36C24618R0176-003.pdf
PDF 4 MB Posted
- Attached to
- Project 590-14-112, SCI Crawlspace Emergent Structural Repairs Federal contract opportunity
- Solicitation number
- 36C24618R0176
About this file
36C24618R0176 CONTRACT ATTACHMENT A - AE DRAWINGS.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24618C0056-000.docx | DOCX document | |
| 36C24618R0176-00003000.docx | DOCX document | |
| 36C24618R0176-00003001.pdf | ||
| 36C24618R0176-00002001.pdf | ||
| 36C24618R0176-00002000.docx | DOCX document | |
| 36C24618R0176-00001000.docx | DOCX document | |
| 36C24618R0176-00001004.pdf | ||
| 36C24618R0176-00001005.pdf | ||
| 36C24618R0176-00001003.pdf | ||
| 36C24618R0176-00001001.pdf | ||
| 36C24618R0176-00001002.pdf | ||
| 36C24618R0176-004.pdf | ||
| 36C24618R0176-007.docx | DOCX document | |
| 36C24618R0176-002.docx | DOCX document | |
| 36C24618R0176-006.docx | DOCX document | |
| 36C24618R0176-001.docx | DOCX document | |
| 36C24618R0176-005.pdf | ||
| 36C24618R0176-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
X
X X
X
X X
2 1
SALVAGE YARD
D R
IV
E W A
YD
IR
T
R O
AD
W A Y
D R
IV
E W A Y
LOT
IMPOUND
PARKING
PARKING
PA
R
KI
N
G
PARKING
PARKING
PA
RK
IN
G
PARKING
PARKING
PARKING
SEW
ELL
AVENUE
AVENUE
AM
ES
S
TR
EE
T
ST
RE
ET
KN
O
ST
RE
ET
W O
O
DF
IN
TH
O
M
PS
O N
S
TR
EE
T
BLACK
BOULEVARD
FRANKLIN BOULEVARD
EM
AN
CI
PA
TI
O
N
DR
IV
E
AV
EN
U E
M cC
LELLA
N
HARRIS
HARRIS AVENUE
HARRIS
AV
EN
UE
AVERILL AVENUE
FRANKLIN
FR
AN
KL
IN
BOULE
VARD
MARTIN L. KING JR. BOULEVARD
BO
ULEVAR
D
SHORE ROAD
AVENUE
PARKING
PARKING
HARRIS AVENUE
HARRIS AVENUE
AVERILL AVENUE
AVERILL AVENUE
FRANKLIN BOULEVARD
M
ARTIN L. KING
JR.
SPRINT NTELOS
VACANT
PA
RK
IN
G
PARKING
PARKING
PARKING
PARKING
PA
RK
IN
G
MALLORY
STREET
6.0
6.
6.0
6.0
20" CRAPE MYRT LE
30" OAK
36" OAK
40" ELM
A1
A2
A3
A4
A5
SS
SS
BO
L L
AR
D
(TY
P
OF
EX
IST
ING
P
AR
KIN
G
LO
T
8'
HIG
H
CH
A I N
LIN
K
FE
NC
E
CO
NC
R
ET
A
IN
IN
G
WA
L L
TR ASH CAN
BULKHE
AD
BU LKHEA D
80" OAK
50" OAK
40" ELM
60" OAK
24" OAK
24" OAK
20" CRAPE MYRT LE
10" CRAPE MYRTLE
10" CRAPE MYRTLE
40" GUM
15" HICKORY
10" CRAPE MYRTLE
20" CRAPE MYRT LE
20" CRAPE MYRT LE
3" CRAPE MYRT LE
(7) 10" HOLLY
GE
NE
RA
TO
R
AC
C
E
XIS
T.
E
LE
C
. VLT.
EX
IST
ING
P
AR
KIN
G
LO
T
#1
EX
IST
ING
P
AR
KIN
G
LO
T
#5
EX
IST
BL
DG
FIN
. F L.= 6.7
JO
NE
S
CREE
K
171 155
147142
138A
115 135
110A 137B
137A172
148T
125140169
148B
148S
148A
148D 148C
173A 152
110B
146B
137D
110D
110C
146A
179 159
15141
1827 31
27A
LEAVE THIS AREA OPEN
LE
AV
E
TH
IS
A
RE
A
OP
EN
RAMPS
4' C.L.F.
4' C.L.F.
6' C.L.F.
6' C.L.F.
8' C.L.F.
8' C.L.F.
AREA OF WORK
ADDITION TO BUILDING 137C,
UNDER CONSTRUCTION.
137C
TO I-64
137-G001 COVER SHEET
137-A100 BUILDING 137 SITE / CRAWLSPACE PLAN
137-A701 PHOTOGRAPHS OF CRAWLSPACE
137-S100A EXISTING FIRST FLOOR FRAMING PLAN - AREA A
137-S100B EXISTING FIRST FLOOR FRAMING PLAN - AREA B
137-S701 RESTORATION DETAILS
137-F100 PIPE BASEMENT PLAN - REMOVALS AND NEW WORK - FIRE SUPPRESSION
137-PP100A PARTIAL PIPE BASEMENT PLAN - AREA A REMOVALS AND NEW WORK - PLUMBING
137-PP100B PARTIAL PIPE BASEMENT PLAN - AREA B REMOVALS AND NEW WORK - PLUMBING
137-MP100 PIPE BASEMENT PLAN REMOVALS AND NEW WORK - HVAC
137-EP100 PIPE BASEMENT PLAN REMOVALS AND NEW WORK - ELECTRICAL
N N.T.S.Scale:
HAMPTON VAMC MAP
Hampton, Virginia
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn
Date
Project No.
Drawing Number
Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne f oo t on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
1-800-362-1523 jpa@johnpoe.com
RDC/JPA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
HEAPY ENGINEERING
MECHANICAL ELECTRICAL
COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
THP LIMITED INC.
STRUCTURAL ENGINEER
100 E. EIGHTH STREET
CINCINNATI, OH 45202
513.241.3222 P
513.241.2981 F
TERRACON INC.
5240 GREEN'S DAIRY ROAD
RALEIGH, NC 27616
919.873.2211 P
919.873.9555 F
SCI Crawlspace Emergent Structural Repairs
06/05/2014
COVER SHEET
137-G001
EKTH
11004.02 590-14-112
Hampton, Va
137C
SCI Crawlspace Emergent Structural Repairs 100 Emancipation Dr.
Hampton, VA 23667
INDEX OF DRAWINGS
APPROVED: INTERIOR DESIGNER
APPROVED: SAFETY MANAGER
APPROVED: GEMS COORDINATOR
APPROVED: PROGRAM MANAGER EMS
APPROVED: PROGRAM MANAGER M+R
APPROVED: PROJECT ENGINEER
APPROVED: ENERGY ENGINEER
APPROVED: DIRECTOR OF ENGINEERING SERVICES
APPROVED: CHIEF, FACILITIES MANAGEMENT SERVICE
APPROVED: INFECTION CONTROL
APPROVED: CHIEF, POLICE SERVICE
APPROVED: CHIEF, INFORMATION RESOURCES MANAGEMENT SERVICE
APPROVED: CHIEF NUTRITION AND FOOD SERVICE
APPROVED: CHIEF, LOGISTICS SERVICE
APPROVED: CHIEF, PHARMACY SERVICE
APPROVED: ASSOCIATE CHIEF, NURSE SCI
APPROVED: CHIEF, SPINAL CORD INJURY AND DISORDERS SERVICE LINE
APPROVED: FACILITY PLANNER
APPROVED: ASSOCIATE DIRECTOR
APPROVED: CHIEF NURSE EXECUTIVE
APPROVED: CHIEF OF STAFF
APPROVED: DIRECTOR, HAMPTON VA MEDICAL CENTER
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
DATE:
REVIEWED: AFGE DATE:
DATE:
DATE:
REVIEWED: NAGE
REVIEWED: PARALYZED VETERANS OF AMERICA
ILSM/ICRA DATE:
Revisions Date
UP
X
X X
X X
7 7a 8 9 9a 10 11 12 13 14 15
CC
BB
AA
Z
Y
X
W
V
U
T
S
R
Q
P
O
N
M
L
K
5' - 9 1/2" 1' - 10"
14' - 4" 4' - 10" 16' - 6" 25' - 8 1/2" 20' - 3 5/8" 25' - 8" 21' - 0 7/8" 22' - 3"
/2
/8
6'
9"
1'
7/
8"
/8
/4
/8
9'
5"
/2
9'
6"
/4
BUILDING 137B
BUILDING 110B
BUILDING 137D
BUILDING
PARKING
FRANKLIN BOULEVARD
1.081.081.081.08
1.071.071.071.07
1.071.071.07 1.071.071.07
1.06
1.04
1.051.051.051.05
1.06
1.04
1.06
1.02
1.03
1.071.07
1.011.011.011.01
1.011.01
BUILDING 137C
BUILDING 6
BUILDING 110C
BUILDING 137A
1.09 TYP.
1.10 TYP.
1.09 TYP.
1.09TYP.
