36C24618R0176-00001004.pdf
PDF 2 MB Posted
- Attached to
- Project 590-14-112, SCI Crawlspace Emergent Structural Repairs Federal contract opportunity
- Solicitation number
- 36C24618R0176
About this file
36C24618R0176 00001 Amendment 00001 - Attachment C - Asbestos Sampling Report.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24618C0056-000.docx | DOCX document | |
| 36C24618R0176-00003000.docx | DOCX document | |
| 36C24618R0176-00003001.pdf | ||
| 36C24618R0176-00002001.pdf | ||
| 36C24618R0176-00002000.docx | DOCX document | |
| 36C24618R0176-00001005.pdf | ||
| 36C24618R0176-00001003.pdf | ||
| 36C24618R0176-00001001.pdf | ||
| 36C24618R0176-00001002.pdf | ||
| 36C24618R0176-00001000.docx | DOCX document | |
| 36C24618R0176-002.docx | DOCX document | |
| 36C24618R0176-006.docx | DOCX document | |
| 36C24618R0176-003.pdf | ||
| 36C24618R0176-001.docx | DOCX document | |
| 36C24618R0176-005.pdf | ||
| 36C24618R0176-004.pdf | ||
| 36C24618R0176-007.docx | DOCX document | |
| 36C24618R0176-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Terracon Consultants, Inc. 2401 Brentwood Road, Suite 107 Rale igh, North Carol ina 27604
P [919] 873 2211 F [919] 873 9555 terracon.com
June 24, 2016
RDC/John Poe Architects 116 East Third Street Dayton, Ohio 45402
Attn: Mr. Tom Hesse, AIA
Re: Limited Asbestos Sampling Report Hampton Veteran’s Affairs Medical Center
100 Emancipation Drive Hampton, Virginia
Terracon Project No.: 70167296
Dear Mr. Hesse:
The purpose of this report is to present the results of the limited asbestos survey performed on
June 15, 2016 for RDC/John Poe Architects (Client) at the above referenced area located on the campus of Hampton Veteran’s Affairs Medical Center in Hampton, Virginia. This survey was conducted in general accordance with Terracon Proposal No. P70167296 dated June 7, 2016.
We understand that these services were requested due to the planned suspect wall material disturbance and proposed work in the crawl space where it has been brought into question about potential asbestos presence/contamination. Our survey activities were limited to the specific areas as detailed to Terracon by site representatives.
Asbestos was identified during the course of our limited survey. Please refer to the attached report for details.
Terracon appreciates the opportunity to provide this service to RDC/John Poe Architects. If you have any questions regarding this report, please contact the undersigned at 919.873.2211.
Sincerely, Terracon Consultants Inc.
For:
Michael Penny, EI Scott D. Rohlf, CIH
Project Environmental Engineer Authorized Project Reviewer
LIMITED ASBESTOS SAMPLING REPORT
Hampton Veteran’s Affairs Medical Center
100 Emancipation Drive
Hampton, Virginia
June 24, 2016
Terracon Project 70167296
Prepared For:
RDC/John Poe Architects
Dayton, Ohio
Prepared By:
Terracon Consultants, Inc.
Raleigh, North Carolina
Responsive ■ Resourceful ■ Reliable i
TABLE OF CONTENTS
Page No.
1.0 INTRODUCTION
1.1 PROJECT OBJECTIVE
2.0 BUILDING DESCRIPTION
3.0 FIELD ACTIVITIES
3.1 VISUAL ASSESSMENT
3.2 PHYSICAL ASSESSMENT
3.3 SAMPLE COLLECTION
3.4 SAMPLE ANALYSIS
4.0 REGULATORY OVERVIEW
5.0 FINDINGS AND RECOMMENDATIONS
6.0 GENERAL COMMENTS
Appendix A Asbestos Survey Sample Summary
Appendix B Identified Asbestos-Containing Materials
Appendix C Asbestos Analytical Laboratory Data
Appendix D General Crawl Space Sample Location Diagram
Responsive ■ Resourceful ■ Reliable 1
LIMITED ASBESTOS SAMPLING REPORT
HAMPTON VETERAN’S AFFAIRS MEDICAL CENTER
100 EMANCIPATION DRIVE
HAMPTON, VIRGINIA
TERRACON PROJECT NO. 70167296
1.0 INTRODUCTION
Terracon conducted asbestos sampling of client-selected areas of the crawl space and patient rooms located on the campus of Hampton Veteran’s Affairs Medical Center in Hampton, Virginia. This limited survey was conducted on June 15, 2016 by a Commonwealth of Virginia
Accredited Asbestos Building Inspectors in general accordance with Terracon Proposal No.
P70167296 dated June 7, 2016.
The select areas were surveyed and homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented. Although reasonable effort was made to survey accessible suspect materials, additional suspect but un-sampled materials could be located in voids or in other concealed areas. Suspect ACM samples were collected in general accordance with the sampling protocols outlined in EPA regulation 40 CFR 763
(Asbestos Hazard Emergency Response Act, AHERA). Samples were delivered to an accredited laboratory for analysis by Polarized Light Microscopy.
1.1 Project Objective
We understand this limited asbestos sampling was requested due to the planned suspect wall material disturbance and proposed work in the crawl space. We understand the purpose of these services is to identify and quantify ACM present prior to renovation activities and work in the crawl space. EPA regulation 40 CFR 61, Subpart M, National Emission Standards for
Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during renovation or demolition activities. The asbestos NESHAP requires that potentially regulated asbestos-containing building materials be identified, classified and quantified prior to planned disturbances, renovation or demolition activities.
