About this file

36C24519B0011 S02 MRI Upgrade Drawings.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Construction Site Preparation for MRI Upgrade Project 540-18-011, newest first.
File Type Posted
36C24519C0223-000.docx DOCX document
36C24519B0011-0002001.pdf PDF
36C24519B0011-0002000.docx DOCX document
36C24519B0011-0002000.docx DOCX document
36C24519B0011-0002001.pdf PDF
36C24519B0011-0001004.pdf PDF
36C24519B0011-0001003.pdf PDF
36C24519B0011-0001001.pdf PDF
36C24519B0011-0001000.docx DOCX document
36C24519B0011-0001002.pdf PDF
36C24519B0011-0001000.docx DOCX document
36C24519B0011-0001003.pdf PDF
36C24519B0011-0001001.pdf PDF
36C24519B0011-0001002.pdf PDF
36C24519B0011-0001004.pdf PDF
36C24519B0011-006.pdf PDF
36C24519B0011-002.pdf PDF
36C24519B0011-004.pdf PDF
36C24519B0011-005.pdf PDF
36C24519B0011-007.pdf PDF
36C24519B0011-003.pdf PDF
36C24519B0011-001.docx DOCX document
36C24519B0011-002.pdf PDF
36C24519B0011-006.pdf PDF
36C24519B0011-007.pdf PDF
36C24519B0011-005.pdf PDF
36C24519B0011-001.docx DOCX document
36C24519B0011-004.pdf PDF
36C24519B0011-000.docx DOCX document
36C24519B0011-000.docx DOCX document
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

FULLY SPRINKLERED

A

B

C

D

E

F

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

ARCHITECTS/ENGINEERS:SEAL

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

BID DOCUMENTS

18030

HVAC UPGRADE FOR

MRI SUITE

LOUIS A. JOHNSON VA MEDICAL CENTER

CLARKSBURG, WEST VIRGINIA

540-18-011

CJC AC

G001 08/05/2019 161

COVER

HVAC UPGRADE FOR MRI SUITE

BUILDING 1

LOUIS A. JOHNSON VA MEDICAL CENTER

1 MEDICAL CENTER DRIVE

CLARKSBURG, WV 26301

PROJECT DIRECTORY

OWNER:

LOUIS A. JOHNSON VA MEDICAL CENTER

1 MEDICAL CENTER DRIVE

CLARKSBURG, WV 26301

(304) 623-3461

CONTACT: LARRY EAKLE

ARCHITECT/ENGINEER

AE WORKS

209 SANDUSKY STREET

PITTSBURGH, PA 15212

(412) 287-7333

CONTACT: CHRIS CHAMPAGNE, PE

DRAWING INDEX

SHEET # SHEET NAME

G001 COVER

G100 ICRA PLAN AND NOTES

M001 HVAC SYMBOLS, ABBREVIATIONS AND GENERAL NOTES

MD101 MRI SUITE HVAC DEMOLITION PLAN

M101 MRI SUITE HVAC NEW WORK PLAN

M102 HVAC ROOF PLAN

M501 HVAC DETAILS

M502 HVAC DETAILS

M601 HVAC CONTROLS

M701 HVAC SCHEDULES

E001 ELECTRICAL SYMBOLS AND ABBREVIATIONS

E101 MRI SUITE ELECTRICAL PLANS

E501 ELECTRICAL DETAILS AND SCHEDULES

S001 GENERAL NOTES

S100 PLANS AND DETAILS

S101 PLANS AND DETAILS II

SITE

SITE

NO REVISION DATE

H S

DUST CONTROL PLAN NOTES / DUST CONTROL PLAN HAZARD ASSESSMENT

PRIOR TO INITIATING WORK, CONTRACTOR AND COR WILL ACCESS THE SCOPE OF THE CONSTRUCTION

ACTIVITIES AND DETERMINE THE POTENTIAL RISK GROUPS INVOLVED BASED ON THE LOCATION OF ACTIVITIES

AND EXTENT AND DURATION OF THE WORK. LOW RISK GROUPS ARE CONSIDERED "OFFICE WORKERS", MEDIUM

RISK GROUPS ARE CONSIDERED ALL INPATIENT AND OUTPATIENT AREAS NOT IN THE HIGH RISK GROUP. HIGH

RISK GROUP DESIGNATION INCLUDES INPATIENT AREAS SUCH AS PEDIATRIC AND ADULT OPERATING/DELIVERY

ROOMS, CATH LABS, MYELO SUPPRESSION UNITS, ICUS, DIALYSIS, NURSERIES AS WELL AS CLINIC AREAS

(CLINICS ASSOCIATED WITH HEMATOLOGY, ONCOLOGY, PEDIATRIC INFECTION DISEASE, OR TRANSPLANT

SERVICES) AND SERVICE AREAS (CENTRAL PROCESSING, STERILE PROCESSING, FOOD PREP & SERVICE AREA

AND PHARMACIES. THE VAMC INFECTION CONTROL GROUP WILL CONFIRM AND APPROVE THE DESIGNATION

PROVIDED IN THIS SUBMITTED DUST CONTROL PLAN. VAMC IS ALSO RESPONSIBLE FOR ANY AND ALL INFECTION

CONTROL MEASURES DETERMINED AND ESTABLISHED BY VAMC POLICY, SUCH AS THE RELOCATION OF HIGH

RISK PATIENTS, APPROVING ALTERNATE TRAFFIC PATHS FOR CONSTRUCTION WORKERS OR ESTABLISH

ALTERNATE TRAFFIC PATTERNS FOR STAFF, PATIENTS AND VISITORS. THE PLAN SHOULD BE REVISED

ACCORDING TO SPECIFIC VAMC POLICIES OR CHANGING CONDITIONS AT THE SITE AS THEY MAY OCCUR.

INTERNAL DEMOLITION AND CONSTRUCTION ACTIVITIES DUST AND DEBRIS CONTROL

• BARRIER SYSTEMS: THE AREA SHOULD BE ISOLATED, AS THE PROJECT REQUIRES. SMALL, SHORT

DURATION PROJECTS GENERATING MINIMAL DUST MAY USE FIRE-RATED PLASTIC SHEETING, BUT

SHOULD BE SEALED AT FULL CEILING HEIGHT WITH AT LEAST 2-FOOT OVERLAPPING FLAPS FOR

ACCESS TO ENTRY. ANY DUST SHALL BE IMMEDIATELY CLEANED IF TRACKED OUTSIDE OF THE

CONSTRUCTION BARRIER. UPON COMPLETION OF THE CONSTRUCTION PROJECT DUST BARRIERS

SHALL BE REMOVED CAREFULLY TO MINIMIZE SPREADING OF DUST AND THE CONTRACTOR SHALL

HAVE TEMPORARY DUST PROTECTION IN PLACE BEFORE REMOVAL OF A PERMANENT BARRIER.

CONTRACTOR PERSONNEL SHALL MONITOR AND PERFORM BARRIER MAINTENANCE AND BE

EDUCATED TO NOTICE SIMPLE CLUES SUCH AS ACCUMULATIONS OF VISIBLE DUST EVIDENCED BY

FOOTPRINTS, OPENED DOORS/WINDOWS EVIDENCED BY PRESENCE OF INSECTS AND FLIES, WET

CEILING TILE, ETC.

• TRAFFIC CONTROL; DESIGNATED ENTRY AND EXIT PROCEDURES SHALL BE DEFINED. EGRESS PATHS

SHOULD BE FREE OF DEBRIS; DESIGNATED ELEVATORS SHOULD BE USED DURING SCHEDULED TIMES;

AND ONLY AUTHORIZED PERSONNEL SHOULD BE ALLOWED TO ENTER THE CONSTRUCTION ZONE.

SIGNAGE SHOULD DIRECT PEDESTRIAN TRAFFIC AWAY FROM THE CONSTRUCTION AREA AND

MATERIALS.

• DEMOLITION DEBRIS: DEBRIS SHOULD BE REMOVED IN CARTS WITH TIGHTLY FITTED COVERS, USING

DESIGNATED TRAFFIC ROUTES. EFFORTS SHOULD BE MADE TO MINIMIZE USE OF ELEVATORS WITH

AN EMPHASIS ON TRANSPORT DURING THE LOWEST PERIOD OF ACTIVITY. DEBRIS SHOULD BE

REMOVED DAILY AND AT TIMES SPECIFIED BY THE VAMC. IF CHUTES ARE USED TO DIRECT DEBRIS

OUTSIDE, HIGH EFFICIENCY PARTICULATE AIR (HEPA) FILTERED NEGATIVE AIR MACHINES SHOULD BE

USED, AND THE CHUTE OPENING SHOULD BE SEALED WHEN NOT IN USE. FILTERS SHOULD BE

BAGGED AND SEALED BEFORE BEING TRANSPORTED OUT OF THE CONSTRUCTION AREA. THE

CONTRACTOR SHALL NOT HAUL DEBRIS THROUGH PATIENT-CARE AREAS WITH PRIOR APPROVAL OF

THE VAMC.

• EXTERIOR WINDOWS: WINDOWS SHOULD BE SEALED TO MINIMIZE INFILTRATION FROM ANY ADJACENT

EXCAVATION DEBRIS.