1.09TYP.1.10TYP.1.09 TYP.
1.09 TYP.
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn
Date
Project No.
Drawing Number
Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne f oo t on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
1-800-362-1523 jpa@johnpoe.com
RDC/JPA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
HEAPY ENGINEERING
MECHANICAL ELECTRICAL
COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
THP LIMITED INC.
STRUCTURAL ENGINEER
100 E. EIGHTH STREET
CINCINNATI, OH 45202
513.241.3222 P
513.241.2981 F
TERRACON INC.
5240 GREEN'S DAIRY ROAD
RALEIGH, NC 27616
919.873.2211 P
919.873.9555 F
SCI Crawlspace Emergent Structural Repairs
06/05/2014BUILDING 137 SITE / CRAWLSPACE
PLAN
137-A100
EKTH
11004.02 590-14-112
Hampton, Va
137C
N Scale: 1" = 20'-0"
BUILDING 137 SITE / CRAWL SPACE PLAN
KEY NOTES
GENERAL NOTES
Revisions Date
1.01 Area of work: See Structural Drawings and Specifications for description of repairs to first floor cast in place concrete slab/beam/pan joist system. See Plumbing, Mechanical and Electrical Drawings and Specifications for description of plumbing, mechanical and electrical piping / conduit resupport and re-insulation. The owner has categorized crawl space as a permit required confined space. See MCM 00-45 in Specifications for the Owner's permit required confined space requirements. Other regulation agency requirements may also apply.
1.02 Existing area well shall serve as contractor's primary point of access / egress to crawl space.
1.03 Existing interior stair between first floor and crawl space shall serve as secondary means of access / egress to crawl space.
1.04 Existing area well shall serve as secondary means of access / egress from crawl space. Area well is located within ongoing construction project by others. Close coordination with separate contractor will be required. Depending on status of construction, access / egress may be through crawl space of new construction.
1.05 New building addition currently under construction by others. No work this area.
1.06 New building area well. Coordinate use of area well with separate contractor. Availability of access / egress will be contingent upon actual cordination at time of project execution.
1.07 Existing space to remain. No work this area.
1.08 Existing parking for VA Staff and Patients. No contractor use without prior coordination with COR.
1.09 Existing foundation wall to remain. See Structural Drawings for beam / wall ledge repairs.
1.10 Existing concrete column to remain.
1. All work shall comply with all applicable local, state or, national codes, rules, ordinances and regulations including the American Disabilities Act (ADA) and the American National Standards Institute (ANSI) guidelines.
2. Verify all conditions and dimensions in the field before fabricating any materials.
3. Existing construction to remain that is damaged or distrubed during construction shall be patched or restored.
4. Crawl space is approximately 4'-0" from dirt / sand floor to underside of cast in place concrete slab / beam / pan joist system to be repaired. Plumbing, mechanical, and electrical systems are suspended from floor slab at various elevations. Protect plumbing, mechanical, and electrical systems at all times. See Sheet 137-A701 for photographs of crawl space.
5. Contractor shall remove all demolished items and construction debris from crawl space.
6. Contractor's staging / laydown area, vehicle parking and dumpster location to be coordinated with contracting officer's representative
(COR).
7. Contractor is responsible to determine characteristics of crawl space and what ventilation equipment, protective devices and operational considerations are required for repair operations.
8. Patients will be removed from first floor areas above crawl space during slab repair. Medical center staff may continue to use portions of first floor above crawl space during slab repair operations.
9. Shut donw of any PME systems must be coordinated with COR.
Some utilities will serve active buildings and may not be shut down.
10. Contractor to coordinate operations with contractor constructing new addition. See Key Note 1.05.
11. Repair operations shall take place between 7:00AM and 7:00PM, Monday through Friday unless otherwise approved by COR.
12. Contractor shall coordinate daily with COR to identify areas where contractor will be chipping, grinding or conducting other noise creating operations.
13. Building 137 will continue to be occupied by staff. Contractor shall maintain all utilities to building 137D. Pedestrian access at first floor thru building 137C to building 137D shall be maintained at all times.
14. The pin anchor installation repair detail indicated on the Structural Drawings will require installation from the upper side of the cast in place concrete slab / beam / pan joist system. Coordinate scheduling and access to spaces on the first floor with COR.
Provide dust protection and clean all spaces at these repair locations.
15. The owner has categorized the crawl space as permit required confined space. See MCM 00-45 in Specifications for the Owner's permit required confined space requirements. Other regulation agency requirements may also apply.
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn
Date
Project No.
Drawing Number
Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne f oo t on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
1-800-362-1523 jpa@johnpoe.com
RDC/JPA Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
HEAPY ENGINEERING
MECHANICAL ELECTRICAL
COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
THP LIMITED INC.
STRUCTURAL ENGINEER
100 E. EIGHTH STREET
CINCINNATI, OH 45202
513.241.3222 P
513.241.2981 F
TERRACON INC.
5240 GREEN'S DAIRY ROAD
RALEIGH, NC 27616
919.873.2211 P
919.873.9555 F
SCI Crawlspace Emergent Structural Repairs
06/05/2014
PHOTOGRAPHS OF CRAWLSPACE
137-A701
MDTH
11004.02 590-14-112
Hampton, Va
137C
Revisions Date
Cast in place concrete column, beam and pan joist floor system 2 Damaged beam and joist to be repaired. 3 Damaged joists to be repaired. 4 Damaged beam to be repaired.
5 Damaged joist to be repaired. 6 Damaged joist to be repaired. 7 Damaged joists to be repaired. 8 Damaged joists to be repaired.
Typical crawl space area well access - Exterior 12 Typical crawl space area well access - Interior9 View of crawl space and piping. 10 View of crawl space.
A Photographs are provided to illustrate general conditions found in crawl space.
B Photographs do not depict appropriate support of Fire Protection, Plumbing, Mechanical and/or Electrical systems.
C Photographs were taken in 2011. Actual conditions may not be identical to photographs.
D The owner has categorized the crawl space as a permit required confined space. See MCM 00-45 in Specifications for the Owner's permit required confined space requirements. Other regulation agency requirements may also apply.
GENERAL NOTES
EA EA.6
W6
E10
W5.9
R
S
U
T
9 10 11 12 13 14
Q
P
O
157a 9a
N
M
L
NEW
ADDITION
NEW
ADDITION
EXISTING BUILDING
7' - 7 1/2" +/- 14' - 4" +/- 21' - 4" +/- 25' - 8 1/2" +/- 20' - 3 5/8" +/- 25' - 8" +/- 21' - 0 7/8" +/- 22' - 3" +/-
158' - 3 1/2" +/-
7"
9'
- 5
7 5
/8"
3 3
/4"
2"
5 1 /8"
1'
- 4
7/ 8"
6'
- 9
4 7 /8"
4 TYP.
2 TYP.
3 TYP.
5TYP.
1 1A
7TYP.
4 TYP.
7TYP.
5TYP.
9 9
LEGEND:
BEAM BOTTOM / BEAM CORNER REPAIR
BEAM / WALL LEDGE REPAIR
JOIST BOTTOM REPAIR
PIN ANCHOR LOCATIONS
PIN ANCHOR LOCATIONS IN AREAS OF ASBESTOS CONTAINING FLOORING
OR MASTIC. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR
ADDITIONAL INFORMATION
SHORE
EXISTING FIRST FLOOR PARTITION WALL
9 10 11
NOTE: FOR ALL REPAIRS LISTED IN LEGEND, REFER TO
SPECIFICATION SECTION 03 01 00, PARAGRAPH 3.2B FOR
BID QUANTITIES.
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn
Date
Project No.
Drawing Number
Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne f oo t on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
1-800-362-1523 jpa@johnpoe.com
VA Project No.
THP Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
THP LIMITED INC.
STRUCTURAL ENGINEER
100 E. EIGHTH STREET
CINCINNATI, OH 45202
513.241.3222 P
513.241.2981 F
HEAPY ENGINEERING
MECHANICAL ELECTRICAL
COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
TERRACON INC.
5240 GREEN'S DAIRY ROAD
RALEIGH, NC 27616
919.873.2211 P
919.873.9555 F
SCI Crawlspace Emergent Structural Repairs
06/05/2014
EXISTING FIRST FLOOR FRAMING
PLAN - AREA A
137-S100A
GODFJE
11171.04 590-14-112
Hampton, Va
137C
1/8" = 1'-0"137-S100A
2 FIRST FLOOR EXISTING REPAIRS NORTH NORTH
DRAWING NOTES:
1. PERFORM ALL WORK IN THE CRAWL SPACE IN ACCORDANCE WITH THE
REQUIREMENTS OF VAMC HAMPTON'S "CONFINED SPACE POLICY" (MCM 00-45). THE
VA HAS DIRECTED THAT THIS WORK IS TO FOLLOW ALL REQUIREMENTS OF "PERMIT
REQUIRED" CONFINED SPACE.