2.0 BUILDING DESCRIPTION
Building 137 – Eastern Unoccupied Patient Rooms
The site structure is a partially occupied medical building. However, the client provided scope of work was limited to walls located on two unoccupied wings on the east side of the building.
The walls were finished with plaster over foam insulation board. Terracon did not assess other portions of the building.
Limited Asbestos Sampling Report
Hampton Veteran’s Affairs Bldg. 137 ■ Hampton, Virginia
June 24, 2016 ■ Terracon Project No. 70167296
Responsive ■ Resourceful ■ Reliable 2
Building 137 – Crawl Space
Terracon assessed the crawl space areas below the two eastern wings of the building. This totaled approximately 4,000 square feet of dirt floor crawl space. The crawl space walls consisted of concrete. Construction debris (floor tiles, insulation, concrete, wood) was observed throughout the crawl space areas.
3.0 FIELD ACTIVITIES
The limited survey was conducted by Commonwealth of Virginia Accredited Asbestos Building
Inspectors Mr. Michael Penny and Ms. Alicia Coley (VA Accredited Asbestos Inspector
Numbers 3303004009 and 3303003481, respectively). The survey was conducted in general accordance with the sample collection protocols established in EPA regulation 40 CFR 763, the Asbestos Hazard Emergency Response Act (AHERA). A summary of survey activities is provided below.
3.1 Visual Assessment
Our survey activities began with a visual observation of the work areas to identify homogeneous areas of suspect ACM. A homogeneous area consists of building materials that appear similar throughout in terms of color, texture and date of application. At the request of the Client, only select suspect wall materials were sampled, and only a select portion of the crawl space was assessed. Building materials identified as concrete, glass, wood, masonry, metal or rubber were not considered suspect. The survey was limited to readily and safely accessible areas of the proposed renovation area.
3.2 Physical Assessment
A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material, which can be crumbled, pulverized or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
3.3 Sample Collection
Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with AHERA sampling protocols. Random samples of suspect materials were collected in each homogeneous area. The inspectors collected bulk samples using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
Building 137 – Eastern Unoccupied Patient Rooms
Eight (8) bulk samples were collected from one homogeneous area of suspect ACM from the vacant patient room walls.
Responsive ■ Resourceful ■ Reliable 3
Building 137 – Crawl Space
Terracon separated the two subject crawl space area into two 16-section grids and collected one surface soil sample from each area within those grids. Terracon collected a total of 32 samples of soil and debris from the crawl space.
A summary of suspect ACM samples collected during the survey is included as Appendix A.
3.4 Sample Analysis
Bulk samples were submitted under chain of custody to EMSL Analytical, Inc. (EMSL) of
Morrisville, North Carolina for analysis by Polarized Light Microscopy (PLM) with dispersion staining techniques per EPA methodology (40 CFR 763, Subpart F). The percentage of asbestos, where applicable, was determined by microscopic visual estimation. EMSL is accredited under the National Voluntary Laboratory Accreditation Program NVLAP
(Accreditation Number 200671-0).
4.0 REGULATORY OVERVIEW
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. It also requires the identification and classification of existing building materials prior to demolition or renovation activity. Under NESHAP, asbestos-containing building materials are classified as either friable, Category I non-friable or Category II non-friable ACM. Friable materials are those that, when dry, may be crumbled, pulverized or reduced to powder by hand pressure. Category I non-friable ACM includes packings, gaskets, resilient floor coverings and asphalt roofing products containing more than
1% asbestos. Category II non-friable ACM are any materials other than Category I materials that contain more than 1% asbestos.
In the state of Virginia, the Virginia Department of Labor and Industry (DOLI) regulates asbestos abatement and removal through Virginia Occupational Safety and Health (VOSH) regulations, Environmental Protection Agency’s National Emission Standards for Hazardous
Air Pollutants (NESHAP), and enforcement of the Asbestos Notification regulations found in the Labor Laws of Virginia (§40.1-51.20). The DOLI requires that any asbestos-related activity conducted in a public building be performed by personnel accredited by the Commonwealth of Virginia Department of Professional and Occupational Regulation (DPOR).
Written notification to DOLI of renovation or demolition activities is required only if asbestos is present and the amount to be disturbed is greater than 10 linear feet or 10 square feet. If non-friable asbestos-containing material, roofing, flooring and siding materials are in good condition and when installed, encapsulated or removed do not become friable, a notification is not required. If the ACM is not in good condition or ACM removal will be conducted using mechanical means, notification is required. The asbestos abatement contractor or facility
Responsive ■ Resourceful ■ Reliable 4 owner must submit an Asbestos Notification of Demolition and Renovation form to the DOLI along with the appropriate fees within at least 20 calendar days prior to the scheduled asbestos removal activity or demolition start date by certified mail or hand delivery.
The EPA requires that no person remove more than 35 cubic feet (1 cubic meter), 160 square feet (15 square meters), or 260 linear feet (80 linear meters) of regulated asbestos-containing material without a permit issued by the EPA. Applications must be postmarked or received by the EPA at least 10 working days prior to the scheduled removal start date. The application, must be mailed to the following address:
• Asbestos Coordinator
USEPA
Region III
Mail Code 3LC62
1650 Arch St.
Philadelphia, PA 19103-2029
Virginia Occupational Safety and Health (VOSH) regulations govern workplace exposure to asbestos. The VOSH Asbestos standard requires employee exposure to airborne asbestos fibers be maintained at or below 0.1 asbestos fibers per cubic centimeter of air (0.1 f/cc). The
VOSH Asbestos standard classifies construction and maintenance activities, which could disturb ACM and specifies work practices and precautions, which employers must follow when engaging in each class of regulated work. This standard also sets forth communication of hazard requirements for building owners, including requirements for posting areas of known or presumed ACM (PACM). The standard requires building owners and lessees who control the management and recordkeeping functions of a building to maintain information regarding the presence, location and quantity of ACM and PACM for the duration of ownership or lease.
