36C24718R0120-00001002.pdf
PDF 4 MB Posted
- Attached to
- Replace Water Tower, Project #557-16-103 Federal contract opportunity
- Solicitation number
- 36C24718R0120
About this file
36C24718R0120 00001 Attachment #1A - Current Tank Inspection Report_Attachment 1B.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24718R0120-00003000.docx | DOCX document | |
| 36C24718R0120-00002001.pdf | ||
| 36C24718R0120-00002000.docx | DOCX document | |
| 36C24718R0120-00002002.pdf | ||
| 36C24718R0120-00001004.pdf | ||
| 36C24718R0120-00001003.pdf | ||
| 36C24718R0120-00001001.pdf | ||
| 36C24718R0120-00001000.docx | DOCX document | |
| 36C24718R0120-00001005.pdf | ||
| 36C24718R0120-002.pdf | ||
| 36C24718R0120-001.docx | DOCX document | |
| 36C24718R0120-003.pdf | ||
| 36C24718R0120-000.docx | DOCX document |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
American Tank Maintenance
Carl Vinson VAMC
Washout Inspection Report
March 18, 2015
250,000 Facility Tank
Prepared For:
Daniel Knight
Prepared By:
Mike Lewis
Date:
March 20, 2015
36C24718R0120 00001
ATTACHMENT #1A - Page 1 of 15
General Information
INTRODUCTION
On March 18, 2015 American Tank Maintenance (ATM) performed a washout inspection of the 250,000 gallon elevated Facility Tank owned by the Carl Vinson VAMC.
250,000 GALLON ELEVATED -FACILITY TANK
Date Inspected March 18, 2015
Inspector Doug Byrd, Garrett Dupree
Capacity 250,000 Gallons
Style Elevated
Construction Material Riveted
Height 78 feet to low water level
Year Built 1943 - R.D. Cole
EXTERIOR COATINGS
The exterior surfaces are coated with an alkyd coating system. The adhesion is good on all areas tested. The coating system averaged 12-21 mils DFT in all areas tested. This coating sytem has begun to experience chalking.
INTERIOR COATINGS
The interior surfaces are coated with an epoxy coating system. This coating system has reached the end of its useful and protective life. Multiple areas of blistering and delamination were noted. This coating system is no longer protecting the steel substrate from continued corrosion.
Steel loss will occur. This coating system averaged between 20-28 mils DFT in all areas tested.
SAFETY
This tank has a notched tube safety climb system installed on the access ladder as well as a cage.
This safety climb system is in good condition and functioning as designed. There is a notched tube safety climb system on the dome ladder.
SANITARY
The roof hatch is a square "shoe box" design and was closed and locked. The vent and screen are in good condition. The over flow has a screen in place.
Carl Vinson VAMC - 250,000 Gallon Facility Tank - Washout Inspection Report Page 2
ATTACHMENT #1A - Page 2 of 15
STRUCTURE
The tank is structurally sound and no defects were noted. Anchor bolts are tightened and in good condition. The wind rods and riser rods are in good condition. All connection points for struts, wind rods and riser rods are in good condition.
SECURITY
The tank is located within a fenced - in area.
RECOMMENDATIONS
• Renovate Interior Surfaces
• Monitor Exterior Surfaces During Annual Inspection - Renovation recommended with 2-
3 Years to allow Over Coating
• Continue to Washout Tank Every Two Years
Carl Vinson VAMC - 250,000 Gallon Facility Tank- Washout Inspection Report Page 3
ATTACHMENT #1A - Page 3 of 15
250,000 Gallon Elevated - Carl Vinson VAMC
Carl Vinson VAMC - 250,000 Gallon Facility Tank - Washout Inspection Report Page 4
ATTACHMENT #1A - Page 4 of 15
Photo #1 Exterior
Photo #2 Leg, Foundation, Antenna Install
Carl Vinson VAMC - 250,000 Gallon Facility Tank- Washout Inspection Report Page 5
ATTACHMENT #1A - Page 5 of 15
Photo #3 Over Flow with Screen
Photo #4 Riser and Riser Manway
Carl Vinson VAMC - 250,000 Gallon Facility Tank - Washout Inspection Report Page 6
ATTACHMENT #1A - Page 6 of 15
Photo #5 Access Ladder
Photo #6 Legs, Struts, Wind Rod & Riser Rod Connections
Carl Vinson VAMC - 250,000 Gallon Facility Tank - Washout Inspection Report Page 7
ATTACHMENT #1A - Page 7 of 15
Photo #7 Legs, Struts, Wind Rod & Riser Rod Connections
Photo #8 Tank Bowl and Underside of Catwalk
Carl Vinson VAMC - 250,000 Gallon Facility Tank- Washout Inspection Report Page 8
ATTACHMENT #1A - Page 8 of 15
Photo #9 Tank Side Wall and Catwalk
Photo #10 Dome Ladder and Tank Side Wall
Carl Vinson VAMC - 250,000 Gallon Facility Tank - Washout Inspection Report Page 9
ATTACHMENT #1A - Page 9 of 15
Photo #11 Catwalk- Note Antenna Installation Blocking Passage
Photo #12 Catwalk - Note Antenna Cable Blocking Passage
Carl Vinson VAMC - 250,000 Gallon Facility Tank- Washout Inspection Report Page 10
ATTACHMENT #1A - Page 10 of 15
Photo #13 Exterior Roof
Photo #14 Roof Vent
Carl Vinson VAMC - 250,000 Gallon Facility Tank - Washout Inspection Report Page 11
ATTACHMENT #1A - Page 11 of 15
Photo #15 Interior Floor Prior to Washout
Photo #16 Interior Floor After Washout
Carl Vinson VAMC - 250,000 Gallon Facility Tank - Washout Inspection Report Page 12
ATTACHMENT #1A - Page 12 of 15
Photo #17 Interior Roof
Photo #18 Interior Side Wall - Note Corrosion Forming Along Steel Substrate
Carl Vinson VAMC - 250,000 Gallon Facility Tank - Washout Inspection Report Page 13
ATTACHMENT #1A - Page 13 of 15
Photo #19 Interior - Note Coating Delamination
Photo #20 Interior - Note Blistering and Corrosion Forming
Carl Vinson VAMC - 250,000 Gallon Facility Tank - Washout Inspection Report Page 14
ATTACHMENT #1A - Page 14 of 15
Photo #21 Interior - Note Blistering
Photo #22 Roof Hatch Closed - Locked
Carl Vinson VAMC - 250,000 Gallon Facility Tank - Washout Inspection Report Page 15
ATTACHMENT #1A - Page 15 of 15