ArcFlash-Final.pdf

PDF 156 KB Posted

Attached to
J059--Electrical Life Study at Butler VAMC Federal contract opportunity
Solicitation number
36C24420Q0992
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

View the file

Other files for this federal contract opportunity

Other files attached to J059--Electrical Life Study at Butler VAMC, newest first.
File Type Posted
Attachment 1--Vendor Questions.pdf PDF
36C24420Q0992 0002_1.docx DOCX document
Maintenance Inventory 2020.pdf PDF
36C24420Q0992 0001_1.docx DOCX document
Final Submission Arc Flash Drawings.pdf PDF
Attachment 02.pdf PDF
36C24420Q0992_1.docx DOCX document
Attachment 01.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Butler VAMC - Arc Flash Analysis - Final Submission

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 1-BUS-1A A 1-CB-1A A-MAIN 0.208 4.61 2.53 4.61 2.53 0.0186 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0001

1-BUS-1A AC 1-CB-1A AC-MAIN 0.208 4.46 2.47 4.46 2.47 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0002

1-BUS-1A B 1-CB-1A B-MAIN 0.208 4.57 2.51 4.57 2.51 0.0187 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0003

1-BUS-1A C 1-CB-1A C-MAIN 0.208 3.98 2.28 3.98 2.28 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0004

1-BUS-1A LS 1-CB-1A LS-MAIN 0.208 4.68 2.55 4.68 2.55 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0005

1-BUS-1A NE 1-CB-1A NE-MAIN 0.208 4.27 2.39 4.27 2.39 0.0188 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0006

1-BUS-1B A 1-CB-1B A-MAIN 0.208 6.42 2.71 6.42 2.71 1.62 0.0000 Yes PNL 25 77 18 12.9 (*N3) (*S13) # 0007

1-BUS-1B AU 1-CB-1B AU-MAIN 0.208 4.58 2.52 4.58 2.52 2 0.0000 Yes PNL 25 83 18 14.7 (*N9) (*S13) # 0008

1-BUS-1B AU2 1-CB-1B AU-2 0.208 4.10 2.33 4.10 2.33 0.017 0.0000 Yes PNL 25 4 18 0.12 (*S12) # 0009 8.00

1-BUS-1B B 1-CB-1B B-MAIN 0.208 6.56 2.75 6.56 2.75 1.564 0.0000 Yes PNL 25 76 18 12.7 (*N3) (*S13) # 0010

1-BUS-1B C 1-CB-1B C-MAIN 0.208 8.09 3.75 8.09 3.75 0.0197 0.0000 Yes PNL 25 7 18 0.23 (*S12) # 0011

1-BUS-1B LS 1-CB-1B LS-MAIN 0.208 6.01 2.59 6.01 2.59 2 0.0000 Yes PNL 25 85 18 15.3 (*N3) (*N9) (*S12) # 0012

1-BUS-1B NE 1-CB-1B NE-MAIN 0.208 1.96 1.18 1.96 1.18 2 0.0000 Yes PNL 25 51 18 6.52 (*N3) (*N9) (*S14) # 0013

1-BUS-1B NE AU 99-CB-NE DPA-4 0.208 2.86 1.54 2.86 1.54 1.449 0.0000 Yes PNL 25 49 18 6.27 (*N3) (*S14) # 0014 305.00

1-BUS-1C A 1-CB-1C A-MAIN 0.208 3.60 2.12 3.60 2.12 0.0215 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0015

1-BUS-1C AC 1-CB-1C AC-MAIN 0.208 3.11 1.63 3.11 1.63 2 0.0000 Yes PNL 25 62 18 9.18 (*N3) (*N9) (*S14) # 0016

1-BUS-1C B 1-CB-1C B-MAIN 0.208 3.54 1.78 3.54 1.78 0.026 0.0000 Yes PNL 25 5 18 0.13 (*N3) (*S13) # 0017

1-BUS-1C LS 1-CB-1C LS-MAIN 0.208 2.96 1.85 2.96 1.85 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0018

1-BUS-1C NE 1-CB-1C NE-MAIN 0.208 2.99 1.58 2.99 1.58 0.0281 0.0000 Yes PNL 25 5 18 0.13 (*N3) (*S14) # 0019

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal

1-BUS-1C NEB 1-CB-1C NEB-MAIN 0.208 3.30 2.00 3.30 2.00 0.0083 0.0000 Yes PNL 25 3 18 0.05 (*S12) # 0020

1-BUS-1CN ANE 1-CB-1CN ANE-MAIN 0.208 4.82 2.61 4.82 2.61 2 0.0000 Yes PNL 25 86 18 15.4 (*N9) (*S12) # 0021

1-BUS-1ET A 99-CB-NELP GB-2 0.208 3.14 1.93 3.14 1.93 0.0083 0.0000 Yes PNL 25 2 18 0.05 (*S12) # 0022 150.00

1-BUS-2A A 1-CB-2A A-MAIN 0.208 4.46 2.47 4.46 2.47 0.0188 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0023

1-BUS-2A AC 1-CB-2A AC-MAIN 0.208 4.28 2.40 4.28 2.40 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0024

1-BUS-2A B 1-CB-2A B-MAIN 0.208 4.42 2.45 4.42 2.45 0.0189 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0025

1-BUS-2A C 1-CB-2A A-1 0.208 1.73 1.27 1.73 1.27 0.0083 0.0000 Yes PNL 25 2 18 0.03 (*S12) # 0026 90.00

1-BUS-2A LS 1-CB-2A LS-MAIN 0.208 4.51 2.49 4.51 2.49 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0027

1-BUS-2A NE 1-CB-2A NE-MAIN 0.208 4.14 2.34 4.14 2.34 0.019 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0028

1-BUS-2B A 1-CB-2B A-MAIN 0.208 6.17 3.10 6.17 3.10 0.0083 0.0000 Yes PNL 25 3 18 0.08 (*S12) # 0029

1-BUS-2B AC 1-CB-2B AC-MAIN 0.208 6.19 3.11 6.19 3.11 0.0083 0.0000 Yes PNL 25 3 18 0.08 (*S12) # 0030

1-BUS-2B AU 1-CB-2B AU-MAIN 0.208 2.14 1.48 2.14 1.48 0.0086 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0031

1-BUS-2B B 1-CB-2B B-MAIN 0.208 6.27 3.13 6.27 3.13 0.0083 0.0000 Yes PNL 25 3 18 0.08 (*S12) # 0032

1-BUS-2B C 1-CB-2B C-MAIN 0.208 7.50 3.02 7.50 3.02 2 0.0000 Yes PNL 25 93 18 17.7 (*N3) (*N9) (*S13) # 0033

1-BUS-2B LS 1-CB-2B LS-MAIN 0.208 5.58 2.89 5.58 2.89 0.0083 0.0000 Yes PNL 25 3 18 0.07 (*S12) # 0034

1-BUS-2B NE 1-CB-2B NE-MAIN 0.208 2.01 1.20 2.01 1.20 1.954 0.0000 Yes PNL 25 51 18 6.51 (*N3) (*S13) # 0035

1-BUS-2C A 1-CB-2C A-MAIN 0.208 3.37 1.72 3.37 1.72 0.0297 0.0000 Yes PNL 25 5 18 0.15 (*N3) (*S13) # 0036

1-BUS-2C AC 1-CB-2C AC-MAIN 0.208 3.02 1.60 3.02 1.60 0.5065 0.0000 Yes PNL 25 27 18 2.28 (*N3) (*S14) # 0037

1-BUS-2C B 1-CB-2C B-MAIN 0.208 3.45 1.75 3.45 1.75 0.028 0.0000 Yes PNL 25 5 18 0.14 (*N3) (*S13) # 0038

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal

1-BUS-2C LS 1-CB-2C LS-MAIN 0.208 2.84 1.80 2.84 1.80 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0039

1-BUS-2C NE 1-CB-2C NE-MAIN 0.208 3.22 1.96 3.22 1.96 0.0083 0.0000 Yes PNL 25 3 18 0.05 (*S12) # 0040

1-BUS-2C-C 1-CB-2C A-1 0.208 2.07 1.44 2.07 1.44 0.0083 0.0000 Yes PNL 25 2 18 0.03 (*S12) # 0041 50.00

1-BUS-3A A 1-CB-3A A-MAIN 0.208 4.84 2.61 4.84 2.61 0.0183 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0042

1-BUS-3A B 1-CB-3A B-MAIN 0.208 4.84 2.61 4.84 2.61 0.0183 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0043

1-BUS-3A C 1-CB-3A C-MAIN 0.208 4.46 2.47 4.46 2.47 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0044

1-BUS-3A LS 1-CB-3A LS-MAIN 0.208 4.36 2.43 4.36 2.43 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0045

1-BUS-3A NE 1-CB-3A NE-MAIN 0.208 3.85 2.23 3.85 2.23 0.0195 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0046

1-BUS-3B B 1-CB-3B B-MAIN 0.208 6.75 3.30 6.75 3.30 0.0083 0.0000 Yes PNL 25 4 18 0.08 (*S12) # 0047

1-BUS-3B C 1-CB-3B C-MAIN 0.208 7.13 2.91 7.13 2.91 1.312 0.0000 Yes PNL 25 70 18 11.2 (*N3) (*S13) # 0048

1-BUS-3B LS 1-CB-3B LS-MAIN 0.208 5.49 2.85 5.49 2.85 1.892 0.0000 Yes PNL 25 87 18 16.0 (*S13) # 0049

1-BUS-3B NE 1-CB-3B NE-MAIN 0.208 4.82 2.61 4.82 2.61 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0050

1-BUS-3B NEA 1-CB-3B NEA-MAIN 0.208 4.52 2.49 4.52 2.49 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0051

1-BUS-3C A 1-CB-3C A-MAIN 0.208 4.07 2.31 4.07 2.31 0.0195 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0052

