36C24418B0580-006.pdf
PDF 6 MB Posted
- Attached to
- SPS Storage Room Climate Control, Project 542-17-102 Federal contract opportunity
- Solicitation number
- 36C24418B0580
About this file
36C24418B0580 02-Drawing-Architecture-SPS.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24418C0218-000.docx | DOCX document | |
| 36C24418B0580-0002002.pdf | ||
| 36C24418B0580-0002001.pdf | ||
| 36C24418B0580-0002000.docx | DOCX document | |
| 36C24418B0580-0001000.docx | DOCX document | |
| 36C24418B0580-002.pdf | ||
| 36C24418B0580-007.pdf | ||
| 36C24418B0580-001.docx | DOCX document | |
| 36C24418B0580-005.pdf | ||
| 36C24418B0580-004.pdf | ||
| 36C24418B0580-003.pdf | ||
| 36C24418B0580-000.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A/C AIR CONDITIONING
ACOUS ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
A&E ARCHITECT AND ENGINEERS
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITIES HAVING JURISDICTION
AHU AIR HANDLING UNIT
ALT ALTERNATIVE
ALT TRANS ALTERNATIVE TRANSPORTATION
ALUM ALMINUM
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AVG AVERAGE
BB BULLETIN BOARD
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOD BASIS OF DESIGN
BRG BEARING
CB CATCH BASIN
CBB CEMENTITIOUS BACKER BOARD
CER CERAMIC
CF CUBIC FEET
CFCI CONTRACTOR FURNISH
CONTRACTOR INSTALL
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD
C & G CURB & GUTTER
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNITS
CO CLEANOUT(S)
COL COLUMN
CONC CONCRETE
CONT COTINUOUS
COORD COORDINATE
CP CONCRETE PIPE
CPT CARPET
CR CRASH RAIL
CRS COLD ROLLED STEEL
CS CAST STONE
CSB CONCRETE SPLASH BLOCK
CSI CONSTRUCTION SPECIFICATIONS
INSTITUTE
CT CERAMIC TILE
CTR CENTER
CU FT CUBIC FEET
CUH CABINET UNIT HEATER
CY CUBIC YARD
D DRYER
DEG DEGREE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DISP DISPENSER
DIV DIVISION
DN DOWN
DR DOOR
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
E EAST
(E) EXISTING
EA EACH
EF EXHAUST FAN
EFTR EXISTING FINISH TO REMAIN
EIFS EXTERIOR INSULATION AND FINISH
SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATED
ETR EXISTING TO REMAIN
ETS EXPOSED TO STRUCTURE
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FF & E FURNITURE FIXTURES & EQUIPMENT
FIN FINISH
FIXT FIXTURE
FL FLOW LINE
FLR FLOOR
FLUOR FLUORESCENT
FO FINISH OPENING
FOS FACE OF STUD
FR FIRE RATED
FSP FIRE STANDPIPE
FT FOOT / FEET
FTG FOOTING
FURR FURRING
FV FIELD VERIFY
FVC FIRE VALVE CABINET
FWC FABRIC WALLCOVERING
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GARBAGE DISPOSAL
GF CMU GROUND FACE CMU
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GI GALVANIZED IRON
GL GLASS
GL BLK GLASS BLACK
GLU LAM GLUE LAMINATED WOOD
GND GROUND
GT GROUT
GYP BD GYPSUM BOARD
GYP GYPSUM
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIB
HC HOLLOW CORE
HCP HANDICAPPED
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HGT HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR, HANDRAIL
HT HEIGHT
HVAC HEATING, VENTILATING & AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IG INSULATING GLASS
IN INCH
INCAN INCANDESCENT
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INV INVERT
ITG INSULATED TEMPERED GLASS
JAN JANITOR