2. THE WORK AREA IS LOCATED IN A CRAWL SPACE BELOW THE GROUND LEVEL
SUPPORTED FLOOR SLAB. TYPICAL DISTANCE BETWEEN CRAWL SPACE DIRT FLOOR
AND BOTTOM SURFACE OF SUPPORTED FLOOR JOIST IS APPROXIMATELY 4’-0”. AN
ACCESS HATCH INTO THE CRAWL SPACE IS LOCATED ON THE WEST SIDE OF THE
BUILDING. NORTHWEST WING OF THE BUILDING. ADDITIONAL ACCESS MAY BE
AVAILABLE ON THE NORTHEAST AND SOUTHEAST SIDE OF THE BUILDING THROUGH
BUILDING ADDITIONAL CURRENTLY UNDER CONSTRUCTION. COORDINATE WITH
COR.
3. UTILITIES (INSULATED STEAM PIPING, SANITARY LINES, ELECTRICAL
LINES/CONDUITS, WATER LINES, MED GAS AND OXYGEN LINES, ETC.) ARE LOCATED
THROUGHOUT THE ENTIRE CRAWL SPACE AREA. DO NOT DAMAGE. THE
CONTRACTOR SHALL PROTECT EXISTING UTILITIES DURING WORK. UTILITIES ARE
CLUSTERED TOGETHER AT MANY LOCATIONS, ESPECIALLY BENEATH OVERHEAD
CONCRETE REPAIR AREAS. THE CONTRACTOR SHALL INCLUDE IN THEIR BID, ALL
COSTS FOR WORKING AROUND UTILITIES. THE CONTRACTOR IS ENCOURAGED TO
VISIT THE SITE PRIOR TO BIDDING TO BECOME FAMILIAR WITH EXISTING SITE
CONDITIONS.
4. AT MISCELLANEOUS LOCATIONS THROUGHOUT THE WORK AREA, UTILITIES ARE
ANCHORED TO THE CONCRETE STRUCTURE. TEMPORARILY SUPPORT UTILITIES
WHERE ANCHORAGE IS DISTURBED DURING OVERHEAD CONCRETE REPAIR
EFFORTS.
5. CONDUITS ARE EMBEDDED IN EXISTING CONCRETE JOIST. LOCATIONS ARE
UNKNOWN. CONTRACTOR SHALL COORDINATE WITH COR AND CONFIRM THAT ALL
CONCRETE ENCASED UTILITIES ARE DISABLED PRIOR TO PERFORMING REPAIRS.
CONDUITS ARE NOT TO BE DAMAGED. DAMAGED CONDUITS WILL BE REPAIRED AT
NO ADDITIONAL COST TO THE GOVERNMENT.
Revisions Date
A. CODES AND SPECIFICATIONS
1. VIRGINIA UNIFORM STATEWIDE BUILDING CODE, 2009.
2. DEPARTMENT OF VETERAN AFFAIRS SIESMIC DESIGN REQUIREMENTS (H-18-8 AUGUST 2013).
3. 2009 INTERNATIONAL BUILDING CODE.
4. ACI 301-05 SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS AS MODIFIED BY THE CONSTRUCTION DOCUMENTS.
B. CONCRETE
1. CONCRETE STRENGTHS:
A. HAND APPLIED REPAIR MORTAR: 7000 PSI
B. SHOTCRETE: 5000 PSI
2. PLACE NO PERMANENT LOAD, SUCH AS MASONRY WALLS, ON SUPPORTED SLABS UNTIL CONCRETE HAS REACHED SPECIFIED STRENGTH
AND ALL SHORING HAS BEEN REMOVED.
3. PLACE NO OPENINGS, SLEEVES, INSERTS, ETC., IN CONCRETE WORK UNLESS CRITERIA INDICATED ON STRUCTURAL DRAWINGS IS MET, OR IS APPROVED IN WRITING BY THE C.O.T.R.
C. REINFORCING STEEL
1. ALL REINFORCING: 60 KSI YIELD
2. PROVIDE CLASS B TENSION SPLICES UNLESS OTHERWISE NOTED.
3. CLEARANCES BETWEEN REINFORCING BARS AND CONCRETE SURFACES SHALL BE ACI MINIMUM UNLESS OTHERWISE NOTED.
D. COORDINATION AND CONSTRUCTION
1. FIELD VERIFY EXISTING DIMENSIONS AND ELEVATIONS WHICH AFFECT FABRICATION PRIOR TO SUBMITTAL OF SHOP DRAWINGS
AND FABRICATION.
2. STRUCTURAL FRAMING PLANS ARE TYPICALLY DRAWN AS REFLECTED PLANS SHOWING BEAMS, WALLS, AND COLUMNS ON THE
UNDERSIDE OF THE LEVEL SHOWN.
3. BRACE ENTIRE STRUCTURE AS REQUIRED TO MAINTAIN STABILITY UNTIL COMPLETE AND FUNCTIONING AS THE DESIGNED UNIT.
4. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. THIS REQUIREMENT WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO WORKING HOURS.
5. THE DUTY OF THE ENGINEER TO CONDUCT CONSTRUCTION REVIEW OF CONTRACTOR'S PERFORMANCE IS NOT INTENDED TO INCLUDE REVIEW OF ADEQUACY OF CONTRACTOR'S SAFETY MEASURES IN, ON, OR NEAR THE CONSTRUCTION SITE.
E. MECHANICAL AND OTHER LOADS SUPPORTED FROM STRUCTURE
1. ALL TRADE CONTRACTORS, MECHANICAL, STAIR, SPECIALITY, ETC., ARE TO DESIGN THEIR SYSTEMS, INCLUDING ATTACHMENTS
TO THE BUILDING’S STRUCTURE WITHIN THE FOLLOWING LIMITATIONS.
2. LOADS ARE TO BE DISTRIBUTED TO THE STRUCTURE IN A MANNER THAT DOES NOT EXCEED THE LOAD ALLOWANCES NOTED UNDER
DESIGN LOADS. ANCHORS ARE TO HAVE AN ULTIMATE SAFETY FACTOR OF AT LEAST 4.0.
3. POINT LOADS EXCEEDING 400 POUNDS MAY NOT BE APPLIED TO ANY OPEN WEB STEEL JOIST.
F. DESIGN LOADS
1. OCCUPANCY CATEGORY OF BUILDING: III
2. EARTHQUAKE DESIGN DATA:
SEISMIC IMPORTANCE FACTOR: Ie = 1.3 MAPPED SPECTRAL RESPONSE ACCELERATION: Ss = 0.122
MAPPED SPECTRAL RESPONSE ACCELERATION: S1 = 0.049
SPECTRAL RESPONSE COEFFICIENT: Sds = 0.130 SPECTRAL RESPONSE COEFFICIENT: Sd1 = 0.078
SITE CLASS: D
SEISMIC DESIGN CATEGORY: B
GENERAL STRUCTURAL NOTES
KEY NOTES:
1. ACCESS INTO CRAWL SPACE VIA. REMOVABLE GRATING AT GRADE LEVEL. ACCESS
OPENING THROUGH WALL INTO CRAWL SPACE IS APPROXIMATELY 3'-0" x 2'-8".
1A. POTENTIAL ACCESS TO CRAWL SPACE IS THROUGH AN ADDITION CURRENTLY UNDER
CONSTRUCTION. COORDINATE ACCESS WITH COR.
2. KNOWN LOCATION OF EXISTING CONCRETE BEAM REQUIRING BEAM BOTTOM REPAIRS,
SHOWN FULLY HATCHED. SURVEY BOTTOM SURFACE OF ALL BEAMS WITHIN THE WORK LIMITS
TO LOCATE DELAMINATED, SPALLED, AND DETERIORATED CONCRETE. WHERE DAMAGED,
PERFORM BEAM BOTTOM REPAIRS PER DETAIL 1 ON DRAWING 137-S701.
3. KNOWN LOCATION OF EXISTING CONCRETE BEAM REQUIRING BEAM CORNER REPAIRS,
SHOWN PARTIALLY HATCHED. SURVEY CORNERS OF ALL BEAMS WITHIN THE WORK LIMITS TO
LOCATE DELAMINATED, SPALLED, AND DETERIORATED CONCRETE. WHERE DAMAGED,
PERFORM BEAM CORNER REPAIRS PER DETAIL 2 ON DRAWING 137-S701.
4. KNOWN LOCATION OF EXISTING CONCRETE BEAM OR WALL LEDGE REQUIRING LEDGE
REPAIRS, SHOWN HATCHED/SHADED. SURVEY ALL BEAM AND WALL LEDGES WITHIN THE WORK
LIMITS TO LOCATE DELAMINATED, SPALLED, AND DETERIORATED CONCRETE. WHERE
DAMAGED, PERFORM BEAM / WALL LEDGE REPAIRS PER DETAIL 3 ON DRAWING 137-S701.
