBREVIATIONS MATERIALS LEGENDSYMBOL LEGEND
D
A
C
B
E
AREA
ANCHOR BOLT
AIR CONDITIONING
ALTERNATING CURRENT
A
AB
A/C
AC
ACCESS FLOOR
AMERICAN CONCRETE INSTITUTE
ACOUSTICAL
ACOUSTICAL CEILING TILE
AMERICANS WITH DISABILITIES ACT
ADDITIONAL
ADJUSTABLE
ADJACENT
ABOVE FINISHED COUNTER
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
AMERICAN INSTITUTE OF
AMERICAN INSTITUTE OF
ACOUSTICAL LINING
ALTERNATE
ALUMINUM
AMPERE
ANCHOR
ANODIZED
ACOUSTICAL PANEL
APARTMENT
APPROXIMATE
ACID RESISTANT
ARCHITECTURAL / ARCHITECT
ASBESTOS
AMERICAN SOCIETY OF
& AIR-CONDITIONING ENGINEERS
AMERICAN SOCIETY OF
ASPHALT
ASSOCIATION
AMERICAN SOCIETY FOR
AUTOMATIC
AUXILIARY
AVENUE
ACFL
ACI
ACOUS
ACT
ADA
ADDNL
ADJ
ADJT
AFC
AFF
AHU
AIA
AISC
AL
ALT
ALUM
AMP
ANC
ANOD
AP
APT
APP
AR
ARCH
ASB
ASHRAE
ASME
ASPH
ASSOC
ASTM
AUTO
AUX
AVE
AWI
BULLETIN BOARD
BOARD
BOTTOM FACE
BITUMINOUS
BLOCK
BLOCKING
BUILDING
BACK
BENCH MARK
BEAM
BOTTOM
BASE PLATE
BEARING
BRITISH THERMAL UNIT
BRITISH THERMAL UNIT PER HOUR
BETWEEN
BASEMENT
BUILT UP ROOFING
BOTH WAYS
BB
BD
BF
BIT
BLDG
BLK
BLKG
BK
B/M
BM
BOT
BP
BRG
BSMT
BTU
BTUH
BTWN
BUR
BW
CABINET
CENTER TO CENTER
CEMENT
CUBIC FEET PER SECOND
CHANNEL
CONTROL JOINT
CENTER LINE
CEILING
CLEAR
CONSTRUCTION MANAGER
CONCRETE MASONRY UNIT
CLEAN OUT
COLUMN
CONNECTION
CONSTRUCTION
CONTINUOUS
CONTRACTOR
COUPLING
CARPET
CARBON STEEL
CERAMIC TILE
CONDENSER UNIT
CUBIC YARD
CENTER
CERAMIC
CUBIC FEET
CUBIC FEET PER MINUTE
COMPUTER
COMPUTER PROCESSING UNIT
CONDUIT
CONCRETE
CORRIDOR
CAB
C/C
CEM
CER
CF
CFM
CFS
CH
CJ
CL
CLG
CLR
CM
CMU
CO
COL
COMP
CND
CONC
CONN
CONST
CONT
CONTR
CORR
CPLG
CPT
CPU
CS
CT
CTR
CU
CY
DEMOLITION
DENSITY
DETAIL
DIAMETER
DIAGONAL
DIFFUSER
DIMENSION
DISCONNECT
DOWN
DOOR
DOWNSPOUT
DRINKING FOUNTAIN
DITTO
DOUBLE
DEAD LOAD
DRAWING
STEEL CONSTRUCTION
ARCHITECTS
HEATING. REFRIGERATION
MECHANICAL ENGINEERS
TESTING & MATERIALS
DBL
DEM
DEN
DET
DF
DIA
DIAG
DIFF
DIM
DISC
DL
DO
DN
DR
DS
DWG
EACH
EXPANSION BOLT
EXHAUST FAN
EFFICIENCY
EXTRA HAZARD
ELEVATION
ELECTRIC / ELECTRICAL
EMERGENCY
ENERGY MANAGEMENT
ENCLOSURE
EXPLOSION PROOF
EQUAL
EQUIPMENT
ESTIMATE / ESTIMATED
EXISTING TO REMAIN
EVAPORATIVE / EVAPORATOR
EACH WAY
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXFILTRATION
EXHAUST
EXPANSION JOINT
EXPANSION
EXISTING RELOCATED
EXISTING
EXTERIOR
& CONTROL SYSTEM
MODULUS OF ELASTICITY
ENGINEER
ENGINEERING
E
EA
EB
EF
EFF
EH
EL
ELEC
EMERG
EMCS
ELEVATOR
ENCL
ENGR
ENGRG
EP
EQ
EQPT
EST
ETR
EVAP
EVTR
EW
EWC
EWH
EXF
EXH
EJ
EXP
EXR
EXST
EXT
AMOUNTAMT
Q
P
O
N
W
V
U
L
K
J
I
T
S
X
Y
F
G
H
M
R
FA
FACP
FBRK
FC
FD
FDC
FDN
FDPR
FE
FEC
FF
FFE
FFF
FG
FH
FHMS
FHS
FHWS
FIN
FJT
FL
FLG
FLSHG
FLR
FP
FPG
FPM
FPS
FO
FOC
FOF
FOM
FR
FRMG
FRTL
FS
FT
FTG
FURR
FV
FIRE ALARM
FIRE ALARM CONTROL PANEL
FIRE BRICK
FLEXIBLE CONNECTION
FLOOR DRAIN
FIRE DEPARTMENT CONNECTION
FOUNDATION
FIRE DAMPER
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISHED FLOOR
FINISHED FLOOR ELEVATION
FROM FINISHED FLOOR
FLANGED CONNECTION
FIRE HYDRANT
FLAT HEAD MACHINE SCREW
FIRE HOSE STATION
FLAT HEAD WOOD SCREW
FINISH / FINISHED
FLUSH JOINT
FLOOR
FLANGE
FLASHING
FLUORESCENT
FIRE PROTECTION
FIREPROOFING
FEET PER MINUTE
FEET PER SECOND
FLAT OVAL
FACE OF CONCRETE
FACE OF FINISH
FACE OF MASONRY
FRAME
FRAMING
FIRE RETARDANT TREATED LUMBER
FULL SIZE
FEET
FOOTING
FURRED / FURRING
FLUSH VALVE
FOS FACE OF STUD
FZR FREEZER
GA
GAL
GALV
GB
GC
GI
GL
GLBK
GP
GPM
GR
GRD
GRND
GS
GST
GWB
GYP
GAGE / GAUGE
GALLON
GALVANIZED
GRAB BAR
GENERAL CONTRACTOR
GALVANIZED IRON
GLASS / GLAZING
GLASS BLOCK
GENERAL PURPOSE
GALLONS PER MINUTE
GROOVED CONNECTION
GRADE
GROUND
GALVANIZED STEEL
GLAZED STRUCTURAL TILE
GYPSUM WALL BOARD
GYPSUM
HB
HC
HCP
HD
HDNR
HDW
HGR
HM
HORIZ
HP
HR
HRS
HSS
HT
HVAC
HZ
HOSE BIBB
HOLLOW CORE
HANDICAPPED
HARD
HARDENER
HARDWARE
HANGER
HOLLOW METAL
HORIZONTAL
HORSEPOWER
HOUR
HOURS
HOLLOW STRUCTURAL STEEL
HEIGHT
HEATING, VENTILATION,
HERTZ / CYCLES PER SECOND
I
IC
ID
IF
IN
INCL
INF
INFO
INSUL
INT
INV
MOMENT OF INERTIA
INTERCOM
INSIDE DIAMETER
INSIDE FACE
INCHES
INCLUDED
INFILTRATION
INFORMATION
INSULATION
INTERIOR
INVERT
IRON PIPEIP
AIR-CONDITIONING
LTWT LIGHTWEIGHT
MASONRY OPENING
NOISE REDUCTION
NOT IN CONTRACT
OUTSIDE DIAMETER
PLASTIC LAMINATE
POLYVINYL CHLORIDE
POUNDS PER SQUARE INCH
POUNDS PER SQUARE FOOT
POUNDS PER LINEAR FOOT
POUNDS PER CUBIC FOOT
PRESSURE TREATED
POST INDICATOR VALVE
QTY
QT
PA
QUARRY TILE
PUBLIC ADDRESS
QUANTITY
PLAM
PVC
PSF
PLF
PCF
PREFAB
PROJ
PRES
PVMT
PLYWD
PSI
PT
PIV
PREFABRICATED
PROJECTION
PRESSURE
PAVEMENT
PLYWOOD
OHD
OPP HD
PTD
PNLB
PNL
PLAS
PART
PR
OD
OH
PAINTED
PAIR
PANEL
PANELBOARD
PLASTER
PARTITION
OVERHEAD
OVERHEAD DOOR