• CEILINGS THAT ARE REMOVED/MODIFIED TO ALLOW CONSTRUCTION OF ICRA BARRIERS SHOULD BE

REINSTALLED TO PRE-CONSTRUCTION CONDITIONS.

VENTILATION AND ENVIRONMENTAL CONTROLS

• AIR SYSTEM FLOW: DETERMINE WHETHER THE CONSTRUCTION AREA USES FRESH/OUTSIDE OR RE-

CIRCULATED AIR; FILTERS SHOULD BE ADDED OR RETURN VENTS COVERED AS NEEDED WITH FILTER

MATERIAL OR PLASTIC. AIR MUST FLOW FROM CLEAN TO DIRTY AREAS.

• NEGATIVE AIR PRESSURE: THE AIR WITHIN THE CONSTRUCTION AREA MUST BE NEGATIVE WITH

RESPECT TO SURROUNDING AREAS AND WITH NO DISRUPTION OF AIR SYSTEMS OF ADJACENT AREAS.

USE OF THE NEGATIVE AIR PRESSURE SYSTEM WITHIN THE ENCLOSURE TO REMOVE DUST SHOULD

PASS AIR THROUGH AN INDUSTRIAL GRADE, PORTABLE HEPA FILTER CAPABLE OF FILTRATION RATES

OF 300-800 CUBIC FEET PER MINUTE (FT3//MIN), OR EXHAUST AIR DIRECTLY TO THE OUTSIDE IF

APPROVED BY VAMC. IF EXHAUST MUST BE TIED INTO A RE-CIRCULATED AIR SYSTEM, A PRE-FILTER

AND HEPA FILTER SHOULD BE USED BEFORE EXHAUST TO PREVENT CONTAMINATION OF THE DUCTS.

• ADJACENT AREAS: THE STATUS OF SEALED PENETRATIONS AND INTACT CEILING SHOULD BE VERIFIED

DAILY.

• AIR EXCHANGE RATES AND PRESSURE RELATIONSHIPS: VAMC AND/OR CONTRACTOR WILL VERIFY AND

MAINTAIN PROPER RATES IN CRITICAL AREAS NEAR CONSTRUCTION ACTIVITY AND ENSURE AIR IS NOT

BEING RE-CIRCULATED WITHOUT FILTRATION FROM THE CONSTRUCTION AREA ELSEWHERE. VAMC

WILL MAKE DETERMINATION ON PROVIDING FOR THE ACCOUNTABILITY AND FREQUENCY OF TESTING

AIR PRESSURE THROUGHOUT THE PROJECT.

• MANOMETERS SHOULD BE LOCATED ON ICRA PARTITION DOOR AND ON THE NON-CONSTRUCTION SIDE

OF THE PARTITION.

INFECTION CONTROL RISK ASSESSMENT FOR CONSTRUCTION

1. CLEAN WORK UPON COMPLETION OF TASK

1. WIPE WORK SURFACES WITH DISINFECTANT.

2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

3. WET MOP &/OR VACUUM BEFORE LEAVING WORK AREA.

4. REMOVE ISOLATION OF HVAC SYSTEM IN AREA WHERE WORK IS BEING PERFORMED.

1. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY

SAFETY MANAGEMENT & INFECTION CONTROL & THOROUGHLY CLEANED BY ENVIRONMENTAL

MANAGEMENT.

2. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT & DEBRIS

ASSOCIATED WITH CONSTRUCTION.

3. VACUUM WORK AREA WITH HEPA-FILTERED VACUUMS.

4. WET MOP WITH DISINFECTANT.

5. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

1. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT & DEBRIS

ASSOCIATED WITH CONSTRUCTION.

2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

3. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.

4. VACUUM WORK AREA WITH HEPA-FILTERED VACUUMS.

5. WET MOP WITH DISINFECTANT.

6. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

CLASS I - UPON COMPLETION OF PROJECTS

CLASS II - UPON COMPLETION OF PROJECTS

CLASS III - UPON COMPLETION OF PROJECTS

CLASS IV - UPON COMPLETION OF PROJECTS

(TO BE COMPLETED BY CONTRACTOR AND COR, THEN SIGNED BY INFECTION CONTROL NURSE)

CONTRACTOR'S SIGNATURE AND DATE

COR SIGNATURE AND DATE

LIGHT GRAY HATCH INDICATES

TYPES AND CLASSES SELECTED

FOR THIS RENOVATION

STEP #1: SELECT ACTIVITY TYPE BELOW:

CONSTRUCTION ACTIVITY TYPES:

TYPE A

INSPECTION AND NON-INVASIVE ACTIVITIES

INCLUDES, BUT NOT LIMITED TO:

• REMOVAL OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO 1 TILE

PER 50 SQUARE FEET.

• PAINTING (BUT NOT SANDING)

• WALL COVERING

• ELECTRICAL TRIM WORK

• MINOR PLUMBING

• ACTIVITIES WHICH DO NOT GENERATE DUST OR REQUIRE CUTTING OF

WALLS OR ACCESS TO CEILINGS OTHER THAN FOR VISUAL INSPECTION

TYPE B

SMALL SCALE, SHORT DURATION (less than 1 day) ACTIVITIES WHICH CREATE

MINIMAL DUST

INCLUDES, BUT NOT LIMITED TO:

• INSTALLATION OF TELEPHONE AND COMPUTER CABLING

• ACCESS TO CHASE SPACES

• CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE

CONTROLLED

TYPE C

WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF DUST OR REQUIRES

DEMOLITION OR REMOVAL OF ANY FIXED BUILDING COMPONENTS OR

ASSEMBLIES

INCLUDES, BUT NOT LIMITED TO:

• SANDING OF WALLS FOR PAINTING OR WALL COVERING

• REMOVAL OF FLOOR COVERING, CEILING TILES AND CASEWORK

• NEW WALL CONSTRUCTION

• MINOR DUCT WORK OR ELECTRICAL WORK ABOVE CEILINGS

• MAJOR CABLING ACTIVITIES

• ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A SINGLE WORK

SHIFT

TYPE D

MAJOR DEMOLITION AND CONSTRUCTION PROJECTS

INCLUDES, BUT NOT LIMITED TO:

• ACTIVITIES THAT REQUIRE CONSECUTIVE WORK SHIFTS.

• REQUIRES HEAVY DEMOLITION OR REMOVAL OF A COMPLETE HVAC

SYSTEM.

• NEW CONSTRUCTION

IS IT LIKELY THE CONTRACTOR'S STAFF WILL BE PLACED AT RISK FOR INFECTION

WITH TUBERCULOSIS? YES / NO

IS IT LIKELY THERE WILL BE PHYSICAL DISRUPTION OF THE WATER

SYSTEM/LINES DURING ACTIVITY? YES / NO

STEP #2: SELECT RISK GROUP BELOW AND MARK BOTTOM OF COLUMN

A) INFECTION CONTROL RISK GROUPS

GROUP 1 - LOW: OFFICE AREAS:

GROUP 2 - MEDIUM: CARDIOLOGY, ECHOCARDIOGRAPHY, ENDOSCOPY, NUCLEAR

MEDICINE, PHYSICAL THERAPY, RADIOLOGY/MRI, RESPIRATORY THERAPY

GROUP 3 - HIGH RISK: CCU, EMERGENCY ROOM, LABORATORIES, OUTPATIENT

SURGERY, PHARMACY, POST ANESTHESIA CARE UNIT, SURGICAL UNITS

GROUP 4 - HIGHEST RISK: ANY AREA CARING FOR IMMUNOCOMPROMISED

PATIENTS, CARDIAC CATH LAB, CENTRAL SUPPLY, INTENSIVE CARE UNITS,

MEDICAL UNITS, NEGATIVE AIRFLOW ROOMS, ONCOLOGY, OPERATING ROOMS

STEP #3: DETERMINE CLASS OF PRECAUTIONS USING MATRIX BELOW:

CONSTRUCTION ACTIVITY / INFECTION CONTROL MATRIX TO DETERMINE CLASS

** ICN MUST BE CONSULTED WHEN THE ASSESSMENT INDICATES THAT CLASS II,

III, IV PRECAUTIONS ARE REQUIRED.

RISK LEVEL TYPE 'A' TYPE 'B' TYPE 'C' TYPE 'D'

GROUP 1 I II II III / IV

GROUP 2 I II III IV

GROUP 3 I II III / IV IV

GROUP 4 II III / IV III / IV IV

CONSTRUCTION TYPE:

C

RISK GROUP:

LOW

RISK ASSESSMENT:

II

ELECTRICAL

YES

POTABLE WATER

NO

HVAC

YES

MEDICAL VACUUM

NO

SEWER

YES

PROJECTED UTILITY OUTAGES IMPACTING INFECTION CONTROL

STEP #4: COMPLETE THE INFECTION CONTROL CONSTRUCTION PERMIT:

1. EXECUTE WORK BY METHOD TO MINIMIZE RAISING DUST FROM CONSTRUCTION OPERATIONS

2. IMMEDIATELY REPLACE A CEILING TILE DISPLACED FOR VISUAL INSPECTION

1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING INTO

ATMOSPHERE.

2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING

3. SEAL UNUSED DOORS WITH DUCT TAPE

4. BLOCK OFF AND SEAL AIR VENTS.

5. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA.

6. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

1. REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

2. COMPLETE ALL CRITICAL BARRIERS, I.E. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA

FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH PLASTIC

COVERING & SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR VACUUMING PRIOR

TO EXIT) BEFORE CONSTRUCTION BEGINS.

3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA-EQUIPPED AIR

FILTRATION UNITS.

4. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORTATION IN TIGHTLY COVERED

CONTAINERS.

5. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID IS USED.

1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION

OF DUCT SYSTEM.

2. COMPLETE ALL CRITICAL BARRIERS, I.E., SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA

FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH PLASTIC

COVERING & SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR VACUUMING PRIOR

TO EXIT) BEFORE CONSTRUCTION BEGINS.

3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA-EQUIPPED AIR

FILTRATION UNITS.

4. SEAL HOLES, PIPES, CONDUITS AND PUNCTURES APPROPRIATELY.

5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO

THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE; OR

THE CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE

THE WORK SITE.

6. ALL PERSONNEL ENTERING THE WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE

COVERS MUST BE CHANGED EACH TIME THE WORKER EXITS THE WORK AREA.

7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY

SAFETY MANAGEMENT & INFECTION CONTROL & THOROUGHLY CLEANED BY ENVIRONMENTAL

MANAGEMENT.

CLASS I - DURING CONSTRUCTION PROJECT

CLASS II - DURING CONSTRUCTION PROJECT

CLASS III - DURING CONSTRUCTION PROJECT

CLASS IV - DURING CONSTRUCTION PROJECT

INFECTION CONTROL NURSE'S SIGNATURE AND DATE

D

17 16 15 11

SOILED UTILITY

TOILET

MED RM

CLEAN UTILITY

OBSERVATION

STAIR

TEL

ELEC

G100

HC BATHROOM

102IV START RM

FOYER

CONTROL RM

EXAM RM

EQUIP RM

1 LAYER 5/8" TYPE-X G.W.B.

INSULATION - SEE SPECIFICATIONS

5/8" G.W.B.

METAL STUDS @16" O.C.

BASE - SEE FINISH

SCHEDULE FOR TYPE

TRACK RUNNER

FLOOR SLAB

S E

E S

C H

E D

U

LE

P A

R T

IT

IO

N W

ID

T

H

FIRESTOPPING SEALANT - SEE SPECIFICATIONS

DECK OR

STRUCTURE

ABOVE

NOTE:

1. FOR EXISTING PARTITIONS USED AS ICRA BARRIERS, THE

CONTRACTOR SHALL COMPLETE THE FOLLOWING:

· MODIFY EXISTING PARTITION TO A ONE-HOUR RATED ICRA BARRIER

· EXTEND PARTITION TO FLOOR DECK WITH 5/8” G.W.B. ON EACH SIDE

· FINISH WALL PARTITION AS DIRECTED BY UL RATING REQUIREMENTS

· INFILL EXISTING OPENINGS WITH 5/8” G.W.B ON EACH SIDE

· PROVIDE FIRESTOPPING AT ALL EXISTING PENETRATIONS

2. PROVIDE 45 MINUTE RATED DOOR TO ACCESS CONSTRUCTION AREA

AT ALL NEW AND EXISTING ICRA BARRIERS

3. THE CONTRACTOR SHALL NOT BLOCK SPRINKLER PROTECTION ON

THE VA-OCCUPIED SIDE OF THE ICRA BARRIER.

EXISTING CEILING

EXISTING METAL STUD PARTITION TO

STRUCTURE ABOVE. IF DRYWALL IS NOT

AS SHOWN, CONTRACTOR TO ADD

DRYWALL AND SEAL AT TOP OF WALL AS

SHOWN ON ICRA BARRIER WALL TYPE.

EXISTING HOLLOW

METAL DOOR ASSEMBLY

NEW ICRA BARRIER FLUSH WITH

SOFFIT. INSTALL PER ICRA BARRIER

WALL TYPE ON THIS SHEET. ADD

SHEET PLASTIC AND ZIPPER ACCESS

DOOR AS REQUIRED FOR ROOM

ACCESS. CONTRACTOR MUST

MAINTAIN ICRA CONTROL AT ALL

TIMES. DEPTH OF THE CONTAINMENT

AREA AS NEEDED TO MEET CLASS IV

REQUIREMENTS.

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

FULLY SPRINKLERED

A

B

C

D

E

F

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

ARCHITECTS/ENGINEERS:SEAL

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

BID DOCUMENTS

18030

HVAC UPGRADE FOR

MRI SUITE

LOUIS A. JOHNSON VA MEDICAL CENTER

CLARKSBURG, WEST VIRGINIA

540-18-011

CJC SB

G100 08/05/2019 162

ICRA PLAN AND NOTES

NORTH

PROJECT

TRUE NORTH = 81

1/4" = 1'-0"

LEVEL 1 OVERALL HVAC PLAN

NOT TO SCALE

ICRA BARRIER WALL TYPE

ICRA KEYNOTES

KEYNOTE DESCRIPTION

1 ICRA BARRIER FLUSH WITH SOFFIT ABOVE. SEE SECTION ON THIS SHEET.

2 COVER OPENING IN BARRIER WITH SHEET PLASTIC WITH ACCESS ZIPPER.

NOT TO SCALE

BARRIER SECTION

CO2

CO

H

HS

NO2

S

TH

TS

T

MS

CHWS

HWR

HWS

(E)

CHWR CHILLED WATER RETURN

CHILLED WATER SUPPLY

HEATING WATER RETURN

HEATING WATER SUPPLY

RL

RS

REFRIGERANT-LIQUID

REFRIGERANT-SUCTION

2"

HVAC PIPING SYMBOLS

KEYNOTE

CONTINUATION SYMBOL

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

GENERAL HVAC SYMBOLS

ROOM NAME AND NUMBER

POINT WHERE NEW CONNECTS TO EXISTING

EXISTING PIPE TAG

ITEM TO BE DEMOLISHED

AREA NOT IN CONTRACT

PIPING BEING DEMOLISHED

ABOVE GROUND PIPING

PIPE SIZE TAG (DIAMETER)

BELOW GROUND PIPING

PIPE INVERT ELEVATION TAG

PIPE SLOPE TAG

* NOTE *

ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN

THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT

BE USED IN THIS SET OF DRAWINGS.

Room

INVERT: -10' - 1"

1/8" / 12" SLOPE

16"x8"

16"/8"

(E)

F

S

M

B

D

C

16"Ø

E/A

O/A

T/A

L/A

R/A

S/A

EXHAUST AIR

OUTSIDE AIR

RELIEF AIR

RETURN AIR

SUPPLY AIR

TRANSFER AIR

GRILLES, REGISTERS & DIFFUSERS TAG

CFM

THROW-150FPM/ 100FPM/ 50FPM

NECK SIZE / MODULE SIZE

EXISTING DUCT TAG

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)

HVAC SYMBOLS

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE

RECTANGULAR RETURN/TRANSFER AIR DUCT RISE

MECHANICAL EQUIPMENT TAGS

ROUND DUCT SIZE TAG (DIAMETER)

LINEAR DIFFUSER TAG

CFM

TYPE (SEE SCHEDULE) NUMBER OF SLOTS /

ACTIVE SLOT LENGTH (PLENUM

LENGTH) /

NECK SIZE

DUCT BEING DEMOLISHED

ELEVATION (CENTER OF FACE)

ROUND SUPPLY/OUTSIDE AIR DUCT RISE

ROUND RETURN/TRANSFER AIR DUCT RISE

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE

ROUND EXHAUST/RELIEF AIR DUCT RISE

DROP

DROP

DROP

DROP

DROP

DROP

GE/A GREASE EXHAUST AIR

SE/A SMOKE EXHAUST AIR

EQUIPMENT BY OTHERS

(REFER TO OTHER DISCIPLINE

FOR ADDITIONAL

INFORMATION)

EXISTING EQUIPMENT

TO REMAIN

FLUE EXHAUST GAS FLUE

C/A COMBUSTION AIR

S-O/A CONDITIONED OUTSIDE AIR

VAV-XX

10' - 0"