J-BOX JUNCTION BOX
JT JOINT
L LONG
LAV LAVATORY
LB(S) # POUND(S)
LF LINEAL FEET
LLV LONG LEG VERTICAL
LT LIGHT
LVR LOUVER
M & BH MOP AND BROOM HOLDER
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MEPF MECHANICAL, ELECTRICAL,
PLUMBING,
FIRE PROTECTION (CONDUIT)
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MSB MOP SERVICE BASIN
MTD MOUNTED
MTL METAL
N NORTH
NA NOT APPLICABLE
NECY NECESSARY
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER,
OVERFLOW DRAIN
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED
OWNER INSTALLED
OH OPPOSITE HAND
OPN OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
P PAINT
PARTN PARTITION
PBD PARTICLE BOARD
PBSW PATIENT BED SERVICE WALL
PCC PRECAST CONCRETE
PI INPATIENT PSYCHIATRIC
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PMU PSYCHIATRIC MEDICAL UNIT
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATED
PROP PROPERTY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT CONC POST-TENSIONED CONCRETE
PTD PAPER TOWEL DISPENSER
PTL PORCELAIN TILE
PVC POLYVINYL CHLORIDE
QA QUALITY ASSURANCE
QT QUARRY TILE
R R-VALUE (INSULATION),
RADIUS, RISER
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE: REFERENCE
REBAR REINFORCING BAR
REC RECESSED
RECPT RECEPTACLE
REF REFRIGERATOR
REG REGISTER
REINF REINFORCE
REQD REQUIRED
RESIL RESILIENT
REV REVISION
RFT RESILIENT FLOOR TILE
RH ROOF HATCH
RM ROOM
RO ROUGH OPENING
RT RUBBER STAIR TREAD
S SOUTH
SAF SEAMLESS ACRYLIC FLOORING
SAP SUSPENDED ACOUSTICAL PANELS
SAT SUSPENDED ACOUSTICAL TILE
SB SPLASHBLOCK
SC SEALED CONCRETE, SOLID CORE
SCHED SCHEDULE
SCP SCUPPER
SD SOAP DISPENSER
SEAL SEALER
SECT SECTION
SECT SECTION
SF SQUARE FOOT
SF CMU SPLIT-FACE CMU
SHR SHOWER
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SL SLOPE
SLV SHORT LEG VERTICAL
SND SANITARY NAPKIN DISPOSER
SNV SANITARY NAPKIN VENDOR
SPECS SPECIFICATIONS
SQ SQUARE
SS SOLID SURFACE
SST STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
TB TACKBOARD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TBD TO BE DETERMINED
TD TUBULAR DAYLIGHTING DEVICE
TEL TELEPHONE
TEMP TEMPERATURE
TG TEMPERED GLASS,
TONGUE & GROOVE,
TRANSFER GRILLE
THRU THROUGH
TO TOP OF
TOC TOP OF CONCRETE
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TTD TOILET TISSUE DISPENSER
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
URN URINAL
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WDP WOOD PANELING
WDW WINDOW
WF WIDE FLANGE
WGL WIRED GLASS
WH WATER HEATER
WR WASTE RECEPTACLE,
WATER RESISTANT
WS WATER STOP
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
ARCHITECTURAL NOTES, SYMBOLS,
AND ABBREVIATIONS
DOOR TAG
ROOM TAG
REVISION TAG
KEYNOTE TAG
SECTION TAG
DETAIL TAG
EXTERIOR
ELEVATION TAG
WALL DEMOLITION
NEW DOOR
A101
REF
A101
SIM
Room
A101 1
DRAWING REFERENCE LEGEND
X
X
SCALE: N.T.S.
1 HR RATED WALL
2 HR RATED WALL
NEW WALL
SWRSJP
FULLY SPRINKLERED
100% CONSTRUCTION DOCUMENTS
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
AE001
GENERAL NOTES
COORDINATE WORK OF ALL TRADES PRIOR TO STARTING
CONSTRUCTION.
ALL DIMENSIONS ARE TO GRID LINES, FACE OF STUD FRAMING,
FINISHED FACE OF EXISTING WALL SURFACE, OR FACE OF
CONCRETE / MASONRY UNITS UNLESS
NOTED OTHERWISE.