5. KNOWN LOCATION OF EXISTING CONCRETE JOIST REQUIRING JOIST BOTTOM REPAIRS,
SHOWN SHADED. SURVEY ALL JOISTS WITHIN THE WORK LIMITS TO LOCATE DELAMINATED,
SPALLED, AND DETERIORATED CONCRETE. WHERE DAMAGED, PERFORM JOIST BOTTOM
REPAIRS PER DETAIL 4 ON DRAWING 137-S701.
6. THROUGHOUT ENTIRE WORK AREA, APPLY CORROSION INHIBITOR TO ALL JOIST AND
BEAMS PER DETAIL 5 ON DRAWING 137-S701.
7. INSTALL STAINLESS STEEL PIN ANCHORS INTO TOPSIDE OF SUPPORTED CONCRETE FLOOR
SLAB WHERE SHOWN ON PLAN. SPACE ADJACENT PINS AT 2'-0" +/- O.C. AND CENTER PINS
OVER EXISTING JOISTS. REFER DETAIL 6 ON DRAWING 137-S701.
8. WORK LIMITS.
9. PROVIDE SHORE - 10 KIP MINIMUM CAPACITY. INSTALL PRIOR TO BEGINNING CONCRETE
REMOVAL OPERATIONS. REMOVE SHORES AFTER CONCRETE REPAIRS HAVE ATTAINED
SPECIFIED STRENGTH AND AFTER A MINIMUM OF 28 DAYS AFTER PLACEMENT.
10. PROVIDE SHORE - 20 KIP MINIMUM CAPACITY. SEE NOTE 9.
11. PROVIDE SHORE - 50 KIP MINIMUM CAPACITY. SEE NOTE 9.
mailto:jpa@johnpoe.com
E19
E12
E14
E17
E18
E11
W9
W6
E10
W8
E13
E15
E16
W5.9
U
T
V
W
X
Y
Z
AA
BB
CC
9 10 11 12 13 14 158
NEW
ADDITION
NEW
ADDITION
NEW
ADDITION
7"
0"
1 1 /4"
7"
9'
- 6
7"
2"
0"
1 1 /2"
21' - 11 1/2" +/- 21' - 4" +/- 25' - 8 1/2" +/- 20' - 3 5/8" +/- 25' - 8" +/- 21' - 0 7/8" +/- 22' - 3" +/-
158' - 3 1/2" +/-
2 TYP.4TYP.
3TYP.
1A
4 TYP.
7TYP.
7 TYP.
5TYP.
4TYP.
6 8
LEGEND:
BEAM BOTTOM / BEAM CORNER REPAIR
BEAM / WALL LEDGE REPAIR
JOIST BOTTOM REPAIR
PIN ANCHOR LOCATIONS
PIN ANCHOR LOCATIONS IN AREAS OF ASBESTOS CONTAINING FLOORING
OR MASTIC. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR
ADDITIONAL INFORMATION
SHORE
EXISTING FIRST FLOOR PARTITION WALL
9 10 11
NOTE: FOR ALL REPAIRS LISTED IN LEGEND, REFER TO
SPECIFICATION SECTION 03 01 00, PARAGRAPH 3.2B FOR
BID QUANTITIES.
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn
Date
Project No.
Drawing Number
Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne f oo t on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
1-800-362-1523 jpa@johnpoe.com
VA Project No.
THP Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
THP LIMITED INC.
STRUCTURAL ENGINEER
100 E. EIGHTH STREET
CINCINNATI, OH 45202
513.241.3222 P
513.241.2981 F
HEAPY ENGINEERING
MECHANICAL ELECTRICAL
COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
TERRACON INC.
5240 GREEN'S DAIRY ROAD
RALEIGH, NC 27616
919.873.2211 P
919.873.9555 F
SCI Crawlspace Emergent Structural Repairs
06/05/2014
EXISTING FIRST FLOOR FRAMING
PLAN - AREA B
137-S100B
GODFJE
11171.04 590-14-112
Hampton, Va
137C
1/8" = 1'-0"137-S100B
1 FIRST FLOOR EXISTING REPAIRS SOUTH NORTH
DRAWING NOTES:
1. PERFORM ALL WORK IN THE CRAWL SPACE IN ACCORDANCE WITH THE
REQUIREMENTS OF VAMC HAMPTON'S "CONFINED SPACE POLICY" (MCM 00-45). THE
VA HAS DIRECTED THAT THIS WORK IS TO FOLLOW ALL REQUIREMENTS OF "PERMIT
REQUIRED" CONFINED SPACE.
2. THE WORK AREA IS LOCATED IN A CRAWL SPACE BELOW THE GROUND LEVEL
SUPPORTED FLOOR SLAB. TYPICAL DISTANCE BETWEEN CRAWL SPACE DIRT FLOOR
AND BOTTOM SURFACE OF SUPPORTED FLOOR JOIST IS APPROXIMATELY 4’-0”. AN
ACCESS HATCH INTO THE CRAWL SPACE IS LOCATED ON THE WEST SIDE OF THE
BUILDING. NORTHWEST WING OF THE BUILDING. ADDITIONAL ACCESS MAY BE
AVAILABLE ON THE NORTHEAST AND SOUTHEAST SIDE OF THE BUILDING THROUGH
BUILDING ADDITIONAL CURRENTLY UNDER CONSTRUCTION. COORDINATE WITH
COR.
3. UTILITIES (INSULATED STEAM PIPING, SANITARY LINES, ELECTRICAL
LINES/CONDUITS, WATER LINES, MED GAS AND OXYGEN LINES, ETC.) ARE LOCATED
THROUGHOUT THE ENTIRE CRAWL SPACE AREA. DO NOT DAMAGE. THE
CONTRACTOR SHALL PROTECT EXISTING UTILITIES DURING WORK. UTILITIES ARE
CLUSTERED TOGETHER AT MANY LOCATIONS, ESPECIALLY BENEATH OVERHEAD
CONCRETE REPAIR AREAS. THE CONTRACTOR SHALL INCLUDE IN THEIR BID, ALL
COSTS FOR WORKING AROUND UTILITIES. THE CONTRACTOR IS ENCOURAGED TO
VISIT THE SITE PRIOR TO BIDDING TO BECOME FAMILIAR WITH EXISTING SITE
CONDITIONS.
4. AT MISCELLANEOUS LOCATIONS THROUGHOUT THE WORK AREA, UTILITIES ARE
ANCHORED TO THE CONCRETE STRUCTURE. TEMPORARILY SUPPORT UTILITIES
WHERE ANCHORAGE IS DISTURBED DURING OVERHEAD CONCRETE REPAIR
EFFORTS.
5. CONDUITS ARE EMBEDDED IN EXISTING CONCRETE JOIST. LOCATIONS ARE
UNKNOWN. CONTRACTOR SHALL COORDINATE WITH COR AND CONFIRM THAT ALL
CONCRETE ENCASED UTILITIES ARE DISABLED PRIOR TO PERFORMING REPAIRS.
CONDUITS ARE NOT TO BE DAMAGED. DAMAGED CONDUITS WILL BE REPAIRED AT
NO ADDITIONAL COST TO THE GOVERNMENT.
Revisions Date
KEY NOTES:
1. ACCESS INTO CRAWL SPACE VIA. REMOVABLE GRATING AT GRADE LEVEL. ACCESS
OPENING THROUGH WALL INTO CRAWL SPACE IS APPROXIMATELY 3'-0" x 2'-8".
1A. POTENTIAL ACCESS TO CRAWL SPACE IS THROUGH AN ADDITION CURRENTLY UNDER
CONSTRUCTION. COORDINATE ACCESS WITH COR.
2. KNOWN LOCATION OF EXISTING CONCRETE BEAM REQUIRING BEAM BOTTOM REPAIRS,
SHOWN FULLY HATCHED. SURVEY BOTTOM SURFACE OF ALL BEAMS WITHIN THE WORK LIMITS
TO LOCATE DELAMINATED, SPALLED, AND DETERIORATED CONCRETE. WHERE DAMAGED,
PERFORM BEAM BOTTOM REPAIRS PER DETAIL 1 ON DRAWING 137-S701.
3. KNOWN LOCATION OF EXISTING CONCRETE BEAM REQUIRING BEAM CORNER REPAIRS,
SHOWN PARTIALLY HATCHED. SURVEY CORNERS OF ALL BEAMS WITHIN THE WORK LIMITS TO
LOCATE DELAMINATED, SPALLED, AND DETERIORATED CONCRETE. WHERE DAMAGED,
PERFORM BEAM CORNER REPAIRS PER DETAIL 2 ON DRAWING 137-S701.
4. KNOWN LOCATION OF EXISTING CONCRETE BEAM OR WALL LEDGE REQUIRING LEDGE
REPAIRS, SHOWN HATCHED/SHADED. SURVEY ALL BEAM AND WALL LEDGES WITHIN THE WORK
LIMITS TO LOCATE DELAMINATED, SPALLED, AND DETERIORATED CONCRETE. WHERE
DAMAGED, PERFORM BEAM / WALL LEDGE REPAIRS PER DETAIL 3 ON DRAWING 137-S701.
