N O
R
TH
NO REVISION DATE
ADDENDUM NO. 1
HVAC UPGRADE FOR
MRI SUITE
LOUIS A. JOHNSON VA MEDICAL CENTER
CLARKSBURG, WEST VIRGINIA
540-18-011
JU BK08/05/2019
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
FULLY SPRINKLERED
A
B
C
D
E
F
2000 GEORGETOWNE DRIVE
PH: 724.444.1100
www.pve-llc.com
PVE PROJECT NUMBER:
ARCHITECTS/ENGINEERS:SEAL
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
WATERFRONT CORPORATE PARK III, SUITE 101
SEWICKLEY, PA 15143
BID DOCUMENTS
161663
FAX: 724.444.1104
1 08/08/2019
GENERAL NOTES
GENERAL NOTES - DIVISION 1
1. ALL CONSTRUCTION WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE MOST RECENT EDITION OF ALL FEDERAL, STATE AND LOCAL REGULATIONS, INCLUDING BUT NOT LIMITED TO THE WEST VIRGINIA BUILDING CODE, AMERICAN INSTITUTE OF
STEEL CONSTRUCTION (AISC), AMERICAN CONCRETE INSTITUTE (ACI) AND THE BRICK INSTITUTE OF AMERICA (BIA). ANY INFORMATION
CONTAINED IN THESE DRAWINGS THAT DIFFERS FROM STANDARD INDUSTRY PRACTICE SHALL BE BROUGHT TO THE ENGINEER'S
ATTENTION PRIOR TO BEGINNING WORK.
2. ALL DETAILS, SECTIONS, AND NOTES SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL APPLY TO SIMILAR
SITUATIONS, UNO.
3. NO CHANGE IN SIZE, DIMENSION OR POSITION OF STRUCTURAL ELEMENTS SHALL BE MADE WITHOUT THE APPROVAL OF THE
STRUCTURAL ENGINEER OF RECORD.
4. FIELD VERIFY ALL EXISTING CONDITIONS AND INFORMATION CONTAINED ON THESE DRAWINGS AND BRING ANY DISCREPANCIES
TO THE ENGINEER'S ATTENTION IMMEDIATELY BEFORE STARTING CONSTRUCTION AND/OR SUBMITTING SHOP DRAWINGS. ANY
DISCREPANCY BETWEEN THESE PLANS AND THE ACTUAL FIELD CONDITIONS SHALL BE THE CONTRACTOR'S RESPONSIBILITY AND BE
PERFORMED AT NO ADDITIONAL COST.
5. TAKE ALL MEASURES NECESSARY TO PROTECT EXISTING AND NEW UTILITIES AND BUILDINGS AND ASSUME FULL RESPONSIBILITY
FOR ANY DAMAGE DURING CONSTRUCTION. RESTORATION OF DAMAGED AREAS SHALL BE TO THE SATISFACTION OF THE OWNER, AT NO COST TO THE OWNER.
6. ALL MATERIALS USED ON THIS PROJECT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
ALL EQUIPMENT USED ON THIS PROJECT SHALL BE OPERATED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
7.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION MEANS AND METHODS TO COMPLETE THE SPECIFIED WORK AND
TO ENSURE THAT ALL WORK IS PERFORMED IN A SAFE MANNER TO THEIR WORKERS AS WELL AS THE PUBLIC. ANY MINOR DETAILS NOT
SHOWN, BUT NECESSARY FOR THE PROPER COMPLETION OF THE SPECIFIED WORK SHALL BE DEEMED INCLUDED IN THE WORK AND BE
PERFORMED AT NO ADDITIONAL COST.
8. THE CONTRACTOR SHALL SUBMIT DETAILED SHOP DRAWINGS TO THE ENGINEER FOR THEIR APPROVAL FOR ALL WORK SPECIFIED ABOVE.
ANY WORK PERFORMED PRIOR TO RECEIVING APPROVAL FROM THE ENGINEER IS PERFORMED AT THE CONTRACTOR'S RISK AND IF DEEMED
UNACCEPTABLE WILL BE REPAIRED AT NO ADDITIONAL COST TO THE OWNER.
9. DO NOT REPRODUCE ANY PORTION OF THE STRUCTURAL CONTRACT DRAWINGS FOR RESUBMITTAL AS SHOP DRAWINGS. SHOP
DRAWINGS PRODUCED IN SUCH A MANNER WILL BE REJECTED AND RETURNED.