The information must be transferred to successive building owners and to employers whose employees may be exposed to asbestos, including tenants who will occupy areas containing
ACM or PACM.
5.0 FINDINGS AND RECOMMENDATIONS
Based on the results of laboratory analysis, asbestos was identified in 3 of the 32 samples of the following material:
Soil (crawl space)
Appendix D includes a general location diagram of areas identified to contain asbestos.
Employees working in these areas and surrounding areas should be at least OSHA Class III workers and should wear proper respiratory and clothing protection.
Responsive ■ Resourceful ■ Reliable 5
Laboratory analytical reports are included in Appendix C. It is possible that additional suspect material be located in concealed areas such as wall cavities or in depths of soil beyond this scope. If additional suspect materials is found during renovation activities, they should be assumed to contain asbestos until laboratory analysis can confirm or deny their asbestos content.
6.0 GENERAL COMMENTS
This limited asbestos sampling was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions and recommendations expressed in this report are based on conditions observed during our survey of the building.
The information contained in this report is relevant to the date on which this survey was performed, and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by RDC/John Poe Architects for specific application to their project as discussed. This report is not a bidding document.
Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information, which may have been used in the preparation of this report. No warranty, expressed or implied is made.
APPENDIX A
ASBESTOS SURVEY SAMPLE SUMMARY
HA Sample No. Description Sample Location Lab Results 1 HVA-1 Plaster with black felt paper and gray mastic on blue foam Wall adjacent to new building on CMU None Detected
1 HVA-2 Plaster with black felt paper and gray mastic on blue foam Wall adjacent to new building on CMU None Detected
1 HVA-3 Plaster with black felt paper and gray mastic on blue foam Wall adjacent to new building on CMU None Detected
1 HVA-4 Plaster with black felt paper and gray mastic on blue foam Wall adjacent to new building on CMU None Detected
1 HVA-5 Plaster with black felt paper and gray mastic on blue foam Wall adjacent to new building on CMU None Detected
1 HVA-6 Plaster with black felt paper and gray mastic on blue foam Wall adjacent to new building on CMU None Detected
1 HVA-7 Plaster with black felt paper and gray mastic on blue foam Wall adjacent to new building on CMU None Detected
1 HVA-8 Plaster with black felt paper and gray mastic on blue foam Wall adjacent to new building on CMU None Detected
2 A1 Soil and debris North-East Wing Crawl Space None Detected
3 A2 Soil and debris North-East Wing Crawl Space None Detected
4 A3 Soil and debris North-East Wing Crawl Space None Detected
5 A4 Soil and debris North-East Wing Crawl Space None Detected
6 B1 Soil and debris North-East Wing Crawl Space None Detected
7 B2 Soil and debris North-East Wing Crawl Space None Detected
8 B3 Soil and debris North-East Wing Crawl Space None Detected
9 B4 Soil and debris North-East Wing Crawl Space None Detected
10 C1 Soil and debris North-East Wing Crawl Space None Detected
11 C2 Soil and debris North-East Wing Crawl Space None Detected
12 C3 Soil and debris North-East Wing Crawl Space None Detected
13 C4 Soil and debris North-East Wing Crawl Space Chrysotile
14 D1 Soil and debris North-East Wing Crawl Space None Detected
15 D2 Soil and debris North-East Wing Crawl Space None Detected
16 D3 Soil and debris North-East Wing Crawl Space Chrysotile
17 D4 Soil and debris North-East Wing Crawl Space None Detected
18 E1 Soil and debris South-East Wing Crawl Space None Detected
19 E2 Soil and debris South-East Wing Crawl Space Chrysotile
20 E3 Soil and debris South-East Wing Crawl Space None Detected
21 E4 Soil and debris South-East Wing Crawl Space None Detected
22 F1 Soil and debris South-East Wing Crawl Space None Detected
23 F2 Soil and debris South-East Wing Crawl Space None Detected
24 F3 Soil and debris South-East Wing Crawl Space None Detected
25 F4 Soil and debris South-East Wing Crawl Space None Detected
26 G1 Soil and debris South-East Wing Crawl Space None Detected
27 G2 Soil and debris South-East Wing Crawl Space None Detected
28 G3 Soil and debris South-East Wing Crawl Space None Detected
29 G4 Soil and debris South-East Wing Crawl Space None Detected
30 H1 Soil and debris South-East Wing Crawl Space None Detected
31 H2 Soil and debris South-East Wing Crawl Space None Detected
32 H3 Soil and debris South-East Wing Crawl Space None Detected
33 H4 Soil and debris South-East Wing Crawl Space None Detected
Results in bold indicate asbestos-containing materials.
*Analyzed by a qualitative PLM analysis; asbestos quantities are not provided
100 Emancipation Drive
Hampton, Virginia
Appendix A
ASBESTOS SURVEY SAMPLE SUMMARY
Hampton Veteran Affair's Building 137
A-1
APPENDIX B
IDENTIFIED ASBESTOS-CONTAINING MATERIALS
HA
Sample
No.
Description Material Location
NESHAP
Classification
Type
Asbestos Condition
Estimated
Quantity*
13 C4 Soil and Debris North-East Wing
Crawl Space N/A Chrysotile Damaged
Approximately
100 square feet
16 D3 Soil and Debris North-East Wing
Crawl Space N/A Chrysotile Damaged
Approximately
100 square feet
19 E2 Soil and Debris South-East Wing
Crawl Space N/A Chrysotile Damaged
Approximately
100 square feet
Note: All quantities should be verified by the asbestos abatement contractor.
