36C24518Q0226-0003001.docx

DOCX document 15 KB Posted

Attached to
Air Balancing and Testing BASE 8/1/18 TO 7/31-19 512-C80455
Solicitation number
36C24518Q0226
Issued by

About this file

36C24518Q0226 0003 Question and Answers.docx

View the file

Other files

File Type Posted
36C24518C0172-000.docx DOCX document
36C24518Q0226-0004009.docx DOCX document
36C24518Q0226-0004011.pdf PDF
36C24518Q0226-0004010.pdf PDF
36C24518Q0226-0003004.pdf PDF
36C24518Q0226-0003005.pdf PDF
36C24518Q0226-0003011.pdf PDF
36C24518Q0226-0003007.pdf PDF
36C24518Q0226-0003003.pdf PDF
36C24518Q0226-0003013.jpg JPG image
36C24518Q0226-0003012.jpg JPG image
36C24518Q0226-0003008.pdf PDF
36C24518Q0226-0003010.pdf PDF
36C24518Q0226-0003009.pdf PDF
36C24518Q0226-0003002.pdf PDF
36C24518Q0226-0003006.pdf PDF
36C24518Q0226-0003000.docx DOCX document
36C24518Q0226-00002000.docx DOCX document
36C24518Q0226-00001000.docx DOCX document
36C24518Q0226-001.docx DOCX document
36C24518Q0226-000.docx DOCX document
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question and Answers

In response to your questions and concerns:

· There are nine (9) operating rooms

· There are several rooms within the OR suite that support the surgical service.

· The SPD / SPS area is currently being renovated. The area will not be returned to service until November 2018. This area should not be included in the scope of work for any testing and balancing activities for the current FY. However starting in FY 2019the area should be included. If necessary we can provide drawings for the area as it is currently designed per the construction documents

· We are providing the necessary drawings that will allow the vendor to establish a the quantity and type of devices that will have to be measured. This will have to be verified by the vendor We do not provide any indication that the drawing reflect the current “as-built” conditions.

· Due the size of the drawing a drawing that the following size of the drawing H33 and H33A that shows the research area HVAC system and the Original Design Air Flow Requirements, respectively, will be sent in a separate emails

· The Rooms for the Endo area are indicated GI Lab Renovation Floor Plan.

· The rooms for the Research area are noted on Drawing H33A

· The Serial number and motor specs are shown on the OR AHU Serial Number and OR AHU Spec Limited photos that are attached

· Each OR has a HEPA filter

· The attached drawings H002 and H004 are schedules that show the original design requirements for the AHU and Return / Exhaust fans respectively

Can we substitute NEBB certification in lieu of AABC? Will answer shortly.