OPPOSITE HAND
NAT
NRC
NTP
N/A
NEG
OPNG
NO
OC
NIC
NUMBER
OPENING
ON CENTER
NATURAL
NOTICE TO PROCEED
NOT APPLICABLE
NEGATIVE
MAXIMUMMAX
MULL
MOD
MOV
MISC
MIRR
MTL
MED
MECH
MM
MIL
MISCELLANEOUS
MULLION
MODEL
MOVABLE
MILLIMETER(S)
MILITARY
MIRROR
METAL
MEDIUM
MECHANICAL
MAT
MAS
MFR
MFD
MH
MO
MK
LL
LF
MANHOLE
MARK
MATERIAL
MASONRY
MANUFACTURER
MANUFACTURED
LIVE LOAD
LINEAR FOOT
VINYL TILEVT
VOLTS
VOLUME
VINYL WALL COVERING
WALL HUNG
WALL TO WALL
WALL CLEANOUT
WEATHER PROTECTED
WELDED WIRE FABRIC
WINDOW
WIDE FLANGE
WOOD
WITHOUT
WITH
WEIGHT
WATER CLOSET
WAINSCOT
WD
WWF
WIN
W/O
WF
W/
WT
WTW
WCO
WAINS
WH
WP
WC
VOL
VWC
V
UNLESS OTHERWISE NOTED
UTILITY
URINAL
UNDERCUT
UNDERGROUND
UNDERWRITER'S
VELOCITY
VARIABLE AIR VOLUME
VAPOR RETARDER
VERTICAL
VINYL COMPOSITION TILE
VINYL
VENT THRU ROOF
VACUUM
TRANSFER
TYPICAL
TRANSFORMER
TACK BOARD
URL
VPR
VAV
VEL
VERT
VCT
VTR
VIN
UTY
VAC
UON
UL
UG
UC
XFR
TYP
XFMR
TB
KILOVOLT AMPERE
KILOVOLTKV
KVA
LAM
LAB
LVG
LTG
LAV
KO
KIT
KW
LABORATORY
LIGHTING
LAVATORY
LEAVING
LAMINATE(D)
KNOCKOUT
KITCHEN
KILOWATT(S)
JT
JB
JST
JOINT
JUNCTION BOX
JOIST
SA SUPPLY AIR
SWITCH
SYMBOL
SYMMETRICAL
SYSTEM
SUSPEND(ED)
TELEVISION
TELEPHONE
THERMOSTAT
THICK(NESS)
TOILET
TONGUE AND GROOVE
TOP
THRESHOLD
TEMPERATURE
TOP OF MASONRY
TOP OF FOOTING
TOP OF CURB
TOP OF BEAM
TOP OF STEEL
TOP OF SLAB
TOP OF
TOP AND BOTTOM
TOP FACE
THK
T/
T/C
T/FTG
T/BM
T/MAS
T/STL
T/SLAB
TLT
T&G
TSHD
T&B
T/F
T
TEL
TSTAT
TEMP
TV
SYMB
SYM
SYS
SUSP
SW
SHEET
SOLID CORE
SPEAKER
SOUNDPROOF
STANDARD
SQUARE
SPRINKLER
STAINLESS STEEL
SQUARE FEET
STRUCTURAL CLAY TILE
SUPPLY
STEAM
STEEL JOIST
STORAGE
STEEL
STATION
SPECIFICATION(S)
SMOKE DETECTOR
SIMILAR
SAWCUT JOINT
SECONDARY
SECTION
SCHEDULE
SPKR
STA
SCT
SUP
STL JST
STM
STL
STOR
STD
SST
SPRK
SQ FT
SPEC
SQ
SHT
SNDP
SIM
SECT
SC
SD
SCH
SEC
SJ
JAN JANITOR
KNOCKDOWNKD
KILOGRAMKG
LBS
LVR
LS
POUNDS
LUMP SUM
LOUVER
LIN LINEAR
LH LEFT HAND
M BENDING MOMENT
MBF 1OOO BOARD FEET
MFG MANUFACTURING
MB MARKER BOARD
MEZZ MEZZANINE
MW MICROWAVE
MR MOISTURE RESISTANT
NEC NATIONAL ELECTRIC CODE
NOA NOTICE OF ACCEPTANCE
OPP OPPOSITE
OZ OUNCE
OF OUTSIDE FACE
OA OUTDOOR AIR
PCS PIECES
PLATEPL
PP POWER POLE
SMALLSM
SQUARE INCHSQ IN
SQUARE YARDSQ YD
STRUCTURALSTRUC
TOLERANCETOL
VINYL BASEVB
WIDE(WIDTH)W
YARDYD
COEFFICIENT
LABORATORY
W/
SOUND TRANSMISSION CLASSSTC
J JUNCTION
KIP / 1000 LBK
L LENGTH
LG LARGE
LO
LOC LOCATION
LOCKOUT
LT/GA LIGHT GAGE
LTH LIGHT HAZARD
LT LIGHT
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MC MEDICINE CABINET
MD MOTORIZED DAMPER
MIN MINIMUM
MTD MOUNTED
MT METAL THRESHOLD
MP MIDPOINT
ML METAL LATH
MS MOP SINK
MTR METER
NFA NET FREE AREA
NTS NOT TO SCALE
O ROUND
OAI OUTDOOR AIR INTAKE
ORDINARY HAZARDODH
OJ OPEN WEB JOIST
PC PHOTOCELL
PRECAST CONCRETEPCC
PHASEPH
PREFORMED JOINT FILLERPJF
PFD PREFORMED
POS POSITIVE
PRESTRESSED CONCRETEPSC
POST TENSIONED CONCRETEPTC
PWR POWER
PER UNITPU
PNT POINT
RIGHT
ROUGH OPENING
ROOF VENT
ROOFING
ROOM
RADIUS
RECIRCULATING
RECIPROCATING
REINFORCE(D),
REQUIRED
REVISION
RIGHT OF WAY
RETURN GRILLE
REVOLUTIONS PER MINUTE
RETURN
RETURN AIR
RELATIVE HUMIDITY
REGULAR
RECEIVER
RECEPTACLE
RT
RFG
ROW
RO
RV
RM
REQD
RPM
REV
RET
RG
RA
RH
RECIP
RECIRC
REINF
REG
RECPT
REC
RAD
REFRIGERATORREFG
REFERENCEREF
REINFORCING
RISER
REQUIREMENTREQT
REFLECTED CEILING PLANRCP
REDUCERED
ROOF DRAINRD
ROOF TOP UNITRTU
RAIN PROOFRP
RAIN WATER COLLECTORRWC
RAIN WATER LEADERRWL
S SANITARY
SQUARE FEETSF
SHEATHINGSHTG
STORM DRAINSDN
SQUARE YARDSY
SERVICESERV
TOP OF PIPET/P
TOP OF WALLT/W
TOP OF PLATET/PL
TOWEL RODTR
TRANSOMTRAN
TOILET PARTITIONTPTN
TREADTRD
THREADEDTHRD
TIME CLOCKTC
UNDER COUNTERUCR
VOLTSVA
VERIFY IN FIELDVIF
VINYL FABRICVF
WORK POINTWPT
EXTRA HEAVY
EXTRA STRONG
XHVY
XSTG
DOUBLE EXTRA STRONGXXSTG
DIMENSIONING CONVENTIONS
GENERAL NOTES
SCALE: 1/2" = 1'-0"1
TEMPORARY PARTITION
DETAIL
ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE GENERAL
CONDITIONS OF THE CONTRACT AND THE PROJECT SPECIFICATIONS, INCLUDING THE
REQUIREMENTS OF DIVISION ONE.
ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF
THE INTERNATIONAL BUILDING CODE (IBC 2012), NFPA 101 (2012 EDITION) AND VA HVAC
DESIGN MANUAL.
IN SOME CASES, THE REQUIREMENTS SET FORTH IN THE CONSTRUCTION DRAWINGS
AND SPECIFICATIONS EXCEED THE MINIMUM REQUIREMENTS OF THE CODE.
GENERAL CONTRACTOR SHALL COORDINATE THE SEQUENCING AND EXECUTION OF ALL
TRADES IN STRICT CONFORMANCE WITH THE REQUIREMENTS OF ALL CONSTRUCTION
DRAWINGS AND CONTRACT DOCUMENTS.
GENERAL CONTRACTOR SHALL MAINTAIN & PROTECT FROM DAMAGE ALL PORTIONS OF
THE EXISTING FACILITY SCHEDULED TO REMAIN OR NOT INDICATED FOR DEMOLITION.