5. KNOWN LOCATION OF EXISTING CONCRETE JOIST REQUIRING JOIST BOTTOM REPAIRS,
SHOWN SHADED. SURVEY ALL JOISTS WITHIN THE WORK LIMITS TO LOCATE DELAMINATED,
SPALLED, AND DETERIORATED CONCRETE. WHERE DAMAGED, PERFORM JOIST BOTTOM
REPAIRS PER DETAIL 4 ON DRAWING 137-S701.
6. THROUGHOUT ENTIRE WORK AREA, APPLY CORROSION INHIBITOR TO ALL JOIST AND
BEAMS PER DETAIL 5 ON DRAWING 137-S701.
7. INSTALL STAINLESS STEEL PIN ANCHORS INTO TOPSIDE OF SUPPORTED CONCRETE FLOOR
SLAB WHERE SHOWN ON PLAN. SPACE ADJACENT PINS AT 2'-0" +/- O.C. AND CENTER PINS
OVER EXISTING JOISTS. REFER DETAIL 6 ON DRAWING 137-S701.
8. WORK LIMITS.
9. PROVIDE SHORE - 10 KIP MINIMUM CAPACITY. INSTALL PRIOR TO BEGINNING CONCRETE
REMOVAL OPERATIONS. REMOVE SHORES AFTER CONCRETE REPAIRS HAVE ATTAINED
SPECIFIED STRENGTH AND AFTER A MINIMUM OF 28 DAYS AFTER PLACEMENT.
10. PROVIDE SHORE - 20 KIP MINIMUM CAPACITY. SEE NOTE 9.
11. PROVIDE SHORE - 50 KIP MINIMUM CAPACITY. SEE NOTE 9.
1'-2"±
3 / 4"
MI
N.
6"±
7 TYP.
86 4 TYP.
5 TYP.
3 TYP.
2 TYP.
EXISTING CONCRETE BEAM.
EXISTING BEAM LEDGE.
EXISTING JOIST BEYOND.
EXISTING DELAMINATION PLANE.
PROVIDE 1/2" SAWCUT AROUND PERIMETER OF REPAIR AREA.
REMOVE ALL SOUND AND UNSOUND CONCRETE WITHIN SHADED AREA. REFER TO
SPECIFICATION SECTION 030100.
EXCAVATE 3/4" CLEAR AROUND ALL REINFORCING. PREPARE AND COAT. REFER TO
SPECIFICATION SECTION 030100.
PREPARE CAVITY SURFACES AND PATCH WITH PRE-PACKAGED CONCRETE OR PNEUMATICALLY
PROJECTED CONCRETE. REFER TO SPECIFICATION SECTION 030100 AND 033713 .
DIMENSION VARIES. ADJUST AS NECESSARY TO REMOVE ALL LOOSE/DETERIORATED
CONCRETE. FOR BIDDING PURPOSES, ASSUME 6" FOR OVERALL AVERAGE DEPTH OF REPAIR.
REPAIR BEAM PER DETAIL 1'-0"± EACH SIDE OF SHORE LOCATIONS PRIOR TO INSTALLING
SHORE. TAPER AND ROUGHEN ENDS TO RECEIVE ADJACENT REPAIRS.
TEMPORARILY SHORE BEAM PRIOR TO CONCRETE EXCAVATIONS. SHORE TO REMAIN UNTIL
AFTER CONCRETE REPAIRS HAVE ATTAINED SPECIFIED STRENGTH AND AFTER A MINIMUM OF
28 DAYS AFTER PLACEMENT.
TYPICAL BEAM BOTTOM REPAIR
UP TO 8"
1 3 TYP.
4TYP. 6 8
7TYP.
2 TYP.5TYP.
EXISTING CONCRETE BEAM.
EXISTING BEAM LEDGE.
EXISTING JOIST BEYOND.
EXISTING DELAMINATION PLANE.
PROVIDE 1/2" SAWCUT AROUND PERIMETER OF REPAIR AREA.
REMOVE ALL SOUND AND UNSOUND CONCRETE WITHIN SHADED AREA.
REFER TO SPECIFICATION SECTION 030100.
EXCAVATE 3/4" CLEAR AROUND ALL REINFORCING. PREPARE AND COAT.
REFER TO SPECIFICATION SECTION 030100.
PREPARE CAVITY SURFACES AND PATCH WITH PRE-PACKAGED
CONCRETE OR PNEUMATICALLY PROJECTED CONCRETE. REFER TO
SPECIFICATION SECTION 030100 AND 033713 .
DIMENSION VARIES. ADJUST AS NECESSARY TO REMOVE ALL
LOOSE/DETERIORATED CONCRETE. FOR BIDDING PURPOSES, ASSUME 6"
FOR OVERALL AVERAGE DEPTH OF REPAIR.
TYPICAL BEAM CORNER REPAIR
6"±
5TYP.
EXISTING CONCRETE BEAM OR WALL.
EXISTING LEDGE.
EXISTING JOIST BEYOND.
EXISTING DELAMINATION PLANE.
PROVIDE 1/2" SAWCUT AROUND PERIMETER OF REPAIR AREA.
REMOVE ALL SOUND AND UNSOUND CONCRETE WITHIN SHADED AREA.
REFER TO SPECIFICATION SECTION 030100.
EXCAVATE 3/4" CLEAR AROUND ALL REINFORCING. PREPARE AND COAT.
REFER TO SPECIFICATION SECTION 030100.
PREPARE CAVITY SURFACES AND PATCH WITH PRE-PACKAGED
CONCRETE OR PNEUMATICALLY PROJECTED CONCRETE. REFER TO
SPECIFICATION SECTION 030100 AND 033713 .
DIMENSION VARIES. ADJUST AS NECESSARY TO REMOVE ALL
LOOSE/DETERIORATED CONCRETE. FOR BIDDING PURPOSES, ASSUME 6"
FOR OVERALL AVERAGE DEPTH OF REPAIR.
TYPICAL BEAM/WALL LEDGE REPAIR
1'- 0"
51/2"
AVERAGE
6TYP.
4 TYP.
9 10
EXISTING CONCRETE SLAB.
EXISTING CONCRETE JOIST OR BRIDGING RIB.
EXISTING DELAMINATION PLANE.
1/2" SAWCUT AROUND PERIMETER OF REPAIR AREA.
REMOVE ALL SOUND AND UNSOUND CONCRETE IN SHADED AREA. REFER TO SPECIFICATION
SECTION 030100.
EXCAVATE 3/4" AROUND ALL REINFORCING. PREPARE AND COAT EXPOSED STEEL. REFER TO
SPECIFICATION SECTION 030100.
PREPARE CAVITY SURFACES AND PATCH WITH PRE-PACKAGED CONCRETE OR PNEUMATICALLY
PROJECTED CONCRETE. REFER TO SPECIFICATION SECTION 030100 AND 033713 .
DIMENSION VARIES. ADJUST AS NECESSARY TO REMOVE ALL LOOSE/DETERIORATED CONCRETE.
FOR BIDDING PURPOSES, ASSUME 6" FOR OVERALL AVERAGE DEPTH OF REPAIR.
TEMPORARILY SHORE JOIST BRIDGING RIB WHERE INDICATED ON PLAN PRIOR TO BEGINNING
EXCAVATIONS. SHORE TO REMAIN UNTIL AFTER CONCRETE REPAIRS HAVE ATTAINED SPECIFIED
STRENGTH AND AFTER A MINIMUM OF 28 DAYS AFTER PLACEMENT.
REPAIR JOIST PER DETAIL 1'-0"± EACH SIDE OF SHORE LOCATIONS PRIOR TO INSTALLING SHORE.
TAPER AND ROUGHEN ENDS TO RECEIVE ADJACENT REPAIRS.
TYPICAL JOIST BOTTOM REPAIR
1'-2"±51/2"
AVERAGE
3 4
32 4
TYP.
43TYP
EXISTING CONCRETE BEAM.
EXISTING CONCRETE JOIST.
APPLY CORROSION INHIBITOR TO ALL CONCRETE SURFACES. REFER TO
SPECIFICATION SECTION 071950.
PRIOR TO APPLICATION OF CORROSION INHIBITOR, PREPARE CONCRETE
SURFACES. REFER TO SPECIFICATION SECTION 071950.
JOIST AND BEAM CORROSION INHIBITOR APPLICATION
1 / 2"
31 / 2"
3TYP.
EXISTING CONCRETE SLAB.
EXISTING CONCRETE JOIST.
EXISTING CRACK IN CONCRETE.
DRILL 3/4" DIA. x 6 1/2" DEEP HOLE TO RECEIVE PIN ANCHOR. BLOW HOLE CLEAN WITH
OIL-FREE COMPRESSED AIR, BRUSH WITH WIRE BRUSH (3) TIMES MINIMUM, AND
RE-BLOW HOLE TO PROVIDE DUST FREE SURFACE.