10. THESE GENERAL DESIGN AND CONSTRUCTION NOTES ARE INTENDED TO BE INTERPRETED IN COMBINATION WITH THE PROJECT
ARCHITECTURAL AND STRUCTURAL SPECIFICATIONS. IN THE EVENT OF ANY INCONSISTENCY, THE MORE STRINGENT REQUIREMENT SHALL
APPLY. IN THE EVENT OF ANY QUESTION OF INTERPRETATION, THE DECISION OF THE ENGINEER SHALL PREVAIL.
11. REFER TO ARCHITECTURAL, CIVIL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR DIMENSIONS AND LOCATIONS OF
OPENINGS, INSERTS, DEPRESSIONS, EQUIPMENT PADS, DRIPS, REVEALS, FINISHES, AND OTHER SUCH PROJECT REQUIREMENTS NOT
SHOWN ON STRUCTURAL DRAWINGS.
12. SUBMIT DIMENSIONED COORDINATED SHOP DRAWINGS SHOWING THE LOCATIONS OF ALL SLEEVES AND OPENINGS REQUIRED BY
ALL TRADES THROUGH STRUCTURAL ELEMENTS. ANY ADDITIONAL OPENINGS NOT SHOWN ON SHOP DRAWINGS WILL REQUIRE WRITTEN
APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD.
13. TAKE ALL MEASURES NECESSARY TO PROTECT EXISTING AND NEW UTILITIES AND BUILDINGS AND ASSUME FULL RESPONSIBILITY
FOR ANY DAMAGE DURING CONSTRUCTION. RESTORATION OF DAMAGED AREAS SHALL BE TO THE SATISFACTION OF THE OWNER, AT NO COST TO THE OWNER.
14. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR DETAILED INFORMATION REGARDING FINISHES, WATERPROOFING, LOCATIONS OF NON-LOAD BEARING PARTITIONS, EXTERIOR FACE OF BUILDING, ETC.
15. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, AND PROCEDURES AND FOR COORDINATING ALL STAGES AND PHASES OF WORK.
16. MINOR DETAILS NOT USUALLY SHOWN OR SPECIFIED, BUT NECESSARY FOR PROPER CONSTRUCTION OF ANY PART OF THE
WORK SHALL BE INCLUDED.
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY
PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK. ALL NECESSARY SIGNS SHALL BE POSTED WARNING AGAINST
DANGER.
18. THE CONTRACTOR SHALL DO ALL CUTTING, PATCHING, REPAIRING AS REQUIRED TO PERFORM ALL OF THE WORK INDICATED
ON THE DRAWINGS, AND ALL OTHER WORK THAT MAY BE REQUIRED TO COMPLETE THE JOB.
19. ALL WORK TO BE PERFORMED IN AN ORDERLY, CLEAN AND LOGICAL MANNER.
20. ALL WORK SHALL BE PERFORMED BY SKILLED TRADESMEN AND SHALL BE PERFORMED IN A WORKMANLIKE MANNER IN
ACCORDANCE WITH GENERALLY ACCEPTED STANDARDS.
21. THE CONTRACTOR SHALL VISIT THE SITE AND HAVE A FAMILIARITY WITH ALL THE BUILDING CONDITIONS AND SYSTEMS.
22. THE CONTRACTOR SHALL PROVIDE ALL SHORING, BRACING, BARRICADES, TEMPORARY FENCING, PARTITIONS AND
EXCAVATIONS TO ACCOMPLISH ALL OF THE WORK IN AN APPROVED MANNER.THE CONTRACTOR SHALL BE RESPONSIBLE
FOR PROTECTING ALL WORK DURING DEMOLITION AND CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, DISTORTION
AND MISALIGNMENT. SPACE SHORING TO NOT OVERSTRESS EXISTING SLABS.
23. THE CONTRACTOR SHALL MAINTAIN THE SITE (REMOVE RUBBISH) AND PROTECT THE OWNER’S PROPERTY, PROVIDING SHIELDING AT AREAS ADJOINING THE WORK. SECURE PROPERTY AT THE END OF EACH WORKDAY.
24. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION, REMOVAL, TRANSPORTATION AND DISPOSAL
OF ALL DEBRIS AND CONSTRUCTION MATERIAL RELATED TO THE WORK IN A LEGAL MANNER.
