Room# Volume CFM CFH ACH Pressure Pressure Rel. to Common Rel. to Corridor
OR# Positive Positive
1 3327 1287 77220 23.2 0.0220 0.0380
2 3327 1254 75240 22.6 0.0270 0.0310
3 3147 2012 120720 38.4 0.0217 0.0252
4 3236 1112 66720 20.6 0.0089 0.0216
5 4980 1789 107340 21.6 0.0215 1.0323
6 4407 1401 84060 19.1 0.0442 0.0481
7 3111 1064 63840 20.5 0.0226 0.0294
8 2406 853 51180 21.3 0.0209 0.0341
Recovery 9048 4899 293940 32.5 NA 0.0210
Rear Core NA NA 0.0214
Break room air lock NA -0.0521
Notes: 1. Room volume is in cubic feet calculated from measurements of room size.
2. CFM is cubic feet per minute of air at standard presssure and temperature
3. CFH is cubic feet per hour (CFM x 60).
4. ACH is Air changes per hour,(CFH/Room volume). Date: Apr-18
5.All OR Rooms are positively pressured to both the orridore and the common Sterile Core
Clean Aire 1006 Rabbit run Hopkins, SC 29061