1-BUS-3C AC 1-CB-3C AC-MAIN 0.208 2.92 1.56 2.92 1.56 0.5265 0.0000 Yes PNL 25 27 18 2.31 (*N3) (*S14) # 0053

1-BUS-3C AC2 1-CB-3C AC2-MAIN 0.208 2.58 1.43 2.58 1.43 0.0402 0.0000 Yes PNL 25 5 18 0.16 (*N3) (*S14) # 0054

1-BUS-3C B 1-CB-3C B-MAIN 0.208 4.04 2.30 4.04 2.30 0.0195 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0055

1-BUS-3C LS 1-CB-3C LS-MAIN 0.208 2.83 1.79 2.83 1.79 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0056

1-BUS-3C NE 1-CB-3C NE-MAIN 0.208 3.26 1.98 3.26 1.98 0.0083 0.0000 Yes PNL 25 3 18 0.05 (*S12) # 0057

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal

1-BUS-4A A 1-CB-4A A-MAIN 0.208 4.24 2.38 4.24 2.38 0.0197 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0058

1-BUS-4A B 1-CB-4A B-MAIN 0.208 4.15 2.34 4.15 2.34 0.0198 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0059

1-BUS-4A C 1-CB-4A B-1 0.208 3.65 2.14 3.65 2.14 0.0083 0.0000 Yes PNL 25 3 18 0.05 (*S12) # 0060 15.00

1-BUS-4A NE(1) 1-CB-4A NE(1)-MAIN 0.208 3.76 2.19 3.76 2.19 2 0.0000 Yes PNL 25 76 18 12.7 (*N9) (*S13) # 0061

1-BUS-4A NE(2) 1-CB-4A NE(2)-MAIN 0.208 3.58 1.80 3.58 1.80 2 0.0000 Yes PNL 25 67 18 10.3 (*N3) (*N9) (*S13) # 0062

1-BUS-4B A 1-CB-4B A-MAIN 0.208 6.40 3.18 6.40 3.18 0.0083 0.0000 Yes PNL 25 3 18 0.08 (*S12) # 0063

1-BUS-4B B 1-CB-4B B-MAIN 0.208 6.41 2.71 6.41 2.71 2 0.0000 Yes PNL 25 87 18 15.8 (*N3) (*N9) (*S13) # 0064

1-BUS-4B C 1-CB-4B C 0.208 6.70 2.79 6.70 2.79 1.511 0.0000 Yes PNL 25 75 18 12.3 (*N3) (*S13) # 0065

1-BUS-4B LS 1-CB-4B LS 0.208 5.27 2.77 5.27 2.77 2 0.0000 Yes PNL 25 89 18 16.5 (*N9) (*S12) # 0066

1-BUS-4B NE 1-CB-4B NE-MAIN 0.208 4.57 2.51 4.57 2.51 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0067

1-BUS-4C A 1-CB-4C A-MAIN 0.208 3.97 2.27 3.97 2.27 0.0197 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0068

1-BUS-4C AC 1-CB-4C AC-MAIN 0.208 2.85 1.53 2.85 1.53 0.5412 0.0000 Yes PNL 25 27 18 2.33 (*N3) (*S14) # 0069

1-BUS-4C B 1-CB-4C B-MAIN 0.208 3.94 2.26 3.94 2.26 0.0197 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0070

1-BUS-4C LS 1-CB-4C LS-MAIN 0.208 2.77 1.77 2.77 1.77 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0071

1-BUS-4C NE 1-CB-4C NE-MAIN 0.208 3.19 1.95 3.19 1.95 0.0083 0.0000 Yes PNL 25 3 18 0.05 (*S12) # 0072

1-BUS-502CB 1-CB-502CB-MAIN 0.208 4.89 2.63 4.89 2.63 0.017 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0073

1-BUS-503CA 1-CB-4B B-1 0.208 5.58 2.89 5.58 2.89 0.0083 0.0000 Yes PNL 25 3 18 0.07 (*S12) # 0074 20.00

1-BUS-506CBB 1-CB-506CBB-MAIN 0.208 3.27 1.98 3.27 1.98 0.0167 0.0000 Yes PNL 25 4 18 0.10 (*S12) # 0075

1-BUS-5A A 1-CB-5A A-MAIN 0.208 4.33 2.42 4.33 2.42 0.019 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0076

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 1-BUS-5B A 1-CB-5B DP-3 0.208 5.37 2.81 5.37 2.81 0.0183 0.0000 Yes PNL 25 5 18 0.15 (*S12) # 0077 15.00

1-BUS-5B AC 1-CB-5B AC-MAIN 0.208 4.59 2.52 4.59 2.52 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0078

1-BUS-5B C 1-CB-5B C-MAIN 0.208 6.09 3.07 6.09 3.07 0.0083 0.0000 Yes PNL 25 3 18 0.08 (*S12) # 0079

1-BUS-5B D 1-CB-5B D-MAIN 0.208 4.36 2.43 4.36 2.43 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0080

1-BUS-5B DP 99-CB-MDP1-7 0.208 5.84 2.98 5.84 2.98 0.065 0.0000 Yes PNL 25 12 18 0.58 (*S12) # 0081 275.00

1-BUS-5B E 1-CB-5B DP-2 0.208 4.02 2.29 4.02 2.29 0.0197 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0082 75.00

1-BUS-5B NE 1-CB-5B NE-MAIN 0.208 3.36 1.72 3.36 1.72 0.0286 0.0000 Yes PNL 25 5 18 0.14 (*N3) (*S14) # 0083

1-BUS-5C A 1-CB-5C A-MAIN 0.208 3.75 2.18 3.75 2.18 1.964 0.0000 Yes PNL 25 75 18 12.4 (*S13) # 0084

1-BUS-5C LS 1-CB-5C LS-MAIN 0.208 2.73 1.75 2.73 1.75 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0085

1-BUS-6A AC 99-CB-MDP2-17 0.208 8.20 3.78 8.20 3.78 0.065 0.0000 Yes PNL 25 14 18 0.75 (*S12) # 0086 325.00

1-BUS-6A ACA 1-CB-6A ACA-MAIN 0.208 2.92 1.83 2.92 1.83 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0087

1-BUS-6A NEPH 1-CB-6A NEPH-MAIN 0.208 3.19 1.95 3.19 1.95 2 0.0000 Yes PNL 25 66 18 10.0 (*N9) (*S13) # 0088

1-BUS-6B A 99-CB-MDP1-10 0.208 5.61 2.90 5.61 2.90 0.065 0.0000 Yes PNL 25 11 18 0.57 (*S12) # 0089 225.00

1-BUS-6B AC 1-CB-6B AC-MAIN 0.208 5.14 2.72 5.14 2.72 0.0083 0.0000 Yes PNL 25 3 18 0.07 (*S12) # 0090

1-BUS-6B NEPH 1-CB-6B NEPH-MAIN 0.208 3.94 1.92 3.94 1.92 2 0.0000 Yes PNL 25 67 18 10.2 (*N3) (*N9) (*S13) # 0091

1-BUS-6C AC 1-CB-6C AC-MAIN 0.208 2.68 1.47 2.68 1.47 2 0.0000 Yes PNL 25 58 18 8.23 (*N3) (*N9) (*S14) # 0092

1-BUS-6C NEPH 1-CB-6C NEPH-MAIN 0.208 2.90 1.82 2.90 1.82 2 0.0000 Yes PNL 25 63 18 9.39 (*N9) (*S13) # 0093

1-BUS-6C/D 1-CB-6A AC-1 0.208 5.60 2.90 5.60 2.90 0.017 0.0000 Yes PNL 25 5 18 0.15 (*S12) # 0094 25.00

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal

1-BUS-A 99-CB-MDP2-3 (1-CB-A-

MAIN)

0.208 3.05 1.61 3.05 1.61 2 0.0000 Yes PNL 25 62 18 9.16 (*N3) (*N5) (*N9) (*S12) # 0095 530.00

1-BUS-AC1 RTU 1-CB-LDPA-1 0.208 3.42 1.74 3.42 1.74 1.264 0.0000 Yes PNL 25 50 18 6.29 (*N3) (*S13) # 0096 125.00

1-BUS-AC2 RTU 1-CB-BA MK AC-1 0.208 1.87 1.34 1.87 1.34 0.017 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0097 100.00

1-BUS-ACCA 1-CB-ACCA-MAIN 0.208 6.18 2.64 6.18 2.64 2 0.0000 Yes PNL 25 84 18 15.1 (*N3) (*N9) (*S14) # 0098

1-BUS-ACCB 1-CB-ACCB-MAIN 0.208 6.30 2.67 6.30 2.67 2 0.0000 Yes PNL 25 85 18 15.3 (*N3) (*N9) (*S14) # 0099

1-BUS-ACNA 1-CB-ACNA-MAIN 0.208 5.86 2.99 5.86 2.99 1.697 0.0000 Yes PNL 25 83 18 14.7 (*S14) # 0100

1-BUS-ACNB 1-CB-ACNB-MAIN 0.208 6.54 2.74 6.54 2.74 2 0.0000 Yes PNL 25 86 18 15.7 (*N3) (*N9) (*S14) # 0101

1-BUS-AH 501 1-CB-6A AC-3 0.208 4.32 2.05 4.32 2.05 2 0.0000 Yes PNL 25 73 18 11.9 (*N3) (*N9) (*S13) # 0102 100.00 11.86

1-BUS-AH 502E 1-CB-6A AC-4 0.208 4.32 2.05 4.32 2.05 2 0.0000 Yes PNL 25 73 18 11.9 (*N3) (*N9) (*S13) # 0103 100.00 11.86

1-BUS-AH 607 1-CB-6A AC-2 0.208 4.32 2.05 4.32 2.05 2 0.0000 Yes PNL 25 73 18 11.9 (*N3) (*N9) (*S13) # 0104 100.00 11.86