25. DIMENSIONS GOVERN - DRAWINGS ARE NOT TO BE SCALED.
CODES AND STANDARDS
1. THE FOLLOWING CODES AND STANDARDS, INCLUDING ALL SPECIFICATIONS REFERENCED WITHIN, APPLY TO THE DESIGN AND
CONSTRUCTION OF THIS PROJECT:
a. IBC, INTERNATIONAL BUILDING CODE - 2015
b. WEST VIRGINIA BUILDING CODE - 2015
c. ASCE 7-16, "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES"
d. ACI 318-14, "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
e. AISC 360-16, "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS," JULY 7, 2016
f. AISI S100-12, "NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS", 2012 EDITION
ABBREVIATIONS
ABV ABOVE
ACI AMERICAN CONCRETE INSTITUTE
ACIP AUGERED CAST-IN-PLACE PILES
ADD'L ADDITIONAL
AE AIR-ENTRAINED
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATELY
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING & MATERIALS
AWS AMERICAN WELDING SOCIETY
B BOTTOM
B/ BOTTOM OF
BLDG BUILDING
BM BEAM
BOT BOTTOM
CJP COMPLETE JOINT PENETRATION
CLR CLEAR
CLSM CONTROLLED LOW STRENGTH MATERIAL
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
COTR CONTRACTING OFFICER'S TECHNICAL
REPRESENTATIVE
db REINFORCING BAR DIAMETER
DIA DIAMETER
DN DOWN
DTLS DETAILS
DWG DRAWING
DWLS DOWELS
EA EACH
EF EACH FACE
EL ELEVATION
ELECT ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
(E) EXISTING
EXP EXPANSION
FT FOOT/FEET
FTG FOOTING
FP FIRE PROTECTION
GALV GALVANIZE
GL GRIDLINE
H HIGH OR HORIZONTAL
HK HOOK
HORIZ HORIZONTAL
HP HIGH POINT
HS HIGH STRENGTH
HSA HEADED SHEAR ANCHOR
IN INCH(ES)
IP INFLECTION POINT
I.F. INSIDE FACE
JT JOINT
SUBMITTALS
MATERIALS - LITERATURE SAMPLES, MSDS SHEETS, PRODUCT DATA SHEETS, ETC. ON ALL MATERIALS TO BE INSTALLED UNDER THIS CONTRACT
SHALL BE SUBMITTED TO THE ENGINEER FOR THEIR REVIEW AND APPROVAL PRIOR TO USE. IF THE CONTRACTOR INSTALLS ANY MATERIALS PRIOR
TO RECEIVING APPROVAL FROM THE ENGINEER, THEY DO SO AT THEIR OWN RISK. ANY WORK THAT NEEDS TO BE REPLACED FOR THIS REASON
SHALL BE PERFORMED AT NO ADDITIONAL COST TO THE OWNER. THE USE OF ASBESTOS OR MATERIALS CONTAINING ASBESTOS IS PROHIBITED.
IN THE EVENT ANY SPECIFIED MATERIALS CONTAIN ASBESTOS IT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER FOR APPROPRIATE ACTION.
CONTRACTOR MUST ALSO SUBMIT DETAILED SHOP DRAWINGS FOR ALL WORK TO BE INSTALLED ON THIS PROJECT.
SHOP DRAWINGS - PREPARE PROJECT-SPECIFIC INFORMATION, DRAWN ACCURATELY TO SCALE OF ALL WORK SPECIFIED IN THE CONTRACT DOCUMENTS.
ALL SHOP DRAWINGS MUST BE PREPARED USING AUTOCAD OR OTHER SIMILAR SOFTWARE. HAND DRAWN SKETCHES SHALL
NOT BE ACCEPTABLE, UNLESS SPECIFICALLY PERMITTED BY THE ENGINEER. DO NOT BASE SHOP DRAWINGS ON REPRODUCTIONS OF THE
CONTRACT DOCUMENTS OR STANDARD PRINTED DATA. ALL SHOP DRAWINGS MUST INCLUDE THE FOLLOWING:
a. DIMENSIONS.
b. IDENTIFICATION OF PRODUCTS.
c. FABRICATION AND INSTALLATION DRAWINGS.
d. DESIGN CALCULATIONS (IF APPLICABLE) WITH ENGINEER'S SEAL AND SIGNATURE.
e. COMPLIANCE WITH SPECIFIED STANDARDS.
f. NOTATION OF DIMENSIONS ESTABLISHED BY FIELD MEASUREMENT.
g. RELATIONSHIP TO ADJOINING CONSTRUCTION CLEARLY INDICATED.
h. SEAL AND SIGNATURE OF PROFESSIONAL ENGINEER IF A STRUCTURAL INSTALLATION (I.E. – RAILINGS, HEADER BEAMS, ETC.)