1/2" DIA. x 6" LONG STAINLESS STEEL THREADED ROD. REFER TO SPECIFICATION
SECTION 030100.
SET IN EPOXY GROUT. REFER TO SPECIFICATION SECTION 030100.
TOP OF FLOOR SLAB TO RECEIVE NEW FLOOR FINISHES/REPAIRS TO EXISTING
FINISHES. PERFORM ALL PIN INSTALLATIONS PRIOR TO FLOOR FINISH REPAIR
OPERATIONS.
PIN ANCHOR INSTALLATION
VA
RI
ES
EXISTING CONCRETE SLAB.
EXISTING CONCRETE JOIST.
JOIST BOTTOM REPAIR PER DETAIL 4 ON 137-S701.
3/8" MIN DIA HANGER ROD.
3/8" MIN DIA EXPANSION ANCHOR.
CLIP ANGLE.
L1 1/2x1 1/2x1/4 FOR PIPES UNDER 2" DIA.
L3x3x1/4 FOR PIPES 2" DIA AND LARGER.
EMBEDMENT INTO EXISTING CONCRETE PER MANUFACTURER'S RECOMMENDATIONS.
SECURING HANGER RODS IN CONCRETE
ANCHORAGE INTO
EXISTING SLAB IS NOT
PERMITTED
PER VA STANDARDS DUE
TO SLAB THICKNESS.
NOTE: INDIVIDUAL ANCHOR LOADS
ARE LIMITED TO 500# IN ORIGINAL
UNREPAIRED AREAS AND 300# IN
CONCRETE REPAIR AREAS.
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn
Date
Project No.
Drawing Number
Dwg. of on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne f oo t on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
1-800-362-1523 jpa@johnpoe.com
VA Project No.
THP Project No.
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
THP LIMITED INC.
STRUCTURAL ENGINEER
100 E. EIGHTH STREET
CINCINNATI, OH 45202
513.241.3222 P
513.241.2981 F
HEAPY ENGINEERING
MECHANICAL ELECTRICAL
COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
TERRACON INC.
5240 GREEN'S DAIRY ROAD
RALEIGH, NC 27616
919.873.2211 P
919.873.9555 F
SCI Crawlspace Emergent Structural Repairs
06/05/2014
RESTORATION DETAILS
137-S701
GODFJE
11171.04 590-14-112
Hampton, Va
137C
1 1/2" = 1'-0"137-S701
1 DETAIL
1 1/2" = 1'-0"137-S701
2 DETAIL
1 1/2" = 1'-0"137-S701
3 DETAIL
1 1/2" = 1'-0"137-S701
4 DETAIL
1 1/2" = 1'-0"137-S701
5 DETAIL
1 1/2" = 1'-0"137-S701
6 DETAIL
Revisions Date
1 1/2" = 1'-0"137-S701
7 DETAIL
5 FT
6 8 10
9 1110 12
1312 14 -16
1614 17 2219
8 1064 532 2 1/21 1/21 1 1/4THRU 3/4
7 7
7 98
NOTE: SEE SPECIFICATIONS FOR
DETAILED HANGER REQUIREMENTS
M A
X
FT.
FT.
IN.
TUBING
PIPE
NOM. SIZE
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
MAXIMUM PIPE/TUBING SUPPORT SPACING
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH
COMPRESSIVE STRENGTH
INSULATION (9 PSF MIN.
DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD
AT HANGER
SADDLE
WELD
1/2" DIA. HANGER
RODS WITH 36"
MAX. SPACING ON
EACH CHANNEL
1-5/8" 12 GAUGE CHANNEL
OR 2"x2"x1/4" ANGLE
BAND
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" MIN.)
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
SIDE VIEW TRAPEZE HANGER FOR UP TO
1000 LB. UNIFORM LOAD
PIPE HANGERS LEGEND
"NOTE" SYMBOL (FOR NOTES ON SAME SHEET)
FIRE SUPPRESSION PIPE (WET)
DIRECTION OF FLOW
F
F F
F F
F
F
4"
2.5"
4"
4"
2.5"
1 2
2.5" FIRE RISER
2.5" FIRE RISER
2.5" FIRE RISER
2.5" FIRE RISER
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn Drawing Number on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
Heapy Project No.: 2011-04008
Date
Project No.
Dwg. of
RDC/JPA Project No.
06/05/2014
SCI Crawlspace Emergent Structural Repairs
11004.01
590-14-112
137C
/4
/2
:0
:2
A
M
PIPE BASEMENT PLAN - REMOVALS
AND NEW WORK - FIRE SUPPRESSION
137-F100
DPBRLT
Hampton, Va.
N Scale: 1/16" = 1'-0"
EXISTING PIPE BASEMENT
GENERAL NOTES:
A ALL PIPING IS SUPPORTED FROM THE UNDERSIDE OF STRUCTURE IN EXPOSED
STRUCTURE AREAS.
B EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON VISUAL OBSERVATION AND/
OR AVAILABLE DRAWING INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK
IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS
AND FIELD VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY
DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE
CONTRACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL BE
BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING FOR
RESOLUTION BEFORE PROCEEDING WITH THE WORK.
C CONTRACTOR IS RESPONSIBLE TO DETERMINE CHARACTERISTICS OF CRAWLSPACE
AND WHAT VENTILATION, EQUIPMENT, PROTECTIVE DEVICES AND OPERATIONAL
CONSIDERATIONS ARE REQUIRED FOR REPAIR OPERATIONS.
D THE MAJORITY OF EXISTING PIPING REQUIRING REMOVAL AND REPLACEMENT OF
HANGERS, SUPPORTS AND PIPING INSULATION IS SHOWN. INCLUDE AN ADDITIONAL
25% (OF EACH SIZE AND TYPE) FOR HANGER/SUPPORT REMOVALS, NEW HANGER/
SUPPORT INSTALLATION, PIPING INSULATION REMOVALS, AND NEW PIPING INSULATION,
TO ACCOMMODATE INCIDENTAL PIPING THAT MAY NOT BE SHOWN BUT IS ASSOCIATED
WITH THE PROJECT SCOPE.
E REFER TO ARCHITECTURAL PLAN 137-A100 FOR INFORMATION REGARDING CRAWL-
SPACE ACCESS LOCATIONS.
F REFER TO DETAIL 7 ON STRUCTURAL DRAWING 137-S701 FOR REQUIREMENTS OF
SECURING HANGERS RODS IN CONCRETE.
G CONTRACTOR SHALL VIEW CRAWLSPACE AS A PERMIT REQUIRED CONFINED SPACE
AND FOLLOW ALL APPROPRIATE REQUIREMENTS FOR PERMIT REQUIRED CONFINED
SPACES OUTLINED IN MCM 00-45 DOCUMENT.
H REFER TO SPECIFICATION SECTION 02 82 11, TRADITIONAL ASBESTOS ABATEMENT,
FOR INSTRUCTIONS IF ASBESTOS SHOULD BE ENCOUNTERED IN PERFORMANCE OF
THIS WORK.
NOTES:
1 EXISTING TO REMAIN.
2 REMOVE ALL PIPING HANGERS IN THIS AREA. TEMPORARILY SUPPORT PIPING FROM
FLOOR DURING REPLACEMENT AND WHILE CONCRETE REPAIR WORK IS PERFORMED.
INSTALL NEW PIPE HANGERS/SUPPORTS PER DETAILS ON THIS SHEET AND
SPECIFICATION SECTION 21 05 11. COORDINATE ALL WORK CLOSELY WITH CONCRETE
REPAIR CONTRACTOR.
3 PIPING IN THIS AREA WILL NOT BE SHUT DOWN. TAKE PRECAUTIONS NECESSARY TO
WORK AROUND PIPES WHILE IN OPERATION.
PIPE BASEMENT DRAWING INDEX - FIRE SUPPRESSION
SHEET DESCRIPTION
137-F100 PIPE BASEMENT PLAN - REMOVALS AND NEW WORK - FIRE
SUPPRESSION
N.T.S.Scale:
KEYPLAN
6 8 10
9 1110 12
1312 14 -16
1614 17 2219
8 1064 532 2 1/21 1/21 1 1/4THRU 3/4
7 7
7 98
NOTE: SEE SPECIFICATIONS FOR
DETAILED HANGER REQUIREMENTS
M A
X
FT.
FT.
IN.
TUBING
PIPE
NOM. SIZE
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
MAXIMUM PIPE/TUBING SUPPORT SPACING
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH
COMPRESSIVE STRENGTH
INSULATION (9 PSF MIN.
DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD
AT HANGER
SADDLE
WELD
1/2" DIA. HANGER
RODS WITH 36"
MAX. SPACING ON
EACH CHANNEL
1-5/8" 12 GAUGE CHANNEL
OR 2"x2"x1/4" ANGLE
BAND
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" MIN.)