1-BUS-AHU 1 1-CB-NEDP-1 0.208 5.37 2.39 5.37 2.39 2 0.0000 Yes PNL 25 80 18 13.9 (*N3) (*N9) (*S12) # 0105 100.00

1-BUS-AHU

AUDITORIUM

1-CB-DISC AHU AUD 0.208 1.83 1.12 1.83 1.12 0.4474 0.0000 Yes PNL 25 20 18 1.39 (*N3) (*S13) # 0106 125.00

1-BUS-AHU KITCHEN 1-CB-BA MK AC-2 0.208 3.45 1.75 3.45 1.75 2 0.0000 Yes PNL 25 66 18 10.0 (*N3) (*N9) (*S13) # 0107 125.00

1-BUS-AHU LAB 99-CB-MDP1-11 0.208 4.42 2.45 4.42 2.45 0.213 0.0000 Yes PNL 25 21 18 1.54 (*S12) # 0108 425.00

1-BUS-AHU PHARM 99-CB-MDP1-12 0.208 6.19 3.11 6.19 3.11 0.065 0.0000 Yes PNL 25 12 18 0.61 (*S12) # 0109 200.00

1-BUS-AHU

RADIOLOGY

99-CB-MDP1-5 0.208 7.27 3.48 7.27 3.48 0.065 0.0000 Yes PNL 25 13 18 0.69 (*S12) # 0110 225.00

1-BUS-AHU1 CC 1-CB-LDPDD-1 0.208 3.89 1.90 3.89 1.90 0.0313 0.0000 Yes PNL 25 6 18 0.17 (*N3) (*S13) # 0111 50.00

1-BUS-AHU1 CLINICAL 1-CB-PDP-4 0.208 7.58 3.58 7.58 3.58 2 0.0000 Yes PNL 25 104 18 21.3 (*N9) (*S13) # 0112 125.00

1-BUS-B2A 1-CB-ACNA-1 0.208 7.62 3.60 7.62 3.60 0.0083 0.0000 Yes PNL 25 4 18 0.09 (*S12) # 0113 8.00

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal

1-BUS-B2EA 1-CB-ACCB-1 0.208 8.86 4.00 8.86 4.00 0.0083 0.0000 Yes PNL 25 4 18 0.10 (*S12) # 0114 5.00

1-BUS-BA KA 1-CB-BA KA-MAIN 0.208 4.97 2.66 4.97 2.66 2 0.0000 Yes PNL 25 85 18 15.4 (*N9) (*S14) # 0115

1-BUS-BA KB 1-CB-BA KB-MAIN 0.208 4.97 2.66 4.97 2.66 2 0.0000 Yes PNL 25 85 18 15.4 (*N9) (*S14) # 0116

1-BUS-BA KC 1-CB-BA KC-MAIN 0.208 4.97 2.66 4.97 2.66 2 0.0000 Yes PNL 25 85 18 15.4 (*N9) (*S14) # 0117

1-BUS-BA KPA 1-CB-BA KPA-MAIN 0.208 5.09 2.71 5.09 2.71 2 0.0000 Yes PNL 25 88 18 16.1 (*N9) (*S12) # 0118

1-BUS-BA KPB 1-CB-BA KPA-MAIN 0.208 4.99 2.67 4.99 2.67 2 0.0000 Yes PNL 25 87 18 15.8 (*N9) (*S12) # 0119 6.00

1-BUS-BA KPC 1-CB-BA KPB-1 0.208 2.95 1.85 2.95 1.85 0.0084 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0120 60.00

1-BUS-BA KPF 1-CB-BA KPF-MAIN 0.208 6.24 3.12 6.24 3.12 2 0.0000 Yes PNL 25 96 18 18.7 (*N9) (*S12) # 0121

1-BUS-BA KPG 1-CB-BA KPF-1 0.208 4.69 2.17 4.69 2.17 0.0258 0.0000 Yes PNL 25 5 18 0.16 (*N3) (*S14) # 0122 15.00

1-BUS-BA LS 1-CB-BA LS-MAIN 0.208 5.01 2.68 5.01 2.68 0.0083 0.0000 Yes PNL 25 3 18 0.07 (*S12) # 0123

1-BUS-BA MK AC 99-CB-MDP2-6 0.208 6.52 3.22 6.52 3.22 0.065 0.0000 Yes PNL 25 12 18 0.63 (*S12) # 0124 265.00

1-BUS-BA NEK 1-CB-BA NEK 0.208 4.32 2.41 4.32 2.41 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0125

1-BUS-BA PP 1-CB-BA PP-MAIN 0.208 5.24 2.76 5.24 2.76 2 0.0000 Yes PNL 25 89 18 16.4 (*N9) (*S12) # 0126

1-BUS-BA PPB 1-CB-BA PP-1 0.208 4.90 2.64 4.90 2.64 2 0.0000 Yes PNL 25 86 18 15.6 (*N9) (*S12) # 0127 20.00

1-BUS-BA WA 1-CB-BA WA-MAIN 0.208 5.87 2.99 5.87 2.99 0.017 0.0000 Yes PNL 25 5 18 0.15 (*S12) # 0128

1-BUS-BA WB 1-CB-BA WB-MAIN 0.208 5.64 2.91 5.64 2.91 0.0083 0.0000 Yes PNL 25 3 18 0.07 (*S12) # 0129

1-BUS-BB A 1-CB-BB A-MAIN 0.208 6.83 2.83 6.83 2.83 1.451 0.0000 Yes PNL 25 74 18 12.1 (*N3) (*S13) # 0130 12.10

1-BUS-BB B 1-CB-BB B-MAIN 0.208 6.98 2.87 6.98 2.87 1.375 0.0000 Yes PNL 25 72 18 11.7 (*N3) (*S13) # 0131

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 1-BUS-BB LS 1-CB-BB LS-MAIN 0.208 6.26 2.66 6.26 2.66 2 0.0000 Yes PNL 25 87 18 15.8 (*N3) (*N9) (*S12) # 0132

1-BUS-BB PM 1-CB-BBPM-MAIN 0.208 4.03 2.30 4.03 2.30 0.0197 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0133

1-BUS-BB PP 1-CB-BB PP-MAIN 0.208 4.21 2.37 4.21 2.37 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0134

1-BUS-BC ALS 1-CB-BC LS-1 0.208 0.77 0.72 0.77 0.72 0.0083 0.0000 Yes PNL 25 1 18 0.02 (*S12) # 0135 150.00

1-BUS-BC LA 99-CB-MDP1-3 0.208 3.45 2.06 3.45 2.06 0.065 0.0000 Yes PNL 25 9 18 0.39 (*S12) # 0136 425.00

1-BUS-BC LS 1-CB-BC LS-MAIN 0.208 2.97 1.85 2.97 1.85 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0137

1-BUS-BC NE 1-CB-BC NE-MAIN 0.208 3.43 2.05 3.43 2.05 2 0.0000 Yes PNL 25 73 18 11.8 (*N9) (*S13) # 0138 11.83

1-BUS-BC NEB 1-CB-BC NEB-MAIN 0.208 3.05 1.61 3.05 1.61 0.0276 0.0000 Yes PNL 25 5 18 0.13 (*N3) (*S14) # 0139

1-BUS-BC RR1 99-CB-NE DPB-8 0.208 3.78 2.20 3.78 2.20 2 0.0000 Yes PNL 25 77 18 12.9 (*N9) (*S12) # 0140 330.00

1-BUS-BCB 99-CB-MDP1-1 0.208 4.24 2.38 4.24 2.38 0.065 0.0000 Yes PNL 25 10 18 0.46 (*S12) # 0141 400.00

1-BUS-BLA 1-CB-BC LA-1 0.208 1.60 1.02 1.60 1.02 2 0.0000 Yes PNL 25 46 18 5.61 (*N3) (*N9) (*S13) # 0142 165.00

1-BUS-BLE 1 1-CB-BC NEB 0.208 2.55 1.67 2.55 1.67 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0143 50.00

1-BUS-BLE 2 1-CB-BC NEB 0.208 2.48 1.63 2.48 1.63 0.0084 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0144 56.00

1-BUS-DISC AC1 RTU 1-CB-LDPA-1 0.208 4.00 1.94 4.00 1.94 1.05 0.0000 Yes PNL 25 48 18 5.88 (*N3) (*S13) # 0145 100.00

1-BUS-DISC ACCU7 1-FU-DISC-ACCU7 0.208 2.19 1.27 2.19 1.27 0.0261 0.0000 Yes PNL 25 4 18 0.09 (*N3) (*S13) # 0146

1-BUS-DISC AHU AUD 1-CB-3A B-1 0.208 2.25 1.53 2.25 1.53 0.0085 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0147 100.00

1-BUS-DISC AHU KIT 1-CB-BA MK AC-2 0.208 3.89 1.90 3.89 1.90 2 0.0000 Yes PNL 25 69 18 11.0 (*N3) (*N9) (*S13) # 0148 100.00

1-BUS-DISC AHU LAB 99-CB-MDP1-11 0.208 4.68 2.55 4.68 2.55 0.213 0.0000 Yes PNL 25 22 18 1.61 (*S12) # 0149 400.00

1-BUS-DISC AHU RAD 99-CB-MDP1-5 0.208 8.20 3.79 8.20 3.79 0.065 0.0000 Yes PNL 25 14 18 0.75 (*S12) # 0150 200.00

1-BUS-DISC AHU1

CLIN

1-CB-PDP-4 0.208 8.04 3.17 8.04 3.17 2 0.0000 Yes PNL 25 96 18 18.6 (*N3) (*N9) (*S13) # 0151

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal

1-BUS-DISC ATR RTU 1-FU-DISC ATR RTU 0.208 6.01 2.59 6.01 2.59 0.0132 0.0000 Yes PNL 25 4 18 0.10 (*N3) (*S13) # 0152

1-BUS-DISC LDPE 99-CB-MDP2-17 0.208 10.64 4.54 10.64 4.54 0.065 0.0000 Yes PNL 25 15 18 0.92 (*S12) # 0153 225.00

1-BUS-DISC-6A NEPH 1-FU-DISC-6A NEPH 0.208 3.06 1.61 3.06 1.61 0.0228 0.0000 Yes PNL 25 4 18 0.11 (*N3) (*S14) # 0154

1-BUS-DISC-6B NEPH 1-FU-DISC-6B NEPH 0.208 4.08 1.97 4.08 1.97 0.0269 0.0000 Yes PNL 25 5 18 0.15 (*N3) (*S14) # 0155

1-BUS-DISC-6C NEPH 1-FU-DISC-6C NEPH 0.208 3.11 1.63 3.11 1.63 0.0221 0.0000 Yes PNL 25 4 18 0.10 (*N3) (*S14) # 0156

1-BUS-DISC-A 1-CB-DISC-A 0.208 10.76 4.58 10.76 4.58 0.025 0.0000 Yes PNL 25 9 18 0.36 (*S12) # 0157

1-BUS-DISC-BC RR1 99-CB-NE DPB-8 0.208 3.84 2.22 3.84 2.22 2 0.0000 Yes PNL 25 77 18 13.0 (*N9) (*S12) # 0158 325.00

1-BUS-DISC-ELEV P1 99-CB-MDP EQ-2 (1-CB-

DISC-ELEV P1)