ALL DAMAGED AREAS & ELEMENTS SHALL BE REPLACED TO MATCH EXISTING ADJACENT
CONSTRUCTION IN ALL RESPECTS.
GENERAL CONTRACTOR SHALL PROTECT THE PUBLIC FROM CONSTRUCTION ACTIVITIES
AND PROVIDE FOR A SECURE CONSTRUCTION SITE.
GENERAL CONTRACTOR SHALL PROVIDE FOR CUTTING, PATCHING & PAINTING OF ALL
EXTERIOR AND INTERIOR FINISHED SURFACES TO MATCH EXISTING CONDITIONS AS
REQUIRED TO FACILITATE SCOPE OF WORK.
GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CEILING CONDITIONS, TYPES
AND HEIGHT PRIOR TO DEMOLITION. ALL NEW CEILINGS ARE TO BE INSTALLED TO
MATCH EXISTING CONDITIONS UNLESS OTHERWISE NOTED.
PROTECT AND MAINTAIN THE INTERIOR FLOOR FINISHES AND CASEWORK DURING
CONSTRUCTION AND DEMOLITION. DAMAGED FINISHES OR MATERIALS AS A RESULT OF
NEW WORK SHALL BE REPLACED AND/OR REPAIRED AT THE CONTRACTOR'S EXPENSE.
PRIOR TO ANY DEMOLITION, GENERAL CONTRACTOR AND OWNER SHALL WALK THROUGH
THE PROJECT AND ESTABLISH A PUNCHLIST OF EXISTING CONDITIONS. ITEMS NOT
IDENTIFIED AND LATER DAMAGED DUE TO CONSTRUCTION SHALL BE THE CONTRACTOR'S
RESPONSIBILITY.
FIELD VERIFY ALL DIMENSIONS PRIOR TO DEMOLITION WORK. COORDINATE AS
REQUIRED FOR NEW WORK.
ISOLATION BARRIERS SHALL BE HARD WALL TYPE CLOSURES. ZIP-WALL CONSTRUCTION
FOR DUST AND INFECTION CONTROL BARRIERS SHALL NOT BE PERMITTED.
IN LIMITED INSTANCES THE RELOCATION OF A SPRINKLER HEAD MAY BE NECESSARY TO
ACCOMMODATE NEW CONSTRUCTION AND SHALL BE INCLUDED IN THE WORK AS
NECESSARY.
GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CEILING CONDITIONS, TYPES
AND HEIGHT PRIOR TO DEMOLITION. ALL NEW CEILINGS ARE TO BE INSTALLED TO
MATCH EXISTING CONDITIONS UNLESS OTHERWISE NOTED
ALL EXISTING WALLS TO REMAIN & SHALL BE PROTECTED FROM DAMAGE. PATCH AND
PAINT WALLS TO MATCH EXISTING AS REQUIRED TO MATCH EXISTING FINISHES.
COORDINATE WITH ALL TRADES.
ALL PENETRATIONS THROUGH WALLS SHALL BE PATCHED TO MATCH WALL FINISH AFTER
REMOVAL OF DUCTWORK, PIPING, CONDUIT, ETC.
ALL ABANDONED WALL PENETRATIONS ABOVE THE CEILING AT EXISTING FIRE RATED OR
SMOKE BARRIER WALLS SHALL BE SEALED WITH UL DETAIL U419 1, 2, 3 OR 4 HOUR
NONBEARING WALL SYSTEM AFTER DEMOLITION OF DUCTWORK, PIPING & CONDUIT.
REFERENCE DETAIL THIS SHEET.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
PROJECT NAME: BAY PINES VA - REPLACE AIR CONDITIONING SYSTEM IN B-102
VA PROJECT #: 516-11-108
L/A PROJECT #: 201140
SCOPE OF WORK:
REPLACE AIR CONDITIONING SYSTEMS THROUGHOUT SUPPORT BUILDING.
PHASING:
PHASE I: BUILDINGS C & D (NIC)
BUILDINGS C & D HVAC REPLACEMENT PROJECT WILL COMMENCE ONCE OCCUPANTS MOVE INTO THE
MENTAL HEALTH BUILDING.
START DATE: TO BE DETERMINED; BASED ON THE ACTIVATION OF THE MENTAL HEALTH BUILDING
PHASE II. BUILDING A (NIC)
BUILDING A WILL MOVE INTO BUILDING D ONCE WORK IS COMPLETED PER ABOVE PHASE 1, AND INTERIOR IS
RENOVATED PER ITEM 3 BELOW.
START DATE: TO BE DETERMINED
PHASE III. BUILDING B (NIC)
BUILDING A WILL MOVE INTO BUILDING 1 ONCE BUILDING 1 IS RENOVATED UNDER THE MENTAL HEALTH
ADDITION PROJECT.
START DATE: TO BE DETERMINED, AND WILL BE BASED ON THE RENOVATION AND ACTIVATION OF BUILDING 1
UNDER THE MENTAL HEALTH ADDITION PROJECT
PHASE IV. SUPPORT BUILDING "SB"
WORK IN THIS AREA WILL BE PHASED TO MAINTAIN FACILITY OPERATIONS.
PROJECT DESCRIPTION
NONBEARING WALL
RATINGS - 1, 2, 3 OR 4 HOUR
PARTITION PENETRATION NOTES
1. REFER TO UL UNDERWRITERS LABORATORIES INC. DIRECTORY LATEST EDITION FOR SPECIFIC REQUIREMENTS FOR EACH U.L. DESIGN INDICATED. CONTRACTOR SHALL PREPARE & SUBMIT ALL NECESSARY & SPECIFIC UL LISTED SYSTEMS FOR PENETRATIONS OF THE UTILITIES THROUGH FIRE
RATED & SMOKE BARRIER WALLS DURING THE SHOP DRAWING PROCESS FROM A SINGLE
MANUFACTURER.
2. ALL PENETRATIONS THROUGH SMOKE BARRIER WALLS SHALL BE SEALED AIRTIGHT ALL AROUND, NO EXCEPTIONS. VERIFY ALL EXISTING SMOKE BARRIER WALLS ARE SEALED TO DECK AS REQUIRED.
NOTE:
THE TERM "TYPICAL" SHALL BE DEFINED IN THESE DRAWINGS AS:
IN EACH SIMILAR CASE WHETHER INDIVIDUALLY IDENTIFIED BY NOTATION OR NOT, AND IN OCCURRENCES WHERE THE TYPICAL KEYNOTED ITEM IS SHOWN MAY NOT IDENTIFY ALL OCCURRENCES. ALL OCCURRENCES ARE TO BE FIELD VERIFIED. THE KEYNOTED ITEM IS SHOWN FOR REFERENCE AND APPLIES TO ALL OTHER
SIMILAR OCCURRENCES.
SCALE: 1 1/2" = 1'-0"2 UL DETAIL U419
Issue & Revision Schedule
No. Description Date
FINAL CONSTRUCTION DOCUMENTS 01/23/15
NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR
CONFLICTS WHICH ARE ALLEGED.
COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
UL DESIGN # W-L-2029
1 & 2 HR FRAMING, 2" PVC PIPE
UL DESIGN # W-L-1089
1 & 2 HR FRAMING, METALLIC PIPE
PARTITION PENETRATION NOTES
REFER TO UL UNDERWRITERS LABORATORIES
INC. DIRECTORY LATEST EDITION FOR SPECIFIC
REQUIREMENTS FOR EACH U.L. DESIGN
INDICATED. CONTRACTOR SHALL PREPARE &
SUBMIT ALL NECESSARY & SPECIFIC UL LISTED
SYSTEMS FOR PENETRATIONS OF THE UTILITIES
THROUGH FIRE RATED & SMOKE STOP WALLS
DURING THE SHOP DRAWING PROCESS FROM A
SINGLE MANUFACTURER
ALL PENETRATIONS THROUGH A SMOKE-STOP
PARTITION SHALL BE SEALED AIRTIGHT ALL
AROUND, NO EXCEPTIONS. VERIFY ALL EXISTING
SMOKE-STOP WALLS ARE SEALED TO DECK AS
REQUIRED
ELEV
UL DESIGN # W-L-1093
1 & 2 HR FRAMING, MULTI-METALLIC
UL DESIGN # W-L-5001
1 & 2 HR FRAMING, INSUL METALLIC
ELEV
UL DESIGN # W-L-7008
1 & 2 HR FRAMING, METALLIC DUCT
ELEV
UL DESIGN # W-J-7002
2 HR BLK, METALLIC DUCT
UL DESIGN # W-J-5007
1 & 2 HR BLK, INSUL METALLIC
UL DESIGN # W-J-2019
1 & 2 HR BLK, NON METALLIC
UL DESIGN # W-J-1028
1 & 2 HR D-2 BLK, METALLIC
ELEV
UL DESIGN # W-J-1033
1 & 2 HR BLK, MULTI-METALLIC
UL DESIGN # W-L-2003
1 & 2 HR FRAMING, 2" PVC PIPE
FIRE CAULK SEALANT
1 HR RATED WALL 5/8" TYPE
"X" GYP BD W/ 3 5/8" MTL
STUDS @16" O.C. (2) LAYERS
FOR (2) HR WALL EA. SIDE
4" PVC PIPE OR SMALLER
FIRESTOP DEVICE GALV
STEEL COLLAR W/
FASTENERS
1 HR RATED WALL 5/8" TYPE
"X" GYP BD W/ 3 5/8" MTL
STUDS 16" O.C. (2) LAYERS
FOR (2) HR WALL EA.SIDE
6" COPPER PIPE , 4"
CONDUIT, 24"
STEEL PIPE OR SMALLER
MINERAL WOOL PACKING
FIRE CAULK SEALANT
2 LAYERS OF 5/8"
TYPE "X" GYP
BD BUILD-UP
2" STEEL PIPE 2
IRON PIPE
2" CONDUIT OR
SMALLER
FIRE CAULK SEALANT
6" COPPER PIPE, 12" STEEL PIPE OR
SMALLER W/ GLASS INSULATION
FIRE CAULK SEALANT
1 HR RATED WALL 5/8" TYPE "X" GYP
BD W/ 3 5/8" MTL STUDS @ 16" O.C. (2)
LAYERS FOR (2) HR WALL EA. SIDE
STEEL VENT
DUCT
FIRE CAULK
SEALANT
ALONG
PERIMETER
STEEL RETAINING
ANGLE
NOTE
PROVIDE TOP AND
BOTTOM TRACK
LIGHT GAGE
FRAMING AROUND
PERIMETER OF
DUCTWORK TO
SECURE GYP BD
8" CONC.
RATED BLK.
STEEL VENT
DUCT
FIRE CAULK
SEALANT
ALONG
PERIMETER
STEEL RETAINING
ANGLE
4" COPPER PIPE, 4" STEEL
PIPE, OR SMALLER W/
GLASS INSULATION
8" CONC. BLK
FIRE CAULK SEALANT
2" PVC OR CPVC PIPE
OR SMALLER
RATED CMU
FIRE CAULK SEALANT
10" STEEL PIPE OR
SMALLER & 4" METALLIC
PIPE OR SMALLER
RATED CMU
FIRE CAULK SEALANT
2 LAYERS OF
5/8" TYPE
"X" GYP BD
BUILD-UP
FIRE CAULK SEALANT
RATED CMU
2" STEEL PIPE 2" IRON
PIPE 2" CONDUIT OR
SMALLER
1 HR RATED WALL 5/8" TYPE
"X" GYP BD W/ 3 5/8" MTL
STUDS @ 16" O.C. (2) LAYERS
FOR (2) HR WALL EA. SIDE
FIRE CAULK SEALANT &
WRAP STRIP
2" PVC TUBE OR SMALLER
1 HR RATED WALL 5/8"
TYPE "X" GYP BD W/ 3
5/8" MTL STUDS @ 16"
O.C. (2) LAYERS FOR
(2) HR WALL EA. SIDE
1 HR RATED WALL 5/8"
TYPE "X" GYP BD W/ 3
5/8" MTL STUDS @ 16"
O.C. (2) LAYERS FOR (2)
HR WALL EA. SIDE
PIPE PENETRATION
SCALE: 3" = 1' - 0"
PIPE PENETRATION
SCALE: 3" = 1' - 0"
UL DESIGN # W-J-1226
3 HR BLK, METALLIC
UL DESIGN #W-J-2190
3 HR BLK, NON METALLIC
2" PVC TUBING OR
SMALLER
RATED CMU
FIRE CAULK SEALANT
4" OR SMALLER METALLIC
PIPE OR CONDUIT
RATED CMU
FIRE CAULK SEALANT
1.
2.
THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION
WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED
4525 S. Manhattan Ave. Tampa, FL 33611-2305
T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991
w w w . l o n g a n d a s s o c i a t e s . c o m
Checked By:
Seal
ALEXANDER M. LONG, A.I.A.
AR 0015104
987654321
B C
D E
F A
98765431 2
A th re e in c h e s o n e fo o t
B
C
D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t
E o n e h a lf in c h o n e fo o t
F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B A Y
P
IN
E S
M E D
IC
A L C E N
TE
R
Drawn By:Approved Division Chief
DIVISION CHIEF
Drawing Title
Approved Service Director
SERVICE DIRECTOR
Location
Building Number
Dwg. Of.
Date
Project No.
Project Title
DRAWING NO.
To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards
:2
:5
P M
AML
01/23/15
G0.3
REPLACE AIR CONDITIONING
SYSTEMS IN B-102
SUPPORT BUILDING
VAMC BAY PINES, FLORIDA 33744
TGS
PARTITION PENETRATION DETAILS
516-11-108
Issue & Revision Schedule
No. Description Date
FINAL CONSTRUCTION DOCUMENTS 01/23/15
NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR
CONFLICTS WHICH ARE ALLEGED.
COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY
FOR CONTINUATION OF CORRIDOR,
SEE DRAWING 5/LS1.1
FOR CONTINUATION OF CORRIDOR,
SEE DRAWING 3/LS1.1
FOR CONTINUATION OF CORRIDOR,
SEE DRAWING 2/LS1.1
FOR CONTINUATION
OF CORRIDOR, SEE
DRAWING 4/LS1.1
158 SF
OFFICE
114 SF
OFFICE
143 SF
OFFICE
151 SF
OFFICE
39 SF
TOILET
39 SF
TOILET
103 SF
RECEPTION
101A
217 SF
OFFICE & MAIL
10 SF
CLOSET
105A
9 SF
CLOSET
132A
7 SF
CLOSET
943 SF
CONF ROOM
306 SF
CONF ROOM
111 SF
CLINIC
146 SF
LOCKER ROOM
133 SF
STORAGE
408 SF
REC THERAPY OFFICES
227 SF
CLINIC
27 SF
TEL
117 SF
OFFICE
102 SF
WALK-IN
422 SF
CORRIDOR
CE-3
196 SF
OFFICE
197 SF
BREAK ROOM
301 SF
DISHWASHING
429 SF
BLDG MGMT STORAGE
121 SF
JANITOR
1126 SF
MECHANICAL
405 SF
ELECTRICAL
228 SF
EMER GEN
425 SF
DIETARY SERVICE
3884 SF
DINING AREA
677 SF
GROUP ROOM
63 SF
TOILET
72 SF
TOILET
119 SF
OFFICE
109A
1298 SF
REC ROOM
829 SF
REC ROOM
107A
388 SF
GROUP ROOM
107B
17 SF
CLOSET
106A
17 SF
CLOSET
106B
24 SF
CLOSET
106C
16 SF
CLOSET
107C
16 SF
CLOSET
107D
16 SF
CLOSET
107E
16 SF
CLOSET
107F
43 SF
HAC
292 SF
CORRIDOR
CE-2
1051 SF
CORRIDOR
CE-1
1151 SF
CORRIDOR
CE-4
380 SF
CORRIDOR C
CE-C
762 SF
CORRIDOR D
CE-D
380 SF
CORRIDOR A
CE-A
719 SF
CORRIDOR B
CE-B
93 SF
OFFICE
109B
225 SF
SERVING LINE
113A
236 SF
LOBBY
49 SF
STORAGE
127A
LS005
LS006LS006
LS005
LS004LS004
LS002
LS002
LS010
LS002
50 SF
HAC
114A
TRAVEL DISTANCE: 129'-0"
LS007LS007
LS099LS099
TRAVEL DISTANCE: 154'-0"
LS010
LS010
LS010
LS002
CODE COMPLIANCE
ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE REQUIREMENTS
OF THE FOLLOWING CODES:
INTERNATIONAL BUILDING CODE, 2012 EDITION
NFPA 101 LIFE SAFETY CODE, 2012 EDITION
CONSTRUCTION TYPE (IBC TABLE 601): TYPE II-B UNPROTECTED
(SPRINKLED)
OCCUPANCY CLASSIFICATION (NFPA 6.1.11): BUSINESS
EXISTING RENOVATION AREA: 7,742 S.F.
