Text version
Room# Room Volume CFM CFH Total ACH Pressure Rel. to:
1A118 Pharmacy 31360 2304 134,100 4.2 -0.0019 Hall 1B175 1st Floor Lab 26712 3826 229560 8.6 0.0014 Hall 1B184 Hystology/Cyst. 4500 707 42420 9.4 -0.0078 1B175 1B185 Cutting Rm. 2268 594 35640 15.7 0.0152 1B175 1B187 Microbiology 5787 878 52680 9.1 -0.01754 1B175
1B186A Microbiology 1028 267 16020 15.6 -0.0098 1B186B 1B186B Microbiology 936 326 19560 20.9 -0.1299 1B187 2C101 GI Clean Storage 720 92 5520 7.7 0.0017 Hall 2C101 GI Wash 1024 -259 -15540 -15.2 -0.0038 Hall 2C107 GU/GI 1134 238 14280 12.6 0.0022 Hall 2C108 GU/GI 1503 276 16560 11.0 0.0021 Hall 2C109 GU/GI 1255 330 19800 15.8 0.0048 Hall 2D135 GU/GI 2927 345 20700 7.1 0.0029 Hall 2D138 GU/GI 2793 315 18900 6.8 0.0033 Hall 4A113 Cath Lab 4617 2178 130680 28.3 0.0061 Hall
New Cath Lab 5149 1301 78060 15.2 0.006 Hall Control Room 3392 519 31140 9.2 0.0054 Control Rm.
Equip. Room 1020 984 59040 57.9 0.0024 Elect. Rm.
A119/106 Pharmacy 4914 177 10620 2.2 0.0014 Hall LB140 Nuclear Hot Lab 2673 235 14100 5.3 -0.0059 LB140
LB140A Nuclear Med. 12159 1701 102060 8.4 -0.0077 Hall Notes: 1. Room volume is in cubic feet calculated from measurements of room size.
2. CFM is cubic feet per minute of air at standard presssure and temperature
3. CFH is cubic feet per hour (CFM x 60).
4. ACH is Air changes per hour,(CFH/Room volume). Date: Apr-18
Room# Room Volume CFM CFH Total ACH Pressure Rel. to:
SPS
LC131G Clean room 8794 715 42900 4.9 0.0110 LC102 LC104A Cart 13514 2213 132780 9.8 0.0141 LC102 LC104 Prep. & Sterile 10854 2505 150300 13.8 0.0119 LC102 LC102 Storage 29282 2280 136800 4.7 0.0079 Hall LA123 Offices 12894 1036 62160 4.8 0.0051 Hall
LC131H Warehouse 6059 687 41220 6.8 0.0021 LC102 LA125 Decontamination 5967 1322 79320 13.3 -0.0189 LA125A
LA125A Decon. Ante 4887 -918 -55080 -11.3 0.0054 Hall
Bldg. 9 122 850 251 15000 17.6 0.0005 Hall 123 860 226 14040 16.3 0.0011 Hall 124 860 312 18060 21.0 0.0088 Hall 125 900 224 13260 14.7 0.0180 Hall 126 1190 274 16380 14.4 0.0048 Hall 231 862 177 10620 12.3 0.0105 Hall 232 1748 354 21240 12.2 0.0319 Hall 233 1657 312 18720 11.3 0.0381 Hall 235 1496 385 23100 15.4 0.0180 Hall
Notes: 1. Room volume is in cubic feet calculated from measurements of room size.
2. CFM is cubic feet per minute of air at standard presssure and temperature
3. CFH is cubic feet per hour (CFM x 60).
4. ACH is Air changes per hour,(CFH/Room volume). Date: Apr-18
Volume CFM CFH Total ACH Pressure Relative to Pharmacy New Area
1A1113 to A113b 1134 1123 67380.0 59.4200 0.0423 1A1113b to A113A 1883 1328 79680.0 21.6000 0.0389 1A113a tocenter Pharm 0.0651
Chemo 5A134 to center common 864 976 58560.0 67.7 -0.0604 5A130 to center common 1080 4416 264960.0 245.3 -0.0714
Clean Aire 1006 Rabbit Run
Hopkins, SC
Apr-18