0.208 3.38 2.03 2.84 1.71 2 0.0000 Yes PNL 25 67 18 10.4 (*N5) (*N9) (*S12) # 0159 470.00

1-BUS-DISC-ELEV P2 99-CB-MDP EQ-3 (1-CB-

DISC-ELEV P2)

0.208 4.52 2.49 3.99 2.20 2 0.0000 Yes PNL 25 78 18 13.4 (*N5) (*N9) (*S12) # 0160 320.00

1-BUS-DISC-ELEV P3 99-CB-MDP EQ-1 (1-CB-

DISC-ELEV P3)

0.208 3.38 2.03 2.84 1.71 2 0.0000 Yes PNL 25 67 18 10.4 (*N5) (*N9) (*S12) # 0161 470.00

1-BUS-DISC-SB SPD 1-CB-DISC-SB SPD 0.208 10.02 4.36 10.02 4.36 0.0193 0.0000 Yes PNL 25 7 18 0.26 (*N21a) (*S12) # 0162

1-BUS-DISC-XRAY 1-CB-5B DP-1 0.208 4.97 2.66 4.97 2.66 0.0187 0.0000 Yes PNL 25 5 18 0.15 (*S12) # 0163 30.00

1-BUS-DP 1-CB-1C NE-1 0.208 0.75 0.71 0.75 0.71 2 0.0000 Yes PNL 25 36 18 3.78 (*N9) (*S12) # 0164 250.00

1-BUS-ELEV P1 99-CB-MDP EQ-2 (1-CB-

DISC-ELEV P1)

0.208 3.27 1.99 2.74 1.66 2 0.0000 Yes PNL 25 66 18 10.1 (*N5) (*N9) (*S12) # 0165 490.00

1-BUS-ELEV P2 99-CB-MDP EQ-3 (1-CB-

DISC-ELEV P2)

0.208 4.37 2.43 3.83 2.13 2 0.0000 Yes PNL 25 77 18 13.0 (*N5) (*N9) (*S12) # 0166 335.00

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal

1-BUS-ELEV P3 99-CB-MDP EQ-1 (1-CB-

DISC-ELEV P3)

0.208 3.27 1.99 2.74 1.66 2 0.0000 Yes PNL 25 66 18 10.1 (*N5) (*N9) (*S12) # 0167 490.00

1-BUS-EPP(1) 1-CB-EPP(1)-MAIN 0.208 7.28 3.48 7.28 3.48 2 0.0000 Yes PNL 25 103 18 21.0 (*N9) (*S12) # 0168

1-BUS-EPP(2) 99-CB-NE DPB-2 0.208 7.16 3.44 7.16 3.44 2 0.0000 Yes PNL 25 102 18 20.7 (*N9) (*S12) # 0169 205.00

1-BUS-K1 1-CB-K1-MAIN 0.208 7.41 3.00 7.41 3.00 2 0.0000 Yes PNL 25 93 18 17.6 (*N3) (*N9) (*S13) # 0170

1-BUS-K2 1-CB-K2-MAIN 0.208 7.26 3.47 7.26 3.47 0.0164 0.0000 Yes PNL 25 6 18 0.17 (*S12) # 0171

1-BUS-K3 99-CB-MDP2-8 0.208 6.84 2.83 6.84 2.83 0.065 0.0000 Yes PNL 25 11 18 0.55 (*N3) (*S12) # 0172

1-BUS-K4 1-CB-K3-1 0.208 6.18 3.10 6.18 3.10 0.0083 0.0000 Yes PNL 25 3 18 0.08 (*S12) # 0173 10.00

1-BUS-LDPA 99-CB-MDP2-18 0.208 11.49 4.79 11.49 4.79 0.065 0.0000 Yes PNL 25 16 18 0.97 (*S12) # 0174 200.00

1-BUS-LDPB 1-CB-LDPA-2 0.208 9.21 4.11 9.21 4.11 0.017 0.0000 Yes PNL 25 6 18 0.22 (*S12) # 0175 15.00

1-BUS-LDPC 1-CB-LDPA-3 0.208 8.90 4.01 8.90 4.01 0.019 0.0000 Yes PNL 25 7 18 0.23 (*S12) # 0176 25.00

1-BUS-LDPD 1-CB-LDPA-4 0.208 8.64 3.34 8.64 3.34 2 0.0000 Yes PNL 25 100 18 19.8 (*N3) (*N9) (*S13) # 0177 40.00

1-BUS-LDPDD 1-CB-LDPEE-1 0.208 6.15 3.09 6.15 3.09 2 0.0000 Yes PNL 25 95 18 18.4 (*N9) (*S13) # 0178 50.00

1-BUS-LDPEE 99-CB-MDP2-17 0.208 7.87 3.68 7.87 3.68 0.065 0.0000 Yes PNL 25 13 18 0.73 (*S12) # 0179 345.00

1-BUS-LDPPH 99-CB-MDP2-5 0.208 6.33 3.15 6.33 3.15 0.065 0.0000 Yes PNL 25 12 18 0.62 (*S12) # 0180 275.00

1-BUS-NEDP 1-CB-NEDP-MAIN 0.208 7.75 3.64 7.75 3.64 2 0.0000 Yes PNL 25 105 18 21.6 (*N9) (*S13) # 0181

1-BUS-PB4C NE 1-CB-PB4C NE-MAIN 0.208 2.96 1.85 2.96 1.85 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0182

1-BUS-PDP 1-CB-PDP-MAIN 0.208 10.57 4.52 10.57 4.52 2 0.0000 Yes PNL 25 121 18 27.1 (*N9) (*S13) # 0183

1-BUS-PNL1 1-CB-BA PP-2 0.208 5.13 2.72 5.13 2.72 2 0.0000 Yes PNL 25 88 18 16.2 (*N9) (*S12) # 0184 6.00

1-BUS-PNL2 1-CB-BA PP-3 0.208 4.68 2.55 4.68 2.55 0.0183 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0185 15.00

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 1-BUS-PY 1-CB-1A A-2 0.208 1.21 0.84 1.21 0.84 1.949 0.0000 Yes PNL 25 40 18 4.44 (*N3) (*S13) # 0186 150.00

1-BUS-SB A 1-CB-SB B-1 0.208 4.89 2.63 4.89 2.63 0.0083 0.0000 Yes PNL 25 3 18 0.07 (*S12) # 0187 30.00

1-BUS-SB B 99-CB-MDP2-7 0.208 6.84 2.83 6.84 2.83 0.065 0.0000 Yes PNL 25 11 18 0.55 (*N3) (*S12) # 0188

1-BUS-SB C 1-CB-SB C-MAIN 0.208 5.77 2.96 5.77 2.96 2 0.0000 Yes PNL 25 91 18 17.2 (*N9) (*S14) # 0189

1-BUS-SB CA 1-CB-SB C-1 0.208 5.54 2.87 5.54 2.87 2 0.0000 Yes PNL 25 90 18 16.7 (*N9) (*S14) # 0190 10.00

1-BUS-SB D 1-CB-SB D-MAIN 0.208 5.82 2.53 5.82 2.53 0.0302 0.0000 Yes PNL 25 7 18 0.23 (*N3) (*S14) # 0191

1-BUS-SE NEC 99-CB-NE DPB-12 0.208 8.16 3.21 8.16 3.21 2 0.0000 Yes PNL 25 98 18 19.2 (*N3) (*N9) (*S12) # 0192 150.00

1-BUS-TRMA 99-CB-NE DPA-12 0.208 5.77 2.96 5.77 2.96 2 0.0000 Yes PNL 25 91 18 17.2 (*N9) (*S14) # 0193 150.00

1-BUS-TRMB 99-CB-NELP GB-1 0.208 3.14 1.93 3.14 1.93 0.0083 0.0000 Yes PNL 25 2 18 0.05 (*S12) # 0194 150.00

1-BUS-UPS DPA 1-CB-UPS DPA-MAIN 0.208 5.32 2.79 5.32 2.79 2 0.0000 Yes PNL 25 89 18 16.5 (*N9) (*S13) # 0195

1-BUS-UPS DPB 1-CB-UPS DPB-MAIN 0.208 5.32 2.79 5.32 2.79 2 0.0000 Yes PNL 25 89 18 16.5 (*N9) (*S13) # 0196

1-BUS-UPS INPUT 1-CB-UPS ISOLATION 0.208 6.21 3.11 6.21 3.11 2 0.0000 Yes PNL 25 96 18 18.5 (*N9) (*S13) # 0197 25.00

1-BUS-XRAY 1-CB-XRAY-MAIN 0.48 3.46 2.65 3.46 2.65 0.0126 0.0000 Yes PNL 25 4 18 0.10 (*S12) # 0199

132-BUS-SMOKE 132-CB-SMOKE-MAIN 0.208 2.32 1.56 2.32 1.56 0.0085 0.0000 Yes PNL 25 2 18 0.04 (*S14) # 0200

133-BUS-A 1-CB-BA NEK-1 0.208 1.91 1.36 1.91 1.36 0.0083 0.0000 Yes PNL 25 2 18 0.03 (*S12) # 0201 115.00

135-BUS-HAZMAT 135-CB-HAZMAT-MAIN 0.208 1.32 1.05 1.32 1.05 0.0083 0.0000 Yes PNL 25 2 18 0.02 (*S12) # 0202

136-BUS-HAZMAT 136-CB-HAZMAT-MAIN 0.208 1.30 1.04 1.30 1.04 0.0083 0.0000 Yes PNL 25 2 18 0.02 (*S12) # 0203

150-BUS-ATS FP (L) 3-CB-FP NORM-MAIN 0.208 6.52 3.22 5.75 2.84 2 0.0000 Yes PNL 25 93 18 17.7 (*N9) (*S12) # 0204 125.00

150-BUS-FP PNL 150-CB-FP PNL-MAIN 0.208 4.87 2.62 4.87 2.62 0.0167 0.0000 Yes PNL 25 5 18 0.13 (*S13) # 0205

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 198-BUS-BV NELP 198-CB-BV NELP-MAIN 0.208 4.46 2.47 4.46 2.47 0.0121 0.0000 Yes PNL 25 4 18 0.09 (*S12) # 0206