THE ENGINEER WILL REVIEW ALL SUBMITTALS AND PROVIDE A WRITTEN RESPONSE AS SOON AS POSSIBLE, BUT NOT TO EXCEED FOURTEEN (14)
DAYS OF RECEIPT OF SAME. IF THERE ARE SUBMITTALS MADE OF A STRUCTURAL INSTALLATION, THEY MUST BE SIGNED AND SEALED BY A
LICENSED PROFESSIONAL ENGINEER IN THE STATE OF WEST VIRGINIA.
BUILDING LOADS
1. SUPERIMPOSED DEAD LOAD AND LIVE LOADS
a. ROOF LIVE LOAD 20 PSF
2. SNOW LOADS
a. GROUND-ROOF SNOW LOAD, Pg 25 PSF
b. FLAT ROOFSNOW LOAD, Pf 21 PSF
c. MAXIMUM DRIFT LOAD 56 PSF
d. SNOW EXPOSURE FACTOR, Ce 1.0
e. SNOW IMPORTANCE FACTOR, Ig 1.1
f. THERMAL FACTER, Ct @ MRI 1.0
THERMAL FACTER, Ct @ DRIVE THRU 1.2
K KIPS (1000 POUNDS)
kN KILONEWTON kPa KILOPASCAL l LITER
L LENGTH
LBS POUNDS
Ld REINF BAR DEVELOPMENT LENGTH
LLH LONG LEG HORIZ
LLV LONG LEG VERT
LP LOW POINT
LTWT LIGHT WEIGHT
m METER mm MILLIMETER
MAX MAXIMUM
MANUF MANUFACTURER
MECH MECHANICAL
MEP MECH/ELECT/PLUMBING
MIN MINIMUM
MPa MEGAPASCAL
MTL METAL
N NEWTON
NLWT NORMAL WEIGHT
(N) NEW
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
O.F. OUTER FACE
PJP PARTIAL JOINT PENETRATION
PSF POUNDS PER SQAURE FOOT
PSI POUNDS PER SQAURE INCH
PT POST-TENSION
R RISER
REF REFERENCE
REINF REINFORCING OR REINFORCEMENT
REQ'D REQUIRED
SCHED SCHEDULE
SC SLIP CRITICAL
SDI STEEL DECK INSTITUTE
SDL SUPERIMPOSED DEAD LOAD
SEC SECONDS
SIM SIMILAR
SOG SLAB-ON-GRADE
STD STANDARD
SJI STEEL JOIST INSTITUTE
STL STEEL
STRUCT STRUCTURAL
T TOP OR TREAD
T/ TOP OF
TOF TOP OF FOOTING
TOS TOP OF STEEL
THK THICK
TMS THE MASONRY SOCIETY
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V VERTICAL
VERT VERTICAL
VIF VERIFY IN FIELD
W/C WATER-CEMENTITIOUS MATERIAL RATIO
W WIDTH
WD WOOD
WP WORK POINT
WWR WELDED WIRE REINFORCEMENT
STRUCTURAL STEEL - DIVISION 5
1. STRUCTURAL STEEL FABRICATION, ERECTION AND CONNECTION DESIGN SHALL CONFORM TO AISC "SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS."
2. STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING DESIGNATIONS, UNO:
WIDE FLANGE BEAMS ASTM A992
HSS RECTANGULAR ASTM A500 GR B
ANGLES ASTM A36
MISCELLANEOUS STEEL PLATES ASTM A36
ANCHOR RODS ASTM F1554, GRADE 36, UNO
THREADED RODS ASTM A36
3. BOLTS SHALL BE MINIMUM 3/4" DIAMETER AND SHALL CONFORM TO REQUIREMENTS OF ASTM A325, UNO.
4. WELDING ELECTRODES AND FLUXES SHALL CONFORM TO ONE OF THE SPECIFICATIONS OF THE AMERICAN WELDING SOCIETY LISTED IN
STRUCTURAL WELDING CODE - STEEL, AWS D1.1. ELECTRODES SHALL HAVE A MINIMUM TENSILE STRENGTH OF 70 KSI.