Appendix B
IDENTIFIED ASBESTOS-CONTAINING MATERIALS
Hampton Veteran Affair's Building 137 100 Emancipation Drive
Hampton, Virginia
B-2
APPENDIX C
ASBESTOS LABORATORY ANALYTICAL REPORT
Sample Description Appearance Result Notes
Test Report: Qualitative asbestos analysis of soils using the EPA 600/R-93/116 method
Attn: Michael Penny Terracon Consultants, Inc.
2401 Brentwood Road Suite 107 Raleigh, NC 27604
Received: 06/16/16 1:00 PM
70167296
Fax: (919) 873-9555 Phone: (919) 873-2211
Project:
6/20/2016Analysis Date:
6/15/2016Collected:
EMSL Analytical, Inc.
2500 Gateway Centre Blvd., Suite 600, Morrisville, NC 27560 Phone/Fax: (919) 465-3900 / (919) 465-3950 http://www.EMSL.com raleighlab@emsl.com
291603935 CustomerID: TITA51 CustomerPO:
ProjectID:
EMSL Order:
A1 291603935-0009
North Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
A2 291603935-0010
North Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
A3 291603935-0011
North Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
A4 291603935-0012
North Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
B1 291603935-0013
North Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
B2 291603935-0014
North Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
B3 291603935-0015
North Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
B4 291603935-0016
North Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
C1 291603935-0017
North Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
Billy Barnes, Asbestos Lab Manager or other approved signatory
1Test Report PLMQualw/Types-7.21.0 Printed: 6/20/2016 3:59:12 PM
Analyst(s)
Soil is a problem matrix due to its inherent heterogeneity and there is a likelihood for false negatives with this analysis. EMSL recommends more specialized methodologies such as the EPA 600/R-93/116 with milling preparation. EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted.
Samples analyzed by EMSL Analytical, Inc. Morrisville, NC
Billy Barnes (5) Joshua Moorman (8)
Roxsee Stover (19)
Initial report from 06/20/2016 14:16:43 http://www.EMSL.com mailto:raleighlab@emsl.com
Attn: Michael Penny Terracon Consultants, Inc.
2401 Brentwood Road Suite 107 Raleigh, NC 27604
Received: 06/16/16 1:00 PM
70167296
Fax: (919) 873-9555 Phone: (919) 873-2211
Project:
6/20/2016Analysis Date:
6/15/2016Collected:
EMSL Analytical, Inc.
2500 Gateway Centre Blvd., Suite 600, Morrisville, NC 27560 Phone/Fax: (919) 465-3900 / (919) 465-3950 http://www.EMSL.com raleighlab@emsl.com
291603935 CustomerID: TITA51 CustomerPO:
ProjectID:
EMSL Order:
C2 291603935-0018
North Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
C3 291603935-0019
North Crawl Space, Soil/Debris
Brown/Gray None Detected Fibrous Homogeneous
C4 291603935-0020
North Crawl Space, Soil/Debris
Gray/White Non-Fibrous Homogeneous
Chrysotile
D1 291603935-0021
North Crawl Space, Soil/Debris
Brown/Black None Detected Fibrous Homogeneous
D2 291603935-0022
North Crawl Space, Soil/Debris
Various None Detected Fibrous Homogeneous
D3 291603935-0023
North Crawl Space, Soil/Debris
Various Fibrous Homogeneous
Chrysotile
D4 291603935-0024
North Crawl Space, Soil/Debris
Brown/Tan/Black None Detected Fibrous Homogeneous
E1 291603935-0025
South Crawl Space, Soil/Debris
Various None Detected Fibrous Homogeneous
E2 291603935-0026
South Crawl Space, Soil/Debris
Brown Fibrous Homogeneous
Chrysotile
Billy Barnes, Asbestos Lab Manager or other approved signatory
2Test Report PLMQualw/Types-7.21.0 Printed: 6/20/2016 3:59:12 PM
Analyst(s)
Soil is a problem matrix due to its inherent heterogeneity and there is a likelihood for false negatives with this analysis. EMSL recommends more specialized methodologies such as the EPA 600/R-93/116 with milling preparation. EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted.
Samples analyzed by EMSL Analytical, Inc. Morrisville, NC
Billy Barnes (5) Joshua Moorman (8)
Roxsee Stover (19)
Initial report from 06/20/2016 14:16:43
Attn: Michael Penny Terracon Consultants, Inc.
2401 Brentwood Road Suite 107 Raleigh, NC 27604
Received: 06/16/16 1:00 PM
70167296
Fax: (919) 873-9555 Phone: (919) 873-2211
Project:
6/20/2016Analysis Date:
6/15/2016Collected:
EMSL Analytical, Inc.
2500 Gateway Centre Blvd., Suite 600, Morrisville, NC 27560 Phone/Fax: (919) 465-3900 / (919) 465-3950 http://www.EMSL.com raleighlab@emsl.com
291603935 CustomerID: TITA51 CustomerPO:
ProjectID:
EMSL Order:
E3 291603935-0027
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
E4 291603935-0028
South Crawl Space, Soil/Debris
Brown/Tan/Black None Detected Fibrous Homogeneous
F1 291603935-0029
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
F2 291603935-0030
South Crawl Space, Soil/Debris
Brown/Tan None Detected Fibrous Homogeneous
F3 291603935-0031
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
F4 291603935-0032
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
G1 291603935-0033
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
G2 291603935-0034
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
G3 291603935-0035
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
Billy Barnes, Asbestos Lab Manager or other approved signatory
3Test Report PLMQualw/Types-7.21.0 Printed: 6/20/2016 3:59:12 PM
Analyst(s)
Soil is a problem matrix due to its inherent heterogeneity and there is a likelihood for false negatives with this analysis. EMSL recommends more specialized methodologies such as the EPA 600/R-93/116 with milling preparation. EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted.