AT FIRE RATED WALLS WHERE OPENINGS ARE GREATER THAN 16
SQUARE INCHES OR WHERE TOTAL AREA OF OPENINGS EXCEEDS
100 SQUARE INCHES IN 100 SQUARE FEET, WRAP 5/8" TYPE 'X'
GYPSUM BOARD BEHIND OPENINGS PER U.L. DESIGN #U510.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTING
THE WORK AND SYSTEMS TO COMPLY WITH ALL APPLICABLE
FEDERAL, STATE, AND LOCAL CODES, LAWS, SAFETY REGULATIONS,
HAZARDOUS WASTE LAWS, ETC. THE CONTRACTOR SHALL FURNISH
ALL NECESSARY PERMITS.
DO NOT SCALE DRAWINGS. DIMENSIONS SHALL GOVERN EACH
BUILDING COMPONENT LOCATION. BRING DISCREPANCIES TO THE
COR'S ATTENTION IN WRITING IMMEDIATELY.
PROVIDE SHEET METAL OR FIRE RETARDANT WOOD BLOCKING IN
WALL CAVITIES FOR ITEMS THAT ARE REQUIRED TO BE SECURED TO
THE WALLS.
PROVIDE SEALANT AT ALL INTERSECTIONS BETWEEN DIFFERENT
MATERIALS.
EXISTING CONDITIONS SHALL BE FIELD VERIFIED PRIOR TO BIDDING
OR BEGINNING OF WORK. ANY ERRORS OR OMISSIONS SHALL BE
BROUGHT TO THE COR'S ATTENTION IN WRITING IMMEDIATELY.
ALL EXISTING SPRINKLER HEADS WITHIN THE AREA OF WORK SHALL
REMAIN. THEY SHALL BE PROTECTED PRIOR TO STARTING
CONSTRUCTION. COORDINATE WITH NEW CEILING WORK. (NOTIFY
COR IMMEDIATELY IF DISCREPANCY HAS BEEN FOUND, THE COR
WILL THEN COORDINATE WITH THE DESIGN TEAM.)
A.
B.
C.
D.
E.
F.
G.
H.
I.
DRAWINGS AND DIMENSIONS
1.
2.
INDICATION OF PROJECT LIMITS OR LINES OF DEMARCATION ARE SHOWN
FOR THE CONVENIENCE OF THE CONTRACTOR, AND ARE NOT TO BE TAKEN
LITERALLY. ACTUAL CONTRACT LIMITS ARE TO BE DETERMINED BY THE
CONTRACTOR AND APPROVED BY THE COR BEFORE
CONSTRUCTION WORK BEGINS.
VERIFY INSTALLATION REQUIREMENTS FOR ALL
PRODUCTS TO BE INCORPORATED IN THE WORK (INCLUDING THICKNESS
FOR RECESSED OR SEMI-RECESSED PRODUCTS), AND
ACCOMMODATE AND COORDINATE CHANGES TO OTHER MATERIALS OR
PRODUCTS THAT ARE NECESSARY BECAUSE OF THESE DIFFERENCES.
3.
4.
THE DRAWINGS AND SPECIFICATIONS, INCLUDING DRAWINGS PREPARED BY
SPECIFIC ENGINEERING DISCIPLINES (SUCH AS CIVIL, STRUCTURAL,
MECHANICAL, ELECTRICAL, ETC.) ARE COMPLEMENTARY; ITEMS SHOWN IN ANY
ONE LOCATION IN THE DRAWINGS SHALL BE CONSIDERED TO BE
REQUIREMENTS OF THE CONTRACT FOR CONSTRUCTION. IN THE EVENT OF AN
INCONSISTENCY BETWEEN THE DRAWINGS AND SPECIFICATIONS, OR WITHIN
EITHER DOCUMENT, THE CONTRACTOR SHALL SEEK CLARIFICATION OR
INTERPRETATION FROM THE COR PRIOR TO BIDDING. WHERE
INCONSISTENCIES ARE NOT CLARIFIED PRIOR TO BIDDING, AND WHERE THE
ACTUAL SOLUTION OR INTENT CANNOT BE REASONABLY INFERRED, THE
CONTRACTOR SHALL PROVIDE THE BETTER QUALITY OR GREATER QUANTITY
OF WORK.
