Text version
EF-1
(E)EF
(E)EF
(E)EF
CU-1
26"x24" L/A
IH-1
EF-2
151617
D
EXISTING MRI CHILLER
ROOF HATCH
EXISTING ROOF DRAIN 2
S-101
CONTRACTOR TO VERIFY SIZES AND LOCATIONS IN FIELD
EXISTING 8" LT GA STUD @ 16" O.C., TYP
DASHED LINES INDICATE ANTICIPATED HVAC
REINFORCEMENT. CONTRACTOR SHALL
VERIFY EXISTING FRAMING IN THE FIELD AND
REFER TO TYPICAL DETAILS FOR OPENING
OPTIONS. SHOULD FRAMING DIFFER FROM
WHAT IS SHOWN THE CONTRACTOR SHALL
NOTIFY THE ENGINEER IMMEDIATELY.
SEE OPENING DETAILS 3A, 3B, 3C
/2
1' - 6 1/2"
CU-1 DESIGN WEIGHT: 493 LBS
IH-1 DESIGN WEIGHT: 134 LBS
EF-1 DESIGN WEIGHT: 63 LBS
EF-2 DESIGN WEIGHT: 410 LBS
/2
3' - 0 1/2"
SEE NOTE NO. 1
CU-1
DUNNAGE BY CONTRACTOR
INTERIOR RAIL LOCATED AS REQ'D PER
MFR SPECIFICATIONS
300HDS-97 (G90) DUNNAGE SPANNING EXISTING
ROOF CURBS
EXISTING ROOFEXISTING ROOF
CURBS TO
REMAIN, TYP
1 1/2"x1 1/2"x0'-3" LONG (MIN)
16 GA LT GA CLIP W/(2) #10
FASTENERS, EA LEG (MIN) (G90)
S-101
1' - 4" TYP
A S
R E
Q 'D
EXISTING OPENING HEADER TO
BE ADJUSTED IN THE FIELD AS
REQ'D +/- 12" MAX,
OR USE NEW 800 S162-54
M A
X
NOTE: CONTRACTOR CAN UTILIZE
EXISTING OPENINGS SHOULD THEY
MEET NEW EQUIPMENT
REQUIREMENTS. MODIFICATIONS
TO EXISTING OPENING HEADERS
ARE PERMITED UP TO 12" MAX
PROVIDED THAT JOIST RELOCATION
IS NOT REQUIRED. EXISTING JOIST
SPACING TO BE VERIFIED IN FIELD
EXISTING 8" LT GA JOIST
CLARK-DIETRICH S545 W/(5) #10
EA LEG (OR EQUAL) IF REQUIRED
EXISTING 8" LT GA JOIST
NEW 8" LT GA JOIST SISTERED TO
EXISTING
EXISTING 8" LT GA JOIST CUT AS REQ'D
TO ACCOMODATE LARGER OPENING
CLARK-DIETRICH S545 W/(5) #10 EA LEG
(OR EQUAL)
800 S162-54 LT GA HEADER, TYP
S-101
1' - 4" TYP
4" MAX
EXISTING 8" LT GA JOIST
NEW 8" LT GA JOIST SISTERED TO
EXISTING
EXISTING 8" LT GA JOIST CUT AS REQ'D
TO ACCOMODATE LARGER OPENING
CLARK-DIETRICH S545 W/(5) #10 EA LEG
(OR EQUAL)
800 S162-54 LT GA HEADER, TYP
S-101
1' - 4" TYP
NEW JOIST TO BE
SISTERED TO EXISTING
EXISTING JOIST
(2)#10 SCREWS @ 16" C/C, TYP
300HDS-97 (G90) DUNNAGE SPANNING
EXISTING ROOF CURBS
EXISTING CURB TO REMAIN
LT GA CLIP W/(2) #10 FASTERNERS, EA LEG
DUNNAGE BY CONTRACTOR
CU-1
1 EF-1
UNIT MARK WEIGHT (LBS) OPENING SIZE
63 18.5"X18.5"
2 (DUCT) N/A SEE MEP
3 EF-2 410 N/A
4 CU-1 493 N/A
5 IH-1 134 36.5"X36.5"
PLAN LEGEND
NOTE: SEE MEP FOR LOCATIONS. CONTRACTOR TO
VERIFY ALL OPENING SIZES, ETC. WITH MEP
N O
R
TH
NO REVISION DATE
ADDENDUM NO. 1
HVAC UPGRADE FOR
MRI SUITE
LOUIS A. JOHNSON VA MEDICAL CENTER
CLARKSBURG, WEST VIRGINIA
540-18-011
JU BK08/05/2019
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
FULLY SPRINKLERED
A
B
C
D
E
F
2000 GEORGETOWNE DRIVE
PH: 724.444.1100
www.pve-llc.com
PVE PROJECT NUMBER:
ARCHITECTS/ENGINEERS:SEAL
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
WATERFRONT CORPORATE PARK III, SUITE 101
SEWICKLEY, PA 15143
BID DOCUMENTS
161663
FAX: 724.444.1104
1 08/08/2019
PLANS AND
DETAILS II
1/4" = 1'-0"
LEVEL 2 PLAN
1" = 1'-0"
CU-1 SECTION
NOTES
1. CONTRACTOR SHALL REUSE EXISTING ROOF CURBS AND PROVIDE NEW DUNNAGE AS REQUIRED. SEE SECTION 2/S-101.
2. CONTRACTOR TO VERIFY ALL OPENING SIZES AND LOCATIONS WITH MEP.
1" = 1'-0" 3A
USE EXISTING OPENING - OPTION 1
1" = 1'-0"
3B
NEW OPENING OPTION 2
1" = 1'-0" 3C
NEW OPENING OPTION 3
3" = 1'-0"
JOIST DETAIL
NOTE: CONTRACTOR TO DOUBLE UP END JOISTS SUPPORTING NEW LT GA HEADERS WHEN OPENING SIZE
EXCEEDS EXISTING JOIST SPACING.
NOTE: CONTRACTOR TO DOUBLE UP END JOISTS SUPPORTING NEW LT GA HEADERS WHEN OPENING SIZE
EXCEEDS EXISTING JOIST SPACING.
1 1/2" = 1'-0"
CU-1 DUNNAGE SECTION
EXISTING
EXISTING
EXISTING
Dwg. of
S101
File details come from the government source that posted it. Updated .