Samples analyzed by EMSL Analytical, Inc. Morrisville, NC
Billy Barnes (5) Joshua Moorman (8)
Roxsee Stover (19)
Initial report from 06/20/2016 14:16:43
Attn: Michael Penny Terracon Consultants, Inc.
2401 Brentwood Road Suite 107 Raleigh, NC 27604
Received: 06/16/16 1:00 PM
70167296
Fax: (919) 873-9555 Phone: (919) 873-2211
Project:
6/20/2016Analysis Date:
6/15/2016Collected:
EMSL Analytical, Inc.
2500 Gateway Centre Blvd., Suite 600, Morrisville, NC 27560 Phone/Fax: (919) 465-3900 / (919) 465-3950 http://www.EMSL.com raleighlab@emsl.com
291603935 CustomerID: TITA51 CustomerPO:
ProjectID:
EMSL Order:
G4 291603935-0036
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
H1 291603935-0037
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
H2 291603935-0038
South Crawl Space, Soil/Debris
Brown/Tan None Detected Fibrous Homogeneous
H3 291603935-0039
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
H4 291603935-0040
South Crawl Space, Soil/Debris
Brown None Detected Fibrous Homogeneous
Vermiculite and Soil are known problem matrices and negative results cannot be guaranteed. Additional analysis such as CARB 435 milling prep or ASTM Draft Soil Sieving is recommended for proper quantification of asbestos in vermiculite and soil.
Billy Barnes, Asbestos Lab Manager or other approved signatory
4Test Report PLMQualw/Types-7.21.0 Printed: 6/20/2016 3:59:12 PM
Analyst(s)
THIS IS THE LAST PAGE OF THE REPORT.
Soil is a problem matrix due to its inherent heterogeneity and there is a likelihood for false negatives with this analysis. EMSL recommends more specialized methodologies such as the EPA 600/R-93/116 with milling preparation. EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted.
Samples analyzed by EMSL Analytical, Inc. Morrisville, NC
Billy Barnes (5) Joshua Moorman (8)
Roxsee Stover (19)
Initial report from 06/20/2016 14:16:43
EMSL Analytical, Inc.
2500 Gateway Centre Blvd., Suite 600 Morrisville, NC 27560
Tel/Fax: (919) 465-3900 / (919) 465-3950 http://www.EMSL.com / raleighlab@emsl.com
291603935EMSL Order:
Customer ID: TITA51
Customer PO:
Project ID:
Attention: Phone:Michael Penny (919) 873-2211
Fax:Terracon Consultants, Inc. (919) 873-9555
Received Date:2401 Brentwood Road 06/16/2016 1:00 PM
Analysis Date:Suite 107 06/17/2016
Collected Date:Raleigh, NC 27604 06/15/2016
Project: 70167296
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light
Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
HVA-1-Skim Coat
291603935-0001
None DetectedNon-fibrous (Other)98%Cellulose2%White
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-1-Base Coat
291603935-0001A
None DetectedNon-fibrous (Other)98%Cellulose
Glass
2%
<1%
Gray
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-1-Felt Paper
291603935-0001B
None DetectedNon-fibrous (Other)76%Cellulose
Synthetic
12%
12%
Black
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-1-Mastic
291603935-0001C
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
Inseparable foam.
HVA-2-Skim Coat
291603935-0002
None DetectedNon-fibrous (Other)98%Cellulose2%White
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-2-Base Coat
291603935-0002A
None DetectedNon-fibrous (Other)100%Cellulose
Glass
<1%
<1%
Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-2-Felt Paper
291603935-0002B
None DetectedNon-fibrous (Other)78%Cellulose
Synthetic
10%
12%
Black
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-2-Mastic
291603935-0002C
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
Inseparable foam.
HVA-3-Skim Coat
291603935-0003
None DetectedNon-fibrous (Other)100%Cellulose<1%White
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
Initial report from: 06/20/2016 14:16:43
Page 1 of 4PLM - 1.69 Printed: 6/20/2016 3:59 PM
Tel/Fax: (919) 465-3900 / (919) 465-3950 http://www.EMSL.com / raleighlab@emsl.com
291603935EMSL Order:
Customer ID: TITA51
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light
Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
HVA-3-Base Coat
291603935-0003A
None DetectedNon-fibrous (Other)100%Cellulose<1%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-3-Felt Paper
291603935-0003B
None DetectedNon-fibrous (Other)76%Cellulose
Synthetic
12%
12%
Black
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-3-Mastic
291603935-0003C
None DetectedNon-fibrous (Other)100%Cellulose<1%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
Inseparable foam.