5. IF PARTS JOINED BY FILLET WELDS ARE SEPARATED BY MORE THAN 1/16 IN. THE LEG OF THE FILLET WELD SHALL BE INCREASED BY THE
AMOUNT OF THE ROOT OPENING. ROOT OPENING SHALL NOT EXCEED 3/16 IN.
6. UNLESS OTHERWISE INDICATED ON THE DRAWINGS FILLET WELDS SHALL HAVE A MINIMUM SIZE OF 1/4".
7. GROUT UNDER STEEL PLATES SHALL HAVE A MINIMUM 28 DAY DESIGN COMPRESSIVE STRENGTH OF 7000 PSI.
8. BOLTED CONNECTIONS SHALL BE MADE WITH HIGH STRENGTH BOLTS, 3/4" MIN DIAMETER, UNLESS OTHERWISE NOTED, PER ASTM A325X.
HIGH STRENGTH BOLTS SHALL BE TIGHTENED BY THE TURN-OF-NUT METHOD.
9. BOLTED CONNECTIONS SHALL HAVE A MINIMUM OF 2 BOLTS.
10. FABRICATOR AND ERECTOR SHALL BE CURRENTLY CERTIFIED IN THE AISC QUALITY CERTIFICATION PROGRAM, CATEGORY STD.
11. FABRICATOR MAY SUBMIT ALTERNATIVE CONNECTION DETAIL PER AISC FOR THE FACTORED SHEAR REACTION SHOWN IN SCHEDULE.
IF ALTERNATIVE CONNECTION IS SUBMITTED DURING THE SHOP DRAWING PHASE, ENGINEER OF RECORD MUST VERIFY AND APPROVE
CHANGE.
12. CONNECTIONS TO COLUMNS SHALL HAVE A MAXIMUM ECCENTRICITY OF 3" WITH RESPECT TO THE FLANGE OR WEB AS APPLICABLE.
13. PROVIDE ONE SHOP COAT OF RUST-INHIBITING GRAY PRIMER, 2 MILS DRY THICKNESS ON ALL STRUCTURAL STEEL MEMBERS AND
DECKING EXCEPT AT FIELD WELD LOCATIONS.
14. ALL STRUCTURAL STEEL SHALL BE FIELD PAINTED BLACK.
15. DO NOT FIELD CUT STRUCTURAL STEEL MEMBERS WITHOUT THE WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD.
16. DO NOT SPLICE STEEL MEMBERS EXCEPT WHERE SPECIFICALLY DETAILED ON THE DRAWINGS WITHOUT THE WRITTEN APPROVAL OF
THE STRUCTURAL ENGINEER OF RECORD.
17. THE CONTRACTOR SHALL PROVIDE ADEQUATE TEMPORARY SUPPORTS UNTIL ALL PERMANENT BRACING AND FLOOR SLABS ARE IN PLACE.
18. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED MINOR STEEL PIECES OF PLATES, ANGLES, STRUCTURAL STEEL SHAPES AND C
ONNECTIONS NECESSARY TO MAKE THE WORK COMPLETE WHETHER OR NOT SHOWN ON DRAWINGS, WITHOUT ADDITIONAL
COMPENSATION.
19. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND SHALL NOT PROCEED WITH THE WORK UNTIL PLANS AND DETAILS HAVE BEEN
FULLY APPROVED.
20. THE CONTRACTOR SHALL NOT REPRODUCE THE CONSTRUCTION DOCUMENTS FOR USE AS SHOP DRAWINGS.
21. THE CONTRACTOR AND SUBCONTRACTORS MUST SUBMIT IN WRITING ANY REQUEST FOR MODIFICATIONS TO THE PLANS AND
SPECIFICATIONS. SHOP DRAWINGS THAT ARE SUBMITTED TO THE ENGINEER FOR THEIR REVIEW DO NOT CONSTITUTE, "IN WRITING", UNLESS IT IS BROUGHT TO THE ATTENTION OF THE ENGINEER THAT SPECIFIC CHANGES ARE BEING SUGGESTED. CHANGES TO THE PLANS
AND SPECIFICATIONS BY MEANS OF SHOP DRAWINGS SHALL BE THE RESPONSIBILITY OF THE PERSON INITIATING THE CHANGES.