USE OF THE WORD "VERIFY" POINTS OUT A SITUATION WHICH MUST BE
CONFIRMED PRIOR TO PROCEEDING WITH THE WORK, FABRICATION OF
EQUIPMENT, OR ORDERING MATERIAL. NOTIFY THE COR OF
DISCREPANCY DISCOVERED.
5.
6.
CHECK ALL FIELD CONDITIONS AND DIMENSIONS AS THEY RELATE TO THIS
PROJECT. SHOULD DISCREPANCIES EXIST BETWEEN THE WORK INDICATED AND
ACTUAL FIELD CONDITIONS NOTIFY THE COR PRIOR TO PROCEEDING WITH THE
WORK.
7.
DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR
REFERENCE ONLY AND ARE NOT INTENDED TO ACCURATELY DEPICT ACTUAL
OR DESIGNATED CONDITIONS. WRITTEN DIMENSIONS SHALL GOVERN.
8.
ALL DIMENSIONS INDICATED ARE TO FACES OF STRUCTURAL MATERIALS OR
COLUMN GRID LINES UNLESS NOTED OTHERWISE. ROUGH OPENINGS SHALL
ALLOW FOR SHIM SPACE.
THE TERM "ALIGN" REFERS TO LOCATING DIFFERENT COMPONENTS OF
CONSTRUCTION TO PROVIDE A FLUSH FINISH SURFACE.
SHOULD DIMENSIONS BE MISSING OR CONFLICTING, NOTIFY COR PRIOR
TO PROCEEDING WITH RELATED WORK.
9.
ARCHITECTURAL ABBREVIATIONS
DEDUCT NO.1: All work associated with Building 4, Room B05A.
DEDUCT NO. 2: All work associated with Building 4, Room B07H.
DEDUCT NO. 3: All work associated with Building 58, Room 105F.
DEDUCT NO. 4: All work associated with Building 58, Room 105G.
DEDUCT NO. 5: All work associated with Building 38.
D3 D2
D1 D4
D5
REMOTE
D1D4
D3
D2
REMOTE
D3
D4
D1 D2
D1
D3
D4 D5
D3D4
D1
REMOTE
D2 D6
D1
D3D4
D5
D3D4
D1
D3
D4
D2
6 3
1 6
5 4
REMOTE
1 6
5 4
5 4
REMOTE
D1
REMOTE
D2
D3
D4 www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
1HR RATED
2HR RATED
20MIN RATED
REMOVE PORTION OF EXISTING SUSPENDED ACT CEILING AS REQUIRED FOR
INSTALLATION OF NEW FAN COIL UNIT - SEE MECHANICAL DRAWINGS.
REMOVE PORTION OF EXISTING MASONRY WALL AS REQUIRED FOR CONNECTION
OF NEW WATER LINES. SEE DETAIL 2/AE500.
SEE NOTE D2 - REMOTE LOCATION - SEE MECHANICAL DRAWINGS.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRANCE.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
REMOVE EXISTING SECONDARY PLASTER CEILING ABOVE SUSPENDED ACOUSTIC
CEILING. SEE SPECIFICATIONS FOR ASBESTOS MASTIC REMOVAL AT PLASTER
CEILING.
REMOVE EXISTING SUSPENDED ACOUSTIC CEILING.
FAN COIL UNIT - SEE MECHANICAL DRAWINGS. BOTTOM OF UNIT TO BE FLUSH
WITH EXISTING ADJACENT SUSPENDED ACOUSTIC CEILING. REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS OF PIPING PENETRATIONS AS
REQUIRED.
HUMIDIFIER (WALL-MOUNTED) - SEE MECHANICAL DRAWINGS. REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS OF PIPING PENETRATION AS REQUIRED.
REPAIR RATED MASONRY WALL - REFER TO DETAIL 2/AE500. SEE MECHANICAL
DRAWINGS FOR NEW WATER LINE CONNECTIONS.