OCCUPANT LOAD (NFPA TABLE 7.3.1.2): 7,742/100 GROSS = 77 PERSONS
OCCUPANCY CLASSIFICATION (NFPA 6.1.2): ASSEMBLY
EXISTING RENOVATION AREA: 9,020 S.F.
OCCUPANT LOAD (NFPA TABLE 7.3.1.2): 9,020/15 NET = 600 PERSONS
TOTAL OCCUPANT LOAD: 77 + 600 = 677 PERSONS
TRAVEL DISTANCE (NFPA 19.2.5.7.2.3(B)(2)): 200'-0" MAX
COMMON PATH OF TRAVEL (NFPA 39.2.5.3.1): 100'-0" MAX
DEAD END CORRIDOR (NFPA 19.2.5.2): 30'-0" MAX
REQUIRED EGRESS WIDTH (NFPA 19.2.3.4): 48" MIN
FIRE RESISTANCE RATING (IBC TABLE 601):
PARTITIONS 0 HOUR
BEARING WALLS: 0 HOUR
FLOOR SEPARATION: 0 HOUR
ROOF CONSTRUCTION: 0 HOUR
STRUCTURAL FRAME: 0 HOUR
CORRIDORS (NFPA 19.3.6.2.4):
EXISTING HEALTH CARE OCCUPANCY WITH AN AUTOMATIC SPRINKLER SYSTEM -
SMOKE COMPARTMENT SEPARATION NOT REQUIRED TO BE FIRE RATED, BUT WALLS
MUST BE CONSTRUCTED TO RESIST THE PASSAGE OF SMOKE
GENERAL LIFE SAFETY NOTES
A. PORTIONS OF THE BUILDING SHALL MAINTAIN OPERATION THROUGHOUT
DEMOLITION & NEW WORK AS REQUIRED. THE WORK SHALL BE PHASED IN
ORDER TO MAINTAIN OPERATION AS REQUIRED, SEE PHASING PLAN.
COORDINATE ALL PHASING WITH OWNER
B. THIS PROJECT WAS REVIEWED BASED ON THE ABOVE CODE INFORMATION.
A FULL CORRECTION OF THIS BUILDING TO THE 2010 FBC IS IS BEYOND THE
SCOPE OF WORK AND IS NOT INCLUDED SUPPORT BLDG
WORK AREA
B
A
D
C
CORRIDOR A
CE-A
LS003 LS002
LS009LS009
LS010
CORRIDOR C
CE-C
LS002 LS003
LS010
LS009LS009
CORRIDOR B
CE-B
LS003
LS002
LS009LS009
LS010
CORRIDOR D
CE-D
LS003
LS002
LS009LS009
LS010
EXISTING TWO HOUR FIRE-RATED PARTITION
LIFE SAFETY LEGEND
EXISTING SMOKE STOP PARTITION
PRIMARY EXIT WAY
SECONDARY EXIT WAY
EXISTING THREE HOUR FIRE-RATED PARTITION
EXISTING PARTITION
EGRESS TRAVEL DISTANCE
EXISTING ONE HOUR FIRE-RATED PARTITION
NOT AN EXIT
2' - 0"
5'
- 0
8" NOT AN EXIT
TEMPORARY SIGN W/
3" GRAPHIC LETTERING
CENTERED ON EACH
DOOR LEAF
SCALE: 1/8" = 1'-0"1
SUPPORT BUILDING
LIFE SAFETY PLAN
THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION
WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED
4525 S. Manhattan Ave. Tampa, FL 33611-2305
T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991
w w w . l o n g a n d a s s o c i a t e s . c o m
Checked By:
Seal
ALEXANDER M. LONG, A.I.A.
AR 0015104
987654321
B C
D E
F A
98765431 2
A th re e in c h e s o n e fo o t
B
C
D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t
E o n e h a lf in c h o n e fo o t
F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B A Y
P
IN
E S
M E D
IC
A L C E N
TE
R
Drawn By:Approved Division Chief
DIVISION CHIEF
Drawing Title
Approved Service Director
SERVICE DIRECTOR
Location
Building Number
Dwg. Of.
Date
Project No.
Project Title
DRAWING NO.
To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards
:2
:0
P M
AML
01/23/15
LS1.1
REPLACE AIR CONDITIONING
SYSTEMS IN B-102
SUPPORT BUILDING
VAMC BAY PINES, FLORIDA 33744
TGS
LIFE SAFETY PLAN
516-11-108
KEYNOTE LEGEND
NO. DESCRIPTION
LS002 EXISTING SMOKESTOP PARTITION. PROVIDE CONSTRUCTION
LOCKSET AT EXISTING DOORS AND AIR BARRIER FOR
DURATION OF DEMOLITION AND NEW WORK. SEE DETAIL 1 ON
SHEET G0.2
LS003 PROVIDE AIR BARRIER FOR DURATION OF DEMOLITION AND
NEW WORK. SEE DETAIL 1 ON SHEET G0.2
LS004 EXISTING 1-HR FIRE RATED PARTITION TO PROTECT &
MAINTAIN
LS005 EXISTING 2-HR FIRE RATED PARTITION TO PROTECT &
MAINTAIN
LS006 EXISTING 3-HR FIRE RATED PARTITION TO PROTECT &
MAINTAIN
LS007 PROVIDE & CONFIRM THIS PORTION OF WALL IS 1 HOUR FIRE
RATED EQUAL TO UL#U465 OR MADE AS SUCH FOR THE
REQUIRED FIRE RATING
LS009 PROVIDE DOOR AT AIR BARRIER WITH TEMPORARY SIGN FOR
THE DURATION OF DEMOLITION AND NEW WORK. TEMPORARY
SIGN SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE
BUILDING SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR
SIDE.
LS010 PROVIDE TEMPORARY SIGN AT EXISTING DOORS FOR THE
DURATION OF DEMOLITION AND NEW WORK. TEMPORARY SIGN
SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE BUILDING
SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR SIDE.
LS099 SEE GENERAL NOTES ON SHEET G0.2 FOR ADDITIONAL NOTES
N
0' 4' 8' 16'
SCALE: NTS
B-102 KEY PLAN
SCALE: 1/8" = 1'-0"2
CORRIDOR A
LIFE SAFETY PLAN
SCALE: 1/8" = 1'-0"3
CORRIDOR C
LIFE SAFETY PLAN
SCALE: 1/8" = 1'-0"4
CORRIDOR B
LIFE SAFETY PLAN
SCALE: 1/8" = 1'-0"5
CORRIDOR D
LIFE SAFETY PLAN
SCALE: 1/2" = 1'-0"
TEMPORARY SIGN DETAIL
NOTE:
THE TERM "TYPICAL" SHALL BE DEFINED IN THESE DRAWINGS AS:
IN EACH SIMILAR CASE WHETHER INDIVIDUALLY IDENTIFIED BY NOTATION OR
NOT, AND IN OCCURRENCES WHERE THE TYPICAL KEYNOTED ITEM IS SHOWN
MAY NOT IDENTIFY ALL OCCURRENCES. ALL OCCURRENCES ARE TO BE FIELD
VERIFIED. THE KEYNOTED ITEM IS SHOWN FOR REFERENCE AND APPLIES TO
ALL OTHER SIMILAR OCCURRENCES.
Issue & Revision Schedule
No. Description Date
FINAL CONSTRUCTION DOCUMENTS 01/23/15
NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR
CONFLICTS WHICH ARE ALLEGED.
COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY
SUPPORT BLDG
WORK AREA
B
A
D
C
158 SF
OFFICE
114 SF
OFFICE
143 SF
OFFICE
151 SF
OFFICE
39 SF
TOILET
39 SF
TOILET
103 SF
RECEPTION
101A
217 SF
OFFICE & MAIL
10 SF
CLOSET
105A
9 SF
CLOSET
132A
7 SF
CLOSET
943 SF
CONF ROOM
306 SF
CONF ROOM
111 SF
CLINIC
38 SF
STORAGE
146 SF
LOCKER ROOM
133 SF
STORAGE
408 SF
REC THERAPY OFFICES
227 SF
CLINIC
27 SF
TEL
117 SF
OFFICE
102 SF
WALK-IN
422 SF
CORRIDOR
CE-3
196 SF
OFFICE
197 SF
BREAK ROOM
301 SF
DISHWASHING
50 SF
HAC
114A
429 SF
BLDG MGMT STORAGE
121 SF
JANITOR
1126 SF
MECHANICAL
405 SF
ELECTRICAL
228 SF
EMER GEN
425 SF
DIETARY SERVICE
3884 SF
DINING AREA
677 SF
GROUP ROOM
63 SF
TOILET
72 SF
TOILET
31 SF
OFFICE
109B
119 SF
OFFICE
109A
1298 SF
REC ROOM
829 SF
REC ROOM
107A
388 SF
GROUP ROOM
107B
17 SF
CLOSET
106A
17 SF
CLOSET
106B
24 SF
CLOSET
106C
16 SF
CLOSET
107C
16 SF
CLOSET
107D
16 SF
CLOSET
107E
16 SF
CLOSET
107F
43 SF
HAC
292 SF
CORRIDOR
CE-2
1051 SF
CORRIDOR
CE-1
1151 SF
CORRIDOR
CE-4
380 SF
CORRIDOR C
CE-C
762 SF
CORRIDOR D
CE-D
380 SF
CORRIDOR A
CE-A
719 SF
CORRIDOR
CE-B
225 SF
SERVING LINE
113A
236 SF
LOBBY
49 SF
STORAGE
127A
FOR CONTINUATION OF CORRIDOR,
SEE DRAWING 5/DA1.1
FOR CONTINUATION OF CORRIDOR,
SEE DRAWING 3/DA1.1
FOR CONTINUATION OF CORRIDOR,
SEE DRAWING 2/DA1.1
FOR CONTINUATION
OF CORRIDOR, SEE
DRAWING 4/DA1.1
DA136
DA102
DA136
DA136
DA132 DA133
DA199DA199
DA102
DA136
DA102
DA102
CORRIDOR A
CE-A
DA103 DA136DA135DA103 /
DA102
CORRIDOR C
CE-C
DA102 DA103DA103DA135 /
DA136
CORRIDOR
CE-B
DA103
DA102
DA103DA135 /
DA136
CORRIDOR D
CE-D
DA103
DA102
DA135
DA136
EXISTING TWO HOUR FIRE-RATED PARTITION
WALL LEGEND
EXISTING SMOKE STOP PARTITION
EXISTING THREE HOUR FIRE-RATED PARTITION
EXISTING PARTITION
EXISTING ONE HOUR FIRE-RATED PARTITION
THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION
WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED
4525 S. Manhattan Ave. Tampa, FL 33611-2305
T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991
w w w . l o n g a n d a s s o c i a t e s . c o m
Checked By:
Seal
ALEXANDER M. LONG, A.I.A.
AR 0015104
987654321
B C
D E
F A
98765431 2
A th re e in c h e s o n e fo o t
B
C
D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t
E o n e h a lf in c h o n e fo o t
F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B A Y
P
IN
E S
M E D
IC
A L C E N
TE
R
Drawn By:Approved Division Chief
DIVISION CHIEF
Drawing Title
Approved Service Director
SERVICE DIRECTOR
Location
Building Number
Dwg. Of.
Date
Project No.
Project Title
DRAWING NO.
To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards
:0
:3
P
M
AML
01/23/15
DA1.1
REPLACE AIR CONDITIONING
SYSTEMS IN B-102
SUPPORT BUILDING
VAMC BAY PINES, FLORIDA 33744
TGS
DEMOLITION FLOOR PLAN
516-11-108
DEMOLITION NOTES
NO. DESCRIPTION
DA102 EXISTING SMOKESTOP PARTITION. PROVIDE CONSTRUCTION
LOCKSET AT EXISTING DOORS AND AIR BARRIER FOR DURATION
OF DEMOLITION AND NEW WORK. SEE DETAIL 1 ON SHEET G0.2
DA103 PROVIDE AIR BARRIER FOR DURATION OF DEMOLITION AND NEW
WORK. SEE DETAIL 1 ON SHEET G0.2
DA132 EXISTING FLOOR FINISHES ARE TO BE PROTECTED DURING
DEMOLITION & CONSTRUCTION WITH LAYER OF 1/8" MASONITE
TAPED TO EXISTING FLOOR CONTINUOUS THROUGHOUT AREA OF
WORK MIN, TYPICAL
DA133 ALL INTERIOR FINISHES, WALLS, SURFACES, DOORS & ITEMS TO
REMAIN SHALL BE PROTECTED & MAINTAINED. WALLS DAMAGED
DURING CONSTRUCTION SHALL BE PATCHED & PAINTED TO
MATCH EXISTING UPON COMPLETION OF NEW WORK, TYPICAL
FOR ENTIRE AREA.
DA135 PROVIDE DOOR AT AIR BARRIER WITH TEMPORARY SIGN FOR THE
DURATION OF DEMOLITION AND NEW WORK. TEMPORARY SIGN
SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE BUILDING
SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR SIDE.
DA136 PROVIDE TEMPORARY SIGN AT EXISTING DOORS FOR THE
DURATION OF DEMOLITION AND NEW WORK. TEMPORARY SIGN
SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE BUILDING
SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR SIDE.
DA199 SEE GENERAL NOTES ON SHEET G0.2 FOR ADDITIONAL NOTES
SCALE: NTS
B-102 KEY PLAN
SCALE: 1/8" = 1'-0"1
SUPPORT BUILDING
DEMOLITION FLOOR PLAN
N
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"2
CORRIDOR A
DEMOLITION FLOOR PLAN
SCALE: 1/8" = 1'-0"3
CORRIDOR C
DEMOLITION FLOOR PLAN
SCALE: 1/8" = 1'-0"4
CORRIDOR B
DEMOLITION FLOOR PLAN
SCALE: 1/8" = 1'-0"5
CORRIDOR D
DEMOLITION FLOOR PLAN
NOTE:
THE TERM "TYPICAL" SHALL BE DEFINED IN THESE DRAWINGS AS:
IN EACH SIMILAR CASE WHETHER INDIVIDUALLY IDENTIFIED BY NOTATION OR NOT,
AND IN OCCURRENCES WHERE THE TYPICAL KEYNOTED ITEM IS SHOWN MAY NOT
IDENTIFY ALL OCCURRENCES. ALL OCCURRENCES ARE TO BE FIELD VERIFIED. THE
KEYNOTED ITEM IS SHOWN FOR REFERENCE AND APPLIES TO ALL OTHER SIMILAR
OCCURRENCES.
Issue & Revision Schedule
No. Description Date
FINAL CONSTRUCTION DOCUMENTS 01/23/15
NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR
CONFLICTS WHICH ARE ALLEGED.
COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY
SEE DRAWING 5/DA3.1
FOR CONTINUATION OF CORRIDOR,
SEE DRAWING 3/DA3.1
FOR CONTINUATION OF CORRIDOR,
SEE DRAWING 2/DA3.1
FOR
CONTINUATION
OF CORRIDOR,
SEE DRAWING
4/DA3.1DA108DA108
DA110
DA110
DA110
DA110
DA110DA110DA110DA110
DA110
DA128DA128 DA128
DA128
DA128
DA128
DA128
DA129
DA129
DA129
DA129
DA109DA109
DA109
DA109
DA132DA199 DA133/
DA134
GYP BD CEILING OR
AND ACOUSTICAL PANEL
2'x2' SUSPENDED CEILING GRID
STRIP LIGHT FIXTURE
FLUORESCENT INDUSTRIAL OR
DOWN LIGHT FIXTURE
SURFACE OR RECESSED
WALL MOUNTED
LIGHT FIXTURE
EXIT SIGN
EMERGENCY
SUPPLY AIR DIFFUSER
RETURN EXHAUST GRILLE
SMOKE DETECTORS
SURFACE FLUORESCENT
1'x4' LIGHT FIXTURE
OPEN-PAINTED FINISH
CURTAIN TRACK
PENDENT SPRINKLER HEAD
CANOPY METAL INSULATED
UPRIGHT SPRINKLER HEAD
SOFFIT DROP
ROOF DECK SYSTEM
SURFACE FLUORESCENT
2'X 4' LIGHT FIXTURE
EMERGENCY
FIRE ALARM SPEAKER
CEILING MOUNTED
SF
STRIP LIGHT FIXTURE
RECESSED FLUORESCENT
FLUORESCENT INDUSTRIAL OR
SURFACE FLUORESCENT
RECESSED FLUORESCENT
2'x4' LIGHT FIXTURE
2'x4' LIGHT FIXTURE
2'X 4' LIGHT FIXTURE
EMERGENCY
EXHAUST FAN
PENDANT FIXTURES
EMERGENCY PENDANT FIXTURES
RECESSED DOWN LIGHT FIXTURE
EMERGENCY SURFACE OR
PENDENT CONCEALED
SPRINKLER HEAD
POWER POLE
ACCESS PANEL
REFLECTED CEILING PLAN LEGEND
SUPPORT BLDG
WORK AREA
B
A
D
C
DA103DA103 DA135 DA102 DA136
DA103DA103DA135 /DA102
DA136
DA103DA103
DA102
DA136
DA135
DA135 /
DA103DA103DA135 /
DA102 DA136
THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION
WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED
4525 S. Manhattan Ave. Tampa, FL 33611-2305
T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991
w w w . l o n g a n d a s s o c i a t e s . c o m
Checked By:
Seal
ALEXANDER M. LONG, A.I.A.