(E)VAV-XX

VAV-XX

Ø ROUND

ABV ABOVE

AC AIR CONDITIONING

AD AREA DRAIN

ADD ADDENDUM

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

ALT ALTERNATE

AP ACCESS PANEL

ARCH ARCHITECT/ARCHITECTURAL

BFF BELOW FINISHED FLOOR

BLW BELOW

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

CAP CAPACITY

CB CATCH BASIN

CFM CUBIC FEET PER MINUTE

CLG CEILING

CO CLEAN OUT

CW COLD WATER

D DEGREE

DB DRY BULB

DIA DIAMETER

DN DOWN

DW DISTILLED WATER

EA EACH

EAT ENTERING AIR TEMPERATURE

ELEC ELECTRICAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

E/A EXHAUST AIR

EXIST EXISTING

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FD FIRE DAMPER

FDV FIRE DEPARTMENT VALVE

FL FLOOR

FO FUEL OIL

FOV FUEL OIL VENT

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPM FEET PER MINUTE

FS FLOOR SINK

FT FOOT/FEET

FTR FIN TUBE RADIATION

GAL GALLON

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

GW GREASE WASTE

HB HOSE BIB

HP HORSE POWER

HTG HEATING

HTR HEATER

HW HOT WATER

HYD HYDRANT

ID INDIRECT

IN INCH

INV INVERT

LB POUND

LB/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M/A MIXED AIR

MAX MAXIMUM

MBH ONE THOUSAND BTU PER HOUR

MCF ONE THOUSAND CUBIC FEET

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MU/A MAKE-UP/AIR

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NUMBER

NO NORMALLY OPEN

NTS NOT TO SCALE

O OXYGEN

O/A OUTSIDE AIR

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PWR POWER

R DUCT RISER

R/A RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF DRAIN

REC RECESSED

RED REDUCER

RH RELATIVE HUMIDITY

RL/A RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RW RAIN WATER

SF SQUARE FOOT

S/A SUPPLY AIR

SAN SANITARY

SF SQUARE FOOT

SD SMOKE DAMPER

SM SURFACE MOUNT

SP STANDPIPE

SP STATIC PRESSURE

STM STEAM

T THERMOSTAT

TD TEMPERATURE DROP

TDR TRENCH DRAIN

TEMP TEMPERATURE

TYP TYPICAL

UG UNDERGROUND

VAC VACUUM

V VENT

VAV VARIABLE AIR VOLUME

VENT VENTILATION

VTR VENT THROUGH ROOF

W WASTE

WB WET BULB

WCO WALL CLEAN OUT

WH WALL HYDRANT

ABBREVIATIONS

AC AIR CONDITIONING UNIT

ACC AIR COOLED CONDENSER

ACCU AIR COOLING CONDENSING UNIT

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

B BOILER

CH CHILLER

CT COOLING TOWER

CUH CABINET UNIT HEATER

CWP CONDENSER WATER PUMP

CHWP CHILLED WATER PUMP

DBP DOMESTIC WATER BOOSTER PUMP

DC DUCT MOUNTED COIL

DCP DOMESTIC WATER CIRCULATING PUMP

EF EXHAUST FAN

EDC ELECTRIC DUCT COIL

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

FCU FAN COIL UNIT

FP FIRE PUMP

GI GREASE INTERCEPTOR

GRV GRAVITY ROOF VENTILATOR

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

HRU HEAT RECOVERY UNIT

PRV POWER ROOF VENTILATOR

RE RETURN/EXHAUST FAN

RTU ROOFTOP UNIT

SEP SEWAGE EJECTOR PUMP

SF SUPPLY FAN

SP SUMP PUMP

UH UNIT HEATER

WH WATER HEATER

EQUIPMENT ABBREVIATIONS

48"x2 1/2"

8" / 24x24

12" / ---

LINEAR BAR GRILLE

LINEAR SLOT DIFFUSER

PERFORATED DIFFUSER

WITH DEFLECTORS

ROUND DIFFUSER WITH

ADJUSTABLE PATTERNS

LOUVERED DOUBLE

DEFLECTION GRILLE

12"x10" / ---

TYPE (SEE SCHEDULE)

10" / 24x24 H-5/7/1422

3-CONE DIFFUSER

THROW PATTERN

MAX NC RATING

1 / 4' - 0" / 8"

8' - 0" AFF

1 / 4' - 0" / 8"

18' - 0"

1 / 4' - 0" / 8"

SECTION TOTAL TRACK LENGTH

12"x10" / 24x12

LOUVERED GRILLE

12"x10" / 24x24

EGGCRATE RETURN

GRILLE

BOTTOM OF EQUIPMENT

ELEVATION

505 lb

RTU-XX

RTU-XX

3.0 ton

115000 Btu/h

115 CFH

RTU-XX

Htg: 3.7 GPM

VAV-XX

HEATING COIL

FLOW

OPERATING WEIGHT

NOT INCLUDING CURB

FUEL INPUT

GAS PIPE FLOW

NOMINAL COOLING

CAPACITY

VAV BOX

ROOFTOP UNIT

DATA DEVICE TAGS

DAMPER TAGS

VAV-XX

RTU-XX

EQUIPMENT ID

SYMBOL

BBB

INLET COLLAR DAMPER

MANUAL BALANCING DAMPER

BACKDRAFT DAMPER

COMBINATION FIRE/SMOKE

DAMPER

FIRE DAMPER

SMOKE DAMPER

MOTORIZED DAMPER

SENSOR

MANUAL SWITCH

THERMOSTAT

TEMPERATURE SENSOR

TEMPERATURE & HUMIDITY SENSOR

HUMIDITY SENSOR

NITROGEN DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

CARBON DIOXIDE SENSOR

HUMIDISTAT

CD CONDENSATE DRAIN LINE

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

FULLY SPRINKLERED

A

B

C

D

E

F

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

ARCHITECTS/ENGINEERS:SEAL

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

BID DOCUMENTS

18030

HVAC UPGRADE FOR

MRI SUITE

LOUIS A. JOHNSON VA MEDICAL CENTER

CLARKSBURG, WEST VIRGINIA

540-18-011

CJC AC

M001 08/05/2019 163

HVAC SYMBOLS, ABBREVIATIONS AND

GENERAL NOTES

HVAC GENERAL NOTES

40 UNLESS OTHERWISE NOTED, ALL PIPING AND DUCTWORK IF OVERHEAD, TIGHT TO UNDERSIDE

OF STRUCTURE OR SLAB, WITH SPACE FOR INSULATION.

41 PROVIDE CHAINWHEEL OPERATORS FOR ALL EXPOSED VALVES MOUNTED GREATER THAN 8'-0"

ABOVE FINISHED FLOOR LEVEL. CHAIN SHALL EXTEND UNOBSTRUCTED TO 7'-0" ABOVE FLOOR

LEVEL.

42 ALL PIPING AND DUCTWORK SHALL CLEAR DOORS, WINDOWS, EQUIPMENT CLEARANCES,

MAINTENANCE REQUIREMENTS, CODE SETBACKS, ETC. TO ASSURE PROPER OPERATION,

INSPECTION AND MAINTENANCE.

43 ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.

44 PROVIDE ALL 90 DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES UNLESS

OTHERWISE INDICATED OR SPECIFIED. PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS

CONTAINING TURNING VANES.

45 ALL DUCTS SHALL BE BONDED ACROSS FLEXIBLE CONNECTIONS WITH FLEXIBLE COPPER

GROUNDING STRAPS. GROUNDING STRAPS SHALL BE BOLTED OR SOLDERED TO BOTH THE

EQUIPMENT AND THE DUCT.

46 ALL EQUIPMENT SUBMITTALS AND SHOP DRAWINGS REQUIRED BY THE SPECIFICATIONS SHALL

BE APPROVED BY THE ENGINEER PRIOR TO PURCHASE, FABRICATION AND INSTALLATION.

47 ALL HEATING DEVICES AND SURFACES WITH ELEVATED TEMPERATURES WHICH CAN BE

ACCESSED OR COME IN CONTACT WITH OWNER PERSONNEL SHALL BE PROTECTED,

INSULATED, OR CONTROLLED TO REMAIN BELOW 120º F.

48 PROVIDE MANUAL VOLUME DAMPERS IN ALL RUN-OUTS TO DIFFUSERS, BRANCH TAKE-OFFS

FROM MAIN SUPPLY DUCT, AND IN ALL OTHER AREAS REQUIRED TO PROVIDE PROPER SYSTEM

AIRFLOW BALANCING.

HVAC GENERAL NOTES

1 NOT ALL SYMBOLS ARE NECESSARILY USED.

2 COORDINATE FINAL LOCATIONS OF DIFFUSERS AND GRILLES WITH ARCHITECTURAL

REFLECTED CEILING PLANS.

3 DRAWINGS ARE DIAGRAMMATIC. CONTRACTOR TO FIELD VERIFY DUCT AND PIPE ROUTING AND

COORDINATE INTERFERENCE BETWEEN TRADES PRIOR TO INSTALLATION.

4 ROOF OPENINGS, FLASHING, AND COUNTER FLASHING BY CONTRACTOR. LOCATION OF

OPENINGS BY CONTRACTOR.

5 DUCTWORK TO BE INSTALLED TIGHT TO UNDERSIDE OF STRUCTURE ABOVE UNLESS NOTED

OTHERWISE.

6 PROVIDE ALL MATERIALS, EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL

COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

7 CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE

INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. CONTRACTOR SHALL BE

RESPONSIBLE TO FIELD SURVEY ACTUAL SITE CONDITIONS AND ACCOMODATE ACTUAL SITE

CONDITIONS AS PART OF SCOPE OF WORK AT NO COST TO OWNER.

8 INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATIONS, CONTRACT DOCUMENTS, APPLICABLE BUILDING,

STATE AND LOCAL CODES, SEISMIC REQUIREMENTS, ENERGY CODES AND INSURANCE

UNDERWRITER REQUIREMENTS.

9 COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,

STRUCTURAL, CIVIL AND ELECTRICAL WORK, ETC. SHOWN ON OTHER CONTRACT DOCUMENT

DRAWINGS.

10 MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS,

SUSPENDED EQUIPMENT, SUPPORTS, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL

ROOMS.

11 ALL TESTS SHALL BE COMPLETED AND ACCEPTED BY THE INSPECTOR BEFORE ANY

MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED.