SEE NEW WORK KEY NOTE #3, REMOTE LOCATION - SEE MECHANICAL DRAWINGS.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRY.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
PATCH SUSPENDED ACT, MATCH CEILING TILE AND GRID TYPE OF EXISTING
ADJACENT ACT.
INSTALL SUSPENDED ACOUSTIC CEILING AT 8'-0" A.F.F.
1. PROVIDE HEPA-FILTERED DUST CONTROL SYSTEM DURING DEMOLITION AND
CONSTRUCTION. BLOCK OFF EXISTING AIR REGISTERS AND GRILLES DURING
DEMOLITION AND CONSTRUCTION.
2. REMOVE AND PATCH BACK EXISTING FINISHES AS REQUIRED TO PERFORM
THE WORK. PATCH BACK TO MATCH EXISTING ADJACENT FINISHES TO
REMAIN.
3. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
4. COORDINATE WITH VA COR FOR SITE ACCESS REQUIREMENTS FOR
CONSTRUCTION PERSONNEL, AND SEPARATION OF CONSTRUCTION AREAS.
5. COMPLY WITH VA REQUIREMENTS FOR ICRA PROTECTIVE BARRIERS AND
ACCESS TO WORK AREAS.
6. REFER TO MECHANICAL PLANS FOR LOCATIONS OF REMOTE PIPING
CONNECTIONS
7. SEE MECHANICAL DRAWINGS FOR TYPICAL PIPING PENETRATION DETAIL AT
RATED AND NON-RATED WALLS.
8. SEE MECHANICAL DRAWINGS FOR TYPICAL DUCTWORK PENETRATION DETAIL
AT RATED AND NON-RATED WALLS.
9. SEE SHEET AE500 FOR WINDOW TYPES AND DETAILS.
10. PROVIDE NEW WEATHERSTRIPPING AND THRESHOLD AT SPS CLOSET DOORS,
TYP.
11. WHERE SUSPENDED ACOUSTIC CEILING IS REMOVED, IN TOTAL OR PORTION
THEREOF TEMPORARILY SUPPORT CEILING MOUNTED EQUIPMENT, FIXTURES
AND DEVICES.
REMOTE
REMOTE
D1
D2
D2
D3
D4
NORTH
NORTH
D5
D6
3 2 1
D1
D2
D3 www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NEW HUMIDIFIER (WALL-MOUNTED) - SEE MECHANICAL DRAWINGS. REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS OF PIPING PENETRATION AS REQUIRED.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRY.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
INSTALL SUSPENDED ACOUSTIC CEILING AT 8'-0" A.F.F.
1. REFER TO SHEET AE101 FOR GENERAL SHEET NOTES.
1HR RATED
2HR RATED
20MIN RATED
NORTH
REMOVE EXISTING SUSPENDED ACOUSTIC CEILING.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRANCE.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
D1
D2
D3
D4 D4
D2
D3
D5
D1
D4
D2
D3
D6
D2 D3
D6
WINDOW
TYPE
WINDOW
TYPE
WINDOW
TYPE
5 5
D2
D3
D6
2 3 www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
REMOVE PORTION OF EXISTING SUSPENDED ACT CEILING AS REQUIRED FOR
INSTALLATION OF NEW FAN COIL UNIT - SEE MECHANICAL DRAWINGS.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRANCE.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
REMOVE EXISTING WINDOW, SEE DETAIL 4/AE500. MAINTAIN TEMPORARY
WEATHER TIGHT CONDITION UNTIL WINDOW IS REPLACED.
EXISTING FCU ABOVE TO BE REMOVED/ REPLACED. SEE MECHANICAL DRAWINGS.
REMOVE EXISTING SUSPENDED ACOUSTIC CEILING.
NEW HUMIDIFIER (WALL-MOUNTED) - SEE MECHANICAL DRAWINGS. REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS OF PIPING PENETRATION AS REQUIRED.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRY.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
PATCH SUSPENDED ACOUSTIC CEILING, MATCH CEILING TILE AND GRID TYPE OF
EXISTING ADJACENT CEILING.