AR 0015104
987654321
B C
D E
F A
98765431 2
A th re e in c h e s o n e fo o t
B
C
D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t
E o n e h a lf in c h o n e fo o t
F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B A Y
P
IN
E S
M E D
IC
A L C E N
TE
R
Drawn By:Approved Division Chief
DIVISION CHIEF
Drawing Title
Approved Service Director
SERVICE DIRECTOR
Location
Building Number
Dwg. Of.
Date
Project No.
Project Title
DRAWING NO.
To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards
:0
:4
P
M
AML
01/23/15
DA3.1
REPLACE AIR CONDITIONING
SYSTEMS IN B-102
SUPPORT BUILDING
VAMC BAY PINES, FLORIDA 33744
TGS
DEMOLITION REFLECTED CEILING
PLAN
516-11-108
SCALE: 1/8" = 1'-0"1
SUPPORT BUILDING
DEMOLITION
REFLECTED CEILING PLAN
SCALE: NTS
B-102 KEY PLAN
DEMOLITION NOTES
NO. DESCRIPTION
DA102 EXISTING SMOKESTOP PARTITION. PROVIDE CONSTRUCTION
LOCKSET AT EXISTING DOORS AND AIR BARRIER FOR DURATION
OF DEMOLITION AND NEW WORK. SEE DETAIL 1 ON SHEET G0.2
DA103 PROVIDE AIR BARRIER FOR DURATION OF DEMOLITION AND NEW
WORK. SEE DETAIL 1 ON SHEET G0.2
DA108 REMOVE EXISTING 2 X 4 ACOUSTIC CEILING IN ITS ENTIRETY,
TYP. SEE ELECTRICAL & MECHANICAL DEMOLITION DRAWINGS
FOR REMOVAL OF LIGHTS, FANS AND MECHANICAL DIFFUSERS.
THIS APPLIES TO ALL AREAS ON THE DRAWINGS.
DA109 REMOVE EXISTING FIRE PROTECTION SPRINKLER HEADS, TYP.
SEE FIRE PROTECTION DRAWINGS FOR DEDUCTIVE ALTERNATE.
COORDINATE ALL WORK WITH FIRE PROTECTION DRAWINGS.
BUILDING SHALL REMAIN FIRE PROTECTED DURING
CONSTRUCTION. COORDINATE AS REQUIRED.
DA110 ALL EXISTING GYPSUM BOARD CEILINGS & SOFFITS SHALL BE
PROTECTED & MAINTAINED. ANY DISTURBED SHALL BE PATCHED
AND FINISHED TO MATCH EXISTING CONSTRUCTION, TYPICAL.
DA128 CAREFULLY REMOVE EXISTING CONVEX MIRROR AND STORE
FOR REINSTALLATION IN SAME LOCATION AS PART OF NEW
WORK, TYPICAL
DA129 CAREFULLY REMOVE EXISTING CEILING MOUNTED SIGNAGE.
STORE FOR REINSTALLATION IN SAME LOCATION AS PART OF
NEW WORK, TYPICAL
DA132 EXISTING FLOOR FINISHES ARE TO BE PROTECTED DURING
DEMOLITION & CONSTRUCTION WITH LAYER OF 1/8" MASONITE
TAPED TO EXISTING FLOOR CONTINUOUS THROUGHOUT AREA
OF WORK MIN, TYPICAL
DA133 ALL INTERIOR FINISHES, WALLS, SURFACES, DOORS & ITEMS TO
REMAIN SHALL BE PROTECTED & MAINTAINED. WALLS DAMAGED
DURING CONSTRUCTION SHALL BE PATCHED & PAINTED TO
MATCH EXISTING UPON COMPLETION OF NEW WORK, TYPICAL
FOR ENTIRE AREA.
DA134 EXISTING EXHAUST HOOD TO REMAIN
DA135 PROVIDE DOOR AT AIR BARRIER WITH TEMPORARY SIGN FOR
THE DURATION OF DEMOLITION AND NEW WORK. TEMPORARY
SIGN SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE
BUILDING SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR
SIDE.
DA136 PROVIDE TEMPORARY SIGN AT EXISTING DOORS FOR THE
DURATION OF DEMOLITION AND NEW WORK. TEMPORARY SIGN
SHALL READ "NOT AN EXIT" AND BE LOCATED ON THE BUILDING
SIDE OF THE DOOR, AS OPPOSED TO THE CORRIDOR SIDE.
DA199 SEE GENERAL NOTES ON SHEET G0.2 FOR ADDITIONAL NOTES
N
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"2
CORRIDOR A DEMOLITION
REFLECTED CEILING PLAN
SCALE: 1/8" = 1'-0"3
CORRIDOR C DEMOLITION
REFLECTED CEILING PLAN
SCALE: 1/8" = 1'-0"4
CORRIDOR B DEMOLITION
REFLECTED CEILING PLAN
SCALE: 1/8" = 1'-0"5
CORRIDOR D DEMOLITION
REFLECTED CEILING PLAN
NOTE:
THE TERM "TYPICAL" SHALL BE DEFINED IN THESE DRAWINGS AS:
IN EACH SIMILAR CASE WHETHER INDIVIDUALLY IDENTIFIED BY NOTATION OR NOT,
AND IN OCCURRENCES WHERE THE TYPICAL KEYNOTED ITEM IS SHOWN MAY NOT
IDENTIFY ALL OCCURRENCES. ALL OCCURRENCES ARE TO BE FIELD VERIFIED. THE
KEYNOTED ITEM IS SHOWN FOR REFERENCE AND APPLIES TO ALL OTHER SIMILAR
OCCURRENCES.
Issue & Revision Schedule
No. Description Date
FINAL CONSTRUCTION DOCUMENTS 01/23/15
NOTICE: BAY PINES VAHCS WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FIELD VERIFY THE ACCURACY OF THE INFORMATION BEING PROVIDED AND THE INTENT IT CONVEYS, OR FOR PROBLEMS WHICH ARISE FROM FAILURE TO OBTAIN AND/OR FOLLOW THE ENGINEERS GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES OR
CONFLICTS WHICH ARE ALLEGED.
COPYRIGHT: COPYRIGHT AND PROPERTY RIGHTS IN THESE DOCUMENTS ARE EXPRESSLY RESERVED BY
SEE DRAWING 5/DA4.1
FOR CONTINUATION OF CORRIDOR,
SEE DRAWING 3/DA4.1
FOR CONTINUATION OF CORRIDOR,
SEE DRAWING 2/DA4.1
FOR
CONTINUATION
OF CORRIDOR,
SEE DRAWING
4/DA4.1
DA006
DA006
DA006
DA006
DA006
DA006
DA006
DA006DA006
DA006
DA006
DA006
DA007
DA007
DA007
DA007
DA006
DA199DA199
DA018
DA017
DA016
DA016
DA019
DA007
DA020
DA020
PROVIDE ALL NECESSARY TEMPORARY
SERVICES AND SYSTEM ISOLATIONS TO
ACCOMODATE PROJECT PHASING. REFER
TO ARCHITECTURE PHASING PLAN.
SUPPORT BLDG
WORK AREA
B
A
D
C
NO NEW
WORK
DA017
NO NEW
WORK
NO NEW
WORK
NO NEW
WORK
ROOF NOTE
EXISTING ROOF IS TO BE PROTECTED AND IS UNDER AN EXISTING WARRANTY TO
REMAIN IN EFFECT. ALL NEW WORK MUST MAINTAIN EXISTING ROOF WARRANTY.
OBTAIN COPY OF WARRANTY FROM VA PRIOR TO STARTING WORK, TYPICAL.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K
L.
M.
PERFORM DEMOLITION WORK AS NOTED TO PROVIDE COMPLETE DEMOLITION
AND PREPARATION FOR NEW WORK. THIS INCLUDES DEMOLITION OF WORK
WHICH IS A PART OF SYSTEMS TO BE REMOVED WHETHER IDENTIFIED TO BE
REMOVED ON THIS DRAWING OR NOT.