198-BUS-BVA CB 99-CB-MDP1-9 0.208 12.30 4.28 12.30 4.28 0.065 0.0000 Yes PNL 25 15 18 0.86 (*N3) (*S12) # 0207

2-BUS-AHU 2 2-CB-EDP-1 0.208 5.70 2.49 5.70 2.49 2 0.0000 Yes PNL 25 83 18 14.6 (*N3) (*N9) (*S13) # 0208 125.00

2-BUS-ATS EDP (L) 20-CB-SWBD1-3 0.208 17.70 6.50 17.70 6.50 0.05 0.0000 Yes PNL 25 17 18 1.04 (*S12) # 0209 110.00

2-BUS-ATS EDP-ECB

(N)

20-CB-SWBD1-3 0.208 18.42 6.68 18.42 6.68 0.05 0.0000 Yes PNL 25 17 18 1.07 (*S12) # 0210 100.00

2-BUS-ATS ELEV (L) 2-CB-ELEV DISC 0.208 7.04 3.40 0.87 0.42 0.0833 0.0000 Yes PNL 25 15 18 0.86 (*S12) 100.00

2-BUS-ATS ELEV (L) FU-XF T12 (2-CB-ATS

ELEV-ECB (N))

0.208 7.04 3.40 6.17 2.98 2 0.0000 Yes PNL 25 96 18 18.6 (*N5) (*N9) (*S12) # 0211 100.00

2-BUS-ATS ELEV-ECB

(E)

2-CB-ELEV DISC 0.208 8.42 3.28 0.87 0.40 0.0833 0.0000 Yes PNL 25 16 18 0.94 (*S14) 120.00

2-BUS-ATS ELEV-ECB

(E)

2-CB-ATS ELEV-ECB

(E)

0.208 8.42 3.28 7.55 2.94 2 0.0000 Yes PNL 25 95 18 18.4 (*N3) (*N9) (*S14) # 0212

2-BUS-ATS ELEV-ECB

(N)

2-CB-ELEV DISC 0.208 7.49 3.55 0.86 0.41 0.0833 0.0000 Yes PNL 25 15 18 0.90 (*S12) 125.00

2-BUS-ATS ELEV-ECB

(N)

FU-XF T12 (2-CB-ATS

ELEV-ECB (N))

0.208 7.49 3.55 6.63 3.14 2 0.0000 Yes PNL 25 99 18 19.7 (*N5) (*N9) (*S12) # 0213 75.00

2-BUS-ATS LS (L) 2-CB-ATS LS-ECB (E) 0.208 6.76 3.30 6.76 3.30 0.015 0.0000 Yes PNL 25 5 18 0.15 (*N21a) (*S14) # 0214 25.00

2-BUS-ATS LS-ECB (E) 2-CB-ATS LS-ECB (E) 0.208 8.25 3.80 8.25 3.80 0.0146 0.0000 Yes PNL 25 5 18 0.17 (*N21a) (*S14) # 0215

2-BUS-ATS LS-ECB (N) 2-CB-ATS LS-ECB (N) 0.208 7.29 3.49 7.29 3.49 0.0148 0.0000 Yes PNL 25 5 18 0.16 (*S12) # 0216

2-BUS-ATS MDP (L) 2-CB-ATS MDP-ECB (N) 0.208 6.99 2.88 6.99 2.88 2 0.0000 Yes PNL 25 87 18 15.8 (*N3) (*N9) (*S12) # 0217 20.00

2-BUS-ATS MDP-ECB

(E)

2-CB-ATS MDP-ECB (E) 0.208 8.39 3.27 8.39 3.27 0.1014 0.0000 Yes PNL 25 16 18 0.99 (*N3) (*S14) # 0218

2-BUS-ATS MDP-ECB

(N)

2-CB-ATS MDP-ECB (N) 0.208 7.46 3.01 7.46 3.01 2 0.0000 Yes PNL 25 89 18 16.5 (*N3) (*N9) (*S12) # 0219

2-BUS-EDP 20-CB-SWBD1-3 0.208 15.86 6.01 15.86 6.01 0.05 0.0000 Yes PNL 25 16 18 0.96 (*S12) # 0220 140.00

2-BUS-ELEV DISC 2-CB-ELEV DISC 0.208 5.78 2.96 4.89 2.50 0.025 0.0000 Yes PNL 25 6 18 0.22 (*S14) # 0221

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal

2-BUS-EV A 2-CB-MDPB-2 0.208 2.01 1.41 2.01 1.41 0.017 0.0000 Yes PNL 25 3 18 0.07 (*S14) # 0223 100.00

2-BUS-HUMID DISC 2-FU-HUMID DISC 0.48 1.07 0.97 1.07 0.97 2 0.0000 Yes PNL 25 44 18 5.20 (*N9) (*S14) # 0224

2-BUS-KPA1 2-CB-KPA1-MAIN 0.208 15.37 5.88 15.37 5.88 0.05 0.0000 Yes PNL 25 16 18 0.94 (*S12) # 0225

2-BUS-KPA2 2-CB-KPA1-MAIN 0.208 15.08 5.80 15.08 5.80 0.05 0.0000 Yes PNL 25 15 18 0.92 (*S12) # 0226 5.00

2-BUS-KPA3 2-CB-KPA1-MAIN 0.208 14.80 5.73 14.80 5.73 0.05 0.0000 Yes PNL 25 15 18 0.91 (*S12) # 0227 10.00

2-BUS-LS B2 2-CB-LS B2-MAIN 0.208 6.32 3.15 6.32 3.15 0.017 0.0000 Yes PNL 25 5 18 0.16 (*S14) # 0228

2-BUS-MDPA 2-CB-MDPA-MAIN 0.208 6.66 2.78 6.66 2.78 0.0921 0.0000 Yes PNL 25 14 18 0.76 (*N3) (*S13) # 0229

2-BUS-MDPB 2-CB-MDPA-2 0.208 7.22 2.94 7.22 2.94 2 0.0000 Yes PNL 25 89 18 16.6 (*N3) (*N9) (*S14) # 0230 8.00

2-BUS-MDPC 2-CB-MDPC-MAIN 0.208 6.59 3.25 6.59 3.25 2 0.0000 Yes PNL 25 96 18 18.5 (*N9) (*S14) # 0231

2-BUS-MP A 2-CB-MP A-MAIN 0.208 3.06 1.89 3.06 1.89 2 0.0000 Yes PNL 25 69 18 10.7 (*N9) (*S14) # 0232

2-BUS-MP B 2-CB-MP B-MAIN 0.208 5.30 2.79 5.30 2.79 2 0.0000 Yes PNL 25 87 18 15.9 (*N9) (*S14) # 0233

2-BUS-PICNIC 2-CB-MDPB-1 0.208 1.11 0.93 1.11 0.93 0.017 0.0000 Yes PNL 25 2 18 0.04 (*S14) # 0234 125.00

2-BUS-PP 1A 2-CB-PP 1A-MAIN 0.208 4.70 2.56 4.70 2.56 2 0.0000 Yes PNL 25 83 18 14.6 (*N9) (*S14) # 0235

2-BUS-PP 1B 2-CB-PP 1B-MAIN 0.208 4.57 2.51 4.57 2.51 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S14) # 0236

2-BUS-PP 2A 2-CB-PP 2A-MAIN 0.208 4.51 2.49 4.51 2.49 2 0.0000 Yes PNL 25 81 18 14.2 (*N9) (*S14) # 0237

2-BUS-PP 2B 2-CB-PP 2B-MAIN 0.208 4.39 2.44 4.39 2.44 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S14) # 0238

2-BUS-PP B 2-CB-PP B-MAIN 0.208 5.14 2.73 5.14 2.73 2 0.0000 Yes PNL 25 86 18 15.6 (*N9) (*S14) # 0239

2-XF HUMID-SEC 2-CB-MDPC-4 0.48 1.08 0.98 1.08 0.98 2 0.0000 Yes PNL 25 44 18 5.22 (*N9) (*S14) # 0240 15.00

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 20-ATRIUM RTU 1-FU-DISC ATR RTU 0.208 4.58 2.14 4.58 2.14 0.0218 0.0000 Yes PNL 25 5 18 0.14 (*N3) (*S13) # 0241 15.00

20-BUS-ACCU 1 20-FU-DISC ACCU 1 0.208 5.70 2.93 5.70 2.93 0.0000 Yes PNL 25 7 18 0.25 (*N4a) (*S12) # 0242 10.00

20-BUS-ACCU 2 20-FU-DISC ACCU 2 0.208 5.70 2.93 5.70 2.93 0.0000 Yes PNL 25 7 18 0.25 (*N4a) (*S12) # 0243 10.00

20-BUS-ACCU 3 20-FU-DISC ACCU 3 0.208 5.70 2.93 5.70 2.93 0.0000 Yes PNL 25 7 18 0.25 (*N4a) (*S12) # 0244 10.00

20-BUS-ACCU 4 20-FU-DISC ACCU 4 0.208 5.14 2.73 5.14 2.73 0.0000 Yes PNL 25 7 18 0.25 (*N4a) (*S12) # 0245 200.00

20-BUS-ACCU 5 20-CB-MDP2-11 0.208 5.58 2.89 5.58 2.89 0.053 0.0000 Yes PNL 25 10 18 0.46 (*S12) # 0246 225.00

20-BUS-ACCU 6 20-CB-SWBD1-2 (20-CB-

MDP2-10)