PROVIDE NEW WINDOW. SEE DETAIL 4/AE500.
NEW FAN COIL UNIT ABOVE TO REPLACE EXISTING - SEE MECHANICAL DRAWINGS.
INSTALL SUSPENDED ACOUSTIC CEILING AT 8'-0" A.F.F.
D1
D2
D3
D4
D5
1. REFER TO SHEET AE101 FOR GENERAL SHEET NOTES.
1HR RATED
2HR RATED
20MIN RATED
NORTH
D3D45 4
D3
D4 5
D6
REMOTE1 3
D3
D4
D1
D2
D5
REMOTE
D4
D2 REMOTE
D3
D1
D1
D2 D4
D3
REMOTE
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
REMOVE PORTION OF EXISTING SUSPENDED ACT CEILING AS REQUIRED FOR
INSTALLATION OF NEW FAN COIL UNIT - SEE MECHANICAL DRAWINGS.
REMOVE PORTION OF EXISTING MASONRY WALL AS REQUIRED FOR CONNECTION
OF NEW WATER LINES, SEE DETAIL 2/AE500.
SEE NOTE D2 - REMOTE LOCATION - SEE MECHANICAL DRAWINGS.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRANCE.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
REMOVE EXISTING SECONDARY PLASTER CEILING ABOVE SUSPENDED ACOUSTIC
CEILING. SEE SPECIFICATIONS FOR ASBESTOS MASTIC REMOVAL AT PLASTER
CEILING.
REMOVE EXISTING SUSPENDED ACOUSTIC CEILING.
NEW FAN COIL UNIT - SEE MECHANICAL DRAWINGS. BOTTOM OF UNIT TO BE WITH
EXISTING ADJACENT SUSPENDED ACT CEILING. REFER TO MECHANICAL
DRAWINGS FOR LOCATIONS OF PIPING PENETRATIONS AS REQUIRED.
NEW HUMIDIFIER (WALL-MOUNTED) - SEE MECHANICAL DRAWINGS. REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS OF PIPING PENETRATION AS REQUIRED.
REPAIR RATED MASONRY WALL - SEE MECHANICAL DRAWINGS FOR NEW WATER
LINE CONNECTIONS. SEE DETAIL 2/AE500.
SEE PLAN NOTE #3, REMOTE LOCATION - SEE MECHANICAL DRAWINGS.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRY.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
PATCH SUSPENDED ACOUSTIC CEILING. MATCH CEILING TILE AND GRID TYPE OF
EXISTING ADJACENT CEILING.
INSTALL SUSPENDED ACOUSTIC CEILING AT 8'-0" A.F.F.
REMOTE
REMOTE
D1
D2
D2
D3
D4
1. REFER TO SHEET AE101 FOR GENERAL SHEET NOTES.
1HR RATED
2HR RATED
20MIN RATED
NORTH
NORTH
D5
D1 D2
D4
D3
D1 D2
D4
D3
D4D3
D1
D2
REMOTE
D1
D2
D4D3
D1
D2
D4 D3
D5
D3
D2
D4
D1
D3 D4
D1D2
REMOTE
3 1
REMOTE
REMOTE
2 6 www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
REMOVE PORTION OF EXISTING SUSPENDED ACT CEILING AS REQUIRED FOR
INSTALLATION OF NEW FAN COIL UNIT - SEE MECHANICAL DRAWINGS.
REMOVE PORTION OF EXISTING MASONRY WALL AS REQUIRED FOR CONNECTION
OF NEW WATER LINES. SEE DETAIL 2/AE500.
SEE NOTE D2 - REMOTE LOCATION - SEE MECHANICAL DRAWINGS.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRANCE.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
REMOVE EXISTING SECONDARY PLASTER CEILING ABOVE SUSPENDED ACOUSTIC
CEILING. SEE SPECIFICATIONS FOR ASBESTOS MASTIC REMOVAL AT PLASTER
CEILING.