12 LOCATE ALL TEMPERATURE, PRESSURE AND FLOW MEASURING DEVICES IN ACCESSIBLE

LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UPSTREAM AND DOWNSTREAM, AS

RECOMMENDED BY THE MANUFACTURER FOR ACCURACY.

13 TESTING ADJUSTING AND BALANCING (TAB) AGENCY SHALL BE A MEMBER OF THE ASSOCIATED

AIR BALANCING COUNCIL (AABC) OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU

(NEBB). TAB FIRM SHALL HAVE A MINIMUM OF 5 YEARS EXPERIENCE ON SIMILAR PROJECTS.

PERFORM TAB IN ACCORDANCE WITH THE REQUIREMENTS OF THE TAB PROCEDURAL

STANDARD RECOMMENDED BY THE TAB TRADE ASSOCIATION THAT APPROVED THE TAB FIRM'S

QUALIFICATIONS.

14 WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE

PRODUCTS OF A SINGLE MANUFACTURER SHALL BE USED.

15 COORDINATE ALL FINAL EQUIPMENT CONNECTIONS WITH THE MANUFACTURERS' CERTIFIED

DRAWINGS. COORDINATE AND PROVIDE ALL DUCTWORK AND PIPING TRANSITIONS REQUIRED

FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND

COORDINATE ALL DUCTWORK AND PIPING DIMENSIONS BEFORE FABRICATION.

16 ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE,

DIVISION 26 OF THE SPECIFICATIONS, ALL LOCAL CODES, AND OWNER'S INSURANCE

UNDERWRITER REQUIREMENTS.

17 THE LOCATIONS AND SIZES OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE

SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE ONLY.

THE EXACT LOCATIONS AND SIZES NECESSARY TO SECURE THE BEST CONDITIONS AND

RESULTS SHALL BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE

APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.

18 PLAN DRAWINGS AND SECTIONS CUTS WHICH SPECIFICALLY IDENTIFY SERVICE ROUTE

OFFSETS, ELEVATION CHANGES, OBSTRUCTIONS, ACCESS DOORS, BALANCING DEVICES, ETC.

ARE SHOWN FOR CLARITY WHERE SPECIFIC KNOWN CONDITIONS EXIST. CONTRACTOR SHALL

COORDINATE EQUIPMENT, DUCTWORK, AND PIPING ROUTINGS WITH ALL OTHER TRADES.

REQUIREMENTS NOT SPECIFICALLY IDENTIFIED SHALL NOT BE INTERPRETED AS EXCLUSION

FROM CONTRACTOR'S SCOPE OF WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR ACTUAL

SITE CONDITIONS AND SHALL INCLUDE SUCH CONDITIONS IN SCOPE OF WORK AT NO

ADDITIONAL COST TO THE OWNER.

19 ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND SUPPORT OF

MECHANICAL WORK AS SHOWN IN DETAILS FOR PIPING, DUCTWORK AND EQUIPMENT (UNLESS

OTHERWISE NOTED) SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR AT NO

ADDITIONAL COST TO THE OWNER.

20 ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED

AND AS REQUIRED TO PROVIDE A VIBRATION FREE INSTALLATION.

21 ALL OPENINGS IN FIRE RATED WALLS AND SMOKE PARTITIONS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE STOPPED WITH APPROVED FIRESTOPPING MATERIALS.

22 REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING AND EQUIPMENT INSTALLATION.

23 UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS WITH TOP AT 48" ABOVE

FINISHED FLOOR IN ACCORDANCE WITH ADA REQUIREMENTS. NOTIFY THE ENGINEER OF ANY

ROOMS WHERE THE ABOVE LOCATION CAN NOT BE MAINTAINED OR WHERE THERE IS A

QUESTION ON LOCATION. COORDINATE FINAL LOCATIONS WITH OWNER.

24 LOCATE ALL MECHANICAL EQUIPMENT (VAV BOXES, CABINET HEATERS, UNIT HEATERS, ETC.,)

FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, FILTERS, CONTROLS AND VALVING.

DO NOT LOCATE FAN POWERED VAV BOXES ABOVE LIGHTING FIXTURES.

25 PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN AND

EXHAUST) CONNECTED TO FANS AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION

ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO

THE EQUIPMENT UNLESS OTHERWISE INDICATED.

26 ALL LOUVERS SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR (UNLESS

OTHERWISE NOTED). CONTRACTOR SHALL COORDINATE SIZES, LOCATIONS, AND

CONNECTIONS. CONNECTIONS TO LOUVERS SHALL BE FURNISHED AND INSTALLED BY

CONTRACTOR.

27 PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN HYDRONIC WATER PIPING

SYSTEMS. ALL PIPING SHALL SLOPE TO LOW POINTS. PROVIDE HOSE END DRAIN VALVES AT

THE BOTTOM OF ALL RISERS AND LOW POINTS.

28 INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES AND OTHER

APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.

29 ALL ISOLATION VALVES SHALL BE IN LOCATION AND ELEVATION WHICH ALLOWS FOR

EQUIPMENT AND BRANCH PIPING REMOVAL, WHILE MAINTAINING SERVICE UPSTREAM OF THE

ISOLATION VALVE.

30 ALL BALANCING VALVES AND ISOLATION VALVES USED TO ADJUST FLOW RATES SHALL BE

PROVIDED WITH POSITIONS INDICATORS AND MAXIMUM ADJUSTABLE STOPS (MEMORY STOPS).

31 ALL ISOLATION VALVES (EXCEPT CONTROL VALVES), STRAINERS, AND PIPING SPECIALTIES

SHALL BE FULL LINE SIZE BEFORE REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT

AND CONTROLS.

32 MECHANICAL JOINTS SUCH AS UNIONS, FLANGES, OR THREADED FITTINGS SHALL BE

INSTALLED AT EACH EQUIPMENT CONNECTION, IN BYPASSES, AT FLOOR PENETRATIONS, AT

CONTROL DEVICES, AND IN LONG PIPE RUNS (100 FEET OR MORE) TO PERMIT DISASSEMBLY

FOR ALTERATION AND REPAIRS.

33 MEASURE, CUT AND INSTALL PIPE LENGTH ACCURATELY TO MINIMALIZE MISALIGNMENT.

INSTALL ALL PIPING WITHOUT FORCING OR SPRINGING.

34 PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS AND OTHER

EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION (EXCEPT WATER COILS). FLEXIBLE

CONNECTIONS SHALL BE PROVIDED AS CLOSE TO THE EQUIPMENT AS POSSIBLE OR AS

INDICATED ON THE DRAWINGS.

35 PROVIDE VIBRATION INSULATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT VIBRATION

TRANSMISSION TO BUILDING STRUCTURE.

36 CONCRETE HOUSEKEEPING PADS SHALL BE FURNISHED AND INSTALLED BY THE GENERAL

CONTRACTOR. MECHANICAL CONTRACTOR SHALL PROVIDE EQUIPMENT WEIGHTS, SIZES AND

LOCATION TO GENERAL CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS SHALL BE IN

ACCORDANCE WITH STRUCTURAL DETAILS. PAD SHALL EXTEND BEYOND THE EQUIPMENT

FOOTPRINT A MINIMUM OF 6 INCHES ON EACH SIDE.

37 ALL DUCTWORK, PIPING, AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL BE

COORDINATED WITH GENERAL CONTRACTOR. ALL ATTACHEMENTS TO STEEL MEMBERS, BAR

JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE APPROVED BY STRUCTURAL ENGINEER.

WELDING TO STRUCTURAL MEMBERS SHALL NOT BE PERMITTED.

38 MECHANICAL EQUIPMENT, DUCTWORK, AND PIPING SHALL NOT BE SUPPORTED FROM ROOF OR

DECK ASSEMBLY. SUPPORTS SHALL ATTACH TO STRUCTURAL MEMBERS. COORDINATE WITH

STRUCTURAL DRAWINGS.

39 PROVIDE MANUFACTURER'S MATCHING ROOF CURBS FOR ALL ROOF MOUNTING EQUIPMENT.

COORDINATE ACTUAL ROOF PITCH AND CONSTRUCTION DETAILS WITH CONTRACTOR.

PROVIDE SLOPED CURBS PER MANUFACTURER'S RECOMMENDATIONS. CONTRACTOR SHALL

INSTALL ROOF CURBS AND FLASHING PER ROOFING MANUFACTURER'S INSTALLATION

REQUIREMENTS.

Title Sheet Revision

AHU-1

M101

D

17 16 15

EXISTING

SKYLIGHT

EXISTING ROOF DRAIN

EXISTING

REMOTE

CONDENSING

UNIT

EXISTING ROOF HATCH

EXISTING MRI CHILLER

D

(E)EF-1

(E)EF2

17 16 15

(E)EF

(E)EF

(E)EF

(E)CU-1

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

FULLY SPRINKLERED

A

B

C

D

E

F

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

ARCHITECTS/ENGINEERS:SEAL

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

BID DOCUMENTS

18030

HVAC UPGRADE FOR

MRI SUITE

LOUIS A. JOHNSON VA MEDICAL CENTER

CLARKSBURG, WEST VIRGINIA

540-18-011

CJC AC

MD101

08/05/2019 164

MRI SUITE HVAC DEMOLITION PLAN

HVAC FLOOR PLAN DEMOLITION KEYNOTES

1 REMOVE ALL HVAC DUCTWORK AND GRILLES IN THIS ROOM SERVING THIS ROOM.

2 DEMOLISH EXISTING AIR HANDLING UNIT AND ASSOCIATED DUCTWORK.

3 DEMOLISH EXISTING OA INTAKE HOOD AND ASSOCIATED DUCTWORK.

4 DEMOLISH EXISTING EXHAUST DUCTWORK UP TO ROOF.

5 REMOVE EXISTING EXHAUST FAN AND ASSOCIATED DUCTWORK.

6 EXISTING EXHAUST FAN TO BE DEMOLISHED AND REPLACED WITH NEW EXHAUST FAN IN

SAME LOCATION. PREPARE ROOF FOR NEW, LARGER OPENING.