0.208 11.42 4.06 11.42 4.06 0.052 0.0000 Yes PNL 25 12 18 0.65 (*N3) (*N5) (*S12) # 0247 175.00

20-BUS-AHU 1 20-CB-CC1A-2 0.208 2.50 1.64 2.50 1.64 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0248 200.00

20-BUS-AHU 2 20-CB-CC1A-3 0.208 2.50 1.64 2.50 1.64 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0249 200.00

20-BUS-AHU 3 20-CB-CC1A-4 0.208 2.50 1.64 2.50 1.64 0.0083 0.0000 Yes PNL 25 2 18 0.04 (*S12) # 0250 200.00

20-BUS-AHU 4 20-CB-CC2A-2 0.208 1.12 0.93 1.12 0.93 0.0083 0.0000 Yes PNL 25 2 18 0.02 (*S12) # 0251 200.00

20-BUS-AHU 5 20-CB-CC2A-3 0.208 3.03 1.88 3.03 1.88 0.0083 0.0000 Yes PNL 25 2 18 0.05 (*S12) # 0252 200.00

20-BUS-AHU 6 20-CB-CC2A-4 0.208 8.22 3.79 8.22 3.79 0.0083 0.0000 Yes PNL 25 4 18 0.10 (*S12) # 0253 50.00

20-BUS-AHU 7 20-CB-CC2A-5 0.208 0.32 0.32 0.32 0.32 0.8214 0.0000 Yes PNL 25 6 18 0.13 (*N11) (*S14) # 0254 200.00

20-BUS-AHU ATTIC 1-CB-2C AC-1 0.208 1.76 1.09 1.76 1.09 1.171 0.0000 Yes PNL 25 35 18 3.53 (*N3) (*S14) # 0255 100.00

20-BUS-ATS 1CC (L) 20-CB-EDP-3 0.208 8.23 3.23 8.23 3.23 2 0.0000 Yes PNL 25 96 18 18.6 (*N3) (*N9) (*S14) # 0256 20.00

20-BUS-ATS 1LS (L) 20-CB-EDP-1 0.208 7.92 3.69 7.92 3.69 0.053 0.0000 Yes PNL 25 12 18 0.60 (*S14) # 0257 20.00

20-BUS-ATS 2CC (L) 20-CB-EDP-4 0.208 7.58 3.04 7.58 3.04 2 0.0000 Yes PNL 25 93 18 17.6 (*N3) (*N9) (*S14) # 0258 60.00

20-BUS-ATS 2LS (L) 20-CB-EDP-2 0.208 6.81 3.32 6.81 3.32 0.053 0.0000 Yes PNL 25 11 18 0.53 (*S14) # 0259 60.00

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 20-BUS-BLDG 2 DISC 20-CB-BLDG 2 DISC 0.208 8.43 3.86 8.43 3.86 0.06 0.0000 Yes PNL 25 13 18 0.71 (*S14) # 0260

20-BUS-CC1A 20-CB-CC1A-MAIN 0.208 7.90 3.69 7.90 3.69 2 0.0000 Yes PNL 25 105 18 21.5 (*N9) (*S14) # 0261

20-BUS-CC2A 20-CB-CC2A-MAIN 0.208 7.28 3.48 7.28 3.48 2 0.0000 Yes PNL 25 101 18 20.3 (*N9) (*S14) # 0262

20-BUS-DISC ACCU5 20-CB-MDP2-11 0.208 6.11 3.08 6.11 3.08 0.053 0.0000 Yes PNL 25 10 18 0.49 (*S12) # 0263 200.00

20-BUS-DISC ACCU6 20-FU-DISC ACCU6 0.208 13.24 4.50 13.24 4.50 0.0462 0.0000 Yes PNL 25 12 18 0.65 (*N3) (*S13) # 0264 50.00

20-BUS-DISC-ACCU 1 20-FU-DISC ACCU 1 0.208 5.90 3.00 5.90 3.00 0.0000 Yes PNL 25 7 18 0.25 (*N4a) (*S12) # 0265

20-BUS-DISC-ACCU 2 20-FU-DISC ACCU 2 0.208 5.90 3.00 5.90 3.00 0.0000 Yes PNL 25 7 18 0.25 (*N4a) (*S12) # 0266

20-BUS-DISC-ACCU 3 20-FU-DISC ACCU 3 0.208 5.90 3.00 5.90 3.00 0.0000 Yes PNL 25 7 18 0.25 (*N4a) (*S12) # 0267

20-BUS-DISC-ACCU 4 20-FU-DISC ACCU 4 0.208 13.77 5.45 13.77 5.45 0.0000 Yes PNL 25 7 18 0.25 (*N4a) (*S12) # 0268

20-BUS-EDP 31-CB-GEN-1 0.208 8.58 3.91 8.58 3.91 0.05 0.0000 Yes PNL 25 12 18 0.60 (*S14) # 0269 125.00

20-BUS-LP1A 20-CB-LP1A-MAIN 0.208 16.46 6.17 16.46 6.17 0.016 0.0000 Yes PNL 25 8 18 0.32 (*S12) # 0270

20-BUS-LP1B 20-CB-MDP1-5 0.208 7.20 3.45 7.20 3.45 0.053 0.0000 Yes PNL 25 11 18 0.56 (*S12) # 0271 150.00

20-BUS-LP1C 20-CB-MDP1-6 0.208 7.20 3.45 7.20 3.45 0.053 0.0000 Yes PNL 25 11 18 0.56 (*S12) # 0272 150.00

20-BUS-LP1E 20-CB-MDP1-7 0.208 7.20 3.45 7.20 3.45 0.053 0.0000 Yes PNL 25 11 18 0.56 (*S12) # 0273 150.00

20-BUS-LP1F 20-CB-MDP1-8 0.208 7.20 3.45 7.20 3.45 0.053 0.0000 Yes PNL 25 11 18 0.56 (*S12) # 0274 150.00

20-BUS-LP1H 20-CB-MDP2-4 0.208 14.99 5.78 14.99 5.78 0.0172 0.0000 Yes PNL 25 8 18 0.31 (*S12) # 0275 40.00

20-BUS-LP1J 20-CB-MDP2-5 0.208 13.77 5.45 13.77 5.45 0.0179 0.0000 Yes PNL 25 8 18 0.31 (*S12) # 0276 50.00

20-BUS-LP1L 20-CB-MDP2-8 0.208 5.49 2.86 5.49 2.86 0.09 0.0000 Yes PNL 25 14 18 0.77 (*S12) # 0277 230.00

20-BUS-LP1M 20-CB-MDP2-9 0.208 5.49 2.86 5.49 2.86 0.09 0.0000 Yes PNL 25 14 18 0.77 (*S12) # 0278 230.00

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 20-BUS-LP1P 20-CB-MDP2-12 0.208 7.36 3.51 7.36 3.51 0.053 0.0000 Yes PNL 25 11 18 0.57 (*S13) # 0279 150.00

20-BUS-LP1R 20-CB-MDP2-2 0.208 6.11 3.08 6.11 3.08 0.053 0.0000 Yes PNL 25 10 18 0.49 (*S12) # 0280 200.00

20-BUS-LS1A 20-CB-LS1A-MAIN 0.208 7.33 2.97 7.33 2.97 1.718 0.0000 Yes PNL 25 83 18 14.7 (*N3) (*S14) # 0281

20-BUS-LS2A 20-CB-LS2A-MAIN 0.208 6.34 2.69 6.34 2.69 2 0.0000 Yes PNL 25 86 18 15.5 (*N3) (*N9) (*S14) # 0282

20-BUS-MDP1 20-CB-SWBD1-1 0.208 19.03 6.83 19.03 6.83 0.1 0.0000 Yes PNL 25 26 18 2.18 (*S13) # 0283 150.00

20-BUS-MDP2 20-CB-SWBD1-2 0.208 22.88 7.78 22.88 7.78 0.052 0.0000 Yes PNL 25 19 18 1.32 (*S12) # 0284 100.00

20-BUS-NELP 1D 20-CB-LS1A-2 0.208 6.34 3.16 6.34 3.16 0.0083 0.0000 Yes PNL 25 3 18 0.08 (*S12) # 0285 75.00

20-BUS-NELP 1G 20-CB-LS1A-1 0.208 4.13 2.34 4.13 2.34 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0286 150.00

20-BUS-NELP 1K 20-CB-LS2A-1 0.208 8.02 3.73 8.02 3.73 0.0083 0.0000 Yes PNL 25 4 18 0.09 (*S12) # 0287 50.00

20-BUS-NELP 1N 20-CB-LS2A-3 0.208 3.04 1.89 3.04 1.89 0.0083 0.0000 Yes PNL 25 2 18 0.05 (*S12) # 0288 230.00

20-BUS-NELP 1Q 20-CB-LS2A-2 0.208 4.22 2.37 4.22 2.37 0.0083 0.0000 Yes PNL 25 3 18 0.06 (*S12) # 0289 150.00

20-BUS-PB 2M 20-CB-PB2M-MAIN 0.208 19.03 6.83 19.03 6.83 0.09 0.0000 Yes PNL 25 24 18 1.97 (*N21b) (*S13) # 0290

20-BUS-PB1M 20-CB-PB1M-MAIN 0.208 17.81 6.52 17.81 6.52 0.0261 0.0000 Yes PNL 25 11 18 0.55 (*S12) # 0291

20-BUS-PM1A 20-CB-CC1A-1 0.208 12.28 5.03 12.28 5.03 0.014 0.0000 Yes PNL 25 6 18 0.22 (*S12) # 0292 20.00

20-BUS-PM2A 20-CB-PM2A-MAIN 0.208 15.68 5.97 15.68 5.97 0.0146 0.0000 Yes PNL 25 7 18 0.28 (*S12) # 0293

20-BUS-SWBD1 20-CB-SWBD1-MAIN 0.208 30.77 9.58 30.77 9.58 0.065 0.0000 Yes PNL 25 25 18 2.06 (*S12) # 0294

21-BUS-ACCU1 21-CB-MDP-11 0.208 9.62 4.23 9.62 4.23 0.0103 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0295 75.00