METAL DECK - DIVISION 5
1. METAL ROOF DECK SHALL BE SUPPLIED PRIME-PAINTED, SIZED PER THE CONFIGURATIONS SPECIFIED ON THE DRAWINGS, MANUFACTURED BY VULCRAFT, OR AN APPROVED EQUIVALENT, AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATION AND STEEL DECK INSTITUTE STANDARDS.
2. STEEL DECK SECTIONS SHALL BE LAP CONNECTED AND ATTACHED TO THE SUPPORTING STRUCTURE AS SPECIFIED ON THE DESIGN DRAWINGS
3. PROVIDE, AS REQUIRED, ALL RIDGE AND VALLEY PLATES, COLUMN CLOSURES, CANT STRIPS, SUMP PLATES AT PIPING PENETRATIONS AND
RECESSED SUMP PANS AT ROOF DRAINS. PROVIDE SUPPLEMENTAL FRAMING AT OPENINGS AS REQUIRED FOR SUPPORT OF THE METAL
DECK. ALL OPENINGS SHALL BE COORDINATED WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION DRAWINGS
4. NO LOADS EXCEEDING 50 POUNDS SHALL BE PERMITTED TO BE HUNG FROM ANY STEEL DECKING. DUCTWORK, PIPING, ETC. SHALL BE HUNG
DIRECTLY FROM STRUCTURAL STEEL, SUPPLEMENTARY MEMBERS OR ANCHORS EMBEDDED IN THE CONCRETE. SUPPLEMENTARY MEMBERS, IF USED, SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
5. ALL SURFACES OF DECKING THAT WILL BE EXPOSED IN THE FINISHED STRUCTURE SHALL BE FIELD-PAINTED BLACK.
LIGHT GAUGE (COLD-FORMED) METAL STRUCTURAL FRAMING:
1. CONTRACTOR IS RESPONSIBLE FOR THE DELEGATED DESIGN OF ALL COLD-FORMED METAL FRAMING. STRUCTURAL PROPERTIES OF
FRAMING MEMBERS SHALL BE CALCULATED IN ACCORDANCE WITH REQUIREMENTS OF THE CURRENT AMERICAN IRON AND STEEL
INSTITUTE’S (AISI) “SPECIFICATIONS FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS”.
2. ALL COLD-FORMED METAL FRAMING MEMBERS SHALL CONFORM TO ASTM A653 WITH A G-60 ZINC COATING. ALL COLD-FORMED
METAL CONNECTIONS SHALL BE G-90.
3. ALL STUDS AND TRACKS SHALL BE 18 GAUGE MINIMUM WITH A MINIMUM YIELD STRENGTH OF 33KSI. PLATES, GUSSETS AND CLIPS
SHALL HAVE MINIMUM YIELD STRENGTH OF 40 KSI AND SHALL HAVE THICKNESS AS REQUIRED FOR SPECIFIC CONDITIONS.
4. ALL LIGHT GAUGE ELEMENTS 16 GAUGE AND HEAVIER SHALL HAVE A MINIMUM YIELD STRENGTH OF 50 KSI, AND ALL ELEMENTS 18
GAUGE AND LIGHTER SHALL HAVE A MINIMUM YIELD STRENGTH OF 33 KSI. ALL EXTERIOR FRAMING SHALL BE A MINIMUM OF 18
GAUGE.
5. MAXIMUM STUD SPACING SHALL BE 16” O.C., UNLESS OTHERWISE NOTED.
6. UNLESS OTHERWISE NOTED, STUD MEMBERS SHALL BE MANUFACTURER’S STANDARD “C” SHAPED STUDS/JOISTS OF THE SIZE, FLANGE, WIDTH AND GAUGE REQUIRED BY DESIGN. ALL MEMBERS SHALL HAVE A MINIMUM FLANGE LIP RETURN OF ½” AND SHALL SATISFY THE
MINIMUM PROPERTIES IN ACCORDANCE WITH THE STEEL STUD MANUFACTURER’S ASSOCIATION (SSMA).