ALL BUILDING SYSTEMS SERVING OCCUPIED AREAS OF THE EXISTING FACILITY
SHALL REMAIN FULLY OPERATIONAL. THE CONTRACTOR SHALL PROTECT AND
MAINTAIN THESE SYSTEMS PASSING THROUGH AND ADJACENT TO THE AREAS
REQUIRING DEMOLITION WORK. WORK THAT REQUIRES DISRUPTION OF THE
OPERATION OF THE OCCUPIED SPACES SHALL BE PERFORMED DURING HOURS,
INCLUDING EVENINGS AND WEEKENDS, WHICH MINIMIZE INTERRUPTION TO THE
OCCUPANTS OF THE BUILDING. THE TIMES AND DURATION OF THIS WORK MUST
BE CAREFULLY COORDINATED WITH THE OWNER. WHERE NECESSARY,
CONTRACTOR SHALL REROUTE EXISTING UTILITIES TO TEMPORARILY SERVE
OTHER AREAS OCCUPIED DURING DEMOLITION AND CONSTRUCTION.
WHERE EXISTING CONDITIONS ARE SHOWN, THEY HAVE BEEN DERIVED FROM
AVAILABLE DRAWINGS AND FIELD INVESTIGATION. THEY REPRESENT THE
ENGINEER'S BEST ESTIMATE OF ACTUAL FIELD CONDITIONS. CONTRACTOR
SHALL VISIT THE JOB SITE AND BECOME FAMILIAR WITH THE SITE CONDITIONS
AND THE EXISTING SYSTEMS BEFORE SUBMITTING A BID.
WHERE DUCTWORK MUST BE REMOVED, IT SHALL MEAN THE COMPLETE
REMOVAL OF DUCTWORK, INCLUDING, BUT NOT LIMITED TO, DUCT FITTINGS,
INSULATION, SUPPORTS, HANGERS, STRAPS, BASES, GUYS, BRACKETS,
BRACES, ANCHORS, DAMPERS, DEVICES AND INCIDENTAL ITEMS FASTENED,
CONNECTED AND SUPPORTED FROM THE DUCTWORK, UNLESS SPECIFICALLY
INDICATED OTHERWISE.
WHERE PIPING MUST BE REMOVED, IT SHALL MEAN THE COMPLETE REMOVAL
OF PIPING, INCLUDING, BUT NOT LIMITED TO, PIPE FITTINGS, VALVES,
STRAINERS, FLANGES, INSULATION, SUPPORTS, HANGERS, STRAPS, BASES,
GUYS, BRACKETS, BRACES, ANCHORS, DEVICES AND INCIDENTAL ITEMS
FASTENED, CONNECTED AND SUPPORTED FROM THE PIPING, UNLESS
SPECIFICALLY INDICATED OTHERWISE.
WHERE EQUIPMENT MUST BE REMOVED, IT SHALL MEAN THE COMPLETE
REMOVAL OF EQUIPMENT, INCLUDING, BUT NOT LIMITED TO, SUPPORTS,
HANGERS, STRAPS, BRACKETS, BRACES, ANCHORS, DUCTWORK, PIPING AND
INCIDENTAL ITEMS FASTENED, CONNECTED AND SUPPORTED FROM THE
EQUIPMENT, UNLESS SPECIFICALLY INDICATED OTHERWISE.
WHERE CONTROLS MUST BE REMOVED, IT SHALL MEAN THE COMPLETE
REMOVAL OF CONTROLS, INCLUDING, BUT NOT LIMITED TO, THERMOSTATS,
SENSORS, CONTROLLERS, PANELS AND ENCLOSURES, RELAYS, SWITCHES,
TRANSFORMERS, AND OTHER CONTROL DEVICES, CONTROL TUBING, WIRING,
CONDUITS, SUPPORTS, HANGERS, STRAPS, BASES, GUYS, BRACKETS,
BRACES, ANCHORS, AND DEVICES FASTENED, CONNECTED AND SUPPORTED
FROM THE CONTROL SYSTEM, UNLESS SPECIFICALLY INDICATED OTHERWISE.
UNLESS OTHERWISE INDICATED, PATCH ALL OPENINGS AND HOLES IN WALLS
AND FLOORS LEFT FROM THE REMOVAL OF DUCTWORK, PIPING AND EQUIPMENT
WITH SAME MATERIALS AND FINISH TO MATCH EXISTING SURFACE. REFER TO
ARCHITECTURAL DRAWINGS FOR SPECIFIC PATCHING DETAILS AND NOTES.
REFER TO STRUCTURAL DRAWINGS FOR PATCHING OF ROOF OPENINGS
CREATED BY REMOVAL OF ROOFTOP MECHANICAL EQUIPMENT AND DEVICES.
SEE DETAIL 8/S2.1.
WHERE EXISTING EQUIPMENT, DUCTWORK, PIPING AND CONTROLS ARE
INDICATED TO REMAIN, PROTECT FROM DAMAGE AND MAINTAIN IN SERVICE.
COORDINATE SHUTDOWN OF ALL UTILITIES AND EQUIPMENT WITH THE VA.
THE VA RESERVES THE RIGHT OF REFUSAL FOR ALL MECHANICAL EQUIPMENT
AND CONTROLS. NOTIFY THE OWNER TO DETERMINE DISPOSITION OF
EQUIPMENT AND CONTROL PRIOR TO DEMOLITION WORK. WHERE THE OWNER
ELECTS TO MAINTAIN OWNERSHIP OF EQUIPMENT AND CONTROLS, TURN OVER
AND TRANSPORT EQUIPMENT AND CONTROLS TO A LOCATION WITHIN 3 MILES
OF PROJECT SITE AS DIRECTED BY THE OWNER. WHERE THE OWNER
REFUSES TO MAINTAIN OWNERSHIP OF EQUIPMENT AND CONTROL ,
OWNERSHIP SHALL CONVEY TO THE CONTRACTOR AND CONTRACTOR SHALL
DISPOSE OF SUCH ITEMS OFF SITE.
NO OPEN BURNING SHALL BE PERMITTED.
GENERAL DEMOLITION NOTES
THIS DOCUMENT IS COPYRIGHT MATERIAL, ANY DISCLOSURE, UNAUTH0RIZED USE, DISSEMINATION OR DUPLICATION
WITHOUT THE EXPRESS WRITTEN CONSENT OF LONG & ASSOCIATES IS PROHIBITED ALL RIGHTS RESERVED
4525 S. Manhattan Ave. Tampa, FL 33611-2305
T: (813) 839-0506 F: (813) 839-4616 AAC001624 1828 QB0013991
w w w . l o n g a n d a s s o c i a t e s . c o m
Checked By:
Seal
ALEXANDER M. LONG, A.I.A.
AR 0015104
987654321
B C
D E
F A
98765431 2
A th re e in c h e s o n e fo o t
B
C
D th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h e s o n e fo o t
E o n e h a lf in c h o n e fo o t
F th re e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B A Y
P
IN
E S
M E D
IC
A L C E N
TE
R
Drawn By:Approved Division Chief
DIVISION CHIEF
Drawing Title
Approved Service Director
SERVICE DIRECTOR
Location
Building Number
Dwg. Of.
Date
Project No.
Project Title
DRAWING NO.
To the best of the Architect's and/or Engineer's knowledge, these plans and specifications comply with the applicable minimum building codes and the applicable fire-safety standards
:0
:4
P
M
AML
01/23/15
DA4.1
REPLACE AIR CONDITIONING
SYSTEMS IN B-102
SUPPORT BUILDING
VAMC BAY PINES, FLORIDA 33744
TGS
DEMOLITION ROOF PLAN
516-11-108
SCALE: 1/8" = 1'-0"1
SUPPORT BUILDING
DEMOLITION ROOF PLAN
N
0' 4' 8' 16'
DEMOLITION NOTES
NO. DESCRIPTION
DA006 DEMOLISH AND REMOVE ROOFTOP MECHANICAL EQUIPMENT &
CURBS TO DECK. REMOVE ALL RELATED UTILITIES AND
SERVICES BACK TO SOURCE, CAP AND TERMINATE AS REQ'D.
REMOVE CONDENSATE DRAIN LINES & SUPPORTS. SEE ELEC &
MECH DWG'S. SEE NEW WORK. ROOF SHALL BE PATCHED BY
ROOF SYSTEM MANUFACTURER'S CERTIFIED REPRESENTATIVE
TO RETAIN ROOF WARRANTY. ROOF PENETRATIONS SHALL BE
RESTORED TO MATCH EXISTING ROOF STRUCTURE, INCLUDING
THE INSTALLATION OF ROOF SLAB STRUCTURAL ELEMENTS.
COORDINATE ROOF RESTORATION WITH NEW SYSTEMS
INSTALLATIONS.
DA007 EXISTING ROOFTOP MECHANICAL EQUIPMENT TO REMAIN. SEE
ELE…