7 EXISTING EXHAUST DUCTWORK TO BE DEMOLISHED. PREPARE ROOF FOR NEW, LARGER

OPENING.

8 EXISTING EXHAUST FAN TO BE DEMOLISHED AND REPLACED WITH NEW EXHAUST FAN IN

SAME LOCATION. STRUCTURAL SUPPORT RAILS TO REMAIN FOR NEW EXHAUST FAN EF-2.

9 EXISTING CONDENSING UNIT TO BE DEMOLISHED AND REPLACED WITH NEW CU-1 IN SAME

LOCATION.

10 EXISTING INTAKE HOOD TO BE DEMOLISHED AND REPLACED WITH NEW INTAKE HOOD IN

SAME LOCATION. PREPARE ROOF FOR NEW, LARGER OPENING.

NORTH

PROJECT

TRUE NORTH = 81

1/4" = 1'-0"

HVAC DEMOLITION PLAN

HVAC GENERAL DEMOLITION NOTES

1 REFER TO FACILITY'S INFECTION CONTROL AND RISK ASSESSMENT (ICRA) FOR ADDITIONAL

REQUIREMENTS.

2 CAP RETURN AIR DUCTS TO CONTRUSTION ZONE TO PREVENT RETURN FROM CONSTRUCTION

ZONE. MINIMIZE SUPPLY AI RPROVICDED TO CONSTRUCTION ZONE.

3 EXISTING SYSTEMS TO REMAIN IN SERVICE UNLESS OTHERWISE NOTED.

4 REFER TO DRAWINGS M101 AND M102 FOR INFORMATION FOR NEW EQUIPMENT.

1/4" = 1'-0"

HVAC DEMOLITION ROOF PLAN

T

T

T

T

H S

T

14"Ø S/A

22"x16" S/A

34"x18" S/A

18"x12" S/A

10"x10" S/A

12"x12" S/A

22"x18" R/A

12"x10" R/A

"x

S /A

"Ø

R /A

12"x12" E/A

10"Ø E/A

8" x6

E

/A

10"Ø S/A

8"Ø S/A

"x

E /A

14"x14" / 24x24

835RG5

14"x14" / 24x24

835RG5

12"x10" / 24x24

500EG-4

8"x6" / 24x24

150EG-2

14"x14" / 24x24

830RG5

12"x8" / 24x24

350EG-3

14"x6" / 24x24

300EG-3

14" / 24x24

625SD5

10" / 24x24

350SD3

10" / 24x24

350SD3

6" / 24x24

100SD1

M101

AHU-1

EQUIP RM

EXAM RM

CONTROL RM

HC BATHROOM

IV START RM

FOYER

14" / 24x24

625SD5

D

H-1

28"x20" R/A

"Ø

E /A

10" / 24x24

250CD3

"x

S /A

RHC-5

RHC-4

"x

8" S

/A

RHC-3

10" / 24x24

250CD3

RHC-2

10"Ø S/A

10"Ø S/A

14"Ø S/A

14" / 24x24

625SD5

14" / 24x24

625SD5

M101

RHC-1

M101

16 15

28"x20" S/A

30"x20" E/A

6 7

24"x14" / ---

1400RR1

D

H-1

AHU-1

1 1/4" CW

1/

4" C

W

EQUIP RM

17 16

RO-1

6"6"

X = DUCT DEPTH AS

INDICATED ON PLAN

AIR FLOWX

X+3"

X

12x12 ACCESS PANEL

MOUNT ON SIDE OF DUCT

OPPOSITE OF HUMIDIFIER

AIR FLOW SWITCH -

INTERLOCK WITH HUMIDIFIER

3'-0"

DRAIN

VALVE

HUMIDIFIER DISPERSION TUBE

STAINLESS STEEL DUCT SECTION

SOLDER DRAIN PAN WATER TIGHT

HIGH LIMIT

HUMIDISTAT

10' - 0"

MIN. FROM

HUMIDIFIER

AIR GAP FITTING

PIPE TO FLOOR

DRAIN W/ FUNNEL

CONDENSATE

DRAIN

HUMIDIFIER

UNION

CW MAKE-UP

SHUT-OFF VALVE

SUPPLY

DUCT

PITCH TO

HUMIDIFIER

DRAIN TEEMANIFOLD

WATER OUTLET

TO RO-1

MIN. 4'-0"

OFF FLOORBALL VALVE

UNION

WALL PIPE SUPPORT

WALL PIPE

SUPPORT

WATER INLET

AIR GAP

DRAIN

STRAINER

REDUCED PRESSURE

BACKFLOW PREVENTER

1" TO NEAREST

FLOOR DRAIN

Level 1 0' - 0"

AHU-1

Level 1 0' - 0"

AHU-1

H-1

Level 1 0' - 0"

AHU-1

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

FULLY SPRINKLERED

A

B

C

D

E

F

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

ARCHITECTS/ENGINEERS:SEAL

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

BID DOCUMENTS

18030

HVAC UPGRADE FOR

MRI SUITE

LOUIS A. JOHNSON VA MEDICAL CENTER

CLARKSBURG, WEST VIRGINIA

540-18-011

CJC AC

M101 08/05/2019 165

MRI SUITE HVAC NEW WORK PLAN

NORTH

PROJECT

TRUE NORTH = 81

HVAC GENERAL NEW WORK NOTES

1 REFER TO FACILITY'S INFECTION CONTROL AND RISK ASSESSMENT

(ICRA) FOR ADDITIONAL REQUIREMENTS.

2 ALL WORK SHALL BE SCHEDULED AND COORDINATED JOINTLY WITH

LOUIS A. JOHNSON VAMC. A DETAILED JOB TIMELINE SHALL BE

ESTABLISHED AND SUBMITTED FOR REVIEW AND APPROVAL.

3 COORDINATE ALL WAVE GUIDE FILTER REQUIREMENTS AT RF

PENETRATIONS WITH RF SHIELD VENDOR AND MRI EQUIPMENT VENDOR.

EXISTING RF SHIELD VENDOR IS BRADEN SHIELDING SYSTEMS – (918)

624-2888. THERE IS A FUTURE PROJECT THAT REPLACES THE MRI

EQUIPMENT. THE PROJECT IS TITLED “AVANTO FIT UPGRADE (MRI

ROOM)” 540-18-011NAC. CONTRACTOR TO COORDINATE WITH COR

BEFORE CONSTRUCTION NOTICE TO PROCEED TO OBTAIN DRAWINGS

FOR THAT PROJECT TO COORDINATE WITH THIS PROJECT.

4 CONTRACTOR TO HAVE THE RF SHIELD TESTED PRIOR TO

CONSTRUCTION AND AT THE END OF CONSTRUCTION. CONTRACTOR TO

REPAIR RF SHIELD AS REQUIRED TO PASS TEST PER BRADEN SHIELDING

SYSTEM REQUIREMENTS

5 ALL DUCTWORK, FASTENERS, HANGERS, AND APPURTENANCES WITHIN

THE RF SHIELD SHALL BE NON-FERROUS.

6 CONTRACTOR TO PROVIDE REMOTE OPERATORS FOR ALL MANUAL

VOLUME DAMPERS LOCATED ABOVE GYPSUM BOARD CEILINGS.

7 RUNOUT BRANCH TO DUCTWORK TO SUPPLY DIFFUSERS, AND EXHAUST

GRILLES TO BE THE SAME SIZE AS THE NECK SIZE ON THE AIR DEVICE

UNLESS NOTED OTHERWISE.

8 MAINTAIN 6" MINIMUM CLEARANCE FROM RATED WALLS AND HVAC

EQUIPMENT.

9 ALL DUCTWORK TO BE LOW PRESSURE (3") PRESSURE CLASS.

10 NOTE: THE CRAWLSPACE BELOW EQUIP RM 106 IS LABELED A

“CONFINED SPACE”. CONTRACTOR TO FOLLOWING VA’S PROCEDURE

FOR WORKING IN A CONFINED SPACE AND COORDINATE WITH COR.

11 NO ONSITE WORK CAN BEGIN UNTIL ALL SUBMITTALS HAVE BEEN

RECEIVED AND APPROVED BY THE AE AND VA.

1/2" = 1'-0"

MRI SUITE HVAC NEW WORK PLAN

HVAC KEYNOTES

1 INSTALL WALL MOUNTED, REMOTE DIGITAL READOUT FOR

TEMPERATURE AND HUMIDITY LEVELS OF EXAM ROOM 105 INSIDE OF

EQUIPMENT ROOM 106. THIS PANEL IS INTENDED FOR LOUIS A.