21-BUS-ACCU2 21-CB-MDP-7 0.208 5.80 2.97 5.80 2.97 0.0115 0.0000 Yes PNL 25 4 18 0.10 (*S12) # 0296 175.00

21-BUS-ATS CC(L) 21-CB-GEN-3 0.208 2.32 1.33 2.32 1.33 2 0.0000 Yes PNL 25 52 18 6.80 (*N3) (*N9) (*S14) # 0297 125.00

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 21-BUS-ATS FP(L) 21-CB-DISC FP 0.208 4.97 2.66 4.66 2.50 2 0.0000 Yes PNL 25 84 18 15.1 (*N9) (*S12) # 0298 30.00

21-BUS-ATS LS(L) 21-CB-GEN-2 0.208 2.24 1.52 2.24 1.52 2 0.0000 Yes PNL 25 57 18 7.94 (*N9) (*S14) # 0299 125.00

21-BUS-CC1A 21-CB-CC1A-MAIN 0.208 2.27 1.54 2.27 1.54 2 0.0000 Yes PNL 25 57 18 7.99 (*N9) (*S14) # 0300

21-BUS-DISC FP 21-CB-DISC FP 0.208 5.85 2.54 5.54 2.40 2 0.0000 Yes PNL 25 82 18 14.4 (*N3) (*N9) (*S12) # 0301

21-BUS-GEN 21-CB-GEN-1 0.208 2.70 1.73 0.40 0.25 0.0833 0.0000 Yes PNL 25 9 18 0.42 (*N2) (*S14)

21-BUS-GEN MaxTripTime @2.0s 0.208 2.70 1.73 2.31 1.55 2 0.0000 Yes PNL 25 61 18 8.92 (*N2) (*N9) (*S14) # 0302

21-BUS-LS1A 21-CB-LS1A-MAIN 0.208 2.17 1.49 2.17 1.49 2 0.0000 Yes PNL 25 56 18 7.78 (*N9) (*S14) # 0303

21-BUS-MDP 21-CB-MDP-MAIN 0.208 16.32 6.14 16.32 6.14 0.36 0.0000 Yes PNL 25 52 18 6.87 (*S12) # 0304

21-BUS-PB1D 21-CB-MDP-14 0.208 13.33 5.32 13.33 5.32 0.01 0.0000 Yes PNL 25 5 18 0.17 (*S12) # 0305 25.00

21-BUS-PB1E 21-CB-MDP-13 0.208 13.33 5.32 13.33 5.32 0.01 0.0000 Yes PNL 25 5 18 0.17 (*S12) # 0306 25.00

21-BUS-PB1F(1) 21-CB-PB1F(1)-MAIN 0.208 7.47 3.55 7.47 3.55 0.0112 0.0000 Yes PNL 25 4 18 0.12 (*S12) # 0307

21-BUS-PB1F(2) 21-CB-PB1F(1)-MAIN 0.208 7.31 3.49 7.31 3.49 0.0112 0.0000 Yes PNL 25 4 18 0.12 (*S12) # 0308 5.00

21-BUS-PB1K 21-CB-MDP-4 0.208 10.19 4.41 10.19 4.41 0.01 0.0000 Yes PNL 25 5 18 0.14 (*S12) # 0309 65.00

21-BUS-PB1M 21-CB-MDP-6 0.208 13.33 5.32 13.33 5.32 0.01 0.0000 Yes PNL 25 5 18 0.17 (*S12) # 0310 25.00

22-BUS-DPB 22-CB-DPB-MAIN 0.208 7.57 3.04 7.57 3.04 0.0637 0.0000 Yes PNL 25 12 18 0.58 (*N3) (*S13) # 0311

22-BUS-PB1B 22-CB-PB1B-MAIN 0.208 5.89 3.00 5.89 3.00 0.0112 0.0000 Yes PNL 25 4 18 0.10 (*S12) # 0312

22-BUS-PB2B 22-CB-PB2B-MAIN 0.208 6.53 3.23 6.53 3.23 0.0112 0.0000 Yes PNL 25 4 18 0.11 (*S12) # 0313

22-BUS-PB3B 22-CB-PB3B-MAIN 0.208 5.89 3.00 5.89 3.00 0.0112 0.0000 Yes PNL 25 4 18 0.10 (*S12) # 0314

23-BUS-DPA1 23-CB-DPA1-MAIN 0.208 5.63 2.47 5.63 2.47 2 0.0000 Yes PNL 25 82 18 14.4 (*N3) (*N9) (*S13) # 0315 250.00

23-BUS-PB1A 23-CB-PB1A-MAIN 0.208 5.06 2.29 5.06 2.29 2 0.0000 Yes PNL 25 78 18 13.3 (*N3) (*N9) (*S13) # 0316

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 23-BUS-PB2A 23-CB-PB2A-MAIN 0.208 5.27 2.36 5.27 2.36 2 0.0000 Yes PNL 25 80 18 13.7 (*N3) (*N9) (*S13) # 0317

23-BUS-PB3A 23-CB-PB3A-MAIN 0.208 4.76 2.20 4.76 2.20 2 0.0000 Yes PNL 25 76 18 12.7 (*N3) (*N9) (*S13) # 0318

23-BUS-PB4A 23-CB-PB4A-MAIN 0.208 4.76 2.20 4.76 2.20 2 0.0000 Yes PNL 25 76 18 12.7 (*N3) (*N9) (*S13) # 0319

24-BUS-DPA2 24-CB-DPA2-MAIN 0.208 4.82 2.21 4.82 2.21 2 0.0000 Yes PNL 25 76 18 12.8 (*N3) (*N9) (*S13) # 0320 315.00

24-BUS-PB1A2 24-CB-PB1A2-MAIN 0.208 4.45 2.09 4.45 2.09 2 0.0000 Yes PNL 25 74 18 12.1 (*N3) (*N9) (*S12) # 0321 12.14

24-BUS-PB2A2 24-CB-PB2A2-MAIN 0.208 4.62 2.15 4.62 2.15 2 0.0000 Yes PNL 25 75 18 12.5 (*N3) (*N9) (*S12) # 0322

24-BUS-PB3A2 24-CB-PB3A2-MAIN 0.208 4.22 2.37 4.22 2.37 2 0.0000 Yes PNL 25 80 18 13.9 (*N9) (*S12) # 0323

24-BUS-PB4A2 24-CB-PB4A2-MAIN 0.208 4.22 2.37 4.22 2.37 2 0.0000 Yes PNL 25 80 18 13.9 (*N9) (*S12) # 0324

25-BUS-DPC 25-CB-DPC-MAIN 0.208 5.29 2.36 5.29 2.36 2 0.0000 Yes PNL 25 80 18 13.7 (*N3) (*N9) (*S13) # 0325

25-BUS-PB1C 25-CB-PB1C-MAIN 0.208 4.02 2.29 4.02 2.29 0.0112 0.0000 Yes PNL 25 3 18 0.08 (*S12) # 0326

25-BUS-PB2C 25-CB-PB2C-MAIN 0.208 4.40 2.44 4.40 2.44 0.0112 0.0000 Yes PNL 25 3 18 0.08 (*S12) # 0327

25-BUS-PB3C 25-CB-PB3C-MAIN 0.208 4.85 2.62 4.85 2.62 0.0112 0.0000 Yes PNL 25 4 18 0.09 (*S12) # 0328

3-BUS-FP NORM 3-CB-FP NORM-MAIN 0.208 13.04 5.24 12.22 4.91 2 0.0000 Yes PNL 25 131 18 31.0 (*N9) (*S12) # 0329

3-BUS-MDP 3-CB-MDP-MAIN 0.208 14.58 5.67 14.58 5.67 0.0208 0.0000 Yes PNL 25 9 18 0.37 (*S12) # 0330

30- XF CT 1-SEC 30-CB-MCC1A-1 0.48 3.29 2.53 2.93 2.26 0.0175 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0331 8.00

30- XF CT 1-SEC 30-FU-DISC CT 1 0.48 3.29 2.53 0.42 0.33 0.0833 0.0000 Yes PNL 25 6 18 0.20 (*S12) 75.00

30- XF CT 2-SEC 30-CB-MCC1A-2 0.48 3.29 2.53 2.93 2.26 0.0175 0.0000 Yes PNL 25 5 18 0.13 (*S12) # 0332 8.00

30- XF CT 2-SEC 30-FU-DISC CT 2 0.48 3.29 2.53 0.42 0.33 0.0833 0.0000 Yes PNL 25 6 18 0.20 (*S12) 75.00

30-BUS-ATS EQ (L) 30-CB-EQH1-3 0.48 2.33 1.61 0.30 0.21 0.0833 0.0000 Yes PNL 25 9 18 0.38 (*N3) (*S14) 10.00

30-BUS-ATS EQ (L) 30-CB-EQH1-4 0.48 2.33 1.61 0.30 0.21 0.0833 0.0000 Yes PNL 25 9 18 0.38 (*N3) (*S14) 10.00

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal

30-BUS-ATS EQ (L) 30-CB-DISC-ATS EQ

(E)

0.48 2.33 1.61 1.74 1.20 2 0.0000 Yes PNL 25 53 18 7.09 (*N3) (*N9) (*S14) # 0333 5.00