NEW FAN COIL UNIT - SEE MECHANICAL DRAWINGS. BOTTOM OF UNIT TO BE WITH
EXISTING ADJACENT SUSPENDED ACT CEILING. REFER TO MECHANICAL
DRAWINGS FOR LOCATIONS OF PIPING PENETRATIONS AS REQUIRED.
NEW HUMIDIFIER (WALL-MOUNTED) - SEE MECHANICAL DRAWINGS. REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS OF PIPING PENETRATION AS REQUIRED.
REPAIR RATED MASONRY WALL - SEE MECHANICAL DRAWINGS FOR NEW WATER
LINE CONNECTIONS. SEE DETAIL 2/AE500.
- SEE PLAN NOTE #3, REMOTE LOCATION - SEE MECHANICAL DRAWINGS.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRY.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
PATCH SUSPENDED ACOUSTIC CEILING. MATCH CEILING TILE GRID TYPE OF
EXISTING ADJACENT CEILING.
REMOTE
D1
D2
D2
D3
D4
1. REFER TO SHEET AE101 FOR GENERAL SHEET NOTES.
1HR RATED
2HR RATED
20MIN RATED
NORTH
NORTH
NORTH
NORTH
REMOTE
D5
D2
D3
D1
D1 1
WINDOW
TYPE
WINDOW
TYPE
WINDOW
TYPE
WINDOW
TYPE
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NORTH
REMOVE EXISTING WINDOW, SEE DETAIL 4/AE500. MAINTAIN TEMPORARY
WEATHER-TIGHT CONDITION UNTIL WINDOW IS REPLACED.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRY.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
PROVIDE NEW WINDOW. SEE DETAIL 4/AE500.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRY.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
D1
1. REFER TO SHEET AE101 FOR GENERAL SHEET NOTES.
1HR RATED
2HR RATED
20MIN RATED
D2
D4
D1D2REMOTE
3REMOTE
D5 D4
D3 www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
REMOVE PORTION OF EXISTING SUSPENDED ACT CEILING AS REQUIRED FOR
INSTALLATION OF NEW FAN COIL UNIT - SEE MECHANICAL DRAWINGS.
REPAIR RATED MASONRY WALL - REMOTE LOCATION - SEE MECHANICAL
DRAWINGS FOR NEW WATER LINE CONNECTIONS. SEE DETAIL 2/AE500.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRANCE.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
REMOVE EXISTING SUSPENDED ACOUSTIC CEILING.
NEW FAN COIL UNIT - SEE MECHANICAL DRAWINGS. BOTTOM OF UNIT TO BE WITH
EXISTING ADJACENT SUSPENDED ACT CEILING. REFER TO MECHANICAL
DRAWINGS FOR LOCATIONS OF PIPING PENETRATIONS AS REQUIRED.
NEW HUMIDIFIER (WALL-MOUNTED) - SEE MECHANICAL DRAWINGS. REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS OF PIPING PENETRATION AS REQUIRED.
REPAIR RATED MASONRY WALL - REMOTE LOCATION - SEE MECHANICAL
DRAWINGS FOR NEW WATER LINE CONNECTIONS. SEE DETAIL 2/AE500.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRY.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
PATCH SUSPENDED ACOUSTIC CEILING. MATCH CEILING TILE AND GRID TYPE OF
EXISTING ADJACENT CEILING.
INSTALL SUSPENDED ACOUSTIC CEILING AT 8'-0" A.F.F.
REMOTE
D1
D2
D3
1. REFER TO SHEET AE101 FOR GENERAL SHEET NOTES.
1HR RATED
2HR RATED
20MIN RATED
D4
NORTH
ROOM 105G
ROOM 105F
NORTH
D5
3 2
3 2
3 2
3 2
9A
10 9
9A 9
3 2
3 2 www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NORTH
NORTH
NORTH
ROOM 158B
ROOM 237
ROOM 125A
ROOM 115
NEW HUMIDIFIER (WALL-MOUNTED) - SEE MECHANICAL DRAWINGS. REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS OF PIPING PENETRATION AS REQUIRED.
