Design/Build Sewage Lift Station
Solicitation number
36C24818R0082
Issued by

About this file

36C24818R0082 00001 QA Responses DB pump station.pdf

View the file

Other files

File Type Posted
36C24818R0082-003.docx DOCX document
36C24818R0082-00002000.docx DOCX document
36C24818R0082-00001008.pdf PDF
36C24818R0082-00001003.tif TIF image
36C24818R0082-00001007.pdf PDF
36C24818R0082-00001006.pdf PDF
36C24818R0082-00001004.tif TIF image
36C24818R0082-00001005.pdf PDF
36C24818R0082-00001002.tif TIF image
36C24818R0082-00001000.docx DOCX document
36C24818R0082-001.docx DOCX document
36C24818R0082-002.doc DOC document
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question Answer Does the existing Sewage Lift Station serve only Building 102?

yes

What is the Building Code Classification for Building 102 and any other buildings served by the existing sewage lift station?

overnight patient care

What is the rated occupancy in numbers or people of Building 102 and any other buildings served by the existing sewage lift station?

250 to 300 people plus a full functioning kitchen

Are Civil Drawings available showing existing site conditions, grading and utilities?

Some are available, but not completely accurate to existing conditions.

How can a copy of the existing Civil Drawings be obtained?

Request from Engineering upon award.

What is the current ground water elevation at the site?

N/A Contractor needs to plan on dewatering.

What is the design flow requirements? No current calcs for design. Lift station had 2 5HP with a max rating of 450gpm wastewater pumps

What is the Total Dynamic Head (TDH) or total static head plus the friction head imposed on the sewage lift?

Information not available.