JOHNSON STAFF TO VIEW. UNIT STATUS MUST BE DISPLAYED.

PANEL MUST BE CONNECTED TO AND REPORT TO EXISTING BAS

SYSTEM/CENTRAL ENGINEERING CONTROL CENTER (ECC).

2 INSTALL A DIGITAL TEMPERATURE SENSOR AT THIS LOCATION.

3 INSTALL A HUMIDITY SENSOR AT THIS LOCATION.

4 INSTALL A DIGITAL PRESSURE SENSOR AT THIS LOCATION.

5 INSTALL DUCT MOUNTED, SHORT ABSORPTION MANIFOLD

CONNECTED TO STEAM HUMIDIFIER H-1 AT THIS LOCATION. REFER

TO DETAIL ON DRAWING.

6 IF INDIVIDUAL SUPPLY, RETURN, AND EXHAUST BRANCH DUCTS

PENETRATE RF SHIELD CONTRACTOR TO PROVIDE WAVE GUIDE

FILTER. COORDINATE WITH RF SHIELD VENDOR.

7 ALL DUCTWORK, SUPPORTS, HANGERS AND FASTENERS IN EXAM

ROOM 105 SHALL BE OF NON-FERROUS CONSTRUCTION.

8 PROVIDE WAVEGUIDE FILTER AT THE INDICATED LOCATION WHERE

DUCTWORK PENETRATES RF SHIELD. COORDINATE WITH RF SHIELD

VENDOR.

9 12“x12” UP TO EF-1 ON ROOF. TRANSITION AS REQUIRED.

10 26“x24” EXHAUST UP TO DUCTWORK ON ROOF.

11 28“x20” UP TO IH-1 ON ROOF. TRANSITION AS REQUIRED.

12 SIDEWALL SUPPLY GRILLE SS-1 DOWNSTREAM OF RHC-1.

CONTRACTOR TO BALANCE TO 1,400 CFM.

13 CONTRACTOR TO RELOCATE EXISTING BAS CONTROL PANELS AS

NEEDED TO COORDINATE WITH RELOCATED ELECTRICAL PANELS.

14 MOTORIZED DAMPER. DAMPER FULLY OPEN DURING NORMAL

OPERATION. IN ECONOMIZER MODE THE DAMPER FULLY SHUTS AND

ALL RETURN AIR IS EXHAUSTED BY EF-2.

15 1-1/4” CONDENSATE DRAIN FROM AHU-1 DOWN TO CRAWLSPACE

BELOW. CONNECT TO SAME PIPE THAT EXISTING AHU’S

CONDENSATE DRAIN CONNECTED TO.

16 1-1/4” DOMESTIC WATER SUPPLY PIPE DIVIDES INTO (2) ½” NPT PIPES

DOWN TO H-1. CONTRACTOR TO COORDINATE EXACT PIPE SIZE AND

TERMINATION LOCATION WITH INSTALLED HUMIDIFIER.

17 3” DRAIN PIPE DOWN FROM HUMIDIFIER TO CRAWLSPACE. DRAIN

PIPE CONNECTS TO HUMIDIFIER AT (2) LOCATIONS. CONTRACTOR TO

COORDINATE EXACT PIPE SIZE AND DISCHARGE LOCATION WITH

INSTALLED HUMIDIFIER. CONNECT TO SAME DRAIN PIPE THAT

EXISTING AHU’S CONDENSATE DRAIN CONNECTED TO IN

CRAWLSPACE.

18 1-1/4” DOMESTIC WATER SUPPLY PIPE DOWN TO RO-1. CONTRACTOR

TO COORDINATE EXACT PIPE SIZE AND TERMINATION LOCATION WITH

INSTALLED REVERSE OSMOSIS SYSTEM. PROVIDE BACKFLOW

PREVENTER ON SUPPLY PIPE PER “BACKFLOW PREVENTER” DETAIL

ON THIS DRAWING.

19 1” DRAIN PIPE DOWN FROM RO-1, ROUTE HORIZONTALLY INTO

EQUIPMENT ROOM 106 AND THEN DOWN TO CRAWLSPACE.

CONTRACTOR TO COORDINATE EXACT PIPE SIZE AND DISCHARGE

LOCATION WITH INSTALLED REVERSE OSMOSIS SYSTEM. CONNECT

TO SAME DRAIN PIPE THAT EXISTING AHU’S CONDENSATE DRAIN

CONNECTED TO IN CRAWLSPACE.

20 INSTALL AN AUDIBLE AND VISUAL ALARM FOR HUMIDITY AND

TEMPERATURE LEVELS OUTSIDE NORMAL OPERATING CONDITIONS

OF AHU/HUMIDIFIER. REPORT GENERAL ALARM TO BAS.

21 LOCATION OF NEW SMOKE DETECTOR AND DAMPER TO BE

CONNECTED TO AHU-1. REFER TO DRAWING M601 FOR ADDITIONAL

INFORMATION.

22 RE-ROUTE EXISTING 4” PVC ROOF DRAIN AS NEEDED TO

ACCOMMODATE NEW DUCTWORK.

1/4" = 1'-0"

LEVEL 1 MRI SUITE HVAC PIPING PLAN

NOT TO SCALE

HUMIDIFIER (H-1) DRAIN PAN DETAIL - DUCT MOUNTED

NOT TO SCALE

HUMIDIFIER (H-1) PIPING DETAIL - ELECTRIC

NOT TO SCALE

BACKFLOW PREVENTER DETAIL

1/4" = 1'-0"

EQUIP RM 106 SECTION LOOKING NORTH

1/4" = 1'-0"

EQUIP RM 106 SECTION LOOKING NORTH 2

1/4" = 1'-0"

EQUIP RM 106 SECTION LOOKING EAST

EXISTING ROOF DRAIN

EXISTING ROOF HATCH

EXISTING MRI CHILLER

D

17 16 15

EF-2

IH-1

26"x24" L/A

CU-1

(E)EF

(E)EF

(E)EF

EF-1

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Dwg. of

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

FULLY SPRINKLERED

A

B

C

D

E

F

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

ARCHITECTS/ENGINEERS:SEAL

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

BID DOCUMENTS

18030

HVAC UPGRADE FOR

MRI SUITE

LOUIS A. JOHNSON VA MEDICAL CENTER

CLARKSBURG, WEST VIRGINIA

540-18-011

CJC AC

M102 08/05/2019 166

HVAC ROOF PLAN

NORTH

PROJECT

TRUE NORTH = 81

1/4" = 1'-0"

ROOF PLAN

HVAC KEYNOTES

1 NEW EXHAUST FAN EF-1. MODIFY ROOF OPENING FOR LARGER DUCT THAN EXISTING.

2 NEW EXHAUST DUCT DOWN. MODIFY ROOF OPENING FOR LARGER DUCT THAN EXISTING.

3 NEW EXHAUST FAN EF-2.

4 NEW CONDENSING UNIT NEW CU-1. ROUTE NEW REFRIGERANT PIPING FROM NEW CU-1 TO

NEW AHU-1 FOLLOWING SAME PATH AS EXISTING REFRIGERANT PIPING. SIZE

REFRIGERANT PIPING PER MANUFACTURER’S RECOMMENDATIONS.

5 NEW INTAKE HOOD IH-1. MODIFY ROOF OPENING FOR LARGER DUCT THAN EXISTING.

HVAC GENERAL NEW WORK NOTES

1 REFER TO FACILITY'S INFECTION CONTROL AND RISK ASSESSMENT (ICRA) FOR ADDITIONAL

REQUIREMENTS.

2 ALL WORK SHALL BE SCHEDULED AND COORDINATED JOINTLY WITH LOUIS A. JOHNSON VAMC.

A DETAILED JOB TIMELINE SHALL BE ESTABLISHED AND SUBMITTED FOR REVIEW AND

APPROVAL.

3 ALL STRUCTURAL AND MISCELLANEOUS STEEL REQUIRED TO SUPPORT AND ANCHOR HVAC

EQUIPMENT ON THE ROOF AND STRUCTURAL AND MISCELLANEOUS STEEL REQUIRED FOR ANY

ROOF PENETRATIONS BEYOND WHAT IS INDICATED ON THE STRUCTURAL DRAWINGS IS THE

RESPONSIBILITY OF THE CONTRACTOR. THIS INCLUDES EQUIPMENT SHOWN AS BASIS OF

DESIGN ON THE CONTRACT DOCUMENTS, EQUIVALENT EQUIPMENT, OR EQUIPMENT ACCEPTED

FROM ALTERNATE MANUFACTURERS.

4 COORDINATE WITH ROOF MANUFACTURER TO MAINTAIN ANY APPLICABLE WARRANTY.

SUPPORT

SADDLE FROM

STRUCTURE

FLEXIBLE DUCT SIZE

SAME AS DIFFUSER

INLET: 5'-0" MAX LENGTH

12"

CEILING

VOLUME DAMPER W/

LOCKING QUAD

LOCKING QUAD

SHEET METAL

SADDLE

CONICAL OUTLET

BRANCH DUCT

USE RIGID ELBOWS

FOR CHANGE OF

DIRECTION GREATER

THAN 45º

[300mm]

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT (TYP.)