HVA-4-Skim Coat
291603935-0004
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-4-Base Coat
291603935-0004A
None DetectedNon-fibrous (Other)100%Glass<1%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-4-Felt Paper
291603935-0004B
None DetectedNon-fibrous (Other)80%Cellulose
Synthetic
10%
10%
Black
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-4-Mastic
291603935-0004C
None DetectedNon-fibrous (Other)100%Cellulose<1%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-5-Skim Coat
291603935-0005
None DetectedNon-fibrous (Other)98%Cellulose2%White
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-5-Base Coat
291603935-0005A
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-5-Felt Paper
291603935-0005B
None DetectedNon-fibrous (Other)76%Cellulose
Synthetic
12%
12%
Black
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-5-Mastic
291603935-0005C
None DetectedNon-fibrous (Other)100%Cellulose<1%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
Page 2 of 4PLM - 1.69 Printed: 6/20/2016 3:59 PM
Tel/Fax: (919) 465-3900 / (919) 465-3950 http://www.EMSL.com / raleighlab@emsl.com
291603935EMSL Order:
Customer ID: TITA51
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light
Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
HVA-6-Skim Coat
291603935-0006
None DetectedNon-fibrous (Other)98%Cellulose2%White
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-6-Base Coat
291603935-0006A
None DetectedNon-fibrous (Other)96%Cellulose
Glass
2%
2%
Gray
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-6-Felt Paper
291603935-0006B
None DetectedNon-fibrous (Other)40%Cellulose60%Brown/Black
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-6-Mastic
291603935-0006C
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-7-Skim Coat
291603935-0007
None DetectedNon-fibrous (Other)95%Cellulose5%White
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-7-Base Coat
291603935-0007A
None DetectedNon-fibrous (Other)98%Cellulose2%Gray
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-7-Felt Paper
291603935-0007B
None DetectedNon-fibrous (Other)40%Cellulose60%Brown/Black
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-7-Mastic
291603935-0007C
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-8-Skim Coat
291603935-0008
None DetectedNon-fibrous (Other)98%Cellulose2%White
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-8-Base Coat
291603935-0008A
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-8-Felt Paper
291603935-0008B
None DetectedNon-fibrous (Other)40%Cellulose60%Brown/Black
Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
HVA-8-Mastic
291603935-0008C
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Wall Adjacent to New
Bldg on CMU -
Plaster w/ Black Felt
Paper & Gray Mastic on Blue Foam
Page 3 of 4PLM - 1.69 Printed: 6/20/2016 3:59 PM
Tel/Fax: (919) 465-3900 / (919) 465-3950 http://www.EMSL.com / raleighlab@emsl.com
291603935EMSL Order:
Customer ID: TITA51
Customer PO:
Project ID:
Analyst(s)
Olivia Bradley (20)
Roxsee Stover (12)
Billy Barnes, Asbestos Lab Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government . Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Morrisville, NC NVLAP Lab Code 200671-0, VA 3333 000278, WVA LT000296
Page 4 of 4PLM - 1.69 Printed: 6/20/2016 3:59 PM
OrderID: 291603935
APPENDIX D
GENERAL CRAWL SPACE SAMPLE LOCAITON DIAGRAM
UP
UP
GENERAL NOTE
A. REFER TO SHEET 137-P001 FOR DRAWING INDEX, LEGEND AND NOTES.
P418
P418
P413
FD1
FD2
P107
FD2
P418
P413
FD1
P107
CO
-2
VR
P418
CO
P413
FD1
P418
FD2
P107
2-
P413
FD1
FD2
P107
P418
P418
P413
FD1
FD2
P107
VR
VR
P413
P107
P418
FD1
VR
FD2
CO CO COCO
P107
FD2
P418
P413FD1
VR
P418
CO
FD1
VR
P413
CO
VR
P418
P413
P418
FD1
FD2
P506
P418
P413
P418
P413
P418
VR
FD1
FD1
FD2
P418
P506
P506 FD2
-2
P418
FD2
P506
P413
VR
FD1
FD1
FD2
P418
P506
P506
2-
FD2
EXISTING SCI PHASE1
ELECTRICAL MANHOLE
EXISTING SCI PHASE1
ELECTRICAL HANDHOLE
EXISTING SCI PHASE1
ELECTRICAL MANHOLE
CO
P413
P418
EXISTING
DUCTBANK
EXISTING
DUCTBANK
P413
CO
0.75"
2"
3"
0.75"
2"
3"
0.75"
2"
3"
CO
CO
1.25" 2"
0.75"
1.5" 2"
CO
CO
10.75"
-2" DCW
1 -0.5" DHWR
1.5" DHW
2"
11"
1"
10.75"
2"
1 -0.5" DHWR
1.5" DHW
1 -2" DCW
1.25"
2"
FD1
CO
P418
P418
P418
P413 P505
P413
FD1
P418
FD2
P107
P418
CO
P418
P529
P531
P529
P107
FD2
P418
P413
FD1
VR
P413
P418
P506
FD2
FD1
P418
FD2
P506
P413
P418
CO
2-
P418
FD1
P413
FD2
P107
CO
P418
4" DS BOOT
BY P.C.
4" DS BOOT
BY P.C.
4" DS BOOT
BY P.C.
ST
S T
S T
S T
4"
4"
4"
4"
4"
4"
ST
15"
ST
ST
S T
S T
AD1
AD1
AD1
AD1
AD1
4" 4"
4"
4"
4"
4"
4"
4"
COTRAP
1 1
P524
CO
M V
M A
O
M V
M A
O
M V
M A
O
0.75"
0.75" DHW &
1.5" DCW TO
1ST FLOOR
ABOVE
1.5"
CO
CO
TO EXISTING
WATER HEATERS
0.75"8
0.75"
CO
CO
CO
CO
VR
0.75"
1.25" 2"
0.75"
P418
2"
0.75"
0.75"
FD4
FD4
0.75"
2" 0.75"
1.5"
0.75"
1.5"
1.5" 0.75" 0.5"EXISTING 1.5" DCW
& 0.75" DHW RISERS
1 1.5" 0.75"
EXISTING 0.75"
DCW & DHW
RISERS
0.5"
P418
P505
VR
-2
14 14
14 14
14 14
14 14
13 13
1 15
1 15
CO
12 12
VR
VR
VR
VR
SS VR
VR
FD1
P103 P418
FD1
VR
VR
-2 2-
VR
VR
SS
MA
MV
O2
MA
MV
O2
M V
M A
O
6" DS
ST
S T
S T
S T
1 -6" DS
1 -6" DS
4" DS
STCO
ST
6" DS
CONNECT WHERE
EXISTING PIPING
DROPS THRU GRADE
CONNECT WHERE
EXISTING PIPING
DROPS THRU GRADE
S T
ST
TEST-Y
& CO
PIPING DROPS
THRU GRADE
A A
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn Drawing Number on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
Heapy Project No.: 2011-04008
Date
Project No.