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
SIDE VIEW TRAPEZE HANGER FOR UP TO
1000 LB. UNIFORM LOAD
PIPE HANGERS
LEGEND
"NOTE" SYMBOL (FOR NOTES ON SAME SHEET)
CLEANOUTCO
DIRECTION OF FLOW
SHUT-OFF VALVE (BALL)
DOMESTIC HOT WATER RETURN PIPE (DHWR)
DOMESTIC COLD WATER PIPE (DCW)
DOMESTIC HOT WATER PIPE (DHW)
SOIL AND OR WASTE PIPE (SP) OR (WP)
DHWR
DHW
DHW
R
S
U
T
9 10 11 12 13 14
Q
P
O
7a 9a
N
M
L
EA EA.6
W1
W3
W4
W5
WC.2
WD
W2
W4.5
WC
4"
4"
2"
3"
2"
1" 0.75"
2" 2"
1"
0.5"
2" 2"
0.75"
0.75"
0.75"
0.75"
2"
2"
2"
3"
4"
4"
4"
4" 4" 4"
4"
4"
2"
2"
2"
2"
2"
4"
4"
4"
4"
4"
2"
2"
2"
4"
4"
4"
4"
4"
4"
0.75" 0.75"
0.75" 2"
3"
0.75"
2"
3"
0.75"
0.75"
0.75"
2"
3"
0.75"
2"
3"
0.75"
2"
3"
0.75"
2"
3"
1.25"2" 2"
2" 0.75"
2" 3"
4" 4" 1.25"2"
1" 0.5"
2"
1"
0.5"
0.75"
0.75"
0.75"
0.75"
0.75"
0.75"
2"1"0.5"
1"
2"
D C
W D
H W
D H
W R
D C
W D
H W
D H
W R
D C
W D
H W
D H
W R
DHWR
DHW
DCW
DHWR
DHW
DCW
DCW
DCW
DHW
DCW
DHW
O
M A
M V
O
M A
M V
O
M A
M V
DCW
DHW
3 1
A A
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn Drawing Number on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
Heapy Project No.: 2011-04008
Date
Project No.
Dwg. of
RDC/JPA Project No.
06/05/2014
SCI Crawlspace Emergent Structural Repairs
11004.01
590-14-112
137C
/4
/2
:0
:2
A
M
PARTIAL PIPE BASEMENT PLAN -
AREA A REMOVALS AND NEW WORK -
PLUMBING
137-PP100A
DPBRLT
Hampton, Va.
N Scale: 1/8" = 1'-0"
PARTIAL PIPE BSMT. - AREA A
GENERAL NOTES:
A ALL PIPING IS SUPPORTED FROM THE UNDERSIDE OF STRUCTURE IN EXPOSED
STRUCTURE AREAS.
B EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON VISUAL OBSERVATION AND/
OR AVAILABLE DRAWING INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK
IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS
AND FIELD VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY
DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE
CONTRACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL BE
BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING FOR
RESOLUTION BEFORE PROCEEDING WITH THE WORK.
C CONTRACTOR IS RESPONSIBLE TO DETERMINE CHARACTERISTICS OF CRAWLSPACE
AND WHAT VENTILATION, EQUIPMENT, PROTECTIVE DEVICES AND OPERATIONAL
CONSIDERATIONS ARE REQUIRED FOR REPAIR OPERATIONS.
D THE MAJORITY OF EXISTING PIPING REQUIRING REMOVAL AND REPLACEMENT OF
HANGERS, SUPPORTS AND PIPING INSULATION IS SHOWN. INCLUDE AN ADDITIONAL
25% (OF EACH SIZE AND TYPE) FOR HANGER/SUPPORT REMOVALS, NEW HANGER/
SUPPORT INSTALLATION, PIPING INSULATION REMOVALS, AND NEW PIPING INSULATION,
TO ACCOMMODATE INCIDENTAL PIPING THAT MAY NOT BE SHOWN BUT IS ASSOCIATED
WITH THE PROJECT SCOPE.
E REFER TO ARCHITECTURAL PLAN 137-A100 FOR INFORMATION REGARDING CRAWL-
SPACE ACCESS LOCATIONS.
F REFER TO DETAIL 7 ON STRUCTURAL DRAWING 137-S701 FOR REQUIREMENTS OF
SECURING HANGERS RODS IN CONCRETE.
G CONTRACTOR SHALL VIEW CRAWLSPACE AS A PERMIT REQUIRED CONFINED SPACE
AND FOLLOW ALL APPROPRIATE REQUIREMENTS FOR PERMIT REQUIRED CONFINED
SPACES OUTLINED IN MCM 00-45 DOCUMENT.
H REFER TO SPECIFICATION SECTION 02 82 11, TRADITIONAL ASBESTOS ABATEMENT,
FOR INSTRUCTIONS IF ASBESTOS SHOULD BE ENCOUNTERED IN PERFORMANCE OF
THIS WORK.
NOTES:
1 EXISTING TO REMAIN.
2 REMOVE ALL PIPING INSULATION IN THIS AREA. RE-INSULATE PIPING PER
SPECIFICATION SECTION 22 07 11.
3 REMOVE ALL PIPING HANGERS IN THIS AREA. TEMPORARILY SUPPORT PIPING FROM
FLOOR DURING REPLACEMENT AND WHILE CONCRETE REPAIR WORK IS PERFORMED.
INSTALL NEW PIPE HANGERS/SUPPORTS PER DETAILS ON THIS SHEET AND
SPECIFICATION SECTION 22 05 11. COORDINATE ALL WORK CLOSELY WITH CONCRETE
REPAIR CONTRACTOR.
4 AS PART OF BID ITEM 3 (DEDUCT ALTERNATE #2), CONTRACTOR SHALL PERFORM ALL
WORK AS NOTED EXCEPT IN LIEU OF REPLACING ALL DOMESTIC WATER PIPING
INSULATION WITHIN THE PIPE BASEMENT, REPLACE THE DOMESTIC WATER PIPING
INSULATION ONLY WHERE REMOVING EXISTING HANGERS AND INSTALLING NEW
HANGERS (APPROXIMATELY 2 FT. AT EACH HANGER). REFER TO SPECIFICATION
SECTION 22 07 11 FOR INSULATION INFORMATION.
5 PLUMBING PIPING IN THIS AREA WILL NOT BE SHUT DOWN. TAKE PRECAUTIONS
NECESSARY TO WORK AROUND PIPES WHILE IN OPERATION.
PIPE BASEMENT DRAWING INDEX - PLUMBING
SHEET DESCRIPTION
137-PP100A PARTIAL PIPE BASEMENT PLAN - AREA A REMOVALS AND NEW
WORK - PLUMBING
137-PP100B PARTIAL PIPE BASEMENT PLAN - AREA B REMOVALS AND
NEW WORK - PLUMBING
N.T.S.Scale:
U
V
W
X
Y
Z
AA
BB
CC
9 10 11 12 13 14 158
W9
W6
WD
W5.9
M V
M A
O
M V
M A
O
M V
M A
O
4"
0.75"
0.75"
2" 2"2"
4"
4"
4"
0.75"
0.75"
0.75"
4"
0.75"
0.75"
0.75"
0.75" 4"
4"
1.5"
4"
0.75"
4"
4"
1.5" 1"
0.5"
2"
1" 0.5"
2"
1.25"
0.75" 1.25"
1.25"
2" 1"
0.75"
0.75"
0.75" 1"
0.75"4" 2"
4"
4"
2"
4"
4"
2"
2"
3" 3"
2"
2"
2"
4"
4"
4"
4" 4"
0.5" 1"
1.5"
0.75"
2"
4"
4"
4"
4"4"
1.5"
2"
2"
4"
4"
1"
1"
2"
2"
2"
2"
2"
2"
4"
0.75"
2"
3"
0.75"
2"
2.5"
0.75"
0.75"
1.25"
2.5"
D C
W D
H W
D H
W R
D C
W D
H W
D H
W R
DHWR
DHW
DCW
DCW
DHW
DHWR
D C
W
D C
W
D C
W
DHW
DCW
DHW
B B
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn Drawing Number on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
Heapy Project No.: 2011-04008
Date
Project No.
Dwg. of
RDC/JPA Project No.
06/05/2014
SCI Crawlspace Emergent Structural Repairs
11004.01
590-14-112
137C
/4
/2
:0
:2
A
M
PARTIAL PIPE BASEMENT PLAN -
AREA B REMOVALS AND NEW WORK -
PLUMBING
137-PP100B
DPBRLT
Hampton, Va.
N Scale: 1/8" = 1'-0"
PARTIAL PIPE BSMT - AREA B
GENERAL NOTES:
A REFER TO SHEET 137-PP100A FOR GENERAL NOTES, LEGEND AND DRAWNG INDEX.
NOTES:
1 EXISTING TO REMAIN.
2 REMOVE ALL PIPING INSULATION IN THIS AREA. RE-INSULATE PIPING PER
SPECIFICATION SECTION 22 07 11.