7. COLD-FORMED METAL FRAMING SYSTEMS, INCLUDING ALL LOAD-BEARING INTERIOR AND EXTERIOR WALLS, LATERAL SYSTEM ELEMENTS
AND PRE-FABRICATED ROOF TRUSSES SHALL BE DESIGNED BY A QUALIFIED PROFESSIONAL ENGINEER AND SHALL BE INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS AND SHOP DRAWINGS. IT IS THE CONTRACTOR’S RESPONSIBILITY TO DESIGN
AND DETAIL ALL COLD-FORMED STEEL FRAMING AND THEIR CONNECTION TO THE PRIMARY STRUCTURE IN ACCORDANCE WITH THE
CURRENT LOCAL BUILDING CODE AND AISI’S STANDARD SPECIFICATIONS. ALL LIGHT GAUGE MEMBERS SHALL BE DESIGNED PER THE
APPLICABLE CODES AND LOADINGS NOTED WITHIN THE DESIGN CRITERIA SECTION OF THESE GENERAL NOTES
8. LIGHT GAUGE CONTRACTOR IS RESPONSIBLE FOR SUPPLYING SHOP DRAWINGS AND DESIGN CALCULATIONS FOR REVIEW AND
APPROVAL. SHOP DRAWINGS SHALL INDICATE STUDS, JAMBS, POSTS, HEADERS, BRACING, AND OTHER NECESSARY COMPONENTS
REQUIRED FOR CONSTRUCTION. ALL MEMBER SIZES, SHAPES, GAUGES, AND SPACES SHALL BE CLEARLY PROVIDED ALONG WITH
CONNECTIONS AND FASTENERS. SHOP DRAWINGS AND CALCULATIONS SHALL BE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER
LICENESED WITHIN THE PROJECT STATE.
9. COLD-FORMED METAL FRAMING SYSTEM SHALL BE DESIGNED TO ACCOMMODATE CONSTRUCTION TOLERANCES, DEFLECTION OF
BUILDING STRUCTURAL MEMBERS AND CLEARANCES OF INTENDED OPENINGS. PROVIDE DEFLECTION ALLOWANCE IN STUD TRACK
DIRECTLY BELOW BUILDING FRAMING FOR ALL NON-LOAD BEARING WALLS. PROVIDE VERTICAL SLIDE CLIPS AND/OR TRACKS WHERE
REQUIRED FOR ALLOW FOR VERTICAL MOVEMENT AS NOTED. THE MAXIMUM PERMISSIBLE DEFLECTIONS FOR THE FRAMING ARE AS
FOLLOWS:
a. EXTERIOR WALL (MASONRY VENEER) L/600 (HORIZONTAL)
b. EXTERIOR WALL (NON-MASONRY VENEER ) L/360 (HORIZONTAL)-
c. NON-LOAD BEARING EXTERIOR WALL: 1” UP & 1” DOWN (VERTICAL)
10. FRAMING COMPONENTS SHALL BE CUT SQUARELY AND CLEANLY FOR ATTACHMENTS TO PERPENDICULAR MEMBERS OR AS REQUIRED
FOR ANGLULAR ATTACHMENTS.
11. FIELD CUTTING OF LIGHT GAUGE MEMBERS MUST BE DONE WITH SAW OR SHEARS. TORCH CUTTING OF COLD-FORMED MEMBERS IS
STRICTLY PROHIBITED.
12. FASTENING SHALL BE MADE WITH SELF DRILLING SCREWS OR WELDING.
13. FASTENERS SHALL BE COMPATIBLE WITH THE MATERIAL, GAUGE, AND FINISH. WIRE TYING IS PROHIBITED.
14. ALL WELDING SHALL BE IN ACCORDANCE WITH AWS SPECIFICATION D1.3. NO WELDING OF MEMBERS LESS THAN 14 GAUGE IN
THICKNESS IS PERMITTED WITHOUT PRE-APPROVAL OF THE ENGINEER OF RECORD. ALL WELDING SHALL BE PERFORMED BY CERTIFIED
WELDERS WITH ALL WELDS TOUCHED UP WITH ZINC RICH PAINT IN ACCORDANCE WITH ASTM A780.
15. LIGHT GUAGE STEEL FRAMING MEMBERS SHALL BE ATTACHED TO THE BUILDING STRUCTURE AS INDICATED WITHIN THE DETAILS. ALL
ATTACHMENTS AND DESIGNS SHALL BE THE RESPONSIBILITY OF THE LIGHT GAUGE CONTRACTOR.
16. PROVIDE BRIDGING IN ALL NON-LOAD-BEARING CURTAIN WALL STUDS AT A MAXIMUM SPACING OF 60” O.C. LOCATE ONE ROW OF
BRIDGING WITHIN 18” OF THE TOP TRACK WHEN A SINGLE DEEP LEG DEFLECTION TRACK IS USED. SPACE BRIDING IN LOAD BEARING
WALLS AT A MAXIMUM SPACING OF 48” O.C.