Dwg. of
RDC/JPA Project No.
Hampton VA, VAMC Renovate / Expand SCI, Phase II, 590-911
PARTIAL PIPE BASEMENT PLAN -
AREA A - NEW WORK
137-P101
DPBRLT
Hampton, Va.
09/14/2012
11004.00
590-911
NOTES:
N Scale: 1/8" = 1'-0"1
PARTIAL PIPE BASEMENT - AREA A - NEW
WORK
N.T.S.Scale:
KEYPLAN
1 EXISTING TO REMAIN.
2 EXTEND 2" DCW, 1" DHW & 0.75" DHWR SUPPLY RISERS UP TO ABOVE
FIRST FLOOR CEILING TO SERVE NEW ADDITION AND RENOVATED AREA AS
INDICATED ON SHEET 137-P103.
3 EXTEND 2" DCW, 1.25" DHW & 0.75" DHWR SUPPLY RISERS UP TO ABOVE
FIRST FLOOR CEILING TO SERVE NEW ADDITION AND RENOVATED AREA AS
INDICATED ON SHEET 137-P103.
4 EXTEND 2" DCW & 1 DHW SUPPLY RISERS UP TO ABOVE FIRST FLOOR CEILING
TO SERVE NEW ADDITION AND RENOVATED AREA AS INDICATED ON SHEET 137-P103.
5 EXTEND 0.75" DHWR PIPING UP TO ABOVE FIRST FLOOR CEILING TO SERVE
RENOVATED AREA AS INDICATED ON SHEET 137-P103.
6 EXTEND 2" DCW, 1.25" DHW & 0.75" DHWR SUPPLY RISERS UP TO ABOVE
FIRST FLOOR CEILING TO SERVE NEW ADDITION AND RENOVATED AREA AS
INDICATED ON SHEET 137-P103.
7 PROVIDE 0.5 GPM FLOW CONTROLLER ON DHWR WITH ISOLATION VALVES.
8 PROVIDE 0.25 GPM FLOW CONTROLLER ON DHWR WITH ISOLATION VALVES.
9 EXTEND 0.5" DCW & 0.5" DHW SUPPLY RISERS UP TO FIRST FLOOR TO SERVE P418
FIXTURE AS INDICATED ON SHEET 137-P103.
10 EXTEND 1.5" DCW & 0.75" DHW SUPPLY RISERS UP TO FIRST FLOOR TO SERVE P505
FIXTURE AS INDICATED ON SHEET 137-P103.
11 UNDER DEDUCT ALTERNATE 5 DELETE ALL WORK ASSOCIATED WITH RESIDENT/WARMING
KITCHEN.
12 UNDER DEDUCT ALTERNATE 4 ALL STORM SYSTEM WORK IN COURTYARD(S) SHALL REMAIN.
13 UNDER DEDUCT ALTERNATE 6 DELETE ALL WORK SHOWN IN THIS AREA. REFER TO DEDUCT
ALTERNATE PLAN(S) ON SHEET 137-P801.
14 UNDER DEDUCT ALTERNATE 6 & 7 REVISE PLUMBING FIXTURE LAYOUT AS REQUIRED TO
MATCH ARCHITECTURAL PLANS. REFER TO DEDUCT ALTERNATE PLAN(S) ON SHEET 137-P801.
15 EXISTING 0.75" DCW EXTENDING UP TO FIRST FLOOR ABOVE TO SERVE EXISTING EXTERIOR
WALL HYDRANT TO REMAIN.
16 EXISTING 0.75" MA & 0.75" O2 MEDICAL GAS RISERS EXTENDING UP TO SERVE FIRST
FLOOR TO REMAIN. EXTEND NEW 1.5" MV PIPING UP TO ABOVE FIRST FLOOR CEILING TO
SERVE FIRST FLOOR AS INDICATED ON SHEET 137-P105.
Revisions Date mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Callout D3 mdpenny Callout C4 mdpenny Text Box General sample location diagram
Highlighted area indicates area that reported asbestos in soil sample.
Samples were analyzed utilizing qualitative PLM analysis.