30-BUS-ATS LS (L) 30-CB-HDP1-1 0.48 20.01 11.86 20.01 11.86 0.0175 0.0000 Yes PNL 25 13 18 0.70 (*S12) # 0334 20.00

30-BUS-CHLR 1 30-CB-MDP-3 0.48 26.30 14.98 24.34 13.86 0.05 0.0000 Yes PNL 25 29 18 2.57 (*S12) # 0335 75.00

30-BUS-CHLR 2 30-CB-MDP-2 0.48 26.30 14.98 24.34 13.86 0.05 0.0000 Yes PNL 25 29 18 2.57 (*S12) # 0336 75.00

30-BUS-CHLR 3 30-CB-MDP-1 0.48 26.30 14.98 24.34 13.86 0.05 0.0000 Yes PNL 25 29 18 2.57 (*S12) # 0337 75.00

30-BUS-DISC CT 1 30-FU-DISC CT 1 0.48 3.02 2.00 2.66 1.77 1.085 0.0000 Yes PNL 25 46 18 5.50 (*N3) (*S13) # 0336

30-BUS-DISC CT 2 30-FU-DISC CT 2 0.48 3.02 2.00 2.66 1.77 1.085 0.0000 Yes PNL 25 46 18 5.50 (*N3) (*S13) # 0337

30-BUS-DISC-ATS EQ

(E)

30-CB-EQH1-3 0.48 2.33 1.61 0.30 0.21 0.0833 0.0000 Yes PNL 25 9 18 0.38 (*N3) (*S14) 15.00

30-BUS-DISC-ATS EQ

(E)

30-CB-EQH1-4 0.48 2.33 1.61 0.30 0.21 0.0833 0.0000 Yes PNL 25 9 18 0.38 (*N3) (*S14) 15.00

30-BUS-DISC-ATS EQ

(E)

30-CB-DISC-ATS EQ

(E)

0.48 2.33 1.61 1.74 1.20 2 0.0000 Yes PNL 25 53 18 7.11 (*N3) (*N9) (*S14) # 0340

30-BUS-DISC-ATS LS

(E)

30-CB-DISC-ATS LS (E) 0.48 2.33 1.89 2.33 1.89 0.0177 0.0000 Yes PNL 25 4 18 0.10 (*S14) # 0341

30-BUS-EQH1 30-CB-EQH1-3 0.48 2.33 1.60 0.30 0.21 0.0833 0.0000 Yes PNL 25 9 18 0.38 (*N3) (*S14)

30-BUS-EQH1 30-CB-EQH1-4 0.48 2.33 1.60 0.30 0.21 0.0833 0.0000 Yes PNL 25 9 18 0.38 (*N3) (*S14)

30-BUS-EQH1 30-CB-DISC-ATS EQ

(E)

0.48 2.33 1.60 1.73 1.19 2 0.0000 Yes PNL 25 53 18 7.08 (*N3) (*N9) (*S14) # 0342 15.00

30-BUS-EQL1 30-CB-EQL1-MAIN 0.208 2.60 1.69 2.60 1.69 0.0161 0.0000 Yes PNL 25 3 18 0.08 (*S12) # 0343

30-BUS-EQL2 30-CB-EQL2-MAIN 0.24 0.52 0.52 0.52 0.52 1.895 0.0000 Yes PNL 25 12 18 0.57 (*N11) (*S13) # 0344

30-BUS-GEN 30-CB-GEN 0.48 2.35 1.90 1.75 1.42 0.06 0.0000 Yes PNL 25 8 18 0.33 (*S14)

30-BUS-GEN 30-CB-DISC-ATS EQ

(E)

0.48 2.35 1.90 0.60 0.49 0.0833 0.0000 Yes PNL 25 9 18 0.37 (*S14) # 0345 25.00

30-BUS-H1 30-CB-HDP1-3 0.48 21.96 12.84 21.96 12.84 0.0175 0.0000 Yes PNL 25 14 18 0.76 (*S12) # 0346 30.00

30-BUS-HDP1 30-CB-MDP-5 0.48 28.94 16.26 28.34 15.92 0.05 0.0000 Yes PNL 25 30 18 2.81 (*S12) # 0347 30.00

30-BUS-HDP1 30-CB-HDP1-2 0.48 28.94 16.26 0.60 0.34 0.0833 0.0000 Yes PNL 25 31 18 2.86 (*S12)

30-BUS-L1 30-CB-LDP1-1 0.208 4.83 2.61 4.83 2.61 2 0.0000 Yes PNL 25 84 18 15.1 (*N9) (*S13) # 0348 30.00

Bus Name Protective Bus Bus Bus Prot Dev Prot Dev Trip/ Breaker Ground Equip Gap Arc Working Incident PPE Level / Notes (*N) Label # Cable Length Incident Incident Device kV Bolted Arcing Bolted Arcing Delay Opening Type (mm) Flash Distance Energy From Trip Device Energy Energy Name Fault Fault Fault Fault Time Time/Tol Boundary (in) (cal/cm2) (ft) at Low at High

(kA) (kA) (kA) (kA) (sec.) (sec.) (in) Marginal Marginal 30-BUS-L2 30-CB-LDP1-2 0.208 4.83 2.61 4.83 2.61 2 0.0000 Yes PNL 25 84 18 15.1 (*N9) (*S13) # 0349 30.00

30-BUS-LDP1 30-CB-LDP1-MAIN 0.208 5.38 2.81 5.38 2.81 0.05 0.0000 Yes PNL 25 10 18 0.42 (*S12) # 0350

30-BUS-LSH1 30-CB-HDP1-1 0.48 18.27 10.97 18.27 10.97 0.0175 0.0000 Yes PNL 25 12 18 0.64 (*S12) # 0351 25.00

30-BUS-LSL1 30-CB-LSL1-MAIN 0.208 0.78 0.62 0.78 0.62 1.884 0.0000 Yes PNL 25 31 18 2.97 (*N3) (*S14) # 0352

30-BUS-MCC1 30-CB-MDP-6 0.48 26.86 15.25 26.10 14.82 0.05 0.0000 Yes MCC 25 29 18 2.62 (*S12) # 0353 60.00

30-BUS-MCC1 30-CB-MCC1-1 0.48 26.86 15.25 0.76 0.43 0.0833 0.0000 Yes MCC 25 29 18 2.68 (*S12)

30-BUS-MCC1A 30-CB-MCC1-1 0.48 22.00 12.86 21.24 12.42 0.0122 0.0000 Yes MCC 25 11 18 0.53 (*S12) # 0354 35.00

30-BUS-MCC1A 30-CB-MCC1A-1 0.48 22.00 12.86 0.38 0.22 0.0833 0.0000 Yes MCC 25 13 18 0.67 (*S12)

30-BUS-MCC1A 30-CB-MCC1A-2 0.48 22.00 12.86 0.38 0.22 0.0833 0.0000 Yes MCC 25 13 18 0.67 (*S12)

30-BUS-MCC2 30-CB-MDP-4 0.48 27.00 15.32 25.73 14.60 0.05 0.0000 Yes MCC 25 29 18 2.63 (*S12) # 0355 60.00

30-BUS-MCC2 30-CB-MCC2-1 0.48 27.00 15.32 1.27 0.72 0.0833 0.0000 Yes MCC 25 30 18 2.74 (*S12)

30-BUS-MCC2A 30-CB-MCC2-1 0.48 22.74 13.23 21.47 12.49 0.0121 0.0000 Yes MCC 25 11 18 0.54 (*S12) # 0356 40.00

30-BUS-MCC2A 30-CB-MCC2A-1 0.48 22.74 13.23 0.64 0.37 0.0833 0.0000 Yes MCC 25 14 18 0.77 (*S12)

30-BUS-MCC2A 30-CB-MCC2A-2 0.48 22.74 13.23 0.64 0.37 0.0833 0.0000 Yes MCC 25 14 18 0.77 (*S12)

30-BUS-MDP 30-CB-MDP-1 0.48 26.69 12.12 1.95 0.88 0.0833 0.0000 Yes SWG 32 36 24 2.16 (*N3) (*S13)

30-BUS-MDP 30-CB-MDP-2 0.48 26.69 12.12 1.95 0.88 0.0833 0.0000 Yes SWG 32 36 24 2.16 (*N3) (*S13)

30-BUS-MDP 30-CB-MDP-3 0.48 26.69 12.12 1.95 0.88 0.0833 0.0000 Yes SWG 32 36 24 2.16 (*N3) (*S13)

30-BUS-MDP 30-CB-MDP-4 0.48 26.69 12.12 1.26 0.57 0.0833 0.0000 Yes SWG 32 36 24 2.16 (*N3) (*S13)

30-BUS-MDP 30-CB-MDP-5 0.48 26.69 12.12 0.60 0.27 0.0833 0.0000 Yes SWG 32 36 24 2.16 (*N3) (*S13)

30-BUS-MDP 30-CB-MDP-6 0.48 26.69 12.12 0.76 0.34 0.0833 0.0000 Yes SWG 32 36 24 2.16 (*N3) (*S13)

30-BUS-MDP 30-CB-MDP-MAIN 0.48 26.69 12.12 18.24 8.29 2 0.0000 Yes SWG 32 244 24 36.4 (*N3) (*N9) (*S13) # 0357

30-XF P10-SEC 30-CB-MCC2A-2 0.48 3.63 2.76 2.89 2.20 0.0161 0.0000 Yes PNL 25 5 18 0.13 (*S12) 8.00

30-XF P10-SEC IndMtr Decay @5cycles 0.48 3.63 2.76 0.78 0.74 0.0833 0.0000 Yes PNL 25 7 18 0.27 (*S12) # 0358

30-XF P9-SEC 30-CB-MCC2A-1 0.48 3.63 2.76 2.89 2.20 0.0161 0.0000 Yes PNL 25 5 18 0.13 (*S12) 8.00

30-XF P9-SEC IndMtr Decay @5cycles 0.48 3.63 2.76 0.78 0.74 0.0833 0.0000 Yes PNL 25 7 18 0.27 (*S12) # 0359

30-XF-TRDP1-SEC 30-CB-MDP-5…