PROVIDE PROTECTIVE PLASTIC BARRIER WITH ZIPPER ENTRY.
PROVIDE STICKY FLOOR MAT AT WORK AREA ENTRY.
PROVIDE PROTECTIVE PLASTIC BARRIER. PROVIDE CONSTRUCTION SIGN TO
PREVENT ENTRY.
1. REFER TO SHEET AE101 FOR GENERAL SHEET NOTES.
1HR RATED
2HR RATED
20MIN RATED
CLEAN, PRIME AND PAINT
EXISTING STEEL ANGLE
CAULK ALL AROUND
FOAM INSULATION
PAN
SECURE W/4" (102mm) CLIPS 18" (457mm) OC
NEW INTERIOR SNAP TRIM
SECURE TO EXISTING FRAME
SEAL ALL AROUND
NEW INTERIOR CASING
EXISTING CEILING DROP BELOW
WINDOW HEAD VARIES- SEE
WINDOW SCHEDULES
TREATED WOOD BLOCK AS
REQUIRED
HEAD DETAIL
FOAM INSULATION
CAULK ALL
AROUND
SILL DETAIL
SECURE TO EXISTING
FRAME
SEAL ALL AROUND
NEW INTERIOR CASING
TREATED WOOD
BLOCK AS REQUIRED
NEW INTERIOR SNAP
TRIM
SECURE W/4" (102MM)
CLIPS 18" (457MM) OC
1" (25mm)
INSULATED
GLASS
JAMB DETAIL
PAN
CAULK ALL
AROUND
1" (25mm)
INSULATED GLASS
SECURE W/4" (102mm) CLIPS 18" (457mm) OC
INTERIOR TRIM
INTERIOR CASING SEAL ALL AROUND
TREATED WOOD BLOCK
AS REQUIRED
SECURE TO EXISTING
FRAME
FOAM INSULATION
SEE DETAIL 5/AE500
FOR HEAD, JAMB
AND SILL DETAILS
C
7'-0"
3'-8"
NOTE:
WINDOW DIMENSIONS SHOWN
ARE APPROXIMATE. G.C. VERIFY
ACTUAL WINDOW DIMENSIONS.2'-10"
2'-0"
B
2'-0"
3'-0"
SEE DETAIL 5/AE500
FOR HEAD, JAMB AND
SILL DETAILS
A
FIXED
SEE DETAIL 4/AE500
FOR HEAD, JAMB
AND SILL DETAILS
FIXED FIXED
4"4" 4" 4"
WATER PIPES, SEE
MECHANICAL SHEETS.
FLOOR
CEILING
FLOOR
CEILING
PROVIDE CONTINUOUS 4" X 1/4 "
STEEL FLAT BAR LINTEL
CONTINUOUS 4" X 1/4 "
STEEL FLAT BAR LINTEL
REMOVE PORTION OF EXISTING
MASONRY AS REQUIRED TO
PERFORM WORK. SEE
MECHANICAL DRAWINGS FOR
ADDITIONAL INFO.
EXISTING MASONRY SHAFT
MINERAL WOOL FILL WITH
FIRESTOP SEALANT.
SEE DETAIL 1/A-500.
1/2 CMU BLOCK INFILL.
CMU BLOCK INFILL.
NOTE:
PATCH/ REPAIR FINISHES AT AREA OF WORK TO MATCH
EXISTING ADJACENT FINISHES AT SHAFT. TO REMAIN.
DEMOLITION PARTIAL ELEVATION NEW WORK PARTIAL ELEVATION
FULLY SPRINKLERED
100% CONSTRUCTION DOCUMENTS
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
ARCHITECTURAL DETAILS
SJP SWR
AE500
1 UL DETAIL-THROUGH PENETRATION FIRE STOP SYSTEM
SCALE: NTS
3 WINDOW TYPES
SCALE: NTS
4 WINDOW DETAILS - FIXED WINDOW
SCALE: NTS
2 ELEVATION AT PIPE SHAFT
SCALE: NTS
| AE001-A-001 |
| AE101-A101 |