GENERAL NOTE
A. REFER TO SHEET 137-P001 FOR DRAWING INDEX, LEGEND AND NOTES.
P413
FD1
FD2
P107
FD2
P418
P413
FD1
P107
CO
-2
VR
CO
CO
FD1
FD1
VR
P413
P413
FD2
P107
FD2
P107
P4182-
P418
CO
P413
CO
P413
VR
CO
FD1
P418
FD2
P107
P418
CO
P418
P107
FD2
P418
FD1
VR
P413
P107
FD2
P418
P418
CO
VR
FD1
P413
P418
P107
P413
FD1
FD2
VR
P418
P418
CO
FD1
P418
FD2
P506
P418
P413CO
CO
VR
P418
P413
P418
FD1
FD2P506
VR
P413
EXISTING SCI PHASE1
ELECTRICAL MANHOLE
EXISTING
DUCTBANK
P418
FD2 P506
P413
P418
P413
P418
P413
P418
P413
P418
FD1
FD1
FD2
FD2
P418
P506
P506
-2
VR
FD1
FD1
FD2
FD2
P418
P506
P506
-2
VR
P413
P418
0.75"
2"
3"
CO
FD2
P506
P418
CO
P413
P418
P418
P413P107
P413
FD2
FD2
VR
P418 P107
FD2
P418
FD1
P413
VR
CO
10.75" -
CO
CO
CO
P418
CO
10.75" -
FD1
- 1.5" DCW
1" DHW
0.5" DHWR
1"
1.5"
2"
1 - 2" DCW
1.25" DHW
0.75"
2"
1.25"
0.75"
2" 1.25"
0.75"
2" 1.25"
1.25"
2.5"
1 - 1"
CO
1.5"
CO
1.5" 1"
0.75"
2"1.25"
0.75"
1.5"1"
CO
FD1
VR
FD1
P418
P418
P418
P418
P529
P808
P529
ST ST ST ST
ST
ST
S T
S T
4"
4"
4"
4"
4"
CO
4" DS BOOT
BY P.C.
4" DS BOOT
BY P.C.
M V
O
M V
O
M V
O
M A
M A
M A
AD1
CO
AD1
AD1
TRAP
4"
4"
4"
4"
4"
AD1
CO
AD1
4"
4"
TRAP
ST
8"8"6"6" 6"
6"
INV. @
722'-7"
EXISTING
DUCTBANK
EXISTING
DUCTBANK
VR
P418
P413
P107
FD2
CO
P413
P529
P531
4"
FD4
FD4
0.75"
0.5"
REC.
PUMP-
0.75"
0.75"
O2
MV
MA
P418
12 12
VR
VR
VR
VR
VR
VR
CO
P530
VR
VR
VR
MV
MA
O2
P808
S T
S T
STST ST
CO
B B
Drawing Title
Approved: Project Director Location
Building Number
Project Title
Checked Drawn Drawing Number on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
A R C H I T E C T SJ O H N P O E
937 461 3290 PHONE
937 461 0260 FAX
jpa@johnpoe.com
ARCHITECT/ENGINEERS:CONSULTANTS:
RDC /
524 FERNWOOD DRIVE
ALTAMONTE SPRINGS, FLORIDA
32701
Heapy Project No.: 2011-04008
Date
Project No.
Dwg. of
RDC/JPA Project No.
Hampton VA, VAMC Renovate / Expand SCI, Phase II, 590-911
PARTIAL PIPE BASEMENT PLAN -
AREA B - NEW WORK
137-P102
DPBRLT
Hampton, Va.
09/14/2012
11004.00
590-911
NOTES:
N Scale: 1/8" = 1'-0"1
PARTIAL PIPE BASEMENT PLAN - AREA B
- NEW WORK
N.T.S.Scale:
KEYPLAN
1 EXISTING TO REMAIN.
2 EXTEND 2" DCW, 1.25" DHW & 0.75" DHWR SUPPLY RISERS UP TO
ABOVE FIRST FLOOR CEILING TO SERVE RENOVATED AREA AND NEW
ADDITION AS INDICATED ON SHEET 137-P104.
3 NEW 0.75" DHWR FROM FIRST FLOOR ABOVE. PIPING CONTINUED
ON SHEET 137-P104
4 EXTEND NEW 1.5" DCW, 1" DHW & 0.75" DHWR SUPPLY RISERS UP TO
ABOVE FIRST FLOOR CEILING TO SERVE RENOVATED AREA AS
INDICATED ON SHEET 137-P104.
5 P.C. SHALL EXTEND 8" STORM PIPING 5'-0" FROM BUILDING EXTERIOR
WALL AND STUB FOR EXTENSION BY S.U.C.
6 RE-INSTALL EXISTING RE-CIRCULATION PUMP IN NEW 0.75" RECIRCULATION
LINE.
7 PROVIDE 0.5 GPM FLOW CONTROLLER ON DHWR WITH ISOLATION VALVES.
8 PROVIDE 0.25 GPM FLOW CONTROLLER ON DHWR WITH ISOLATION VALVES.
9 PROVIDE COMBINATION BALANCING/SHUT-OFF VALVE. SET UNIT TO
MAINTAIN FLOW OF 0.5 GPM.
10 EXISTING 0.75" DCW EXTENDING UP TO FIRST FLOOR ABOVE TO SERVE
EXISTING EXTERIOR WALL HYDRANT TO REMAIN.
11 UNDER DEDUCT ALTERNATE 4 ALL STORM SYSTEM WORK IN COURTYARD(S)
SHALL REMAIN.
12 UNDER DEDUCT ALTERNATE 6 & 7 DELETE ALL WORK IN THIS AREA. REFER
TO DEDUCT ALTERNATE PLAN(S) ON SHEET 137-P801.
13 EXISTING 0.75" MA & 0.75" O2 MEDICAL GAS RISERS EXTENDING UP TO SERVE
SERVE FLOOR TO REMAIN. EXTEND NEW 1.5" MV PIPING UP TO ABOVE FIRST
FLOOR CEILING TO SERVE FIRST FLOOR AS INDICATED ON SHEET 137-P106.
Revisions Date mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Rectangle mdpenny Callout E2 mdpenny Text Box General sample location diagram
Highlighted area indicates area that reported asbestos in soil sample.
Samples were analyzed utilizing qualitative PLM analysis.
| 291603935_007.pdf |
| 291603935_008.pdf |
| 291603935_coc.pdf |
| 2016-06-24T14:06:57-0400 | |
| Weaver, Dwight D. |
| 2016-06-24T14:11:32-0400 | |
| Rohlf, Scott D. |
File details come from the government source that posted it.