36C24818R0082-00001001.pdf
PDF 58 KB Posted
- Attached to
- Design/Build Sewage Lift Station
- Solicitation number
- 36C24818R0082
About this file
36C24818R0082 00001 QA Responses DB pump station.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24818R0082-003.docx | DOCX document | |
| 36C24818R0082-00002000.docx | DOCX document | |
| 36C24818R0082-00001008.pdf | ||
| 36C24818R0082-00001003.tif | TIF image | |
| 36C24818R0082-00001007.pdf | ||
| 36C24818R0082-00001006.pdf | ||
| 36C24818R0082-00001004.tif | TIF image | |
| 36C24818R0082-00001005.pdf | ||
| 36C24818R0082-00001002.tif | TIF image | |
| 36C24818R0082-00001000.docx | DOCX document | |
| 36C24818R0082-001.docx | DOCX document | |
| 36C24818R0082-002.doc | DOC document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Question Answer Does the existing Sewage Lift Station serve only Building 102?
yes
What is the Building Code Classification for Building 102 and any other buildings served by the existing sewage lift station?
overnight patient care
What is the rated occupancy in numbers or people of Building 102 and any other buildings served by the existing sewage lift station?
250 to 300 people plus a full functioning kitchen
Are Civil Drawings available showing existing site conditions, grading and utilities?
Some are available, but not completely accurate to existing conditions.
How can a copy of the existing Civil Drawings be obtained?
Request from Engineering upon award.
What is the current ground water elevation at the site?
N/A Contractor needs to plan on dewatering.
What is the design flow requirements? No current calcs for design. Lift station had 2 5HP with a max rating of 450gpm wastewater pumps
What is the Total Dynamic Head (TDH) or total static head plus the friction head imposed on the sewage lift?
Information not available.