NOTE:

THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT

PERMITTED FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.

TYPICAL

DIFFUSER OR

REGISTER IN

LAY-IN CLG.

THERMAL INSULATION

SEE SPECIFICATIONS

NOTE:

1. UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.

BRANCH DUCT TAKE-OFF PLAN VIEW

W

1/4 W

OR 4" MIN.

MAIN SUPPLY

DUCT

PROVIDE VOLUME DAMPER

A

IR

F

LO

W

AIR

FLOW

SUPPLY REGISTER TAKE-OFF PLAN VIEW

AIR

FLOW

AIR

FLOW

VOLUME EXTRACTOR; ADJUSTABLE

FROM FULLY CLOSED POSITION TO CFM

NOTED ON FLOOR PLANS

ADJUSTABLE

METAL ROD OR

LINKAGE

TOP REGISTER

MAIN

SUPPLY

DUCT

SEE FLOOR PLAN FOR

SPLIT DIMENSION

MAIN

SUPPLY

DUCT

TURNING VANES

AIR

FLOW

AIR

FLOW

A

IR

F

LO

W

PROVIDE

VOLUME

DAMPER

AIR SPLIT DUCT TAKE-OFF PLAN VIEW

SUPPLY REGISTER OR

BRANCH DUCT

NOTES:

1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

SIDE ELEVATION SECTION

HANDLE WITH

LOCKING

QUADRANT

INSIDE END BEARING

1/8"CLEARANCE ALL

AROUND

DAMPER BLADE

INSULATION STAND-

OFF

DUCT

INSULATION SEE

SPECIFICATION

STIFFEN BLADE

AS REQUIRED

OUTSIDE END BEARING

1/2" ROUND ROD PIN

LAY-IN CEILING DIFFUSER INSTALLATION

GYP BOARD CEILING DIFFUSER INSTALLATION

FOR GYPSUM BOARD CEILING INSTALLATION, LOCATE

VOLUME DAMPER IMMEDIATELY UPSTREAM OF DIFFUSER

DROP OR AT TAP COLLAR. SUCH THAT VOLUME DAMPER AT

TAP CAN BE ACCESSED FROM DIFFUSER OPENING IN CLG.

D D

BRANCH DUCTCLOSED END OF

BRANCH DUCT

OBD

DIFFUSER

FLEXIBLE DUCTWORK

TAP COLLAR

CEILING

GYP-BOARD

FRAME

VOLUME DAMPER

AIR FLOW

USE CONICAL TAP WHERE DUCT SIZE &

ELEVATION PERMITS, OTHERWISE USE

CYLINDRICAL TAP

CLOSED END OF

BRANCH DUCT

OBD

DIFFUSER

FLEXIBLE DUCTWORK

TAP COLLAR

USE CONICAL TAP WHERE DUCT SIZE &

ELEVATION PERMITS, OTHERWISE USE

CYLINDRICAL TAP

BRANCH DUCT

VOLUME DAMPER

NOTE:

1. ALL FLEXIBLE DUCTWORK SHALL BE UL-181 CLASS 1 RATED.

LAY-IN FRAME

CEILING

D D D D

VOLUME DAMPER

AIR FLOW

24" MAX

UNLESS FOOT STRAP IS

PLACED UNDER A BOTTOM

REINFORCEMENT

SCREWS

1" MIN.

STRAP HANGERS LOAD RATED

FASTENERS

HANGER

BAND OF SAME SIZE AS

HANGER STRAP

36" DIA.

MAX.

24" DIA.

MAX.

LOWER HANGER ATTACHMENTS

TRAPEZE HANGERS

L

HANGERS MUST NOT

DEFORM DUCT SHAPE

HANGER RODS

OR STRAPS

BAND ONE HALF-ROUND MAY BE

USED IF DUCT IS MAINTAINED.

W

2" 2"

ROD

UPPER ATTACHMENT DEVICES

STRAP HANGER OR

HANGER ROD (NOT

SHOWN)

EXPANSION SHIELD

CONCRETE ANCHOR

NOTE: NOT PERMITTED IN

METAL ROOF DECK.

WASHER

METAL DECK

CONCRETE

FLOOR SLAB

NOTE:

EXPANSION SHIELD ANCHORS ARE PERMITTED IN SHEAR

ONLY. DO NOT INSTALL VERTICALLY.

FRICTION CLAMP OR

CADDY CLAMP

NUT & BOLT

STRAP HANGER OR

ALL THREAD ROD

HANGER ROD

RETAINING CLIP

6aC - CLAMP W/ RETAINING CLIP

6bC - CLAMP W/ LOCK NUT(OPTIONAL)

STRAP

HANGER

WASHER MAY BE OMITTED

WITH 100 LB. MAX. LOAD ON

22 GA STRAP WHEN

FOLDED.

BENT ALL THREAD

HANGER ROD

SLOT IN DECK

HANGER STRAP

BOLT, PIN OR SCREW

PENETRATION

NOTE:

1.

2.

3.

4.

5.

ACCESS DOORS SHALL BE GASKETED AND HINGED TO OPEN

AGAINST FAN OPERATING PRESSURE TO PREVENT AIR LEAKAGE.

MINIMUM ACCESS DOOR WIDTH SHALL BE 24" [600mm].

ACCESS DOOR HEIGHT SHALL BE DETERMINED BY UNIT CASING

BUT NOT TO EXCEED 6'-0" [1800mm].

ACCESS DOORS ON FAN SUCTION SHALL OPEN OUTWARD.

ACCESS DOORS ON FAN DISCHARGE SIZE SHALL OPEN INWARD.

14 15 1613121110987654321

AIR INTAKE FOR MISSION

CRITICAL FACILITIES, SEE

VA STANDARD DETAILS.

RETURN AIR INTAKE.

MIN CLEARANCE - 36"

COIL PULL DISTANCE

AIR HANDLING UNIT ITEM

MIN OA

TWO BEDS OF

FILTERS VAV

MIN OA THREE BEDS

OF FILTERS CV

100% OA

TWO BEDS

OF FILTERS CV

100% OA

THREE BEDS OF

FILTERS CV

* MIXING BOX 1 YES YES NO NO

* BLENDER SECTION 2 YES YES NO NO

PRE-FILTERS (SIDE

ACCESS)

3 YES YES YES YES

INSPECTION

SECTION, SMALL

4 YES YES YES YES

AFTER FILTER (SIDE

ACCESS)

5 YES YES YES YES

ACCESS SECTION,

MED-LARGE

6 YES YES YES YES

* HEAT RECOVERY COIL 7 NO NO YES YES

ACCESS SECTION,

MED-LARGE

8 NO NO YES YES

* PRE-HEAT COIL 9 YES YES YES YES

INSPECTION

SECTION,SMALL

10 YES YES YES YES

HUMIDIFIER 11 YES YES YES YES

COOLING COIL 12 YES YES YES YES

FAN 13 YES YES YES YES

* DIFFUSER PLATE 14 NO NO NO YES

ACCESS

SECTION,MED-LARGE

15 NO NO YES YES

* HEPA FILTER 16 NO NO NO YES

DISCHARGE PLENUM

(VERTICAL)

17 YES YES YES YES

* AS REQUIRED

ACCESS DOOR

NOTE 3

SUPPLY

STEAM HUMIDIFIER

42" MAX

ACCESS DOOR

NOTE 3

NOTE 1

AIR HANDLING UNIT

NOTE 3

ROUTE TO

FLOOR SINK

3'-0" 3'-0"

NOTES:

1. TRANSITION WELDED STAINLESS STEEL 3' UPSTREAM OF HUMIDIFIER AND 3'

DOWNSTREAM OF HUMIDIFIER.

2. INTEGRAL STAINLESS STEEL DRAIN PAN SLOPE FROM ALL DIRECTIONS TO DRAIN

CONNECTION. SLOPE 0.125" PER 1'-0".

3. PROVIDE MIN. 18" WIDE ACCESS DOOR DIRECTLY UPSTREAM AND DOWNSTREAM OF

HUMIDIFIER.

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15

ACCESS DOOR

ACCESS PANEL

SECTION "B-B"

SECTION "A-A"

INSULATION

GASKET

DUCT

INSULATION

"A"

"A"

HANDLE INSIDE

NEOPRENE GASKET

CASING

FLEXIBLE WASHER

FACTORY FABRICATED

LATCH/HANDLE

1-1/2" MIN.

INSULATION

"B" "B"

NOTES:

1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS.

ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,

SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

3. FOR R < 1-1/2 W, VANES SHALL BE USED.

R SHALL

EQUAL OR

BE

GREATER

THAN W.

W

R

STANDARD RADIUS OR

LONG RADIUS ELBOW

R SHALL

EQUAL OR

BE

GREATER

THAN 1/3W.

R SHALL

EQUAL OR

BE

GREATER

THAN 1/6W.

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

W W

2/3 W

1/2 W

VANE

VANER

R

1/

W

1/6 W

1/

W

W

W1

NOTES:

1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS

DETAILED BY SMACNA.

2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS

VANE TYPE REGARDLESS OF W DIMENSION.

3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2"

MAXIMUM SPACE BETWEEN VANES AND A 3/4" TRAILING EDGE.

4. WHEN W EQUALS W2 AND W1…