17. INSTALL SUPPLEMENTARY FRAMING, BLOCKING, AND BRACING IN METAL FRAMING SYSTEM WHEREVER WALLS OR PARTITIONS ARE
INDICATED TO SUPPORT FIXTURES, EQUIPMENT, SERVICES, CASEWORK, HEAVY TRIM AND FURNISHING AND SIMILAR WORK REQUIRING
ATTACHMENT TO THE WALL OR PARTITION.
18. NO NOTCHING OR COPING OF STUDS IS PERMITTED UNLESS EXPLICITLY SHOWN ON THE DESIGN AND SHOP DRAWINGS. ALL FIELD-CUT
HOLES MUST BE REINFORCED.
19. ALL HEADERS AND BUILT-UP BEAMS SHALL BE CONSTRUCTED OF UNPUNCHED MATERIAL ONLY AND SHALL HAVE APPROPRIATE
INSULATION PLACED IN BUILT-UP MEMBERS THAT ARE INACCESSIBLE UPON COMPLETION OF FRAMING WORK.
20. COORDINATE ALL MECHANICAL OPENINGS AND LOUVERS WITH MEP.
21. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
CAST-IN-PLACE CONCRETE- DIVISION 3
1. PROVIDE CAST-IN-PLACE CONCRETE FOR EACH CLASS OF CONCRETE SHOWN IN THE CONCRETE MATERIAL SCHEDULE AND AS REQUIRED BY
CONSTRUCTION METHODS AND SCHEDULES.
2. REINFORCING SHALL BE AS FOLLOWS:
a. CONVENTIONAL DEFORMED REINFORCING BARS NOT INDICATED TO BE WELDED - ASTM A615, GRADE 60.
b. CONVENTIONAL DEFORMED REINFORCING BARS INDICATED TO BE WELDED - ASTM A706, GRADE 60.
c. WELDED WIRE REINFORCEMENT - ASTM A185, SUPPLIED IN FLAT SHEETS.
3. CONCRETE COVER OVER REINFORCING SHALL BE AS FOLLOWS, UNO:
a. CONCRETE CAST AGAINST & PERMANENTLY EXPOSED TO EARTH OR WEATHER - 3 in.
b. REINFORCING IN SLABS & WALLS NOT EXPOSED TO EARTH OR WEATHER - 3/4 in.
c. REINFORCING EXPOSED TO EARTH OR WEATHER
• #5 & SMALLER - 1 1/2 in.
• #6 & LARGER - 2 in.
d. COVER TO STIRRUPS & TIES IN BEAMS & COLUMNS - 1 1/2 in.
4. SPLICE REINFORCING BARS PER ACI 318 WITH CLASS B TENSION LAP SPLICES, UNO. LAP LENGTHS ARE INDICATED IN THE REINFORCING BAR
DEVELOPMENT LENGTH TABLE NOTES.
5. WWR SHALL BE LAP SPLICED PER ACI 318 AND TIED SECURELY.
6. DOWELS SHALL MATCH AND BEE CLASS B TENSION LAP SPLICED WITH THE MAIN REINFORCEMENT, UNO.
7. WHERE REINFORCEMENT IS NOT PROVIDED CONTACT THE STRUCTURAL ENGINEER OR RECORD.
8. FIELD BENDING OF REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE IS NOT PERMITTED UNLESS INDICATED ON THE DRAWINGS OR
APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD. REBAR SHALL NOT BE HEATED WITH A TORCH IN THE FIELD.
9. DO NOT WELD REINFORCING UNLESS INDICATED OR APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD.
10. ALL CONSTRUCTION JOINTS SHALL BE WIRE BRUSHED, CLEANED, AND COATED WITH A BONDING AGENT OR MOISTENED WITH A CEMENT
SLURRY SCRUBBED INTO THE JOINT IMMEDIATELY PRIOR TO PLACING NEW CONCRETE.
11. PROVIDE A WATERSTOP IN ALL WALL AND SLAB CONSTRUCTION JOINTS EXPOSED TO EARTH OR WEATHER, COVERED WITH A WATERPROOF
MEMBRANE AND WHERE INDICATED.
12. CHAMFER ALL EXPOSED CORNERS 3/4 in, UNO.
Dwg. of
S001