3 REMOVE ALL PIPING HANGERS IN THIS AREA. TEMPORARILY SUPPORT PIPING FROM
FLOOR DURING REPLACEMENT AND WHILE CONCRETE REPAIR WORK IS PERFORMED.
INSTALL NEW PIPE HANGERS/SUPPORTS PER DETAILS ON THIS SHEET AND
SPECIFICATION SECTION 22 05 11. COORDINATE ALL WORK CLOSELY WITH CONCRETE
REPAIR CONTRACTOR.
4 AS PART OF BID ITEM 3 (DEDUCT ALTERNATE #2), CONTRACTOR SHALL PERFORM ALL
WORK AS NOTED EXCEPT IN LIEU OF REPLACING ALL DOMESTIC WATER PIPING
INSULATION WITHIN THE PIPE BASEMENT, REPLACE THE DOMESTIC WATER PIPING
INSULATION ONLY WHERE REMOVING EXISTING HANGERS AND INSTALLING NEW
HANGERS (APPROXIMATELY 2 FT. AT EACH HANGER). REFER TO SPECIFICATION
SECTION 22 07 11 FOR INSULATION INFORMATION.
5 PLUMBING PIPING IN THIS AREA WILL NOT BE SHUT DOWN. TAKE PRECAUTIONS
NECESSARY TO WORK AROUND PIPES WHILE IN OPERATION.
N.T.S.Scale:
6 8 10
9 1110 12
1312 14 -16
1614 17 2219
8 1064 532 2 1/21 1/21 1 1/4THRU 3/4
7 7
7 98
NOTE: SEE SPECIFICATIONS FOR
DETAILED HANGER REQUIREMENTS
M A
X
FT.
FT.
IN.
TUBING
PIPE
NOM. SIZE
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
MAXIMUM PIPE/TUBING SUPPORT SPACING
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH
COMPRESSIVE STRENGTH
INSULATION (9 PSF MIN.
DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD
AT HANGER
SADDLE
WELD
1/2" DIA. HANGER
RODS WITH 36"
MAX. SPACING ON
EACH CHANNEL
1-5/8" 12 GAUGE CHANNEL
OR 2"x2"x1/4" ANGLE
BAND
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" MIN.)
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
SIDE VIEW TRAPEZE HANGER FOR UP TO
1000 LB. UNIFORM LOAD
PIPE HANGERS
UP
UP
CLEAN OUT
AS AN AID IN COORDINATING THE VARIOUS TRADES.)
LISTED SIZE OF PIPE OR EQUIPMENT ITEM. (TO BE USED
APPROXIMATE ELEVATION FROM FLOOR TO CENTER OF
BUTTERFLY VALVE
BALL VALVE
EX. EXISTING
DIRECTION OF FLOW
SIDE CONNECTION
RISE OR DROP IN PIPE
BOTTOM CONNECTION, 45 DEG. OR 90 DEG.
TOP CONNECTION, 45 DEG. OR 90 DEG.
GATE VALVE
CO
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLY
MEDIUM PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
HWS
HWR
MPS
MPR
HEATING
MAXIMUM
(16 PSIG THRU 59 PSIG)
MEDIUM PRESSURE STEAM SUPPLY
MEDIUM PRESSURE STEAM CONDENSATE RETURNMPR
MAX
NOM
MIN
MPS
NOMINAL
MINIMUM
HIGH PRESSURE STEAM SUPPLY (60 PSIG & ABOVE)
HIGH PRESSURE STEAM CONDENSATE RETURNHPR
HPS
FLR. FLOOR
CHILLED WATER RETURN
CHILLED WATER SUPPLYCHS
CHR
AIR CONDITIONING
DEGREEDEG
DIAMETERDIA
F FAHRENHEIT
FT FEET
CHILLED WATER RETURNCHR
CHILLED WATER SUPPLYCHS
HEATING HOT WATER RETURNHWR
HEATING HOT WATER SUPPLYHWS
INCHESIN
HIGH PRESSURE STEAM CONDENSATE RETURN
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)HPS
HPR
PIPE UP
PIPE DOWN
9'-6"
COR CONTRACTING OFFICERS REPRESENTATIVE
GENERAL
PIPING EXTENDS IN SAME DIRECTION
PIPING SYMBOLS
GENERAL
VALVES
ABBREVIATIONS
BB
AA
Z
Y
X
W
V
U
T
S
R
7 9 10 12 13 14 15
Q
P
O
CHR
4"
H W
S C
H R
C H
S
3" 4"4"3"
CHS
4"
HWR
2.5"
HWS
2.5"
1.5"
4"
1.5"
4"
H P
R H
P S
C H
R C
H S
4"4"
C H
S C
H R
CHS
CHR
M P
R M
P S
MPSMPR
H P
R H
P S
H W
S H
W R
C H
S C
H R
HWR
HWS
2.5"2.5"
MPS
1.5"
3"3"
M P
R M
P S
1" 1.5"
2"2"
4"4"
1" 1.5"
4" 4" 1.5"
1"
1"
1.25"
CHR
CHS
MPR
2"2"
1"
1 1
3 4
5 8
3 4
5 8
H W
R
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn Drawing Number on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
Heapy Project No.: 2011-04008
Date
Project No.
Dwg. of
RDC/JPA Project No.
06/05/2014
SCI Crawlspace Emergent Structural Repairs
11004.01
590-14-112
137C
/4
/2
:2
:2
A
M
PIPE BASEMENT PLAN REMOVALS
AND NEW WORK - HVAC
137-MP100
PCWDLE
Hampton, VA.
1. EXISTING PIPING TO REMAIN.
2. PIPING (SUPPLY AND RETURN) UP TO FIRST FLOOR AND ROOF.
3. REMOVE ALL PIPING INSULATION IN THIS AREA. RE-INSULATE PIPING PER
SPECIFICATION SECTION 23 07 11.
4. REMOVE ALL PIPING HANGERS IN THIS AREA. TEMPORARILY SUPPORT
PIPING FROM FLOOR DURING REPLACEMENT AND WHILE CONCRETE REPAIR
WORK IS PERFORMED. INSTALL NEW PIPE HANGERS/SUPPORTS PER
DETAILS ON THIS SHEET AND SPECIFICATION SECTION 23 05 11.
COORDINATE ALL WORK CLOSELY WITH CONCRETE REPAIR CONTRACTOR.
5. AS PART OF BID ITEM 2 (DEDUCT ALTERNATE #1), CONTRACTOR SHALL
PERFORM ALL WORK AS NOTED EXCEPT IN LIEU OF REPLACING ALL HVAC
HYDRONIC, STEAM AND CONDENSATE PIPING INSULATION WITHIN THE PIPE
BASEMENT, REPLACE THE HVAC HYDRONIC, STEAM AND CONDENSATE
PIPING INSULATION ONLY WHERE REMOVING EXISTING HANGERS AND
INSTALLING NEW HANGERS (APPROXIMATELY 2 FT. AT EACH HANGER).
REFER TO SPECIFICATION SECTION 23 07 11 FOR INSULATION INFORMATION.
6. NEW PIPING TO BE INSTALLED UNDER PROJECT RENOVATE/EXPAND SCI
PHASE II, 590-911. NO WORK REQUIRED.
7. CHILLED WATER PIPING INSULATION WORK SHALL OCCUR WHEN THE
CHILLED WATER CAN BE SHUT DOWN. COORDINATE ALL/ANY OUTAGES
WITH COR.
8. STEAM AND CONDENSATE PIPING INSULATION WORK SHALL OCCUR WHEN
THE STEAM SERVICE CAN BE SHUT DOWN. COORDINATE ALL/ANY OUTAGES
WITH COR.
NOTES
GENERAL NOTES
1. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.
2. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. COORDINATE
WITH ALL OTHER TRADES.
3. INSULATE PIPING WHERE EXISTING INSULATION HAS BEEN DAMAGED AND/OR
REMOVED IN THE PERFORMANCE OF WORK IN THIS PROJECT.
4. THE CONTRACTORS SHALL REFER TO ALL SPECIFICATION SECTIONS AND
THESE DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE
SPACE AND SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS
DRAWINGS COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED
JOINTLY AT ALL TIMES. EACH CONTRACTOR SHALL REFER TO THE GENERAL
REQUIREMENTS OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED
ON THE DRAWINGS ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE
PROJECT AND MUST BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF
DISCREPANCIES OCCUR, CONTACT THE COR THRU THE CONTRACTING
OFFICER FOR CLARIFICATION BEFORE PROCEEDING.
5. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES,
THE CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR
THE CONDITIONS ON THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND
PROPERTY DURING PERFORMANCE OF THE WORK. THIS WILL APPLY
CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. SEE
SPECIFICATIONS FOR MORE SPECIFIC DETAILS ON RESPONSIBILITIES.
6. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND
COR TO MAINTAIN OPERATION OF THE EXISTING FACILITY.
7. EACH CONTRACTOR SHALL COORDINATE HIS WORK WITH THE…